APPROVED BOBO REVISION- MANUAL J
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Project Summary MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information CHRISTOPHER AND DIANE BOBO, PACE 2000, INC.For: 4955 S. INDIAN RIVER DRIVE, FORT PIERCE, FL 34982 Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh35010 Struc ture Btuh25808 Ducts Btuh7725 Ducts Btuh5169 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh42735 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh29428 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3364 Ducts Btuh2972 Central vent (0 cfm)Btuh0 CoolingHeating (none) 26992699Area (ft²)Equipment latent load Btuh6337 3020130201Volume (ft³) Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh35765 Equiv. AVF (cfm)81161 Req. total capacity at 0.70 SHR ton3.5 Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1642AJ1 AHRI ref Coil RH1T4821STAN AHRI ref 201290216 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW12.3 Sensible cooling Btuh28000 Heating output Btuh41887 Latent cooling Btuh12000 Temperature rise °F28 Total cooling Btuh40000 Actual air flow cfm1383 Actual air flow cfm1383 Air flow factor cfm/Btuh0.032 Air flow factor cfm/Btuh0.045 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.83 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House UTILITY 2 Exposed wall 245.9 ft 28.0 ft 3 Room height 11.2 ft 10.0 heat/coolft 4 Room dimensions ft20.0x8.0 5 Room area 2699.0 ft²160.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 805 700 2801 1531 200 176 705 385 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 60 0 941 806 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 21 0 335 287 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 24 24 262 248 24 24 262 248 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 705 499 1996 1091 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 7 2 113 188 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 108 6 1693 3281 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 7 2 113 117 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 36 2 564 672 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 48 2 753 904 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 576 519 2078 1136 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 12 12 188 161 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 45 45 706 604 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 584 452 1810 989 80 80 320 175 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 12 1 188 352 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 24 1 376 729 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 96 4 1505 2942 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 2699 2699 4279 3693 160 160 254 219 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2699 246 9351 0 160 28 1065 0 6 c) AED excursion 0 -98 Envelope loss/gain 30053 19730 2605 929 12 a) Infiltration 4957 1328 520 139 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 4750 0 Subtotal (lines 6 to 13)35010 25808 3125 1068 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 72 26 14 Subtotal 35010 25808 3197 1094 15 Duct loads 22%20%7725 5169 22%20%706 219 Total room load 42735 30977 3903 1313 Air required (cfm)Air required (cfm)1383 1383 126 59 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 4 HALL 2 Exposed wall 18.9 ft 2.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft214.5x1.0 ft5.0x6.0 5 Room area 214.5 ft²30.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 20 20 80 44 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 190 160 641 350 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 30 30 470 403 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 215 215 340 293 30 30 48 41 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 215 19 719 0 30 2 76 0 6 c) AED excursion -163 -8 Envelope loss/gain 2170 884 204 77 12 a) Infiltration 353 94 37 10 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 800 0 Subtotal (lines 6 to 13)2523 1778 241 87 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 60 22 -241 -87 14 Subtotal 2583 1800 0 0 15 Duct loads 22%20%570 360 22%20%0 0 Total room load 3153 2160 0 0 Air required (cfm)Air required (cfm)102 96 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 3 WIC 4 2 Exposed wall 0 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft8.0x6.0 ft37.5x1.0 5 Room area 48.0 ft²37.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 48 48 76 66 38 38 59 51 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 48 0 0 0 38 0 0 0 6 c) AED excursion -6 -4 Envelope loss/gain 76 60 59 47 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)76 60 59 47 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 72 26 0 0 14 Subtotal 148 86 59 47 15 Duct loads 22%20%33 17 22%20%13 9 Total room load 181 103 73 56 Air required (cfm)Air required (cfm)6 5 2 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 WIC 3 2 Exposed wall 12.0 ft 0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft12.0x12.0 ft8.0x4.0 5 Room area 144.0 ft²32.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 120 105 420 230 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 15 15 235 201 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 144 144 228 197 32 32 51 44 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 144 12 456 0 32 0 0 0 6 c) AED excursion -175 -4 Envelope loss/gain 1340 453 51 40 12 a) Infiltration 223 60 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1400 0 Subtotal (lines 6 to 13)1563 1913 51 40 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 53 20 53 20 14 Subtotal 1616 1932 103 60 15 Duct loads 22%20%357 386 22%20%23 12 Total room load 1972 2319 126 72 Air required (cfm)Air required (cfm)64 104 4 3 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALLWAY BATH 2 2 Exposed wall 4.0 ft 6.