HomeMy WebLinkAboutSprinkler Design Info Sheet—Fm�--! i Commercial ADT COMMERCIAL 3150 SW 42ND AVE. PALM CITY, FL. 34990 772.232.2001 Job Name 280607287 FP GOTO RESIDENCE Drawing NORTH REGENCY Location JENSEN BEACH Remote Area 1 Contract 280607287 Data File 280607287 FP GOTO RESIDENCE Area 1.WXF Ftlln�E COPY Computer Programs by Hydratec Inc. Revision: 50.54.4 ADT COMMERCIAL Page 1 280607287 FP GOTO RESIDENCE Date HYDRAULIC DESIGN. INFORMATION SHEET Name - 280607287 FP GOTO RESIDENCE Date - 03.12.2021 Location - JENSEN BEACH Building - NORTH REGENCY System No. - 1 Contractor - ADTC Contract No. - 280607287 Calculated By - JPC Drawing No. - FP1 Construction: ( ) Combustible ( ) Non -Combustible Ceiling Height OCCUPANCY - RESIDENTIAL S Type of Calculation: (X)NFPA 13 Residential ( )NFPA 13R ( )NFPA 13D Y Number of Sprinklers Flowing: ( )l ( )2 ( )4 ( ) S ( )Other T ( )Specific Ruling Made by Date E M Listed Flow at Start Point - 23 Gpm System Type Listed Pres. at Start Point - 15.7 Psi (X) Wet ( ) Dry D MAXIMUM LISTED SPACING 16 x 20 ( ) Deluge ( ) PreAction E Domestic Flow Added - Gpm Sprinkler or Nozzle S Additional Flow Added - 100 Gpm Make Model I Elevation at Highest Outlet - Feet Size K-Factor 5.8 G Note: Temperature Rating N Calculation Gpm Required 201.437 Psi Required 85.291 At Test Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - Rated Cap. 1000 Cap. T Time of Test - @ Psi 170 Elev. E Static (Psi) - Elev. 0 R Residual (Psi) - Other Well Flow (Gpm) - Proof Flow Gpm S Elevation - P Location: P L Source of Information: PRO TECH PUMP TEST Y Computer Programs by Hydratec Inc. Revision: 50.54.4 Water Supply Curve ADT COMMERCIAL Page 2 280607287 FP GOTO,RESIDENCE Date Pump Data: Demand: P1 - Pump Churn Pressure 203 D1 - Elevation 38.546 P2 - Pump Rated. Pressure 170 D2 - System Flow : 101.437 P2 -Pump Flow 1000 D2 -System Pressure 85.291- , P3 - Pump Pressure @ Max Flow 110.5 Hose,( (Demand) : 100 P3 - Pump Max Flow 1500 D3 - System Demand : 201.437 Safety Margin : 117.305 210 _ 196 182 P2 P 168 R 154 E 140 S 126 3 S 112 U 98 D2 R 84 E 70 56 42 D1 28 14 200 400 '600 800 1000 1200 1400 1600 1800 FLOW ( N " 1.85 ) Computer Programs by Hydratec Inc. Revision: 50.54.4 ADT COMMERCIAL Page 3 280607287 FP GOTO RESIDENCE Date 23 23 50.7 50.7 101.4 201.4 101 E- 102 F 103 E- 104 <- 105 F 106 F 107 E- 108 E- 109 E- 110 F 111 F PUMP 23 50.7 50.7 50.7 101.4 24.7 112 <- 113 f- 109 50.8 26.1 26.1 114 E- 115 E- 116 E- 113 26.1 27.7 117 E- 104 Computer Programs by Hydratec Inc. Revision: 50.54.4 Fittings Used Summary i j ADT COMMERCIAL Page 4 280607287 FP GOTO RESIDENCE Date Fitting Legend Abbrev. Name 1/2'/ 1 14 1'/2 2 2'/z 3 3'/z 4 5 6 8 10 12 14 16 18 20 24 I B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9_ 10 12 19 21 0 0 0 0 0 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14. 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VS Fitting generates a Fixed Loss Based on Flow T NFPA 13 90' Flow thru Tee 3. 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 1 i } } l j :i Units Summary .i Diameter Units Inches i Length Units Feet Flow Units US Gallons per Minute - Pressure Units Pounds per Square Inch ,y {Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. I Equivalent lengths shown are standard -for actual diameters of Sched 40 pipe rand CFactors of 120 except as noted with *. The fittings- marked with a * show equivalentlengths values supplied by manufacturers based on specific pipe diameters and -CFactors and they require no adjustment. All values for. fittings. not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. i 1 I Computer Programs by Hydratec Inc. Revision: 50.54.4 i i i ADT COMMERCIAL Page 5 280607287 FP GOTO RESIDENCE, Date SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure PUMP See Information on Pump Curve 202.596 201.44 85.291 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes 101 89.0 5.8 15.7 22.98 0.1 1 102 89.0 23.06 103 89.0 23.31 104 89.0 23.66 105 89.0 27.15 106 89.0 27.99 107 89.0 30.44 108 89.0 31.05 109 89.0 31.61 110 89.0 39.19 ill 89.0 45.0 100.0 PUMP 0.0 85.29 112 89.0 5.8 18.14 24.7 0.1 1 113 89.0 21.8 114 89.0 5.8 20.21 26.08 0.1 1 115 89.0 21.06 116 89.0 21.42 117 89.0 5.8 22.77 27.67 0.1 1 Computer Programs by Hydratec Inc. Revision: 50.54.4 ADT COMMERCIAL Page 6 280607287 FP GOTO RESIDENCE Date Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ***""** Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 101 89 5.80 22.98 0.75 2E 8.053 11.080 150 15.700 to T 8.653 16.104 0.0 102 89 22.98 0.874 27.184 0.2709 7.363 Vel = 12.29 102 89 0.0 1 2.760 150 23.063 to 0.0 103 89 22.98 1.101 2.780 0.0880 0.243 Vel = 7.74 103 89 0.0 1.25 T 9.523 3.170 150 23.306 to 9.523 0.0 104 89 22.98 1.394 12.693 0.0279 0.354 Vel = 4.83 104 89 27.68 1.25 T 9.523 14.730 150 23.660 to E 4.762 14.284 0.0 105 89 50.66 1.394 29.014. 