Please note not all notes may apply.
1. CONTRACTOR SHALL PROVIDE A COMPLETE AND OPERABLE MECHANICAL SYSTEM. ARE NOTED ON THE MECHANICAL PLANS.
2. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE. CAREFUL ATTENTION SHALL BE PAID TO PRECISE LOCATION AND 15. FOR EACH RETURN AIR GRILLE, PROVIDE 3M FILTRETE 1000 MICRO ALLERGEN PLEATED AIR FILTERS (3M, 800-49403552,
COORDINATION OF DIFFUSERS, REGISTERS, AND GRILLES WITH STRUCTURAL FRAMING AND ELECTRICAL FIXTURES AT www.filtrete.com, MERV RATING: 11, PRESSURE DROP:.2 @ 300 FPM, OR APPROVED SUBSTITUTE). PRIOR TO INSTALLATION,
CEILING LOCATIONS. ELECTRICAL FIXTURES AT CEILING TAKE PRIORITY OVER DUCT LAYOUT. ELECTRICAL FIXTURES AT THE CONTRACTOR SHALL VERIFY THAT THE AIR VELOCITY NOICE ACROSS EACH RETURN AIR FILTER WILL BE LOW, BASED
CEILING ARE NOT 0 BE MOVED FROM THEIR PROPOSED LOCATIONS. SEE THE REFLECTED CEILING PLANS, WHERE ON THE PRESSURE DROP FOR PROPOSED FILL ER TYPE AND THE PROPOSED RETURN AIR GRILLE SIZE(S). ANY RETURN AIR
AVAILABLE, FOR EXACT LOCATIONS OF CEILING FIXTURES. NO STRUCTURAL MEMBER SHALL BE CUT WITHOUT PERMISSION FILTER GRILLES THAT ARE REQUIRED TO BE RFSIZED BY THE CONTRACTOR, ARE TO BE SIZED FOR FILTER SIZES THAT ARE
FROM STRUCTURAL ENGINEER. READILY AVAILABLE AT HOME SUPPLY STORES. CUSTOM SIZES ARE NOT PERMITTED.
3. THE CONTRACTOR SHALL OBTAIN, AT HIS EXPENSE, ALL NECESSARY FEES, P RMITS, AND TESTS. 16. ALL BATH, KITCHEN, AND DRYER EXHAUST(S) SHALL BE VENTED TO THE EXTERIOR.
4. ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS, ORDINAI 4CES AND REQUIREMENTS OF AUTHORITIES 17. ALL BATH EXHAUST FANS SHALL BE DUCTED WITH 4" R-FIN. SLOPE AND FULLY SUPPORT ALL BATHROOM EXHAUST DUCTS
HAVING JURISDICTION. NO CONTRACTOR SHALL BID UNLESS FAMILIAR WITH HESE CODES. ALL WORK SHALL BE TO AVOID ANY SNAGS IN THE DUCT AND TO ALLOW FOR PROPER DRAINAGE. TERMINATE AT SOFFIT WITH SCREENED
EXECUTED IN A WORKMANLIKE MANNER AND SHALL PRESENT A NEAT, PROF SSIONAL APPEARANCE WHEN COMPLETED. GRILLE, UNLESS OTHERWISE NOTED.
ALL MATERIALS AND EQUIPMENT SHALL BE NEW. STORE AND INSTALL MATERIALS AND EQUIPMENT IN ACCORDANCE WITH 18. PROVIDE BACKDRAFT DAMPERS FOR ALL EXHAUST FANS.
THE MANUFACTURER'S INSTRUCTIONS. 19. ALL EXHAUST AIR DUCTS SHALL BE GALVANIZED SHEET METAL CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE HVAC SYSTEM(S) TO BE INSTALLED (REFRIGERANT LINES, EQUIPMENT, ASHRAE AND SMACNA STANDARDS.D
DUCTWORK, GRILLES, ETC.). ADDITIONAL OFFSETS, TRANSITIONS, ETC. MAY E REQUIRED TO PROVIDE A COMPLETE 20. TESTING, ADJUSTING, AND BALANCING: THE CONTRACTOR SHALL BALANCE THE AIRFLOW DISTRIBUTION SYSTEMS,
SYSTEM. NO ABRUPT TRANSITIONS SHALL BE PERMITTED. THE MECHANICAL WORK HEREIN INCLUDES COMPLETE INCLUDING SUB MAINS, BRANCHES, AND TERMINALS TO QUANTITIES INDICATED ON THE UPDATED MANUAL J LOAD
SYSTEMS OF HEATING, AIR CONDITIONING (TEMPERATURE AND HUMIDITY CONTROL), VENTILATION, BATHROOM EXHAUST, ANALYSIS (FOR RESIDENTIAL PROPERTIES) AND MANUAL J (COMMERCIAL PROPERTIES).
