HomeMy WebLinkAboutAPPROVED, 006 HVAC Energy Calcs Manual JsProject Name: Owner: Builder Name: Permit Office: Jurisdiction: ST LUCIE COUNTY ST LUCIE COUNTY ROCHE GUEST HOUSE Street: City, State, Zip: FORT PIERCE , FL , 2744 BROCKSMITH ROAD Permit Number: Design Location: FL, Fort Pierce CHECKAIR BARRIER CRITERIA A continuous air barrier shall be installed in the building envelope. The exterior thermal envelope contains a continuous air barrier. Breaks or joints in the air barrier shall be sealed. The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and any gaps in the air barrier shall be sealed. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. The junction of the foundation and sill plate shall be sealed. The junction of the top plate and the top of exterior walls shall be sealed. Knee walls shall be sealed. The space between window/door jambs and framing, and skylights and framing shall be sealed. Rim joists shall include the air barrier. The air barrier shall be installed at any exposed edge of insulation. Exposed earth in unvented crawl spaces shall be covered with a Class I vapor retarder with overlapping joints taped. Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Narrow cavities Shafts, penetrations Crawl space walls Floors (including above-garage and cantilevered floors) Rim joists Windows, skylights Walls Ceiling/attic General COMPONENT Garage separation Recessed lighting Plumbing and wiring S h o w e r / t u b HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub-floor, wall covering or ceiling The air barrier shall be installed behind electrical or communication boxes or air-sealed boxes shall be installed. The air barrier installed at exterior walls adjacent to showers and tubs shall separate them from the showers and tubs. Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Recessed light fixtures installed in the building thermal envelope shall be sealed to the finished surface. Air sealing shall be provided between the garage and conditioned spaces. When required to be sealed, concealed fire sprinklers shall only be sealed in a manner that is recommended by the manuf acturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or ceilings. C o n c e a l e d Electrical/phone box on exterior walls Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA INSULATION INSTALLATION CRITERIA EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software3/5/2021 6:36 AM Page 1 of 1 Air-permeable insulation shall not be used as a sealing material. The insulation in any dropped ceiling/soffit shall be aligned with the air barrier. Cavities within corners and headers of frame walls shall be insulated by completely filling the cavity with a material having a thermal resistance of R-3 per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Rim joists shall be insulated. Floor framing cavity insulation shall be installed to maintain permanent contact with the underside of subfloor decking, or floor framing cavity insulation shall be permitted to be in contact with the top side of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. and doors on exterior wall requirements Recessed light fixtures installed in the building thermal envelope shall be air tight and IC rated. sprinklers Where provided instead of floor insulation, insulation shall be permanently attached to the crawlspace walls. Exterior walls adjacent to showers and tubs shall be insulated. 