0.1203 3.491 Vel = 10.65 105 89 0.0 1.25 7.000 150 27.151 to 0.0 106 89 50.66 1.394 7.000 0.1204 0.843 Vel = 10.65 106 89 0.0 1.25 2E 9.523 10.830 150 27.994 to 9.523 0.0 107 89 50.66 1.394 20.353 0.1203 2.449 Vel = 10.65 107 89 0.0 1.25 5.050 150 30.443 to 0.0 108 89 50.66 1.394 5.050 0.1202 0.607 Vel = 10.65 108 89 0.0 1.25 4.680 150 31.050 to 0.0 109 89 50.66 1.394 4.680 0.1203 0.563 Vel = 10.65 109 89 50.78 1.25 E 4.762 3.150 150 31.613 to T 9.523 14.284 0.0 110 89 101.44 1.394 17.434 0.4348 7.580 Vel = 21.32 11.0 89 0.0 2 E 6.153 10.000 120' 39.193 to Fsp 0.0 25.844 3.000 * * Fixed Loss = 3 111 89 101.44 2.157 B 7.384 35.844 0.0784 2.810 Vel = 8.91 T 12.307 111 89 H100 100.00 6 5E 88.0141081.000 120 45.003 to T 37.72 125.734 38.546 PUMP 0 201.44 6.357 . 1206.734 0.0014 1.742 Vel = 2.04 0.0 PUMP 201,.44 85.291 K Factor = 21.81 System Demand Pressure 85.291 Safety Margin 117.305 Continuation Pressure 202.596 112 89 5.80 24.70 0.75 T 8.053 3.750 150 18.143 to 8:052 0..0 113 89 24.7 0.874 11.802 0.3096 3.654 Vel = 13.21 113 89 26.08 1-.25 2T 19.046 43.110 150 21.797 to 4E 19.046 38.094 0.0 109 89 50.78 1.394 81.204 0.1209 9.816 Vel = 10.67 0.0 109 50.78 31.613 K Factor -= 9.03 114 89 5.80 26.08 1 E 3.825 3.750 150 20.213 to 3.825 0.0 115 89 26.08 1.101 7.575 0.1112 0.842 Vel = 8.79 Computer Programs by Hydratec Inc. Revision: 50.54.4 ADT COMMERCIAL Page 7 280607287 FP GOTO RESIDENCE Date Node1 Elev1 K Qa N.om Fitting Pipe CFact Pt to or Ftngs Pe *"***** Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 115 89 0.0 1 3.280 150 21.055 to 0.0 116 89 26.08 1.101 3.280 0.1113 0.365 Vel = 8.79 116 89 0.0 1.25 10.720 150 21.420 to 0.0 113 89 26.08 1.394 10.720 0.0352 0.377 Vel = 5.48 0.0 113 26.08 21.797 K Factor = 5.59 117 89 5.80 27.67 0.75 2.340 150 22.766 to 0.0 104 89 27.67 0.874 2.340 0.3821 0.894 Vel = 14.80 0.0 104 27.67 23.660 K Factor = 5.69 Computer Programs by Hydratec Inc. Revision: 50.54.4 tyco. Worldwide wwwtyco-fire.com Contacts RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Pendent and Recessed Pendent Wet Pipe Systems General Description The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY3934) are dec- orative, fast response, frangible bulb sprinklers designed for use in residen- tial occupancies such as homes, apart- ments, dormitories, and hotels. When aesthetics and optimized flow charac- teristics are the major consideration, the Series LFII Residential Sprinklers (TY3934) should be the first choice. The Series LFII Residential Sprinklers are intended for use in the following scenarios: • wet pipe residential sprinkler sys- tems'for one- and two-family dwell- ings and mobile homes per NFPA 13D • wet pipe residential sprinkler sys- tems for residential occupancies up to and including four stories in height per NFPA 13R • wet pipe sprinkler systems for the residential portions of any occu- pancy per NFPA 13 The recessed version of the Series LFII Residential Sprinklers is intended for use in areas with finished ceil- ings. It employs a two-piece Style 20 Recessed Escutcheon. The Recessed Escutcheon provides 1/4 in. @,4 mm) of recessed,adjustment or up to 1/2 in. (12,7 mm) of total adjustment from the flush ceiling position. The adjustment IMPORTANT Refer to ,Technical Data Sheet TFP2300 for warnings pertaining to regulatory'and health information. Always refer to Technical Data Sheet TFP700 for the `INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nerits and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. . Page 1 of 4 provided by the Recessed Escutcheon reduces the accuracy to which the pipe drops to the sprinklers must be cut. The Series LFII Residential Sprinklers have been designed with heat sensi- tivity and water distribution charac- teristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Corrosion -resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo- spheres. Although corrosion -resistant coated sprinklers have passed the standard corrosion tests of the appli- cable Approval agencies, the testing is not representative of all possible cor- rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit- ability of these coatings for any given