KITCHEN EXHAUST, AND ALL DUCTWORK. THE CONTRACTOR SHALL PROVIDE EACH ELEMENT THEREOF, AS INDICATED 21. PROVIDE DRAW -THROUGH CONDENSATE TRAP AT EACH UNIT CONDENSATE DRAIN. DEPTH SHALL BE AT LEAST 1-1/2 TIMES
HEREIN, OR REASONABLY INFERRED (WHETHER OR NOT SPECIFICALLY CALLED FOR BY ITEM), REASONABLY NECESSARY TO THE TOTAL S.P DROP OF THE UNIT.
FACILITATE EACH SYSTEM'S FUNCTIONING AS INDICATED BY THE DESIGN AND EQUIPMENT SPECIFIED. CONTRACTOR SHALL 22. PROVIDE PROGRAMMABLE SERIES 7-DAY THERMOSTAT, PRIOR TO ORDERING THE THERMOSTAT, THE CONTRACTOR SHALL
VERIFY SPACE CONDITIONS PRIOR TO THE FABRICATION OR INSTALLATION OF ANY WORK. VERIFY THAT THE SPECIFIED THERMOSTAT WILL OPERATE PROPERLY WITH THE PROPOSED AIR CONDITIONING EQUIPMENT.
6. THE CONDENSING UNIT AND AIR HANDLING UNIT EQUIPMENT SHALL BE AS SPECIFIED OR ARCHITECT APPROVED IF A SUBSTITUTE IS REQUIRED, CONTRACTOR MUST SUBMIT PRODUCT INFORMATION TO ARCHITECT FOR PRODUCT
SUBSTITUTE. APPROVAL. COORDINATE THERMOSTAT LOCATION WITH FURNITURE/EQUIPMENT LAYOUTS, WINDOWS AND DOOR SWINGS.
7. PRIOR TO START OF THE HVAC WORK, THE CONTRACTOR SHALL SUBMIT, TO THE ARCHITECT, AN UPDATED MANUAL J LOAD THERMOSTAT MUST BE LOCATED AT 54" A.F.F. AND NOT LOCATED ON AN OUTSIDE WALL.
ANALYSIS, BASED ON THE FINAL CONTRACTOR DOCUMENTS AND ACTUAL MATERIALS AND PRODUCTS SELECTED (ie: 23. SUPPLY AND RETURN AIR GRILLES SHALL MAINTAIN A MINIMUM DISTANCE OF 3'-01, FROM CEILINGS FANS.
BUILDING ENVELOPE INSULATION, EXTERIOR DOOR GLAZING, AND ANY OTHE APPLICABLE FACTORS THAT WOULD AFFECT 24. ALL DUCT BRANCHES, PER ACCA MANUAL D, SHOULD INCLUDE DAMPERS FOR PROPER AIR FLOW AND BALANCING.
THE UPDATED MANUAL J LOAD ANALYSIS). THE SIZING OF THE ACTUAL HVAC SYSTEMS TO BE UTILIZED (REFRIGERANT 25. NO EQUIPMENT SHALL BE PURCHASED UNTIL REVIEW BY THE PROFESSIONAL OF RECORD, EVEN IF EQUIPMENT HAS BEEN
LINES, EQUIPMENT, DUCTWORK, GRILLES, ETC.) SHALL BE BASED ON THE UPDATED MANUAL J LOAD ANALYSIS. THE SPECIFIED.
CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR PROPERLY SIZING THE HVAC SYSTEM. 26. ANY VARIATION FROM THE DESIGN PRESENTED COULD AFFECT SYSTEM PERFORMANCE.
8. THE CONTRACTOR SHALL COORDINATE A "MECHANICAL WALK-THROUGH" MEETING, WHICH IS TO OCCUR PRIOR TO THE 27, EQUIPMENT SHALL BEAR A U.L. OR OTHER RECOGNIZED LABEL, NAMEPLATES, WIRING DIAGRAMS, AND ENERGY RATINGS,
START OF THE MECHANICAL ROUGH -IN. THE PURPOSE FOR THIS MEETING IS TO ALLOW THE OWNER, ARCHITECT, AND AS APPLICABLE.
