DATE: 5/20/21
Phone: 954-784-2941
.875
.
..
Environmental I Geotechnical I Materials Testing Roof Testing Inspections GPR
CLIENT: Cardinal Roofing and Siding of Florida
Order No
21R0417
ADDRESS: 1601 S.E. South Niemeva Circle: Port St Lucie, FL 34990
PROJECT: Roesemann Residence
ADDRESS: 11100 Lando End Chase; Port St. Lucie, FL 34986
ASCE 7-16 DESIGN PRESSURE CALCULATIONS RECEIVED
In Accordance with Chapter 30, Part I JUN 0 1 1011
Permitting Department
Project Information: Sloped Wood Deck Roof St. Lucie County
Height = 20' Exposure: C
Length = 75' Category: H
Width = 37' Slope: 6:12
Design Calculations:
Ultimate Windspeed: Vint= 170 mph
Basic Windspeed: Veld = 132 mph
Kt= 0.90 Kd=0.85
Velocity Pressure: q = 0.00256*[(0.90)(0.85)(1.00)(1.00)(132)2]
= 34.2 psf
Width of Pressure Coefficient Zone: 0.1(37') = 3.7'
0.4(20') = 8.0' } use: a = 4'0"
Effective Wind Area: <10ft2
For parapet height three feet (3) or larger, zone three (3) can be treated as zone two (2) (ASCE7-16).
External Pressure Coefficient:
1)
GCP1 =
-1.4
2r)
GCP2r =
-2.0
2e)
GCP2e =
-2.0
3)
GCP3 =
-2.0
Design Pressures:
1) Field
2r) Perimeter Ridge:
2e) Perimeter Eave
3) Corners
Internal Pressure Coefficient
1) GCPi = 0.18
P1 = 34.2*(-1.4
— 0.18) =
-54.0 psf
P2r = 34.2*(-2.0
— 0.18) =
-74.6 psf
P2e= 34.2*(-2.0
— 0.18) =
-74.6 psf
P3 = 34.2*(-2.0
— 0.18) =
-74.6 psf
�c- M E
Approved laboratory
F�r�
Page 3
1 1100 Lando End Chase
Port St Lucie, FL
Based on RAS-127 and F.L. #7849.25, the following are our recommended tile attachment
requirements:
Attachment Requirements:
Tile System: Moment Based (Boral Saxony 900 Flat Roof Tile)
Aerodynamic Multiplier: 0.315 ft3 (Direct Deck Attachment)
Restoring moment due to gravity: Mg = 7.17 ft. lb (6:12 slope)
Attachment resistance expressed as a moment: Me = 83 ft-lb
Single Medium Patty Foam Adhesive Set (24 g)
Zone 1 Field: Mrt = (54.0*0.315) — 7.17 ft. lb = 9.9 ft. lb. < 83 ft. lb = PASS
Zone 2e Perimeter Eave: Mrze = (74.6*0.315) — 7.17 ft. lb =16.3 ft. lb. < 83 ft. lb = PASS
Zone 2r Perimeter Ridge: Mrz, _ (74.6*0.315) — 7.17 ft. lb = 16.3 ft. lb. < 83 ft. lb = PASS
Zone 3 Corners: Mr3 = (74.6*0.315) — 7.17 ft. lb = 16.3 ft. lb. < 83 ft. lb = PASS
System is acceptable as approved with ICP Adhesives Polyset AH-160
(Single Medium Paddy placement of 24 grams)
Notes: All work shall be in compliance with the local building code product control notice of
acceptance and manufacturer specifications and the Florida Building Code 2020 edition.
Wind load calculations based on ASCE 7-16 and information provided by client.
All work shall be inspected by our field engineer or city inspector to verify compliance
with specifications.
Sincerely,
Keith LeBlanc, P.E. _7t Z,
Federal Engineering & Testing, Inc.
Florida Reg. No. 59394
Certificate of Authorization #5471
Miami -Dade County Certification #21-0201.02