corrosive. environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity should be considered, as a minimum, along. with the corrosive nature of the chemical to which the sprinklers will be exposed. The Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY3934) described herein must be installed and maintained in compliance with this doc- ument and the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. DECEMBER 2018 Sprinkler Identification Number (SIN) TY3934 TFP401 TFP401 Page 2 of 4 Components: 1 - Frame 2 - Button 3 - Sealing 1 Assembly 4 - Bulb 3 5 - Compression Screw 2 6 - Deflector* 4 * Temperature 5 rating is indicated 6, on Deflector Technical Data ESCUTCHEON PLATE 1/2" 7/16" (11,1 mm) SEATING SURFACE NPT NOMINAL MAKE -IN 2" it . (50,8 mm) Fr 1-3/8" (34,9 mm) WR FI DEFLECTOR * CROSS SECTION PENDENT STYLE 20 RECESSED ESCUTCHEON 2-7/8" (73,0 mm) DIA. RECESSED PENDENT FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY3934) Approvals UL and C-UL Listed Certified to all requirements of NSF/ANSI 61 Note: Sprinklers with a polyester finish are UL Listed as corrosion -resistant sprinklers. Discharge Coefficient K = 5.8 GPM/psi'/2 (83,5 LPM/bar/) Temperature Rating 1550F (68°C) or 175OF (79°C) Finishes Natural Brass, Pure White Polyester Coated, Signal White Polyester Coated, Jet Black Polyester Coated, or Chrome Plated Physical Characteristics Frame ...... .......................Brass Button............................Bronze Sealing Assembly.. Beryllium Nickel w/TEFLON Bulb (3 mm)........................ Glass Compression Screw .................. Brass Deflector...........................Brass Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and flow water. Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY3934) are to be installed in accordance with this section. Residential Sprinkler Design Guide When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufactur- er's recommendations that may be acceptable to the local authority having jurisdiction. Ceiling Types Smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the minimum required sprin- kler flow rates are given in Table A as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum, required discharge from each of the total number of design sprinklers as specified in NFPA 13D, or NFPA 13R. The number of design sprinklers speci- fied in NFPA 13D and 13R for wet pipe systems is to be applied when design- ing dry pipe systems. Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis- charge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Table A as a function of temperature rating and the maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ft2 over the design area comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers. Obstruction to Water Distribution Sprinklers are to be located in accor- dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational Sensitivity Sprinklers are to be installed with a deflector -to -ceiling distance of 1 in. to 4 in. below smooth ceilings. For Beamed Ceiling .conditions as allowed by NFPA, the maximum deflec- tor distance below the bottom of a beam is 1-3/4 in. Refer to the NFPA Standards for allowed beam configurations. Sprinkler Spacing The minimum spacing between sprin- klers is 8 ft (2,4 m), The maximum spacing between sprinklers cannot exceed the length of the coverage area (Table A) being hydraulically calculated (for example, maximum 12 ft for a 12 ft x 12 ft coverage area, or 20 ft for a 20 ft x 20 ft coverage area). TFP401 Page 3 of 4 WET PIPE SYSTEM Minimum Flow and Residual Pressure(b, c) Max. Coveragge ordinary Temp. Rating Intermediate Temp. Rating Area (a). 155-F (68-C) 175-F (79-C) Minimum Deflector to Installation Spacing Flow Pressure Flow Pressure ft x ft Ceiling Type ft (m x m) gpm psi gpm psi (m) (Ipm) (bar) (Ipm) (bar) 12 x 12 16 7.6 16 7.6 Smooth (3,7 x 3,7) (60,6) (0,52) (60,6) (0152) Ceilings 1 in. to 4 in. Beamed Recessed Sle Escu heon2or 8 14x14 (4,3 x 4,3) 16 (60,6) 7.6 (0,52) 16 (60,6) 7.6 (0,52) 16 x 16 16 7.6 .16 7.6 (4,9 x 4,9) (60,6) (0,52) (60,6) (0,52) Ceilings per NFPA 13D or13R non -recessed per NFPA 13D, 13R,or13 (2,4) 18x18 18 9.6 18 9.6 (515 x 5,5) (68,1) (0,66) (68,1) (0,66) 1 in. to 1-3/4 in. below bottom 20 x 20 20 F 11.9 20 11.9 (6,1 x 6,1) (75,7) 1 (0,82) (75,7) (0,82) of beam. Notes: a. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic Design under the Design Criteria section. c. For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY3934) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA 2-7/8" DIA. (73,0 mm) FACE OF SPRINKLER 2-1/4" DIA. FITTING (57,2 mm) 5/16±1/4" 1/2" (12,7 mm) (7,9±6,4 mm) FLUSH i MOUNTING 1/8" SURFACE (3,2 mm) CLOSURE TY3934 MOUNTING 1-3/8" (34,9 mm) PLATE 7/8" (22,2 mm) FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER (TY3934) Installation The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY3934) must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm). A leak -tight 1/2 in. NPT sprinkler joint should' be obtained by applying a minimum -to -maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N-m). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutch- eon Plate by under- or over- tightening the sprinkler. Re -adjust the position of the sprinkler fitting to suit. / WRENCH RECESS (USE ONLY END "A") FIGURE 3 W-TYPE 6 SPRINKLER WRENCH WRENCH RECESS t PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 4 W-TYPE 7 RECESSED SPRINKLER WRENCH TFP401 Page 4 of 4 Series LFII Residential: Pendent Sprinkler Installation The Series LFII Residential Pendent Sprinklers must be installed in accor- dance with the following instructions. Step 1. Install pendent sprinklers in the pendent position with the deflector par- allel to the ceiling. Step 2. With pipe thread sealant applied to the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the .sprinkler fitting using only the W Type 6 Sprinkler Wrench (Figure 3). With ref- erence to Figure 1, apply the W-Type 6 Sprinkler Wrench to the wrench flats. Series LFII Residential Recessed Pendent Sprinkler Installation The Series LFII Residential Recessed Pendent Sprinklers must be installed in accordance with the following instructions. Step A. Install recessed pendent sprin- klers in the pendent position with the deflector parallel to the ceiling. Step B. After installing the Style 20 Mounting Plate over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. Step C. Tighten the sprinkler into the sprinkler fitting using only the W Type 7 Recessed Sprinkler Wrench (Figure 4). With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Step D. After the ceiling has been installed or the finish coat has been applied, slide on the Style 20 Closure over the Series LFII Residential Sprin- kler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. Care and Maintenance The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY3934) must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non - operation in the event of a fire or inad- vertent operation may result. Sprinklers which are found to be leaking or exhibiting. visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the, sprinklers - before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. See the Installation Section. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, for example, NFPA 25, in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or product manufacturer regarding any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assembly Specify: Series LFII (TY3934), K = 5.8, Residential Pendent Sprinkler, (specify) temperature rating, (specify) finish, P/N (specify): 155oF(6B°C) Natural Brass ................. 51-058-1-155 Pure White (RAL 9010) Polyesters. 2 .................. 51-058-3-155 Signal White (RAL 9003) Polyesters .................... 51-058-4-155 Jet Black (RAL 9005) Polyesters .................... 51-058-5-155 Chrome Plated ................51-058-9-155 175eF(79oC) Natural Brass ................. 51-058-1-175 Pure White (RAL 9010) Polyesters. 2 .................. 51-058-3-175 Signal White (RAL 9003) Polyesters....................51-058-4-175 Jet Black (RAL 9005) Polyesters .................... 51-058-5-175 Chrome Plated ................51-058-9-175 1. UL Listed as corrosion -resistant. 2. Eastern Hemisphere sales only. Recessed Escutcheon Specify: Style 20 Recessed Escutch- eon with (specify') finish, P/N (specify*) 'Referto Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 1400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700 02019 Johnson controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION a,d NFPA are registered traderaarlm of National Fire Prolecii-Association; TEFLON is a registered mrdemedt of OuPmd Johnson 41t, Controls tyco Worldwide I www.tyco-fire.com Contacts RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 3 Optimi- d Wet Pipe Systems General Description The TYCO RAPID RESPONSE Series LFII (TY4334) Residential Horizontal Sidewall Sprinklers are decorative, fast response, frangible bulb sprin- klers designed for use in residential occupancies such as