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400. a ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� ����������������������������������������������������� Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-26 11:04:30 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Project Summary Feb 26, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information ROCHE GUEST HOUSEFor: 2744 BROCKSMITH ROAD, FORT PIERCE, FL Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh25721 Struc ture Btuh18086 Ducts Btuh6024 Ducts Btuh8630 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh31745 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh25380 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3067 Ducts Btuh2369 Central vent (0 cfm)Btuh0 CoolingHeating (none) 20622062Area (ft²)Equipment latent load Btuh5436 1855818558Volume (ft³) Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh30816 Equiv. AVF (cfm)4999 Req. total capacity at 0.70 SHR ton3.0 Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR6036J1 AHRI ref Coil TEM4A0C37S31++TDR AHRI ref 201763705 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW9.0 Sensible cooling Btuh24640 Heating output Btuh30754 Latent cooling Btuh10560 Temperature rise °F24 Total cooling Btuh35200 Actual air flow cfm1173 Actual air flow cfm1173 Air flow factor cfm/Btuh0.037 Air flow factor cfm/Btuh0.044 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.83 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-26 11:04:30 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Right-J® Worksheet Feb 26, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House UTILITY RM 2 Exposed wall 198.0 ft 6.0 ft 3 Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft12.0x6.0 5 Room area 2062.0 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 279 249 997 545 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 15 0 273 225 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 10.6810.68 15 0 273 160 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 504 424 1698 928 54 42 168 92 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 80 0 1457 2703 12 0 218 405 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 495 445 1781 973 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 16.0316.03 50 0 912 803 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 504 409 1637 895 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 80 0 1458 2705 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 15 0 273 315 0 0 0 0 CC 18A-10zd18A-10zd 0.0760.076 --2.132.13 3.043.04 2062 2062 4388 6268 72 72 153 219 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2062 198 7529 0 72 6 228 0 6 c) AED excursion 0 -32 Envelope loss/gain 22675 16520 768 684 12 a) Infiltration 3046 816 92 25 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 750 0 Subtotal (lines 6 to 13)25721 18086 860 709 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 31 41 14 Subtotal 25721 18086 891 750 15 Duct loads 23%48%6024 8630 23%48%209 358 Total room load 31745 26715 1100 1107 Air required (cfm)Air required (cfm)1173 1173 41 49 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-26 11:04:30 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Right-J® Worksheet Feb 26, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 HALLWAY 2 Exposed wall 14.0 ft 0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft12.0x6.0 ft4.0x12.0 5 Room area 72.0 ft²48.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 54 54 216 118 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 72 52 208 114 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 16.0316.03 20 0 366 322 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 CC 18A-10zd18A-10zd 0.0760.076 --2.132.13 3.043.04 72 72 153 219 48 48 102 146 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 72 14 532 0 48 0 0 0 6 c) AED excursion -12 -10 Envelope loss/gain 1475 760 102 136 12 a) Infiltration 215 58 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1691 818 102 136 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 31 41 -102 -136 14 Subtotal 1721 859 0 0 15 Duct loads 23%48%403 410 23%48%0 0 Total room load 2125 1268 0 0 Air required (cfm)Air required (cfm)79 56 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-26 11:04:30 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Right-J® Worksheet Feb 26, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 2 BEDROOM 2 2 Exposed wall 0 ft 5.