Loading...
HomeMy WebLinkAboutProject Information-- wrightsoft Manual S Compliance Report Job: Lot 121 Block 5 Waterston... ® Date: 06.07.12 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Project• • For: ADAMS HOMES = 5346 San Benedetto Place, Fort Pierce, FL 34951 •• III• • Mr, Design Conditions Outdoor design DB: 90.4 OF Sensible gain: 22403 Btuh Entering coil DB: 77.1 cF Outdoor design WB: 77.4`F Latent gain: 4018 Btuh Entering coil WB: 63.5OF Indoor design DB: 75.0 cF Total gain: 26421 Btuh Indoor FIR 50% Estimated airflow: 947 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SplitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00 Actual airflow: 947 cfm Sensible capacity: 22710 Btuh 101%of load Latent capacity: 4736 Btuh 118% of load Total capacity: 27445 Btuh 104%of load SHR: 83% Heating Equipment Design Conditions design DB: 41.0 cF Heat loss: 25950 Btuh Indoor design DB: 70.0 cF Manufacturer's Performance Data at Actual Design Conditions Equipment type: SplitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00 Actual airflow: 947 cfm Output capacity: 27731 Btuh 1071% of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 947 cfm Output capacity: 5.6 kW 74% of load Temp. rise: 18 cF Meets all requirements ofACCA Manual S. Entering coil DB: 69.1 OF Capacity balance: 38 OF Economic balance: -99 OF 1 -F- wrightsoftm 2021-Apr-2608:41.4; •� •� ate-=mw� Rig1t-Sute@Uriversa12021 21.0.02 RSU23828 Page 1 terstore1780BGLtLot121BIk5Waterstone1780BGL.np Calc=MJ8 Hotsefaces:NW Component Constructions Job: Lot 121 Block 5 Waterston... -�+ wrightsc p Date: 06.07.12 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM mmWect intormation For: ADAMS HOMES 5346 San Benedetto Place, Fort Pierce, FL 34951 Design Conditions Location: St Lucie Co Inti, FL, US Indoor: Indoor temperature (OF) Heating 70 Cooling 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 28 °N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration - Daily range (OF) - Wet bulb (OF) - 15 (L 77 ) Method Simplified Wind speed (mph) 15.0 7.5 Construction quality Fireplaces Average 0 Construction descriptions Walls Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh 16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fnsh Partitions 12C-Osw: Fnn wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2N4"wood frm, 16"o.c. stud Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft� Btuh/ftz F ftz`FBtuh BtutVft2 Btuh BtulVft� Btuh n 17 0.201 4.1 5.83 99 4.06 69 ne 291 0.201 4.1 5.83 1698 4.06 1183 se 269 0.201 4.1 5.83 1571 4.06 1094 sw 383 0.201 4.1 5.83 2232 4.06 1555 w 17 0.201 4.1 5.83 99 4.06 69 nw 68 0.201 4.1 5.83 399 4.06 278 all 1046 0.201 4.1 5.83 6098 4.06 4247 ne 30 0.049 19.0 1.42 43 2.59 78 se 30 0.049 19.0 1.42 43 2.59 78 sw 30 0.049 19.0 1.42 43 2.59 78 nw 30 0.049 19.0 1.42 43 2.59 78 all 120 0.049 19.0 1.42 171 2.59 310 250 0.091 13.0 2.64 660 1.31 328 Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.3 it overhang w (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht nw all 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" ne thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang se (5.3 ft window ht, 0.8 It sep.); 6.67 ft head ht sw all 1 OC-m: 2 glazing, dr low-e outr, air gas, mtl no brk frm mat, clr innr, 1/4" se gap, 1/8" thk; NFRC rated (SHGC=0.70); 14.33 ft overhang (6.7 ft window ht, 0.8 ft sep.); 6.67 ft head ht Doors 12 0.330 0 9.57 114 8.22 98 12 0.330 0 9.57 114 20.9 249 23 0.330 0 9.57 224 16.6 389 47 0.330 0 9.57 452 15.6 736 33 0.330 0 9.57 313 