Product Approval
li! USER: publLC User
Product Aooroval Menu � 1'roliaLWi_appllr,L0 Search . , Rplica(ion,t„il , Application Detail
FL FL10758-R8
Application Type Revision
Code Version 2020
Application Status Approved
Comments
Archived
Product Manufacturer
Owens Corning
Address/Phone/Email
One Owens Corning Parkway
Toledo, OH 43659
(740) 404-7829
greg. Keeler@owenscorning -com
Authorized Signature
Greg Keeler
greg,keeler@owenscorning.com
Technical Representative
Greg Keeler
Address/Phone/Email
2790 Columbus Road
Granville, OH 43023
(740) 32 1- 6345
greg keeler@owenscorning.com
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Roofing Accessories that are an Integral Part of the Roofing System
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed Zachary R, Priest
the Evaluation Report
Florida license
PE-74021
Quality Assurance Entity
PRf Construction Matenals reciinolegies, LLC
Quality Assurance Contract Expiration Date
12/31/2024
Validated By
Steven M VriCh, PE
Validation Checklist - Hardcopy Received
Certificate of independence
FL10J56_R8 C6[_(�CRk40� 4- 2 FBC Eyal Vent final �df
Referenced Standard and Year (of Standard)
Equivalence of Product Standards
Certified By
Sections from the Code
1708.2
Product Approval Method Llethod 2 Option fS
llttps:lJlvN�-�4,Iloi-id,lbuilding.oi-glprlp) app_dtl,iispr`?]),tram wGEVXQkvtD(IvIdAvlteOYO... 2/23/2021
Florida Building Code Online Page 2 of 2
Date Submitted 08/ 10/2020
Date Validated 1211.612020
Date Pending FBC Approval 09/18/2020
Date Approved 12/17/2020
FL if "Model, Number or Name
Description
10758.1 VentSure 4-foot Strip Heat and
Copolymer plastic low profile attic ridge vents for installation
Moisture Ridge Vents
in shingle roof systems
Limits of Use
Installation Instructions
Approved for use In HVHZ: No
t1 1075B RB II. OCR14003 4 2020 FBC Evai Vents fl_n, Did
Approved for use outside HVHZ; Yes
Verified By: Zachary R. Priest 74021
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: N/A
Evaluation Reports
Other: Refer to evaluation report
FI 10758 RA AE OCR I4003 4 2020 FBC Eva[ Vent
final rudf
Created by Independent Third Party: Yes
10758.2 VentSure Low Profile Slant Back
Galvanized metal roof vent
Roof Vent With Exterior Louver
—
Limits of Use
Installation Instructions
Approved for use In HVHZ: NO
FI 10.158_ RB it ,OCR140g1g 10201PC E9.gl Vet3Sz. finpl_ Pdf
Approved for use outside HVHZ: Yes
Verified By: Zachary R. Priest 74021
Impact Resistant: N/A
Created by Independent Third Party Yes
Design Pressure: N/A
Evaluation Reports
Other: Refer to evaluation report.
FI lmSR RR AE OCR14003 4 2020 FBC Eval Vent
final .odF
Created by Independent Third Party_ yes
10758.3
VentSure Rigid Roll Ridge Vent
Ridge Ventilation System
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
tL10758 RB IL OCR14003.4 20201 Ey l Vii,hilk-,2i
Approved for use outside HVHZ: Yes
Verified By: Zachary R. Priest 74021
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: N/A
Evaluation Reports
Other: Refer to evaluation report
FL 10758 RB AE OCR14003 4 2020 FBC Eval Vents
Third Party: Yes
MEW
Centel, 11 290t ea r Stone &ad Ta imicul re_L JD29 name: 850 4871824
Me Stale of Florae is an WHO emporcer cool 4007 2013 State of Flecks. pnvacv stat'reall IAncesuelliro Statement Refund statement
under Florida law, smel addresses are Public rtmrds. II you do not want you, a -mail address released in response to a Public el requesl do+at Send elalcomp
mail to this anti,, Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 83n.4ay 1395, 'Purl to Section 455.275
Iq, Honda Statutes, efeatiye October L 2012, iterates licensed under Chapter 455, ES. must provide the cepadment with an email address if the/ have one. The
emads Provided may be used for official c0lnnlumcab0n with the licensee. However small addresses are Public record. It mu do not Wran la soppiy a pertbnal address
please provide the Department with 3n amed address which can be made available to the Public. To determine if you are a licensee umber chapter 455, F. 5.i please
click sm,
Product Approval Accepts:
® is V21et. E
Credit Card
Safe
MuslimilwilmottKo
littps:/lwww. tloridabtiil(liiig.org/pr/pr_app_dtl.aspx?pai-am=wGE VXQwtDgv l dAvfteC Y0... 2/23/2021
CREEK certificate of Authorization 2gh Dr
17520 Edinburgh
urgh Dr
Tampa, FL 33647
TECHNICAL SERVICES, LLC (913) 480.3421
EVALUATION REPORT FLORIDA BUILDING CODE, 7`a EDITION (2020)
Manufacturer:
OWENS CORNING ROOFING AND ASPHALT LLC Issued December 15, 2020
1 Owens Corning Parkway
Toledo, OH 43657
(800) 438.7465
www. owe ns co rni ng. cam
Quality Assurance:
PRI Construction Materials Technologies (OUA9110)
SCOPE
—
Category:
Roofing
Roofing Accessories that are an Integral Part of the Roofing System
Subcategory:
Code Sections:
1708.2
Properties:
Roof Ventilation
REFERENCES
--
Entity
Report No.