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft2.0x8.0 ft140.0x1.0 5 Room area 16.0 ft²140.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 45 30 120 66 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 15 0 273 225 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 16.0316.03 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 CC 18A-10zd18A-10zd 0.0760.076 --2.132.13 3.043.04 16 16 34 49 140 140 298 426 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 16 0 0 0 140 5 190 0 6 c) AED excursion -3 -106 Envelope loss/gain 34 45 881 610 12 a) Infiltration 0 0 77 21 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 750 Subtotal (lines 6 to 13)34 45 958 1381 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -34 -45 54 72 14 Subtotal 0 0 1013 1453 15 Duct loads 23%48%0 0 23%48%237 693 Total room load 0 0 1250 2146 Air required (cfm)Air required (cfm)0 0 46 94 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-26 11:04:30 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Right-J® Worksheet Feb 26, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name OFFICE KITCHEN 2 Exposed wall 30.0 ft 24.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft12.0x12.0 ft326.0x1.0 5 Room area 144.0 ft²326.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 108 93 372 203 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 10.6810.68 15 0 273 160 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 216 165 662 362 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 51 0 923 1712 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 54 54 216 118 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 16.0316.03 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 108 93 372 203 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 15 0 273 315 0 0 0 0 CC 18A-10zd18A-10zd 0.0760.076 --2.132.13 3.043.04 144 144 306 438 326 326 694 991 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 144 30 1141 0 326 24 913 0 6 c) AED excursion 41 -137 Envelope loss/gain 2954 1478 3191 2928 12 a) Infiltration 461 124 369 99 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3416 1602 3560 3027 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 20 27 14 Subtotal 3416 1602 3581 3054 15 Duct loads 23%48%800 764 23%48%839 1457 Total room load 4216 2366 4419 4511 Air required (cfm)Air required (cfm)156 104 163 198 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-26 11:04:30 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Right-J® Worksheet Feb 26, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name FOYER/LIVING RM PANTRY 2 Exposed wall 30.0 ft 0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft414.0x1.0 ft5.0x4.0 5 Room area 414.0 ft²20.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 54 54 216 118 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 16.0316.03 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 216 166 664 363 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 50 0 912 1692 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 CC 18A-10zd18A-10zd 0.0760.076 --2.132.13 3.043.04 414 414 881 1259 20 20 43 61 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 414 30 1141 0 20 0 0 0 6 c) AED excursion 409 -4 Envelope loss/gain 3814 3841 43 56 12 a) Infiltration 461 124 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)4275 3965 43 56 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 4275 3965 43 56 15 Duct loads 23%48%1001 1892 23%48%10 27 Total room load 5277 5856 53 83 Air required (cfm)Air required (cfm)195 257 2 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-26 11:04:30 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Right-J® Worksheet Feb 26, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name MASTER BEDROOM M WIC 1 2 Exposed wall 39.0 ft 9.