HomeMy WebLinkAboutProduct Approval (3) Ffle Copy,
EXTERIOR RESEARCH&DESIGN, LLC.
Certificate of Authorization tl9503
T'RINIT Y I 353 CHRISTIAN STREET, UNIT
QOERD OXFORD,CT 06478478
PHONE:(203)262-9245
FAX: (203)262-9243
EVALUATION REPORT
lll� Entegra Roof Tile, LLC Evaluation Report E39310.11.11-2-R4
r.NTEGRA 1289 NE 9"Avenue FL7804-R9
R O O F T I L E Okeechobee, FL 34972 Date of Issuance:11/02/2011
Revision 4:04/18/2016
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 5th Edition (2014) Florida Building Code (non-
HVHZ)sections noted herein.
i
DESCRIPTION: Entegra Concrete Roof Tiles (non-HVHZ jurisdictions)
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. TrinityJERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinityl ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed,then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by:
The facsimile seal appearing was authorized by Robert Nieminen,
Robert J.M.Nieminen,P.E. P,E.on04/18/2016.This does not serve as an electronically signed
Florida Registration No.59166,Florida DCA ANE1983 '' S j- x o m document.Signed,sealed hardcopies have been transmitted to the
Product Approval Administrator and to the named client
CERTIFICATION OF INDEPENDENCE:
1. Trinity ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E.does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E.does not have, nor will acquire,a financial interest in any other entity involved in the approval process of the
_ product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained
- specifically for that purpose.
TRINITY I ERD
ROOFING SYSTEM EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Roofing Tiles
Compliance Statement: Entegra Concrete Roof Tiles, as produced by Entegra Roof Tile, LLC, have demonstrated
compliance with the following sections of the Florida Building Code through testing in accordance with the following
Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth
herein.