17.7 579 33 0.330 0 9.57 313 15.7 512 49 0.330 0 9.57 469 15.7 768 114 0.330 0 9.57 1095 16.2 1859 18 0.550 0 16.0 285 16.2 289 11 JO: Door, mtl fbrgl type nw 20 0.600 6.3 17.4 350 17.6 353 11 DO: Door, wd sc type n 18 0.390 0 11.3 202 11.4 204 ti - wrightsc ft`" 2021-Apr-2608:41:48 �� ^a • ;a,�Fw�u.,� p r Right-Sute®Uriversal2021 21.0.02 RSU23828 Page 1 terstore1780BGL1Lot121Blk5Waterstore1780BGL.np Calc=MJ8 Hotsefaces:NW Ceilings 16B-30ad:Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1/2" 1972 0.032 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 189 0.989 - wrigt>ttsoftw �A m.w:.•w��..,�m Y Bight-Sute®Uriversal202121.0.02RSU23828 terstore1780BGL1Lot121 BIk5Waterstone1780BGL.np Calc= MJ8 Ho se faces: NW 30.0 0.93 1830 1.69 3332 28.7 5425 2021-Apr-26 08A1 AB Page 2 - wrightsoft Project Summary Job: Lot 121 Block 5 Waterston... ® Date: 06.07.12 Entire House By- FLeTCH DEL -AIR HEATING & AIR CONDITIONING 531CODISCOWAY,,SANFORD,FL32771Phone:407-333-2665Fax: 407-333-3853 Web:WWW.DEL-AIR.COM Project• • For: ADAMS HOMES 5346 San Benedetto Place, Fort Pierce, FL 34951 Notes: L. S. 4-26-21 VWK Design Information Weather: St Lude Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 Inside db 70 OF OF Outside db Inside db 90 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 Moisture difference 57 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19749 Ducts Btuh Structure 15440 Btuh 6201 Central vent (0 cfm) 0 Btuh Btuh Ducts Central vent (0 cfm) 6963 0 Btuh Btuh none Humidification 0 Btuh Blower e) 0 Btuh Piping 0 Btuh Equipment load 25950 Btuh Use manufacturer's data y Infiltration Rate/swin multipplier Equipmen1sensible load 1.00 22403 Btuh Method Simplified Construction quality Average Latent Cooling Equipment Load Sizing Fireplaces 0 Structure 2830 Btuh Ducts 1188 Btuh Central vent (0 cfm) 0 Btuh Heatingg Area (ftz) 1780 Cooling 1780 (none) Equipment latent load 4018 Btuh Volume (ft3) 15760 15760 Air changes/hour 0.38 Equiv. AVF (cfm) 100 0.20 Equipment Total Load (Sen+Lat) 26421 Btuh 53 Req. total capacity at 0.75 SHR 2.5 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Trade Make Carrier Model 25HBC530AP03 Trade Cond 25HBC530AP03 AHRI ref 204840289 Coil FX4DNF031 L00 Efficiency 8.5 HSPF AHRI ref 204840289 Efficiency 12.5 EER,15 SEER Heating Input Heating output 28200 Btuh Qa 47OF Sensible cooling Latentcooling 21300 7100 Btuh Btuh Temperature rise 27 Actual airflow 947 OF cfm Total cooling Actual airflow 28400 947 Btuh cfm Air flow factor 0.036 Static pressure 0.40 cfm/Btuh in H2O Air flow factor Static pressure 0.042 0.40 cfm/Btuh in H2O Space thermostat Capacity balance point=38 OF Load sensible heat ratio 0.85 Backup: Input = 6 kW, Output =19107 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. - wrightsoft' 2021-Apr-2608.41.48 Right-Srile®Uriversal 2021 21.0.02 RSU23828 �CAPage 1 ...terstorel780BGL\Lotl21Blk5Waterstone1780BGL.rrp Calc=MJ8 Housefaces:NW -�+ wrightsofta Right-M Worksheet Job: Lot 121 Block 5 Waterston 1... Entire House Date: 06.07.12 DEL -AIR HEATING & AIR CONDITIONING By: FLETCH 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WW W.DEL-AIR.COM 1 Room name Entire House LAU 2 Exposed vvall 1892 8 7.0 ft 3 Room height 8.8 ft 8.0 ft heat/000l 4 Room dimensions 7.0 x 7.0 ft 5 Room area 1792.0 ftz 49.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftz-IF) (Btuh/ftz) or perimeter ft () (Stuh ) or perimeter (ft) (Btuh) Gross N/P/S Heat Cool Gross N/PiS Heat Cool Heat Cool 6 _ VI+; _ Blkwall gucp?ex< _r0201 %' n 583 4.06 29 .,_ 17 gg ,.. 