homes, apart- ments, dormitories, and hotels. When enhanced flow characteristics for resi- dential portions of any occupancy per NFPA 13 is the major consideration, the Series LFII (TY4334) should be the first choice. When higher flow demands are required for residential sprinklers used in an NFPA 13 design, the large 5.8 K-factor of the Series. LFII (TY4334) is an attractive choice. Although mostly intended where residential sprinklers are to be used, in an NFPA 13 design, the Series LFII (TY4334) can also be used in wet pipe residential sprin- kler systems for one- and two-family dwellings and mobile homes per NFPA 13D,, and wet pipe residential sprinkler systems for'residential occupancies up to and including four stories in height per NFPA 13R. The recessed version of the Series LFII (TY4334) is'intended for use in areas with finished walls. It employs a two- piece Style 20 Recessed Escutcheon. The Recessed Escutcheon provides 1/4 in. (6,4mm) of recessedadjustment or up to 1/2 in. (12,7 mm) of total adjust- ment from the flush mounting surface IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to. Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation'can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe nipples to the sprinklers must be cut. The Series LFII (TY4334) has been designed with heat sensitivity and water distribution characteristics proven to help in the control of residen- tial fires and to improve the chance for occupants to escape or be evacuated. Corrosion -resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo- spheres. Although corrosion -resistant coated sprinklers have passed the standard corrosion tests of the appli- cable Approval agencies, the testing is not representative of all possible cor- rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit- ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity should be considered, as a minimum, along with the corrosive nature of the chemical to. which the sprinklers will be exposed. The Series LFII (TY4334), Residen- tial Horizontal Sidewall Sprinklers described herein must be installed and maintained in compliance with this document, as .well as with the applica- ble standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. MARCH 2O19 NSF® Sprinkler Identification Number (SIN) TY4334 TFP417 TFP417 Page 2 of 6 Components: 7 WRENCH 1 - Frame FLATS WRENCH 2- Button FLATS 3 - Sealing O Assembly TOP -OF- a 1/2" NPT 4- Bulb DEFLECTOR 5 - Compression 7/16" (11,1 mm) Screw NOMINAL 7 6- Deflector* 6* 5 4 3 I r MAKE -IN 7 - Ejection Spring \ \ E7�� * Temperature rating is indicated on top of Deflector. 3/8� 1 — — STYLE 20 --- RECESSED ` (9,5 mm) 1 5/8" \ ESCUTCHEON END -OF- (41,3 mm) ESCUTCHEON DEFLECTOR 2-1/4" PLATE SEATING CENTERLINE OF WATERWAY BOSS (57,2 mm) SURFACE RECESSED FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL. SIDEWALL SPRINKLERS (TY4334) 7/16t1/8" (11,1t3,2 mm) MOUNTING FACE OF SURFACE SPRINKLER FITTING CLOSURE TOP -OF - DEFLECTOR TY4334 JJ \� 2-7/8" DIA. (73,0 mm) 2-1/4" DIA. (57,2 mm) 3/8" (9,5 mm) MOUNTING PLATE END -OF - DEFLECTOR 1/8" BOSS (3,2 mm) 1-3/8" (34,9 mm) 1/2" (12,7 mm) 1-1/8" (28,6 mm) 1/4" (6,4 mm) FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE RAPID`RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER (TY4334) 2-7/8" DIA. (73,0 mm) / WRENCH RECESS (END "A" USED FOR TY4334) FIGURE 3 W-TYPE 6 SPRINKLER WRENCH WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 4 W-TYPE 7RECESSED SPRINKLER WRENCH TFP417 Page 3 of 6 Technical Data Approvals: UL and C-UL Listed FM Approved Certified to all requirements of NSF/ANSI 61 Note: Sprinklers with a polyester finish are UL Listed as corrosion -resistant sprinklers. See the Design Criteria section for details on these approvals. Maximum Working Pressure: 175 psi (12,1 bar) Discharge Coefficient: K = 5.8 GPM/psi" (83,5 LPM/bar") Temperature Rating: 155T (68°C) or 175°F (79°C) Finishes: Natural Brass, Signal White Polyester Coated, or Chrome Plated Physical Characteristics: Frame .............................Brass Button............................Bronze Sealing Assembly.. Beryllium Nickel w/TEFLON Bulb ...................... 