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft416.0x1.0 ft9.0x8.0 5 Room area 416.0 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 171 141 565 308 81 81 324 177 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 16.0316.03 30 0 546 481 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 180 150 601 328 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 30 0 546 1013 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 CC 18A-10zd18A-10zd 0.0760.076 --2.132.13 3.043.04 416 416 885 1265 72 72 153 219 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 416 39 1483 0 72 9 342 0 6 c) AED excursion 35 -31 Envelope loss/gain 4625 3430 820 365 12 a) Infiltration 600 161 138 37 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)5225 3591 958 402 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 5225 3591 958 402 15 Duct loads 23%48%1224 1713 23%48%224 192 Total room load 6449 5304 1183 594 Air required (cfm)Air required (cfm)238 233 44 26 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-26 11:04:30 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Right-J® Worksheet Feb 26, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC 2 M TOILET 2 Exposed wall 0 ft 4.0 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft62.0x1.0 ft4.0x8.0 5 Room area 62.0 ft²32.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 10.6810.68 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 36 36 144 79 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 16.0316.03 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 33.7733.77 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 20.9720.97 0 0 0 0 0 0 0 0 CC 18A-10zd18A-10zd 0.0760.076 --2.132.13 3.043.04 62 62 132 188 32 32 68 97 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 62 0 0 0 32 4 152 0 6 c) AED excursion -13 -14 Envelope loss/gain 132 175 364 162 12 a) Infiltration 0 0 62 16 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)132 175 426 179 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 132 175 426 179 15 Duct loads 23%48%31 84 23%48%100 85 Total room load 163 259 526 264 Air required (cfm)Air required (cfm)6 11 19 12 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-26 11:04:30 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Right-J® Worksheet Feb 26, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M BATH 2 Exposed wall 37.0 ft 3 Room height 9.0 heat/coolft 4 Room dimensions ft228.0x1.0 5 Room area 228.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 n 4.00 2.19 72 72 288 158 .G 2 glazing, clr low-e 0.650 n 18.20 14.99 0 0 0 0 .G 2 glazing, clr low-e 0.650 n 18.20 10.68 0 0 0 0 .W 13A-4ocs 0.143 e 4.00 2.19 180 163 651 356 11 G 2 glazing, clr low-e 0.650 e 18.20 33.77 17 0 315 585 W 13A-4ocs 0.143 s 4.00 2.19 81 81 324 177 G 2 glazing, clr low-e 0.650 s 18.20 16.03 0 0 0 0 W 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 33.77 0 0 0 0 G 2 glazing, clr low-e 0.650 w 18.20 20.97 0 0 0 0 C 18A-10zd 0.076 -2.13 3.04 228 228 485 693 F 22A-tph 1.358 -38.02 0.00 228 37 1407 0 6 c) AED excursion -121 Envelope loss/gain 3471 1848 12 a) Infiltration 569 152 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)4041 2001 Less external load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 4041 2001 15 Duct loads 23%48%946 955 Total room load 4987 2955 Air required (cfm)184 130 2021-Feb-26 11:04:34 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Job:Duct System Summary Feb 26, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information ROCHE GUEST HOUSEFor: 2744 BROCKSMITH ROAD, FORT PIERCE, FL CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1173cfm1173 Total effective length (TEL)ft218 