69 ., .... 0 _ -0 W 2A 2ov4". .__. n_ _ 0330 _- n - - - _957. __-822 _., __12 -.-_._0 . _ _. 114 -98 _ . o 0 A 16B 19ad 0.049 ne 1.42 2b9 30 30 43 78 0 -,_-:._0 0 - - - 0 - 0 VjJ Blklnell,stu000e# 0201 ne 5.83 .__..__ -_ 11 2A-2ov---. - ____.0330 _ne - 957 _.. 17.70 _:..�33 W 161319ad 0.049 se ..se _ 1.42 -.2.59 30 30 43 78 0 0 0 0 Blkvall siucooe# 10C m 0201 0550 ' se 5.83 15.95 -4.06 1620 320 18 _ -269 18 - 1571 285 _ 1094 289 _._ _0 0 __ ___ 0 __----.-0 .___,-_ 0 W 2A 2ov._957 16B 19ad 0.049 - 1.42 W_ 15,.67 ,_.. _ _ 33 80 . , . 8 .,,... 3,13 __. _..y..512 . _ __._._0 0 _ O 0 M ..__ 0. 0 _..: _ _'__0. V}I , . Blk v�all, stucoo e 0 201 sw _svv _5.83 259 4.062 30 _.:.... 383 43 - 2232 78 ___ _ 1555 0 - - _ ._ _ O 0 , . _ 0 _. _. 0 _ ,, ._ _.. 0 _ _ ._- 0 _ .._ 2A-2ov_ .___... Blk vall, stu000 e# -` _0.330 0201 __sw_ w __. 9:57 5B3 _15.67 4.06 _ --: - 49 29 _-__ _-_12 17 .._._�_469 99 ----- 768 69 - .0 _ 0 ----. _._ 0 0 _ 0 0 2A2ov --__0,.330 w 9.57 -- 20.92 _ 12, 1. 0 0 0 w_... _ 16619ad__..-._0049 _.riw _ _ 142 259 . _ . _. m30 - .-... _--- -._.30 -114 :-- _. .43 ,_--__249 ... - _.. __.. 0 U _ 0 Blk veil, stucco e# 2A-2ov 0201 0.330 nw nw 5.83 957 4.06 16.61 112 23 68 0 399 224 ._ _78 278 _._ __.__0 0 -_ _ 0 __ . _ 0 _ - ____ 0 11J0 0.600 nw 17AO 1758 20 20 350 389 353 0 0 0 0 0 0 0 0 RR 12C-Osw 0 091 z 64 1 31 268 250 ' 660 _. _ _ 328 _. _ . -_ 38 101 50 _r D_ C .11D0 .- -- _. v.--- - 16B 30ad .---...._0390 _D. -_11,31 _. _11,43 _ __._18 .___-. _ 1$ ___. .202._. 2.04 ___ ...:JB -__..._78 _ _-.__202 :_ F_-. _ 22A ip(- 0.032 -- - 023 1.69 _ 1972 1972 1830 '_ 3332 49 - 49 45 _ ._204. 83 -- _- 0989 _ -_ ._ ._2668 0.00 1792 49 - - 6 c) AED excursion 171 _ ^ n 46 Envelope loss/gain 16568 11831 549 291 12 a) Infiltration 3181 889 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 4 920 0 0 Appliancesrother 1800 600 Subtotal (lines 6 to 13) 19749 15440 549 891 Less external load 0 0 Less transfer 0 0 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 19749 15440 549 891 31 % 45% 6201 6963 31 % 45% 172 402 Total room load Air required (dm) 25950 22403 721 1293 9471 947 26 55 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. A-!'I.F- wrigF�tsoft^ 2608:41:48 ' Right-Srite�alUniversal 2021 21.0.02 RSU23828 2021-Apr-Page 1 terstore1780BGL\Lot121Blk5Waterstone1780BGL.rLp Calc=MJ8 Hoisefaces:NW -+ wrightsoftm Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM Job: Lot 121 Block 5 Waterston 1... Date: 06.07.12 By: FLETCH 1 Room name BR3 BATH2 2 EVosedvdl 26.0 ft 0 ft 3 Room height 8.0 It heaVmol 8.0 ft heat/000l 4 Room dimensions 1.0 x 146.5 ft 9.0 x 6.0 ft 5 Room area 146.5 1112 54.0 ftz Ty Construction U-value Or HTM Area (ft) Load Area (ftz) Load number (Btuhfltz-fl (Btuh/t2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blkvall,slu000eiQ 0201 rj .583 4.06 W 2A2oy_; ;_-.-- -,---0.330_._n-_----;957.__._822.... __ �` _ ..0.-_.__ 0..__._..��0 s0 16B-19ad _ 0.049 . ne_ 1.42 259 0 0 0 0 0 _ 0 -0 0 11 yJ Blk vtell, stucco ext 0201 ne _ _ _ 5.83 .-._ 4:06 _.-_--.-.--_ 104 _ .__.--- � - 88 _ -.- _ .__ 511 . _ 356 _._ ___ 0 --__ - 0 _ _0 2A 2ov_.___- -- - _ _.� � 0.330 - ne --957. _-17.70 _ _ Y 16 _-..�. 0 - --156 --- --- W 16B-19ad.. BIk vv311 stu000 e# 10C 0.049 0201 se se __ 1.42 5 83 259 4.06 _.-- 0 0 0 0 0 . - - p _0 - ____ 0 - ._.: --0 0 _ _ _ 0 - ._.__0 0 . _ _ ._ 0 _ •v. ,0 0 _ _ __ . 0 --- -Q 0 • - -- ---_0 m 0550 se 15.95 1620 0 0 0 0 0 0. 0 0 0.33o se- :,947 :..1.5:67, .._'._ 0 •_. ,.. _0 ._._____ °._0 __.-__ 0 0 ' 0 W _ 16B-19ad 0049 sw 1.42 259 0 9 0 0 -..