2. STANDARDS:
Section Property Standard Year
1507.3.5,R905.3.5 Physical Properties ASTM C1492 2003
1507.3.7,R905.3.7 Attachment Requirements FRSA/TRI April 2012(04-12) 2012
1711.2.1 Overturning Moment SSTD 11 1997
3. REFERENCES:
Entity Examination Reference Date
ATL(TST3782) Physical Properties RT0615.01-11 06/28/2011
ATL(TST3782) Physical Properties RT0615.02-11 06/28/2011
ATL(TST3782) Physical Properties RT0615.03-11 06/28/2011
ATL(TST3782) Physical Properties RT0615.04-11 06/28/2011
ATL(TST3782) Physical Properties RT0615.05-11 06/28/2011
ATL(TST3782) Physical Properties RT0316.01-12 05/31/2012
ATL(TST 3782) Physical Properties RT1103.01-15 11/07/2015
ATL(TST 3782) Physical Properties RT1103.02-15 11/07/2015
ATL(TST 3782) Physical Properties RT1103.03-15 11/07/2015
ATL(TST 3782) Physical Properties RT1103.04-15 11/07/2015
ATL(TST 3782) Physical Properties RT1103.05-15 11/07/2015
PRI(TST5878) Physical Properties ESI-001-02-01 11/06/2006
PRI(TST5878) Physical Properties ESI-002-02-01 11/06/2006
PRI(TST5878) Physical Properties ESI-003-02-01 11/06/2006
PRI(TST5878) Physical Properties ESI-004-02-01 11/06/2006
PRI(TST5878) Physical Properties ESI-005-02-01 12/12/2006
PRI(TST5878) Physical Properties HRT-023-02-01 11/19/2007
PRI(TST5878) Physical Properties HRT-026-02-01 01/08/2008
Tile Roof Institute SSTD 11 Membership Confirmation Current
PRI(QUA9110) Quality Assurance Inspection Report 11/04/2015
Exterior Research and Design,LLC. Evaluation Report E39310.11.11-2-R4
Certificate of Authorization#9503 FL7804-R9
Revision 4:04/18/2016
Page 2 of 6
TRINITY I ERD
4. PRODUCT DESCRIPTION:
4.1 BERMUDA FLAT,PLANTATION FLAT and HORIZON FLAT are ASTM C1492,Type III (low-profile)concrete roof tiles.
16' -�
1-1/4'
10'
r
16'
2'
w 10'
r
Bermuda Flat
Plantation Flat
/ 17-1/4"
13"
- Horizon Flat
Exterior Research and Design,LLC. Evaluation Report E39310.11.11-2-R4
Certificate of Authorization#9503 FL7804-R9
Revision 4:04/18/2016
Page 3 of 6
��TRINFFY�ERD
4.2 BELLA HIGH"S",ESTATE"S"and HACIENDA are ASTM D1492,Type II (medium-profile)concrete roof tiles.
16-2j„ 13-4.1
Bella High"S"
Nail Holes
•
•
I& ,
�3 =
Estate"S"
0
e
Hacienda
Exterior Research and Design,LLC. Evaluation Report E39310.11.11-2-R4
Certificate of Authorization#9503 FL7804-R9
Revision 4:04/18/2016
Page 4 of 6
TRINITY ERD
4.3 GALENA SPANISH"S"and REGAL are ASTM C1492,Type I (high-profile)concrete roof tiles.
17"
10"
Galena Spanish"S"
o e
13 1/4"
Regal
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity[ERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire classification is not part of this evaluation; refer to FBC Section 1505, Exception 2 or current Approved
Roofing Materials Directory for fire rating of this product.
5.4 Underlayment shall be that approved by Entegra Roof Tile, which holds Florida Local or Statewide Product
Approval for use with tile roofing systems. The underlayment Product Approval shall specify allowable
method(s) of tile installation (mechanical attachment, mortar-set and/or adhesive-set) for use with the
specific underlayment. For mortar-set or adhesive-set tile roofing applications, the underlayment Product
Approval shall specify attachment methods for the underlayment system to resist wind uplift design loads in
accordance with Table 1A of FRSA/TRI April 2012(04-12).
_ 5.5 All products in the roof assembly shall have quality assurance audit in accordance with the Florida Building
Code and F.A.C. Rule 61G20-3.
Exterior Research and Design,LLC. Evaluation Report E39310.11.11-2-R4
Certificate of Authorization#9503 FL7804-R9
Revision 4:04/18/2016
Page 5 of 6
rl�
Q0TRINrry I ERD
6. INSTALLATION:
6.1 Entegra Concrete Roof Tiles may be mechanically fastened, mortar-set or adhesive-set. Installation shall
comply with manufacturer's current published instructions, but not less than the requirements of FBC
Section 1507.3, the FRSA/TRI Florida High Wind Concrete and Clay Tile Installation Manual, 5th Edition and,
for mortar-set or adhesive-set applications,the mortar or adhesive manufacturer's Product Approval.
6.2 Attachment:
Mechanically Attached Tile:
Wind load resistance shall be in accordance with Table 3 of FRSA/TRI April 2012 (04-12) to resist the Uplift
Moment determined in Table 2A or 2B of FRSA/TRI April 2012(04-12).
Mortar-Set or Adhesive-Set Tile:
Wind load resistance shall be in accordance with FBC Section 1609.5.3 in conjunction with the mortar or
adhesive manufacturer's Product Approval.
Hip and Ridge Tile: _
Tile shall be installed in accordance with FRSA/TRI April 2012 (04-12). For hip and ridge tile installations atop
hip and ridge metal, refer to the hip and ridge metal manufacturer's Product Approval (e.g., FL5374) or test
report in accordance with SSTD 11 for allowable loads to resist those determined in accordance with Table _
1A of FRSA/TRI April 2012(04-12).
7. LABELING:
7.1 Each unit shall bear the imprint and/or identifiable marking of the manufacturer's name or logo. Tile lots
shall be labeled in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the noted QA agency for information on product locations covered for F.A.C. Rule 61G20-3 OA
requirements.
10. QUAUTYASSURANCE ENTITY:
PRI Construction Materials Technologies, LLC.—QUA9110; (813)621-5777
-END OF EVALUATION REPORT-
Exterior Research and Design,LLC. Evaluation Report E39330.11.11-2-R4
Certificate ofAuthorization#9503 F1.7804-119
Revision 4:04/18/2016