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st1115.024.7VlFx0x06.01.00056792125hBATH 2 st2115.017.9VlFx0x07.01.00094462146cBEDROOM 2 st2115.016.7VlFx0x07.01.000129982928cFOYER/LIVING RM st3135.044.4VlFx0x07.01.000129982928cFOYER/LIVING RM-A st1115.022.1VlFx0x07.01.00099822256cKITCHEN st1115.030.4VlFx0x07.01.00099822256cKITCHEN-A st4155.062.5VlFx0x07.01.0001301844987hM BATH st4155.060.0VlFx0x04.01.0001219526hM TOILET st4155.058.3VlFx0x05.01.00026441183hM WIC 1 st4155.060.5VlFx0x04.01.000116259cM WIC 2 st3135.042.1VlFx0x07.01.0001161193225hMASTER BEDROOM st3135.050.1VlFx0x07.01.0001161193225hMASTER BEDROOM-A st2115.019.7VlFx0x07.01.0001041564216hOFFICE st3135.047.2VlFx0x04.01.0004283cPANTRY st1115.030.4VlFx0x06.01.00049411107cUTILITY RM Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 253 179 1.000 726 8.0 0x0 VinlFlx st3 st3 Peak AVF 591 544 1.000 753 12.0 0x0 VinlFlx st2 st2 Peak AVF 891 871 1.000 833 14.0 0x0 VinlFlx st1 Peak AVF 283 302 1.000 555 10.0 0x0 VinlFlx 2021-Feb-26 11:04:34 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\ROCHE GUEST HOUSE.rup Calc = MJ8 Front Door fac es: W Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 11730 1173 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� ����������������������������������������������������� EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 63/5/2021 6:35 AM Project Name: Owner: Builder Name: Permit Office: Jurisdiction: ST LUCIE COUNTY ST LUCIE COUNTY ROCHE GUEST HOUSE Street: City, State, Zip: FORT PIERCE , FL , 2744 BROCKSMITH ROAD Permit Number: Design Location: FL, Fort Pierce County: St. Lucie (Florida Climate Zone 2 ) 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area above grade (ft²) New (From Plans) Detached 1 No 2062 7. Windows a. U-Factor: S H G C : b. U-Factor: S H G C : c. U-Factor: S H G C : Sgl, U=0.65 174.83 ft² SHGC=0.25 Sgl, U=0.65 80.00 ft² SHGC=0.30 N/A f t ² 9. Floor Types a. Slab-On-Grade Edge Insulation b. N/A c. N/A R=0.0 2062.00 ft² R=f t ² R=f t ² 10. Wall Types a. Concrete Block - Int Insul, Exterior R=4.1 1782.00 ft² b. Frame - Wood, Adjacent R=13.0 216.00 ft² c. N/A R=f t ² 11. Ceiling Types a. Roof Deck (Unvented)R=20.0 2062.00 ft² f t ² R=b. N/A c. N/A R = f t ² 12. Ducts a. Sup: Attic, Ret: Attic, AH: Garage 13. Cooling systems 14. Heating systems 15. Hot water systems a. Propane Cap: 1 gallons b. Conservation features None d. N/A R=f t ² Area Weighted Average Overhang Depth:0.000 ft. Area Weighted Average SHGC:0.266 Description Area Insulation Area Insulation Area Insulation Area 16. Credits None 2 (254.8 sqft.) (1998.0 sqft.) (2062.0 sqft.) (2062.0 sqft.) Conditioned floor area below grade (ft²) 0 a. Central Unit a. Electric Strip Heat k B t u / h r 35.2 SEER:16.00 Efficiency k B t u / h r Efficiency 27.0 COP:1.00 f t ² R 6 150 Tankless EF: 0.590 8. Skylights c. U-Factor:(AVG) S H G C ( A V G ) : N/A N/A f t ² Area Glass/Floor Area: 0.124 Total Proposed Modified Loads: Total Baseline Loads: 58.10 62.88 PASS I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code. PREPARED BY: DATE: I hereby certify that this building, as designed, is in compliance with the Florida Energy Code. OWNER/AGENT: DATE: BUILDING OFFICIAL: DATE: Review of the plans and specifications covered by this calculation indicates compliance with the Florida Energy Code. Before construction is completed this building will be inspected for compliance with Section 553.908 Florida Statutes. - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory-sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 5.00 ACH50 (R402.4.1.2). FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method FORM R405-2020 3-5-2021 PROJECT Title: Owner Name: # of Units: Builder Name: Permit Office: Jurisdiction: ST LUCIE COUNTY ST LUCIE COUNTY 1 ROCHE GUEST HOUSE Family Type: New/Existing: Bedrooms: Conditioned Area: Total Stories: Worst Case: Rotate Angle:0 