- .._ _0 0 -- -- 0 ._ __.. 0 _.._-_..._WO 0 uall,sW000ext j4:06 , _ 0 0 _. p _ _ • _ ._ _. 0 0 ._ ...,-- 0 - _..._0 _ 0 - Blk v"l, stucco ext 0330 -0201 _sv w _. 983 5.83 . 5.67 4.06 _ 0 ^0 -___._0 0 _.._.._ 0 0 _ .--. -0 0 --._.__ 0 0 ----- ---__0 0 _ j. ._ 0 0 -.------ z0. 0 _ 2A-2ov_-_ v__ 03- v_v_ _ -,_ -. - -- __ 20.92 0 0 0 Q � 0 W_-- - 16B 19ad..__---_.... _ _. 0.049 -nw. _-- 1,42 ___2.59 . _..._,_ -,-._.',.0 _-- .. _ . _ Q _-. _ : _. 0 ------__ _0 _ _ _ .__ 0 _ _ _--. _ 0 0 -- -_-__0 Blk vtall, stucco ext 2A-2ov 0.201 0230 nw nw 523 957 4.06 16.61 0 0 0 0 0 0 .__ __.._0 0 0 . 0 0 0 __.._ _ _ 0 0 11J0 0.600 nw _ 17.40 1758 0 0 0 0 0 0 0 0 0 0 0 R t 12C Osw 0091 - 2.64 131 104 104 274 - 136 .._._ 0 .. __. __..O _. ,. _0 _ - �D C .11DOw_ .:_ _ _. _...- 16B-30ad -._._0390 n- _,,, 11.31. _ ___1143 0 •:.._ 0 _ ...__ __0 _._.. _...0 __.0 _�. 0 _.: _ ._:0 --------., 0 0032 0.93 .__ 1.69 147 147 136 2.48 54 54 50 91 F - 22A �l- - 0 989 _ 28.68 26 - - --- 7` - 0 - -V _ ~ o - -- H 6 c) AED excursion -38 -4 Envelope loss/gain 1823 991 50 87 12 a) Infiltration 242 68 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Applianoestother 0 0 Subtotal (lines 6 to 13) 2066 1059 50 87 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2066 1059 50 87 15 Dud loads 31 % 459/61 649 478 31 % 45% 16 39 Total room load T Air required (0fm) 1. 2714 1537 66 126 - 99 65 2 5 Calculations approved byACCAto meet all requirements of Manual J 8th Ed ♦I'F' wrigl�tsoft^ �A Right-Sute®Uriversal 2021 21.0.02 RSU23828 2021-Apr-2608:41:48Page 2 terstore1780BGL\Lot121Blk5Waterstore1780BGL.np Calc=MJB Hoisefaces:NW -�- wrightsoft, Right-J® Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 121 Block 5 Waterston 1... Date: 06.07.12 By: FLETCH 1 Room name BR2 MBR 2 Dosed wall 13.0 ft 325 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1 D x 137.5 ft 1.0 x 270.5 ft 5 Room area 137.5 ftz 270.5 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (BtuhHt-'F) (BtuMP) or perimeter (ft) (13 h) or perimeter (ft) (Btuh) Heat Cool Gross N/PPS Heat Cool Gross N/PIS Heat Cool 6 y! _. I--1 BlkKell stucooext D201 n; 5.83 406 r 0 0 T 0 0- 0 p p 2A.2ov .. 330 . _ n . __..957 _.__, 822 __._�: 0 _. , Q 0 __ _.,._ 0 . _.. �0 W 168-19ad 0049 nee 1.42 2.59 0 0 0 0 0 .: .... ___0 0 0 0 11 Blk Kali stucco ext 0201 ne 5 7 4.06 104 88 511 ��� '356 �� 116 �16676 ,2A,2ov ___<s 0330 Rneu 957 17.70.E _ ._, 16 _0 , _ w_151 289..u_. _0. _.. .:-0 .0 _'_.0. W 166` 19ad 0.049 se 1.42 2.59 0 0 0 0 0 0 _ _ 0 Blk wall stucco ext 10C m 0201 0.550 se. se 5$3 4.06 1620 n0 0 0 0 0 0 0 0 0 144 0 , 111 0 649 0 452 10 0330 _se ,.1525 957 15,6Z 41 0 0 , 0 _.. _0 ._._ _ 33 ._ _ $ ,. 313 512. W 166-19a8 0049 sw_ 1.42 259 0 0 0 0 0 0 0 0 BIk Kell stucco ext 0201 sw 5 83 4.06 .15;67 ._ _0 _ 0 . .: w, 0 � ._ _0 _-2.._ 0 0 0 VI! Blk Kell, stucco ext 0.201 w 523 4.06 0 0 0 _ 0 0 __ _ ,-- 0 0 mm 0 2A 2ov „_} 0.330 w, 957 20.92 0 0 0 0 0 0 _0 _ _ ._ _ __.0 _ Blk v,dl, stucco ext 2A-2ov 0201 0.330 nw nw 5,83 957 4.06 16.61. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11J0 0600 nw 17AO 1758 0 0 0 0 0 0 0 0 R 12C Osw'' `0091 A 264 1131 137 0 0 0 0-=' t7 - 0 A --U .__ _ _._1143 _ _. <0 _ 0 . ,_: __ 0._.. _0 :__...___0 .__ .MO C 16B-30ad 0032 0.93 169 138 138 128 232 271 271 252 458 A.000 138 '13 373 "._.. .... _ ..-� __ __., _..}.. .: ..-._. _..... .... ... .._ .:�"... v .. to ......_... ...7 ...._. 1 _ ._.. _ .. ,,.,..s.,._ ... _._ _ . .