CONTRACTOR TO REVIEW AND COORDINATE FINAL DUCT AND AIR DEVICE LOCATIONS. THE MECHANICAL 28. CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND ACCESSORIES SO THAT IT IS READILY ACCESSIBLE FOR SERVICING,
SUBCONTRACTOR'S FOREMAN IS TO ATTEND THIS MEETING AS WELL. TESTING, BALANCING AND REPLACEMENT.
9. NO CHANGES TO THE HVAC PLANS OR NOTES SHALL BE PERMITTED WITHOUI PROCALCS, LLC. PRIOR APPROVAL. 29. CONTRACTOR SHALL PROVIDE A WRITTEN GUARANTEE AGAINST DEFECTS INALL MATERIALS AND WORKMANSHIP FOR ONE
10. REFRIGERANT PIPING SHALL BE TYPE "L" SOFT DRAWN COPPER, ASTM B280,AND SHALL BE MILL CLEANED, DRIED AND (1) YEAR FROM ACCEPTANCE WITH FOUR ADDITIONAL YEARS OF WARRANTY ON COMPRESSORS.
CAPPED. INSULATE REFRIGERANT SUCTION LINE WITH " WALL FOAMED PLAS IC INSULATION SLIPPED OVER TUBING AND 30. PRIOR TO ACCEPTANCE BY THE OWNER, THE SYSTEMS SHALL BE TESTED AND BALANCED BY A AABC OR NEBB CERTIFIED
ALL JOINTS THOROUGHLY SEALED. PAINT REFRIGERANT PIPING INSULATION VMTH TWO (2) COATS OF ACRYLIC PROTECTIVE T&B CONTRACTOR EXPERIENCED WITH THIS SYSTEM. THE CONTRACTOR SHALL CERTIFY THE TESTING AND BALANCING
PAINT WHERE INSULATION IS EXPOSED TO WEATHER. WITHIN +/- 10% OF DESIGN CFMS AND PROVIDE BALANCE TEST SHEETS.
11. ALL FIBERGLASS DUCTWORK SHALL BE 1-1/2" FIBROUS GLASS ANTI -MICROBIAL DUCTBOARD INSTALLED IN ACCORDANCE 31. AIR BALANCE TO BE PERFORMED BY THE AIR CONDITIONING CONTRACTOR TO THE OWNER'S COMFORT. ALL SUPPLY AND
WITH THE LATEST EDITION OF S.M.A.C.N.A. FIBROUS GLASS DUCT CONSTRUCTION STANDARDS. 1" FIBROUS GLASS RETURN DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND LOCAL BUILDING CODES.
ANTI -MICROBIAL DUCTBOARD MAY BE USED IN THOSE LOCATIONS WHERE ALLOWED BY CODE. NO ABRUPT TRANSITIONS 32. PROVIDE ALL CONTROLS, STARTERS, CONTROL WIRING, DISCONNECTS, AND OTHER ELECTRICAL EQUIPMENT AS REQUIRED
SHALL BE PERMITTED. PROVIDE AIR TURNING VEINS IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS. FOR A COMPLETE AND OPERATIONAL SYSTEM. MECHANICAL CONTRACTOR IS TO COORDINATE WITH OTHER
12. FLEXIBLE DUCTWORK SHALL BE THERMAFLEX M-KA TYPE WITH 1-112" ONE -POUND DENSITY INSULATION AND VINYL VAPOR CONTRACTORS TO ENSURE THAT ALL ITEMS REQUIRED ARE INCLUDED IN
BARRIER OR ARCHITECT APPROVED SUBSTITUTE. NO ABRUPT TRANSITIONS HALL BE PERMITTED. 33. COORDINATE ALL POWER AND CONTROL WIRING WITH ELECTRICIAN.
13. DUCT SIZES SHOWN ARE INSIDE NET DIMENSIONS. 1
14. ALL AIR DEVICES SHALL BE MANUFACTURED BY TITUS, 250 SERIES, OR APPROVED SUBSTITUTE. COLOR TO BE APPROVED
BY THE PROFESSIONAL OF RECORD PRIOR TO PAINTING GRILLES BUT ASSUMED TO BE WHITE FOR BID/BUDGET PURPOSES.
SUPPLY AIR REGISTERS SHALL BE DOUBLE DEFLECTION TYPE WITH OPPOSED BLADE DAMPERS. ALL :;IZES AND PATTERNS
0
'We are the missing piece'
PO Box 882032
Port Saint Lucie, FL 34988
Phone: 772-882-5700
www.ProCalcs.Net
tom@procalcs.net
License CAC1815254
i
■
i
+
1
No. Revision/Issue =Date
1 Issue /3/2021
For:
Cooke Construction, Inc
1276 NE Business Park PL,
Jensen Beach, FL 34957
Drawn By: Sheet
ZWM
Checked By:
TP
Date:
2/3/2021
Scale:
As Shown
CN
lol
LJ
CONDENSING UNIT BOLTED TO
CONCRETE PAD TO WITHSTAND
HURRICANE FORCE WINDS. AS
PER FBCM 301.12
COND. UNIT
ISOMODE
a n
4" CONC. PAD `
4" CONCRETE SLAB. TOP OF
SLAB.