No 1 2062 2 New (From Plans) Detached Address Type: Lot # Block/Subdivision: PlatBook: Street: County: City, State, Zip: FL , FORT PIERCE , St. Lucie 2744 BROCKSMITH R Street Address Comment: Building Type: User Cross Ventilation:No Whole House Fan:No TMY Site Design Temp Int Design Temp Heating Design Daily Temp Design Location 2.5 %97.5 %Degree Days Moisture RangeWinter Summer CLIMATE 90 70 75 299 62 Low39FL_VERO_BEACH_MUNIFL, Fort Pierce______ Number Name Area Volume BLOCKS 1 Entire House 2062 18558 Number Name Area Volume SPACES Kitchen Occupants Bedrooms Cooled HeatedInfil ID Finished 1 UTILITY RM 72 648 No 0 Yes Yes1 Yes 2 BATH 2 72 648 No 0 Yes Yes1 Yes 3 HALLWAY 48 432 No 0 Yes Yes1 No 4 CLST 2 16 144 No 0 Yes Yes1 No 5 BEDROOM 2 140 1260 No 0 1 Yes Yes1 Yes 6 OFFICE 144 1296 No 0 Yes Yes1 Yes 7 KITCHEN 326 2934 Yes 0 Yes Yes1 Yes 8 FOYER/LIVING RM 414 3726 No 0 Yes Yes1 Yes 9 PANTRY 20 180 No 0 Yes Yes1 No 10 MASTER BEDROO 416 3744 No 0 1 Yes Yes1 Yes 11 M WIC 1 72 648 No 0 Yes Yes1 Yes 12 M WIC 2 62 558 No 0 Yes Yes1 No 13 M TOILET 32 288 No 0 Yes Yes1 Yes 14 M BATH 228 2052 No 0 Yes Yes1 Yes # Floor Type Area Tile Wood Carpet FLOORS Perimeter R-Value Joist R-ValueSpace Perimeter 1 72 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -6 ft UTILITY RM 2 72 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -14 ft BATH 2 3 48 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -1 ft HALLWAY 4 16 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -1 ft CLST 2 3/5/2021 6:35 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT # Floor Type Area Tile Wood Carpet FLOORS Perimeter R-Value Joist R-ValueSpace Perimeter 5 140 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -5 ft BEDROOM 2 6 144 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -30 ft OFFICE 7 326 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -24 ft KITCHEN 8 414 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -30 ft FOYER/LIVING R 9 20 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -1 ft PANTRY 10 416 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -39 ft MASTER BEDRO 11 72 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -9 ft M WIC 1 12 62 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -1 ft M WIC 2 13 32 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -4 ft M TOILET 14 228 ft² 1 0 0______ Slab-On-Grade Edge Insulation - - - -37 ft M BATH # Type Materials Color Absor. Roof Solar Deck Insul. Pitch ROOF Tested Roof Area Gable Area Emitt Tested EmittSA (deg) Rad Barr 1 Flat Concrete 2062 ft² Medium 0.3 20 0______No0 ft² 0.9 NoN ATTIC # Type Ventilation Area RBS IRCCVent Ratio (1 in) ______ 1 No attic Unvented 2062 ft² N N0 # Ceiling Type R-Value Area Framing Frac Truss Type CEILING Space Ins Type 1 Under Attic (Unvented)0 72 ft² 0.1 Wood______UTILITY RM Blown 2 Under Attic (Unvented)0 72 ft² 0.1 Wood______BATH 2 Blown 3 Under Attic (Unvented)0 48 ft² 0.1 Wood______HALLWAY Blown 4 Under Attic (Unvented)0 16 ft² 0.1 Wood______CLST 2 Blown 5 Under Attic (Unvented)0 140 ft² 0.1 Wood______BEDROOM 2 Blown 6 Under Attic (Unvented)0 144 ft² 0.1 Wood______OFFICE Blown 7 Under Attic (Unvented)0 326 ft² 0.1 Wood______KITCHEN Blown 8 Under Attic (Unvented)0 414 ft² 0.1 Wood______FOYER/LIVING R Blown 9 Under Attic (Unvented)0 20 ft² 0.1 Wood______PANTRY Blown 10 Under Attic (Unvented)0 416 ft² 0.1 Wood______MASTER BEDRO Blown 11 Under Attic (Unvented)0 72 ft² 0.1 Wood______M WIC 1 Blown 12 Under Attic (Unvented)0 62 ft² 0.1 Wood______M WIC 2 Blown 13 Under Attic (Unvented)0 32 ft² 0.1 Wood______M TOILET Blown 14 Under Attic (Unvented)0 228 ft² 0.1 Wood______M BATH Blown 3/5/2021 6:35 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT WALLS #Wall Type R-Value Area Adjacent Framing Solar Ornt Fraction Absor. HeightWidth Ft In Ft InTo Cavity Sheathing R-ValueSpace