3 mm dia. Glass Compression Screw .................Bronze Deflector...........................Brass Ejection Spring .............. Stainless Steel Operation The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria UL AND C-UL LISTING CRITERIA The TYCO RAPID RESPONSE Series LFII (TY4334) Residential Horizontal Sidewall Sprinklers are UL and C-UL Listed for installation in accordance with this section. Residential Sprinkler Design Guide When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufactur- er's recommendations that may be acceptable.to the local authority having jurisdiction. System Type Only wet pipe systems may be utilized. Ceiling Types Smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the minimum required sprin- kler flow rate are given in Table A as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of design sprinklers as specified in NFPA 13D or NFPA 13R. Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis- charge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Table A as a function of temperature rating and the Maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ft2 over the design area comprised of the four most hydraulically demand- ing sprinklers for the actual coverage areas being protected by the four sprinklers. Example No. 1: A corridor being pro- tected is 8 ft wide; consequently, an actual coverage area of 8 ft x 20 ft is being contemplated. Based on using the LFII (TY4334) Residential Horizontal Sidewall Sprinklers, the flow rate pro- vided in Table A for a 16 ft x 20 ft cover- age area is 29 gpm. However based on minimum discharge of 0.1 gpm/ft2 the flow rate would be 16 gpm. In this case a minimum flow rate of 29 gpm for this design sprinkler must be utilized. Example No. 2: The room being pro- tected is 16 ft x 16 ft. Based on using the LFII (TY4334) Residential Horizontal Sidewall Sprinklers, the. flow rate pro- vided in Table A for a 16 ft x 16 ft cover - ace area is 21 gpm. However based on minimum discharge of 0.1 gpm/ftz the flow rate would be 26 gpm. In this case a minimum flow rate of 26 gpm for this design sprinkler must be utilized. Obstruction To Water Distribution Sprinklers are to be located in accor- dance with the obstruction rules of NFPA 13D, 13R, and 13 as applica- ble for residential sprinklers as well as with the obstruction criteria described. within the TYCO Technical Data Sheet TFP490. Operational Sensitivity The sprinklers are to be installed with an end -of -deflector -boss to wall distance of 1-1/4 in. to 6 in. In addition the top -of -deflector -to - ceiling distance is to be within the range (see Table A) being hydraulically calculated. Sprinkler Spacing The minimum spacing between sprin- klers is 8 ft (2,4 m). The maximum spacing between sprinklers cannot exceed the width of the coverage area (see Table A) being hydraulically calcu- lated (for example, maximum 12 ft for a 12 ft x 12 ft coverage area, or 16 ft for a 16 ft x 20 ft coverage area). FM APPROVAL CRITERIA The Series LFII (TY4334) Residential Horizontal Sidewall Sprinklers are FM Approved for installation in accordance with the applicable Factory Mutual Loss Prevention Data Sheet FM 2-5. Criteria provided by FM may differ for UL and/or NFPA, therefore the designer should review and become familiar with Factory Mutual requirements before proceeding with design. The following information pertaining to System Type, Hydraulic Design, and Sprinkler spacing are provided for ref- erence and are not intended to provide complete installation criteria as pro- vided in the applicable Factory Mutual Loss Prevention Data Sheet. Residential Sprinkler Design Guide When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufactur- er's recommendations that may be acceptable to the local authority having jurisdiction. System Type Only wet pipe systems may be utilized. Hydraulic Design The number of design sprinklers is to be the four most hydraulically demand- ing sprinklers. The minimum required discharge from each of the four sprin- klers is to be greater than the following: • The flow rates given in Table B as a function of the maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ft2 over the design area comprised of the four most hydraulically demand- ing sprinklers for the actual coverage areas being protected by the four sprinklers. Example No. 1: A corridor being pro- tected is 10 ft wide; LFII Sidewall Sprin- klers_ are being installed at 16 ft apart along the corridor. Consequently, an actual coverage area of 10 ft x 16 ft is being contemplated. Based on using the LFII (TY4334) Residential Horizontal Sidewall Sprinklers, the flow rate pro- vided in Table B for a 16 ft x 20 ft cover- age area is 32 gpm. However based on minimum discharge of 0.1 gpm/ft2 the flow rate would be 16 gpm. In this case a minimum flow rate of 24 gpm for this design sprinkler must be utilized. TFP417 