Standard
Year
Architectural Testing. Inc (TST1558)
01-38660.04
TAS 100(A)
1995
1995
Architectural Testing. Inc (TST1558)
01-38660.06
TAS 100(A)
TAS 100(A)
1995
Architectural Testing, Inc (TST1558)
C1774.01-109-18
ASTM D 635
2014
ASTM D 1929
2016
ASTM D 2943
2018
PRI Construction Materials Technologies (TST5878)
AVIG-005.02.01
ASTM D 635
4
ASTM D 929
201
ASTM D 2843
2016
PRI Construction Materials Technologies (TST5878)
AVIG-006.02-01
ASTM G 155
2013
PRI Construction Materials Technologies (TST5878)
OCF•111.02.01
ASTM D 635
4
STM D 929
201
ASTM D 2843
2016
PRI Construction Materials Technologies (TST5878)
0CF-112-02.01
ASTM G 155
2013
PRI Construction Materials Technologies (TST5878)
OCF-118-02-01
TAS 100(A)
1995
PRI Construction Materials Technologies (TST5878)
OCF-223-02.Oi
TAS 100(A)
1995
PRI Construction Materials Technologies (TST5878)
OHI-007-02-01
TAS 100(A)
1995
OCR14003 4 FL10758-Ra
This evaluation report is provided for State of Florida product approval under Rule 61G20 3. The manufacturer snail notify GRE
EK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
\1 TECHNICAL CREEKICES,LLC
PRODUCT DESCRIPTION AND
OWENS CORNING
Vent$uroO Roof Ventilation
VenlSure`" 4-Foot Strip 1.114' x 14-7/8" x 48" low -profile attic ridge vent consisting of a two -layer nylon -
Heat and Molsture Ridge polyester composite. Available with or without a polyester fabric moisture barrier for
Vents: installation in shingle roof systems
48"
i'
14.7/8"
l'
Deck Type.
Roof deck shall be constructed of closely fitted sheathing for new or existing
construction, Roof deck shall be designed and installed in accordance with FBC
requirements.
Roof slope.
Minimum 3:12 to maximum 16/12
Installation Height
Maximum 50-ft
Attachment Method
Cut a 2-inch opening (I -inch on each side of the ridge) centered in the deck at the
ridge for ventilation. The slot shall terminate approximately 6-inches from the rake
edges. Apply a Y.-inch wide bead of ASTM D 4586 roofing cement along the entire
length of the outside edges of the vent to seal the vent to the field shingles, taking
care to not completely cover the weep slots in the vent. Center the vent over the
opening and fasten to the deck using the 11 ga. 2'F,-inch galvanized ring shank nails
(shall comply with FBC Section 1506.5) provided with the vent. Fasteners are to be
installed on both sides of the vent 1, 12, 24, 36, and 47-inches from the start of each
vent piece.
Prepare the adjacent vent section by applying the roofing cement along the edges,
snap together with fixed vent, and fasten to the deck in the same manner as the first
section. Fasten the ridge shingles over the vent to the deck on the marked "shingle
nail line" with two (2) minimum 11 ga. 2%-inch galvanized ring shank roofing nails
(shall comply with FBC Section 1506.5) provided with the vent or as directed by the
shingle manufacturer's installation instructions.