« _... _. _. ._... ....._ � ___,_. e , 6 c) AED excursion -30 165 Envelope loss/gain 1168 847 2822 2058 12 a) Infiltration 242 68 606 169 b) Room ventilation 0 0 0 0 13 Internal gains: Omupantspn 230 0 0 1 230 Applianoes/other 0 0 Subtotal (lines6 to 13) 1410 915 3427 2457 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1410 915 3427 2457 15 Duct loads 31 % 45 % 443 413 31 % 45 % 1076 1108 Total room load 1853 1328 4504 3566 Air required (dm) 68 56 1 164 151 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. Right-SuiteO Universal 2021 21.0.02 RSU23828 2021-Apr-26 08:41:48 Page 3 terstone1780BGL\Lot121Blk5Waterstore1780BGL.np Calc=MJB Housefaces:NW - wrightsoft° Right-JO Worksheet Job: Lot 121 Block 5 Waterston 1... Entire House Date: 06.07.12 DEL -AIR HEATING & AIR CONDITIONING By: FLETCH 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM 1 Room name MBATH WIC 2 3 Bposed wall Room height 21.0 ft 75 ft 4 Room dimareensions 8.0 ft heat/000l 8.1 ft heat/000l 5 Room 1.0 116.0 f12 x 116.0 ft 1.0 x 87.0 ft 87.0 112 Ty Construction U-value Or HTM Area (ft) Load Area (ft2) Load number (Btuh4t2 (Btuh4t2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blkvall;stu000eM 0201 n 583 .06 _._._0.., _0 0 _ 0 _..- --_.0 .0 - - 0330 W- - 16B-19ad . n . - 957 ---.822 - 0 .......... 0 , 0 __'_ _ 0 ______0 ____0 --- -- 0 0 - 0.049 y/ Blk wall, stu000 ext 0201 ne_ ne __ _ _1.42 6_ 259 4,06 0 0 0 _ - - 6 0 ---- - "-_,Q 0 - p 0 -. - 6 ---_ _ _ "0 - 0 _ 0 -0 __ _.. 0 _ 0 11 L�­(_ 2A-2oy - --------- -:,w._.0.330,_-ne. .57 ,L17,70 __._..0 .. 0 0 0--_---�_0 W _ . 16B 19ad- _ 0 049 BI viall stu000ext 0201 se , se. _ 1.42 5b83 259 4.06 _ _- 0 112 _ 0 112 0 _ _ 653 0 "-455 0 " 0 _ 0 _0 0 0 0 100m 0550 • se 15.95 „ 1620 0 0 0 0 0 0' 0 0 2A26v w H._ .. . _.. _....... _0330 W _. 16B-19ad 0049 __se 957 15.67 ;.. _. 0 _.w _ U " a_ .. 0 _"._._...__� .., 0 . 0 .__.'� 0 0 V� Blk well stuaoo ext . 0201 sw sw 142 5,83 2.59 4 06 0 "6 . 0 _. 56 0 - , _ _ '326 0 . .' j 0 __..._ _ _So 0 _ 80 0 0 _ 350 _-.._ _. 244 L-C 2A2ov_.; - _ ..___ _ ._ 0330 V)/ Blk %dl, slucoo eM 0.201 .-sw. w "__9,57 5.83 1.5.67.__ 4.06 -. 0 0 0 0 0 0 -_;•...__ _._0 0 _ 0 - 0 D 0 ".__ ___ 0. 0 0 Imo` 0330 _ w . _ _ _ 957. _ _.:20.92 0 0 o 0 0 1.42 ._ 259 __. _ _ . .''. _ 0--". _ _0 ----_. -- _�._..,0 _ _ :0_.----_..0 _. _ 0 .__ . Blk well, stu000 e)d 0201 V�--G 2A-2cv 0330 nw nw 5,83 957 4.06 16.61 0 0 0 0 0 0 _ 0 0 ._:_ _. 0 _ __0 _.__.0 0 0 �-D 11i0 0.600 -- -- nw -- ... 17AO _ __ 1758 0 0 0 0 0 0 0 0 0 0 0 0 0 R 12C0snr 0091 2.64 __ .12j _l. 0 _ 0 - 0 0 ._ _ 0 .. _-0 _ --__, 0 .__ _ 0 Al Do _ _ _. -_ . __0390 C 16B-30a_d 0032 .-n- 1.1.31 0.93 1143 1,69 _ '.. 0 ._ . _ 0 _ .__ 0 =•_ 0 - -__ 0 0 _ � ._0 _ _- -0- F 22A tpl- _ - 0 989 . 28,6$ 0.00 116 _. _ _ e 116 116 . _ _ 21 108 602 196 '. 0 88 87 88 v_8 61 148 __.215 _ . _ _0 _. 6 0) AED excursion _48 Envelope losstgain 1689 830 646 371 12 a) Infiltration b) Room ventilation 391 109 140 39 0 0 0 0 13 Internal gains: Oooupan1s@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 2081 939 786 410 Less eMernalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 2081 939 786 410 31 % 45 % 653 424 31 %, 45 % 247 185 Total room load Air required (ctm) 2734 1363 1033 594 100158 38 25 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed ,465A -*- wrigF�tsoft^ 2021-Apr-2608AIA8 Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 4 terstore1780BGL1Lot121Blk5Waterstore1780BGL.rLp Calc=MJ8 Hoisefaces:NW -�+ wrightsoft' Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 121 Block 5 Waterstone 1... Date: 06.07.12 By. FLETCH 1 Room name FAM/HALL(S) Krr 2 Exposed wall 24.0ft 30.5ft 3 Room height 95 It heat/cool 95 It heatbool 4 Room dimensions 1.0 x 451.0 It 1.0 x 290.0 It 5 Room area 451.0 ftz 290.0 ft2 Ty Construdion U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftz-9 (Btuh/R2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blkvdl stuome# 0201 n 5;83 406 0 0 0 0 0 O 0 --o _. 