PAD (TYPICAL)
NOTE:
CONDENSING UNITS TO BE INSTALLED ABOVE FLOOD LEVEL CRITERIA.
CONDENSING UNIT MOUNTING DETAIL
1 1/2' MIN. —�
5TRAP HANGER
FLEXIBLE DUCT SAG
NOT TO EXCEED 1/2'
PER FOOT MAX=--�,
16 GA. HURRICANE \
STRAP
1/4" X 2" SELF -DRILLING \
SHEET METAL SCREW
3/8" X 2 112" QUICK -BOLT
EXPANSION ANCHOR.
(TYPICAL OF 4 ONE PER
CORNER OF UNIT)
n � /
NOTES:
1. ALLOW SUFFICIENT SPACE BELOW DRAIN
PAN FOR TRAP.
2. PITCH DRAIN FOR PROPER RUNOFF.
3. MANUALLY PRIME FILL TRAP BEFORE
START-UP TO FORM INITIAL DRAIN SEAL.
4. SUPPORT LENGTHY DRAIN LINES TO
PREVENT SAG AND CONDENSATE OVERFLOW.
THIS STANDARD DETAIL
MUST BE REVIEWED AND
SITE ADAPTED BY
CONTRACTOR PRIOR TO USE
FOR FINAL EQUIPMENT.
A/C UNIT CLEANOUT
(TYPICAL)
PITCH
? DRAIN PAN —'
DRAIN PIPE TO
MATCH DRAIN
OUTLET SIZE.
PITCH
(a) THIS DIMENSION IN INCHES MUST BE
EQUAL TO THE MAXIMUM FAN SUCTION
(NEGATIVE) STATIC PRESSURE IN INCHES WC
(WITH DIRTY FILTERS, COILS, AND MAXIMUM
AIR FLOW) + 1" W.C.
(b) THIS DIMENSION IN INCHES MUST BE
EQUAL TO MIN, 1/2 OF THE (a) ABOVE.
(c) EQUAL (a) + (b) + PIPE CIA. + INSULATION.
(d) TRAP SEAL SHALL BE 2" MIN. ON UNITS
LARGER THAN 3 TONS SHALL BE 3" MIN. PER
F.B.C.-4606.7 WHERE APPLICABLE.
(e) TRAP SEAL SHALL BE 2" MIN. TO 4" MAX.
PER S.B.C.C.I.-1002.4 WHERE APPLICABLE.
VENT LINE PERFORATED CAP. 1/2"
ABOVE BOTTOM OF DRAIN PAN
NTS DRAW THROUGH UNIT CONDENSATE TRAP
HANGER (TYPJ
2' MIN. SUPPORT STRAP
118" MAX. FROM DEVICE AND
5'-0" ON CENTER
WALL
NTS
FLEX
HEATER
SECTION
* RETURN AIR BROUGHT IN THROUGH SEALED PLENUM.
DUCT ) i MAXIMUM ALLOWABLE AIR
LENGTH OF FLEX. DUCT HANDLING
8'-01 UNIT * PLACE AIR HANDLING UNIT IN THE ROOM SO THAT
SERVICE TO THE UNIT & FILTER CAN BE
— — — — FLEX DUCT ACCOMPLISHED.