Allowable Roof Coverings: Asphalt shingles
OCR14003.4
2 of
This evaluation report is provided for Slate of Florida product approval under Rule 61G20.3. The manufacturer shall notity l:l(ttR
Technical Services. LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
\,1 TECHNICAL SERVICES, LLC
OWENS CORNING
VentSui Roof Ventilation
VentSui Low Profile 18" x 24" x 2-3116" (32" x 23' Flange base) static off -ridge vent composed of ASTM
Slant Back Roof Vent A653 galvanized steel (available with painted finish). Material shall conform with
with Exterior Louver: FBC Section 150743
Deck Type Roof deck shall be constructed of closely fitted sheathing for new or existing
construction Roof deck shall be designed and installed in accordance with FBC
requirements.
Roof slopeMinimum 3.12
Installation Height. Maximum 33-ft
Attachment Method Cut an 11 x 11-inch hole through wood sheathing only approximately 18-inches from
the ridge. Apply 114-inch thick by 3-inch wide bed of ASTM D 4586 roofing cement
around inner and outer flange. Place vent directly over the hole, ensuring the vent
sits flat on the roof. Fasten vent 4-inches o.c. and 1-inch from outside edge of flange
with minimum 12 ga. ring shank roofing nails (shall comply with FBC Section
1506.5), ensuring '%-inch penetration through wood deck (Minimum 18 nails per
vent)
Install baffle in %-inch bed of ASTM D 4586 roofing cement and secure with
minimum 12 ga. ring shank roofing nails (shall comply with FBC Section 1506.5)
spaced 8-inches 0.0. (total of (3) nails) while ensuring '%-inch penetration through
wood deck. Seal all nails and vent flange with ASTM D 4586 roofing cement,
Allowable Roof Coverings. Asphalt shingles
OCR14003.4 FL10758-R8 Page 3 of 5
This evaluation report is provided for State of Florida product approval under Rule 81G20.3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express not imply warranty, installation. recommended use, or other product attributes that are not
specifically addressed herein.
CREELL,K I OWCORNING
VenlSure® Roof Ventilation
TECHNICAL SERVICES, LLC
VentSureeRigid Roll 5/8' x 11-1/4" x 20' attic ridge vent composed of high density polypropylene with a
Ridge Vent: spun -bond polypropylene fabric.
Deck Type. Roof deck shall be constructed of closely fitted sheathing for new or existing
construction. Roof deck shall be designed and installed in accordance with FBC
requirements.
Roof slope: Minimum 2.12 to maximum 20.12
Installation Height: Maximum 60-ft
Attachment Method. Cut a 2-inch opening (1-inch on each side of the ridge) centered In the deck at the
ridge for ventilation. The slot shall terminate approximately 12-inches from the rake
edges. Apply a continuous bead of polyurethane adhesive sealant along the entire
length of the outside edges of the vent to seal the vent to the field shingles. Center
the vent over the opening and fasten the vent 24-inches o.c. to the deck using
minimum 12 ga. ring shank roofing nails (shall comply with FBC Section 15055),
ensuring %-inch penetration through wood deck.
Fasten the ridge shingles over the vent to the deck on the marked "shingle nail line'
with two (2) minimum 12 ga. ring shank roofing nails (shall comply with FBC Section
1506.5) or as directed by the shingle manufacturer's installation instructions,
ensuring'% -inch penetration through wood deck. Outside edges of the shingles shall
be sealed with Flashing cement.
Allowable Roof Coverings: Asphalt shingles
1) This report is not for use in the HVHZ.
2) Fire Classification is outside the scope of this evaluation.
3) The roof deck and deck attachment shall be designed by others in accordance with the FBC.
4) Owens Corning vents shall be installed in strict compliance with this evaluation report and the
manufacturer's published installation instructions. In the event of conflict, the more restrictive installation
shall be enforced.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion prior to installation.
6) Installation of the roof assembly is outside the scope of this evaluation.
7) Owens Corning vents are intended to provide passive ventilation for an enclosed attic in residential
construction applications.
8) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
OCR14003.4 ruv1oo-10 - - - -- -
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty. installation, recommended use, or other product attribules that are not
specifically addressed herein.
,\\W TECHNICAL CREEK
tCES,LLC
COMPLIANCE STATEMENT
OWENS CORNING
VentSureO Roof Ventilation
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 7"' Edition (2020) as evidenced in the referenced documents submitted by the named manufacturer
. 0
No 74021
— k _
�0 STATE OF :•14,
i
SS10 N A' %0`1111110
CERTIFICATION OF INDEPENDENCE
2020.12.15
13:59:34
-05'00'
Zachary R. Priest, P.E
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
GREEK Technical Services, LLC is not owned, operated. or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest. P E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation
Zachary R. Priest, P E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT
OCR14003 4 FL10758-R6 Page 5 of 5
This evaluation report is provided for Stale of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services. LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.