Grade% Below 1 4.1 0UTILITY RM 0006 9E Concrete Block - Int Insul 0.30Exterior54.0 ft² ____ 2 13 0UTILITY RM 00012 9N Frame - Wood 0.30.1Garage108.0 ft² ____ 3 4.1 0BATH 2 0006 9E Concrete Block - Int Insul 0.30Exterior54.0 ft² ____ 4 4.1 0BATH 2 0008 9S Concrete Block - Int Insul 0.30Exterior72.0 ft² ____ 5 13 0HALLWAY0004 9N Frame - Wood 0.30.1Garage36.0 ft² ____ 6 13 0CLST 2 0002 9N Frame - Wood 0.30.1Garage18.0 ft² ____ 7 4.1 0BEDROOM 2 0005 9N Concrete Block - Int Insul 0.30Exterior45.0 ft² ____ 8 13 0BEDROOM 2 0006 9N Frame - Wood 0.30.1Garage54.0 ft² ____ 9 4.1 0OFFICE00012 9N Concrete Block - Int Insul 0.30Exterior108.0 ft² ____ 10 4.1 0OFFICE0006 9S Concrete Block - Int Insul 0.30Exterior54.0 ft² ____ 11 4.1 0OFFICE00012 9W Concrete Block - Int Insul 0.30Exterior108.0 ft² ____ 12 4.1 0KITCHEN00024 9E Concrete Block - Int Insul 0.30Exterior216.0 ft² ____ 13 4.1 0FOYER/LIVIN 0006 9N Concrete Block - Int Insul 0.30Exterior54.0 ft² ____ 14 4.1 0FOYER/LIVIN 00024 9W Concrete Block - Int Insul 0.30Exterior216.0 ft² ____ 15 4.1 0MASTER BE 00019 9S Concrete Block - Int Insul 0.30Exterior171.0 ft² ____ 16 4.1 0MASTER BE 00020 9W Concrete Block - Int Insul 0.30Exterior180.0 ft² ____ 17 4.1 0M WIC 1 0009 9S Concrete Block - Int Insul 0.30Exterior81.0 ft² ____ 18 4.1 0M TOILET 0004 9S Concrete Block - Int Insul 0.30Exterior36.0 ft² ____ 19 4.1 0M BATH 0008 9N Concrete Block - Int Insul 0.30Exterior72.0 ft² ____ 20 4.1 0M BATH 00020 9E Concrete Block - Int Insul 0.30Exterior180.0 ft² ____ 21 4.1 0M BATH 0009 9S Concrete Block - Int Insul 0.30Exterior81.0 ft² ____ #Door Type U-Value AreaStorms DOORS Ornt Space Width Ft In Ft In Height 1 Insulated .23 17.8 ft² None______N HALLWAY 8682 # Ornt Panes NFRC U-Factor SHGC Area Depth Separation Int ShadeFrame Screening WINDOWS Overhang Orientation shown is the entered, Proposed orientation. Wall ID Imp 1 E Low-E Single 0.65 0.25 12.0 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes1 Y 2 S Low-E Single 0.65 0.3 20.0 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes4 Y 3 N Low-E Single 0.65 0.25 15.0 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes7 Y 4 N Low-E Single 0.65 0.25 15.0 ft² 0 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes9 Y 5 W Low-E Single 0.65 0.25 15.0 ft² 0 ft 0 in 1 ft 4 in Drapes/blindsMetal Exterior 5______Yes11 Y 6 E Low-E Single 0.65 0.25 10.5 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes12 Y 7 E Low-E Single 0.65 0.3 40.0 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes12 Y 8 W Low-E Single 0.65 0.3 20.0 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes14 Y 9 W Low-E Single 0.65 0.25 30.0 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes14 Y 10 S Low-E Single 0.65 0.25 30.0 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes15 Y 11 W Low-E Single 0.65 0.25 30.0 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes16 Y 12 E Low-E Single 0.65 0.25 17.3 ft² 0 ft 0 in 1 ft 4 in NoneMetal None______Yes20 Y 3/5/2021 6:35 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT # Floor Area Ceiling Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation GARAGE 1 576 ft² 576 ft² 24 ft 9 ft 13______ Method CFM 50 ACH 50ELASLAScope INFILTRATION ACHEqLA# 1546.5 584.85.000286Wholehouse .0946159.29Proposed ACH(50)1 HEATING SYSTEM # System Type Efficiency Capacity DuctsSubtypeBlockSpeed 1 Electric Strip Heat/COP:1 27 kBtu/hr ______sys#1None1 # System Type Efficiency Capacity Air Flow SHR COOLING SYSTEM DuctsSubtypeBlockSubtype 1 Central Unit/SEER: 16 35.2 kBtu/hr 1056 cfm 0.8______sys#1Split1 Single # System Type EF Cap Use SetPnt Conservation HOT WATER SYSTEM SubType Location 1 Propane 0.59 1 gal 62.3 gal 120 deg None______Tankless Exterior FSEC Company Name System Model #Collector Model # Collector SOLAR HOT WATER SYSTEM Storage FEFCert #Area Volume None None f t ² ______ # Location R-Value Area Location Area ---- Supply -------- Return ---- Leakage Type Handler CFM 25Air QN RLF DUCTS Heat Cool HVAC # TOT OUT CFM25 1 Attic 6 150 ft² Attic 15 ft² Default Leakage Garage (Default) c______1 1 (Default) c 3/5/2021 6:35 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT TEMPERATURES Programable Thermostat: N Ceiling Fans: Cooling [ ] Jan [ ] Feb [ ] Mar [ ] Apr [ ] May [X] Jul [X] Aug [X] Sep [ ] Oct [ ] Nov [ ] Dec [ ] Dec [X] Dec[X] Nov [X] Nov [ ] Oct [X] Oct [ ] Sep [ ] Sep [ ] Aug [ ] Aug [ ] Jul [ ] Jul[ ] Jun [ ] Jun [X] Jun [ ] May [ ] May [ ] Apr [X] Apr [X] Mar [X] Mar [X] Feb [ ] Feb [X] Jan [ ] Jan Heating Venting Thermostat Schedule:HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (WD)AM PM 78 80 78 80 78 80 78 80 78 78 78 78 78 78 78 78 80 78 80 78 80 78 80 78 Cooling (WEH)AM PM 78 80 78 80 78 80 78 80 78 78 78 78 78 78 78 78 80 78 80 78 80 78 80 78 Heating (WD)AM PM 65 68 65 68 65 68 65 68 65 68 65 68 65 68 68 68 68 68 68 68 68 68 68 68 Heating (WEH)AM PM 65 68 65 68 65 68 65 68 65 68 65 68 65 68 68 68 68 68 68 68 68 68 68 68 MASS Mass Type Area Thickness Furniture Fraction Space Default(8 lbs/sq.ft.0 ft² 0 ft 0.3 MASTER BEDROO Default(8 lbs/sq.ft.f t ² f t 0.3 GREAT RM Default(8 lbs/sq.ft.f t ² f t 0.3 M WIC 2 Default(8 lbs/sq.ft.f t ² f t 0.3 M WIC 1 Default(8 lbs/sq.ft.f t ² f t 0.3 M BATH Default(8 lbs/sq.ft.f t ² f t 0.3 M TOILET Default(8 lbs/sq.ft.f t ² f t 0.3 ENTRY Default(8 lbs/sq.ft.f t ² f t 0.3 KITCHEN Default(8 lbs/sq.ft.f t ² f t 0.3 BEDROOM 2 Default(8 lbs/sq.ft.f t ² f t 0.3 WIC 2 Default(8 lbs/sq.ft.f t ² f t 0.3 BATH 2 Default(8 lbs/sq.ft.f t ² f t 0.3 WIC 3 Default(8 lbs/sq.ft.f t ² f t 0.3 BEDROOM 3 Default(8 lbs/sq.ft.f t ² f t 0.3 W/D Default(8 lbs/sq.ft.f t ² f t 0.3 HALL Default(8 lbs/sq.ft.f t ² f t 0.3 GARAGE AREA 3/5/2021 6:35 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 6 of 6 FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� ����������������������������������������������������� 2744 BROCKSMITH ROAD, FORT PIERCE, FL, EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 92 The lower the EnergyPerformance Index, the more efficient the home. 1. New construction or existing 2. Single family or multiple family 3. Number of units, if multiple family 4. Number of Bedrooms 5. Is this a worst case? 6. Conditioned floor area (ft²) New (From Plans) Detached 1 2 No 2062 7. Windows** a. U-Factor: S H G C : b. U-Factor: S H G C : c. U-Factor: S H G C : d. U-Factor: S H G C : Sgl, U=0.65 174.83 ft² SHGC=0.25 Sgl, U=0.65 80.00 ft² SHGC=0.30 N/A f t ² N/A f t ² 9. Floor Types a. Slab-On-Grade Edge Insulation b. N/A c. N/A R=0.0 2062.00 ft² R= f t ² R= f t ² 10. Wall Type and Insulation a. Concrete Block - Int Insul, Exterior R=4.1 1782.00 ft² b. Frame - Wood, Adjacent R=13.0 216.00 ft² c. N/A R= f t ² 11. Ceiling Type and insulation level a. Roof Deck (Unvented) R=20.0 2062.00 ft² f t ² R=b. N/A c. N/A R = f t ² 12. Ducts, location & insulation level 13. Cooling systems 14. Heating systems k B t u / h r 15. Hot water systems a. Propane Cap: 1 gallons EF: 0.59 b. Conservation features None d. N/A R= f t ² Description Area Insulation Area Insulation Area Insulation Area Credits (Performance method)None Area Weighted Average Overhang Depth: Area Weighted Average SHGC: 0.000 ft. 0.266 a. Electric Strip Heat 27.0 COP:1.00 a. Central Unit 35.2 SEER:16.00 k B t u / h r Efficiency Efficiency a. Sup: Attic, Ret: Attic, AH: Garage 6 150 R f t ² 8. Skylights a. U-Factor(AVG): S H G C ( A V G ) : Description Area N/A N/A f t ² I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code compliant features. Builder Signature:Date: Address of New Home:City/FL Zip: *Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. Page 1 of 1 FORM R405-2020 3/5/2021 6:35 AM ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������