FASTENERS MAY BE
OMITTED IF HANGER
LOOPS UNDER DUCT. 20 GAUGE GALVANIZED DROP PAN
FASTENS MAINTAIN RADIUS OF BEND AIR UNDER
ENTIRE UNIT W/ MOISTURE
RETURN
TO NOT LE55 THAN ONS
DUCT DIAMETELGi DUCT PLENUM BOX FL
RIND RECTANGULAR DUCT OOR
DUCTWORK SUPPORT DETAILS NTS VERTICAL AHU DETAIL NTS
NOTEPROVIDE CABLE CONTROL DAMPER FOR HARD CEILING AREAS
LOCKING QUADRANT GALV. STEEL ROD OR
TO BE EXPOSED STRAP SUPPORTS PER
SMACNASTANDARDS
FLEXIBLE DUCT WITH SIDE TAKE -OFF FITTING
INSULATION & WITH DAMPER, BELL MOUTH
VAPOR BARRIER OR SHOETAP TYPE (SEE NOTE)
MAIN SUPPLY AIR
TIE TO DUCT, SEE PLANS FOR
STRUCTURAL TYPEANDI SULATION TURNING VANES MAIN TRUNK DUCT
SUPPORTS WITH SHEET METAL
— — SCREW FASTENERS / �I
2" WIDE METAL BAND ` \ ' ' ( Jy45° FLAREDJAP
PROVIDE CLASS 1 FLEX i ` v
SUPPORT INTO TRUNK D CT
DUCT TO DIFFUSERS /
L_ 1-1/2" X 1-1/2" X 118" GALV. C t
SQUARE TO ANGLE OR STRAP PER SMACNA (((( rr
ROUND I CONNECT INNER DUCT WITH DRAWBAND /lJ CIRCULAR DUC
FOR CONNECTION
ADAPTER AND SEAL WITH TAPE/MASTIC OUTERDUCT AIR FLOW
AT NECK CONNECTION LINEAR DIFFUSER TO FLEX DUCT
SSS
PLENUM BOX
PROVIDE THERMAL INSULATION BLANKET LINEAR DIFFUSER
IF INSTALLED IN UNCONDITIONED SPACE
CEILING
SUSPENDED TYPE LOUVERED FACE CEILING DIFFUSER
CEILING SYSTEM
TYPICAL DIFFUSER DETAIL NTS LINEAR DIFFUSER DETAIL
NTS
Signature can only be verified and
validated with electronic copy of
documents.
EQUIPMENT SCHEDULE
CU NUMBER
CU-1
CU-2
NOMINAL TONNAGE
4 ton(s)
2.5 ton(s)
H
MODEL
4A7L6048A1
4A7L6030A1
z
SEER/EER
15.30/13.00
15.50/13.00
O
CAPACITY TOTAL/SENS.
43824/36582
27004/23057
Z
STAGES
Single
Single
H
RLA - LRA
18.5 - 124
12.8 - 67.8
W
G
Z
O
Voltage
Phase
MCA/MOP
208/230 1XI
4601
208/230 1XI
460
Single 1XI
Three
I
I
Single 1XI
Three
24/40
17/25
V
WEIGHT
216
160
AHU NUMBER
AHU-1
AHU-2
AHU-MODEL
TEM6AOD48H41++TDR
TEM6AOB3OH21++TDR
STATIC PRESSURE
0.60
0.60
REFRIGERANT
R-41 OA
R-41 OA
LOCATION
Mech Closet
Mech Closet
CFM
1567
967
FAN MOTOR HP - FLA
3/4 - 6.8
1/3 - 2.8
W
J
ELECTRIC HEATER Voltage
Phase
kW
Model Number
MCA/MOP
208
1XI
230
1XI
4601
208 1XI
230
460
Single 1XI
Three
I
I
Single 1XI
Three
5.76 (208V) - 7,68 (240V)
3.60 (208V) - 4.80 (240V)
BAYHTR1508BRKC
BAYHTR1505BRKC
43/45 208V - 49/50 240V
25/25 208V - 29/30 230V
Z
DIMENSIONS H x W x D
55-3/4 x 23-1/2 x 21-1/8
46-3/4 x 18-1/2 x 21-1/8
a
WEIGHT
174
117
REF LINES SIZES
7/8, 3/8
3/4, 3/8
a
NOTES: American Standard
AHRI #: 10299034
AHRI #: 10225066
GRILLE SCHEDULE
Titus Series 250
Size
Velocity (FPM)
400
500
8 x 4
CFM
65
80
Throw (ft)
4-way
3-way
2-way
1-way
12
14
13
15
14
17
117
21
GRILLE SCHEDULE
Titus Series FL Linear
SDL-1
2 x 1" Slot
CFM/ft
50
75
Throw (ft)
20
25
SDL-2
2 x 1.5" Slot
CFM/ft
60
85
Throw
(ft)
22
27
TT 'c ®
'We are the missing piece'
PO Box 882032
Port Saint Lucie, FL 34988
Phone: 772-882-5700
www.ProCalcs.Net
tom@procalcs.net
License CAC1815254
`'I
o
Cl�
O
Mll
�
�
�
U
O
4-1
U
O
V1
o
�
No. Revision/Issue Date
1 Issue /3/2021
For:
Cooke Construction, Inc
1276 NE Business Park PL
Jensen Beach, FL 34957
C3�
By_ Sheet
Zwm
Checked By:
TIP DateM_3
:
2/3/2021
Scale:
As Shown
0
a�'M