2A2ov;.,: _ _ : .__ __. 0330.,.n, ._ .957. _ __. 822 .:_._.0 4 _ r. 0 0 _._ ,-_ 0 W 1613-19ad_ .__._-.._. 0049 ne 1.42 2.59 30 30 43 78 0 0 0 Blk Hell sluwo ext 0 201 ne 583 , . ,4.06 0 . . , . "' 0 , 0 0 _._. ., 0 ; 0 __ __ ._0 0 .:0 330 _ _ne ..- . 957 _ 17070 __.,.. 0 _ .-...._9 . W-11­1 ,16B-19ad _ _ _0 049 se 1.42 259 30 30 43 78 0 0 0 0 Blk wall; stuao ext 10C m 0201 0.550 se se 5 83 15.95 4.06 1620 64 18 46 18 --- ' ' 269 285 _ _ 187 269 __ ,- __0 0 __. 0 0 0 0 0 ' 0 G 2A2ov_W, - ._. .. 0330 se..... .957 .__;_ 567 R _ v.__0 .__ w._. 0 0 0 0 :., 0 :.. W 16B-1gad 0.049 sw 1.42 2.59 30 30 43 _w..., 78 _: 0 _. .._R_ 0 _. 0 _.._0. 0 1TI - Blk vtell slucao ext -0201 sw, 5 83 4.06 128 95 556 387 96 96 560 390 _,. - _W._557 15,�? ,.., ,.:33 .. 8 .:_ 313 ..._. 512-_-_ _0_ 0 0. Blk wall,stuccoext 0. 0� ��_ 83 4.06 0 0 0 0 _ 0 .._.__;0 0 _ 0 0 W _ 2A 2ov _ 166198d`. _. .__W , _ „0.330 0049, w hw 957 1.42 20.92 _. .259,._._. 0 30 0 30..__, 0 0 �. -_ 0 -_, ., _ 0 0 0 0 Blk utiell, stucco ext 2A-2ov 0 201 0.330 nw nw 5.83 957 4.06 16.61 0 0 0 0 _43 0 0 ...'?8.__._.. 0 0 _0 40 0 .__0._ 20 0 .__.._..0 116 0 81 11J0 0600 nw 17.40 1758 0 0 0 0 20 20 350 0 353 q 12COsiu, 0.091 "2.64 1 1 0 0 0 •_ .6` _ 108 108 ------- 285 -_ 142 C 16B-30ad 0390_.rL-, �11.,31 0.93 11.93 G 0 _.. _"._-0 _0--.-- 0.__ ,, ,___ 0 _.__: M,. 0.032 1.69 _ 538 538 499 909 346 346 321 584 F W 0.00 . .. 461 . -- _ _ 6 c) AED excursion 8 -139 Envelope loss(gain 2780 2604 2506 1411 12 a) Infiltration 727 203 317 89 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupants@ 230 2 460 0 0 Appliancesbther 0 1200 Subtotal (lines 6 to 13) 3507 3267 2823 2699 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3507 3267 2823 2699 15 1 Dud loads 31 % 45 % 1101 1473 31 % 45 % 886 1217 Total room load Air required (cfm) 4608 4740 3709 3917 1 1 168 200 135 166 Calculations approved byACCAto meet all requirements of Manual J 8th Ed �- wrigi�tsoft^ Aft. R gM-Sute® Uriversal 2021 21.0.02 RSU23828 2021-Apr-26 08:41:48 ...terstone1780BGL1Lot121BIk5Waterstone1780BGL.np Calc=tvlJB Houseiaces:NW Page 5 -- wrightsoft' Right-JO Worksheet Job: Lot 121 Block 5 Waterston 1... Entire House Date: 06.07.12 DEL -AIR HEATING & AIR CONDITIONING By: FLETCH 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W WW.DEL-AIR.COM 1 Room name DIN/FOY 2 E)posedvdl 27.7 ft 3 Room height 9.5 ft heaUcool 4 Room dimensions 1.0 x 190.5 It 5 Room area 190.5 ftz Ty Construction U-value Or HTM Area (ft2) Load Area Load number (Btuh/ftz-cq (BtuhHtz) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 vd Blk d slu000ext, 0207 t G n 583 _.._ 406 29 17 99 69 µ y_.. _ .. _._ -_._.. _. 2A 2ov, e,_ 0330 W 16B 19ad _ n 9 57 ____..822 _ _.. _,12 _._ _.. 0 114 �. _ _ - _ 0,049 ne 11.42 259 0 0 0 0 Blkvall 5u000e# 0201 —ne 583 4.06 O __.0 _ ._0330 ne_ _.._.957, _: 17,70 --_._:.. _0 W 1613-19ad _..0049 _se 1.42 2.59 0 0 0 0 Blkvell stu000eM 0201 tOC m'., 0.550 se : se 583 1595 4.06 0 0 1620 0 0 0 A _ . 2A 2ov __: _0 330 ,,,957 15.67 0 p 0 +, W . 16B-19ad 0049 - sw 1.42 _. _. 259 -0 '- p . - 0 VN k .: Blk Drell stu000 e 0201 `'-C -sw 5 83 4;06 " ` 92 76 441 307 - 2A2oy__.. _._. _ =0330 __sw_. :957 _,___15,67 4 156 256 Blk u�all, stucco ext 0.201 w 5B3 , _L_,_16 .• . 