Page 4 of '6 WET PIPE SYSTEM Max. Coverage Max. Minimum Flow and Residual Pressure(',.) - Ordinary Temp. Rating Temp. Rating InHPM Area (e) Spacing Width x Length c� (m) 155-F (68-C) (79°C) Deflector Installation Minimum Spacing Flow Pressure Pressure ft x ft to Ceiling Type ft (m x m) GPM PSI PSI (m) L/min bar bar 12 x 12 12 19 10.7 19 10.7 (317 x 3,7) (3,7) (71,9) (0,74) (71,9) (0,74) 14 x 14 14 21 13.1 21 13.1 (4,3 x 4,3) (4,3) (79,5) (0,90) (79,5) (0,90) 16 x 1.4 16 21 13.1 21 13.1 (4,9 x 4,3) (4,9) (79,5) (0,90) (79,5) (0,90) Recessed usinSle 16 x 16 16 21 13.1 21 13.1 Escut heon2or (4,9 x 4,9) (4,9) (79,5)) (0,90) (79,5)) (0,90) 4 in. to 6 in. non -recessed per NFPA 13D, 16 x 18 16 23 15.7 23 15.7 13R, or 13 (4,9 x 5,5) (4,9) (87,1) (1,08) (87,1) (1,08) 16 x 20 16 29 25.0 29 25.0 (4,9 x 6,1) (4,9) (109,8) (1,72) (109,8) (1,72) 18 x 18 18 29 25.0 29 25.0 (5,5 x 5,5) (5,5) (109,8) (1,72) (109,8) (1,72) 16 x 22 16 38 42.9 38 42.9 Non -recessed per NFPA 13D, (4,9 x 6,7) (4,9) (143,8) (2,96) (143,8) (2,96) 13R,or13 8 12 x 12 12 19 10.7 19 10.7 (2,4) (3,7 x 3,7) (3,7) (71,9) (0,74) (71,9) (0,74) 14 x 14 14 23 15.7 23 15.7 (4,3 x 4,3) (4,3) (87,1) (1,08) (87,1) (1108) 16 x 14 16 23 15.7 23 15.7 (4,9 x 4,3) (4,9) (87,1) (1,08) (87,1) (1,08) Recessed usin16 x 16 16 23 15.7 23 15.7 Escut heon or (4,9 x 4,9) (4,9) (87,1) (1,08) (87,1) (1,018) 6 in. to 12 in non -recessed per NFPA 13D, 16 x 18 16 24, 17.1 24 17.1 13R, or 13 (4,9 x 5,5) (4,9) (90,8) (1,18) (90,8) (1,18) 16 x 20 16 30 26.8. 30 26.8. (4,9 x 6,1) (4,9) (113,6) (1,85) (113,6) (1,85) 18 x 18 18 30 26.8. 30 26.8. (5,5 x 5,5) (5,5) (113,6) (1,85) (113,6) (1,85) 16 x 22 16 40 47.6 40 47.6 Non -recessed per NFPA 13D, (4,9 x 6,7) (4,9) (151,4) (3,28) (151,4) (3,28) 13ii,.or 13 Notes: a. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic Design under the,Design Criteria section. c. For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used. d. The Width x Length dimension refers to the Width (backwall where the sprinkler is located) times the Length (horizontal throw of sprinkler). TABLE A WET PIPE SYSTEM UL AND C-UL LISTED SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY4334) NFPA 13D, 130, AND 13 HYDRAULIC DESIGN CRITERIA TFP417 Page 5 of 6 WET PIPE SYSTEM Max. Coverage Minimum Flow and Residual Pressure (b.°I Area(.) Max. Spacing Ordinary Temp. Rating Intermediate Temp. Rating Width x Length(d) ft 155°F ( 68°C) ( 175°F 79'C) Deflector Minimum ftx ft (m) Installation Spacing Flow Pressure Flow M Pressure (b) (m x m) ceiling Type ft GPM PSI GPM Pst (m) L/min bar (L/min) (bar) 12 x 12 12 22 14.4 22 14.4 (3,7 x 3,7) (3,7) (83,3) (0,99) (83,3) (0,99) 14 x 14 14 22 14.4 22 14.4 (4,3 x 4,3) (4,3) (83,3) (0,99) (83,3) (0,99) 16 x 16 16 24 17.1 24 17.1 (4,9 x 4,9) (4,9) (90,8) (1,18) (90,8) (1,18) Recessed 4 in. to 12 in. using Style 20 Escutcheon or non -recessed 8 (2,4) 16 x 18 16 28 23.3 28 23.3 (4,9 x 5,5) (4,9) (106,0) (1,61) (106,0) (1,61) 16 x 20 16 32 30.4 32 30.4 (4,9 x 6,1) (4,9) (121,0) (2,10) (121,0) (2,10) 18 x 18 18 33 32.4 33 32.4 (5,5 x 5,5) (5,5) (125,0) (2,23) (125,0) (2,23) Notes: a. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic Design under the -Design Criteria section. c. For FM residential applications, the greater of 0.1 gpm/ftz over the design area (i.e., SxQ or the flow in accordance with the criteria in this table must be used. d. The Width x Length dimension refers to the Width (backwall where the sprinkler is located) times the Length (horizontal throw of sprinkler). TABLE B WET PIPE SYSTEM FM APPROVED SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS (TY4334) HYDRAULIC DESIGN CRITERIA Example No. 2: The room being pro- tected is 16 ft x 16 ft. Based on using the LFII (TY4334) Residential Horizontal Sidewall Sprinklers, the, flow rate pro- vided in Table B for ar 16 ft x 16 ft cover- age area is 24 gpm. However based on minimum discharge of 0.1 gpm/ftz the flow rate would be 26 gpm. In this case a minimum flow rate of 26 gpm for this design sprinkler must be utilized (in no case shall the design pressure be less than-7 psi). Sprinkler Spacing The minimum spacing between sprin- klers is 8, ft (2,4.m). The maximum spacing, between sprinklers cannot exceed the width' of the coverage area (see Table B) being hydraulically calcu- lated (for example, maximum 12 ft for 12 ft x 12 ft coverage area, or 16 ft for a 16 ft x 20 ft coverage area). Installation The TYCO RAPID RESPONSE Series LFII (TY4334) Residential Hori- zontal and Recessed Horizontal Side - wall Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present The diameter of the air bubble is approximately 1/16 in. (1,6 mm). A leak -tight 1/2 in. NPT sprinkler joint should be obtained with a minimum to maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N•m). Higher levels of torque may distort the sprinkler inlet with conse- quent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutch- eon Plate by under- or over -tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. Series LFII Residential Horizontal Sidewall Sprinklers The Series LFII Horizontal Sidewall Sprinklers must be installed in accor- dance with the following instructions. Step 1. Horizontal sidewall sprinklers are `to be installed in the horizontal position with their centerline of water- way perpendicular to the back wall and parallel to the ceiling. The word "TOP" on the Deflector is to face towards the ceiling with the front edge of the Deflector parallel to the ceiling. Step 2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the. sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (see Figure 3). With reference to Figure 1, the W Type 6 Sprinkler Wrench is to be applied to the wrench flats. Series LFII Residential Recessed Horizontal Sidewall Sprinklers The Series LFII Recessed Horizontal Sidewall Sprinklers must be installed in accordance with the following instructions. Step A. Recessed horizontal sidewall sprinklers are to be installed in the hori- zontal position with their centerline of waterway perpendicular to the back wall and parallel to the ceiling. The Word. "TOP" on the Deflector is to face towards the ceiling. TFP417 Page 6of6 Step B. After installing the Style 20 Mounting Plate over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step C. Tighten the sprinkler into the sprinkler fitting using only the W Type 7 Recessed Sprinkler Wrench (see Figure 4). With reference to Figure 1, the W-Type 7 Recessed Sprin- kler Wrench is to be applied to the sprinkler wrench flats. Step D. After the wall has been installed or the finish coat has been applied, slide on the Style 20 Closure over the Series LFII Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the wall. Care and Maintenance The TYCO RAPID RESPONSE Series LFII (TY4334) Residential Hori- zontal and Recessed Horizontal Side - wall Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system which it controls; permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Absence of an Escutcheon Plate may delay the sprinkler operation in a fire situation. The owner must assure that the sprin- klers'are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non - operation in the event of a fire or inad- vertent operation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi- fied sprinklers must be replaced to corrosive products of combustion, but have not operated, should be replaced if they can not be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers- before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. See the Installation section for additional information. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, for example, NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national code. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure When placing an order, indicate the full product name. Contact your local dis- tributor for availability. Sprinkler Assembly Specify: Series LFII (TY4334), K=5.8, Residential Horizontal Sidewall Sprin- kler, (specify) temperature rating, (specify) finish, P/N (specify). 155eF(68°C) Natural Brass ................. 51-534-1-155 Signal White (RAL9003) Polyester' .................... 51-534-4-155 Chrome Plated................51-534-9-155 175eF(79eC) Natural Brass ................. 51-534-1-175 Signal White (RAL9003) Polyester' .................... 51-534-4-175 Chrome Plated ................ 51-534-9-175 1. UL Listed as corrosion -resistant. Recessed Escutcheon Specify: Style 20 Recessed Escutcheon with (specify*) finish, P/N (specify*). 'Refer to Technical Data Sheet TFP770. Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 1400 Pennbrook Parkway, Lansdale, PA 19446 I Telephone +1-215-362-0700 L AN®201gJohnson Controls. All rights resemed.All apecificationsand otherinformation shown were currentas of document revision dateand are subjectto change without notice. JJohnsonn sI NATIONAL FIRE PROTECTION ASSOCIATION and NFPA ere registered trademarks of N,Vonal Flre Protection Association; Cots TEFLON Is a registered trademark of OuPord Controls 1^tro