4.06 29 17 99 - 69 2A 2oy_ _- _ _ 0.330 W _.., 16B-19ad_. .� ._ . , _.. -`0049 -w ,nw 9.57 _ 1.92 20.92 12 1, _ _ -_114 _ y 2a9 � 249 Blk mll, stucco ext 0.201 2A-2ov 0.330 nw nw 5.83 9.57 _ ._.___ .� _� _Q ..._•.._ _.0._._ 4.06 72 49 283 16.61 23 0 224 �.._0 197 389 � -_-.-. 11J0 0.600 nw 17.40 17b8 0 0 0 0 12C Osw 0 091 L--0' _ 2.64 MI 0 0 0 0 '- 11D0 ,_0390 C 16B-30ad :n.a 1131 .11.43 _ .e_-, 0 __ T: _0 . :_,.. -_0 _- ___.. _0 _...._. _ 0032 093 1.69 227 227 210 383 22A Wh: �_- 0.989 __. - - -_ 6 c) AED excursion 324 Envelopeloss/gain 2534 2341 12 a) Infiltration 516 144 b) Room ventilation 0 0 13 Internal gains: Oocupantst7a 230 1 230 Appliancestother 0 Subtotal (lines 6 to 13) 3050 2716 Less extemalload 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 3050 2716 151 Duct loads 31 % 45%1 958 1225 Total room load 4008 3940 Air required (cfm) 1461 167 Calculations approved byACCA to meet all requirements of Manual J 8th Ed -* wr➢ghtsoTt^ Right-Su2021-Apr-2608.41A8 te®Uriversal 2021 21.0.02 RSU23828 Page 6 terstone1780BGLtLol121BIk5Waterstone1780BGL.rup Calc=MJS Hosefaces:NW - wrightsofto Duct System Summary Job: Lot 121 Block 5 Waterston... Date: 06.07.12 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: WW W.DEL-AIR.COM For: ADAMS HOMES 5346 San Benedetto Place, Fort Pierce, FL 34951 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170/0.170 in H2O 0.312 in/100ft 947 cfm 109 Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.312 in/100ft 947 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH2 c 126 2 5 0.460 4.0 Ox 0 VIFx 3.9 70.0 BR2 h 1853 68 56 0.420 6.0 Ox 0 VIFx 11.0 70.0 BR3 h 2714 99 65 0.443 6.0 Ox 0 VIFx 6.7 70.0 DIN/FOY c 3940 146 167 0.374 7.0 Ox 0 VIFx 20.9 70.0 FAMMALL(S) c 4740 168 200 0.434 8.0 Ox 0 VIFx 8.3 70.0 KIT c 3917 135 166 0.381 7.0 Ox 0 VIFx 19.1 70.0 LAU c 1293 26 55 0.456 4.0 Ox 0 VIFx 4.5 70.0 MBATH h 2734 100 58 0.312 6.0 Ox 0 VI Fx 24.0 85.0 st1 MBR h 4504 164 151 0.322 8.0 Ox 0 VIFx 20.7 85.0 st1 WIC h 1033 38 25 1 0.333 4.0 Ox0 VIFx 17.1 85.0 st1 Name Trunk Type Htg (cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st1 PeakAVF 302 233 0.312 553 10.0 0 x 0 VinlFlx Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR(fpm) Veloc Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat! Trunk rb2 Ox 0 947 947 0 0 0 0 Ox 0 VI Fx wrightsoft- 2021-Apr-26 08:4149 ^� a VDmksLb. NethewvCorryM RigFt-Sute@UNversa12021 21.0.02 RSU23828 terstore1780BGL\l.ot121Blk5Waterstone1780BGL.np Calc=MJ8 Hoisetaces:NW Page 1 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 121 Block 5 Waterstone 1780 BGL Builder Name: ADAMS HOMES Street: 5346 San Benedetto Place Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Owner: Jurisdiction: 661000 Design Location: FL, ST LUCIE_CO_INTL COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealin material. g Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace wall . Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and w s ring, Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids 4/26/2021 8:53 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 4/26/2021 8:52:45 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Duct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job' Information Builder: ADAMS HOMES Community: Lot: NA I Address: 5346 San Benedetto Place City: Fort Pierce State: FL Zip: 34951 Duct"Leakage Test Results System 1 cfm25 System 2 cfm25 System 3 cfm25 Sum of others cfm25 Total of all cfm25 - 1780 Qn Total of all Total Conditioned systems Square Footage PASS [:]FAI L Q Pre'scrliptive Method;. cfm25 (Total). %T9',q "substantially leak free" QrnTotal,must'be less than or equal�to 04 if,air handler unit isinstalled. If -air handler unit is;;not'; installed, Qn TOial.must", i6e less tf anzor equal;to 0 03 -This testing mett od,meets therequiremenfs in accordance with,Sectlon;R4,03.3:3. Is the air handlet unit, installed during testing? O YES (o° n• F Q Performance/ERI Method: 6fm25 (Out"or Totaiy,.., To qualify'using this method, Qn must not be greater thanthe,' proposed'duct leakage 'Q'n specified on Form R405-2020'or R40672020 3s Leakage,Type selected on Form Qn specified on Form R405-2020 R4D5 2020 (EnergyCalc) or R406 2020 ;'-(Energy.Calc' or R40 "2020 Proposed Qn 0.05 Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. I;Testing Corripany` Company Name: Phone: I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Signature of Tester: Printed Name of Tester: License/Certification #: Date of Test: Issuing Authority: 4/26/2021 8:53:40 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: r c Job Information 'n. Builder: ADAMS HOMES Community: Lot: NA Address: 5346 San Benedetto Place City: Fort Pierce State: FL Zip: 34951 .7, Alr Leakage Test Results Rass�ng results must meet etther'the Performance, Prescnptrve, or ER/ Method ''y � PRESCRIPTIVE METHOD The bwlding or dwellmg<urni 'shall b'e�ested and verrfied, as having an air leakage rate of not,exceeding 7 air; _`j t changes per hour at'a pressure of 0 2^inch w g.'(50 Pascals) m.Climate Zones 1 and 2 l 4 PERFORMANCE or ERI METHOD The building or dwelling unit shall be tested and,verrfled:as having an air'Ieakage rate of not exceeding the selected ACH,(50) value, as shown on Form R405r2020 (Performance) or R406-2020`(ERI} section labeled"as infiltrationsubseciion ACH50: ACH(50) specified on =Form R405 2020 Energy Calc (Performance) or R406 2020 (ERQ < 6.500 x 60 _ 15664 = Method for calculating building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans F-1 PASS • Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. :Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Printed Name of Tester: License/Certification #: Date of Test: Issuing Authority: 4/26/2021 8:53:27 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods F7777S 5346 San Benedetto Place Permit Number: Fort Pierce , FL , 34951 ivlHntuN► I UKY KLIQUIKEMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 4/26/2021 8:53 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ElR403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105"F (41"C) or below 55°F (13"C) shall be insulated to a minimum of R-3. EJ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 4/26/2021 8:53 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) EiR403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'Y2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140OF (38°C to 600C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main bumer(s) of combustion types of service water -heating systems to be turned off. EiR403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. EJ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 4/26/2021 8:53 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas, 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 4/26/2021 8:53 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 QR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal El efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. El R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 4/26/2021 8:53 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5