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft18.0x4.0 ft6.0x12.0 5 Room area 72.0 ft²72.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 40 40 160 88 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 60 48 192 105 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 12 12 188 161 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 72 72 114 99 72 72 114 99 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 72 4 152 0 72 6 228 0 6 c) AED excursion -17 -33 Envelope loss/gain 426 169 723 332 12 a) Infiltration 74 20 111 30 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)501 189 834 361 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -501 -189 195 69 14 Subtotal 0 0 1029 431 15 Duct loads 22%20%0 0 22%20%227 86 Total room load 0 0 1256 517 Air required (cfm)Air required (cfm)0 0 41 23 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 2 BEDROOM 2 2 Exposed wall 2.0 ft 30.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft2.0x12.0 ft12.0x12.0 5 Room area 24.0 ft²144.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 60 60 240 131 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 120 84 336 184 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 0 0 0 0 36 2 564 1094 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 20 20 80 44 120 120 480 263 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 24 24 38 33 144 144 228 197 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 24 2 76 0 144 30 1141 0 6 c) AED excursion -7 -130 Envelope loss/gain 194 69 2991 1738 12 a) Infiltration 37 10 557 149 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)231 79 3547 1887 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -231 -79 195 69 14 Subtotal 0 0 3742 1956 15 Duct loads 22%20%0 0 22%20%826 391 Total room load 0 0 4568 2348 Air required (cfm)Air required (cfm)0 0 148 105 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name DINING RM FOYER 2 Exposed wall 13.0 ft 7.0 ft 3 Room height 13.0 heat/coolft 13.0 heat/coolft 4 Room dimensions ft15.0x13.0 ft9.0x7.0 5 Room area 195.0 ft²63.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 169 126 504 275 91 43 172 94 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 7 2 113 117 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 36 2 564 672 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 48 2 753 904 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 195 195 309 267 63 63 100 86 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 195 13 494 0 63 7 266 0 6 c) AED excursion 66 175 Envelope loss/gain 1985 1398 1291 1259 12 a) Infiltration 314 84 169 45 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2298 1482 1460 1304 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 723 544 -1460 -1304 14 Subtotal 3021 2026 0 0 15 Duct loads 22%20%667 405 22%20%0 0 Total room load 3688 2431 0 0 Air required (cfm)Air required (cfm)119 109 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name STUDY LIVING RM 2 Exposed wall 10.0 ft 17.0 ft 3 Room height 12.0 heat/coolft 13.0 heat/coolft 4 Room dimensions ft122.0x1.0 ft410.0x1.0 5 Room area 122.0 ft²410.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 120 77 308 168 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 7 2 113 188 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 36 2 564 1094 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 221 125 501 273 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 96 4 1505 2942 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 122 122 193 167 410 410 650 561 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 122 10 380 0 410 17 646 0 6 c) AED excursion -122 926 Envelope loss/gain 1559 1494 3302 4703 12 a) Infiltration 223 60 410 110 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1781 1554 3713 4813 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 526 469 409 365 14 Subtotal 2307 2023 4121 5178 15 Duct loads 22%20%509 405 22%20%909 1036 Total room load 2816 2428 5031 6214 Air required (cfm)Air required (cfm)91 108 163 277 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 9 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN NOOK 2 Exposed wall 0 ft 19.0 ft 3 Room height 12.0 heat/coolft 12.0 heat/coolft 4 Room dimensions ft183.0x1.0 ft13.0x11.0 5 Room area 183.0 ft²143.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 96 75 299 163 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 21 0 335 287 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 132 108 432 236 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 24 1 376 729 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 183 183 290 250 143 143 227 196 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 183 0 0 0 143 19 722 0 6 c) AED excursion -172 130 Envelope loss/gain 290 78 2391 1741 12 a) Infiltration 0 0 423 113 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 1800 0 Subtotal (lines 6 to 13)290 1878 2815 1855 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 36 13 14 Subtotal 290 1878 2851 1868 15 Duct loads 22%20%64 376 22%20%629 374 Total room load 354 2254 3480 2241 Air required (cfm)Air required (cfm)11 101 113 100 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 10 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M BATH M TOILET 2 Exposed wall 25.0 ft 3.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft190.0x1.0 ft3.0x8.0 5 Room area 190.0 ft²24.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 110 90 360 197 30 30 120 66 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 20 0 314 269 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 140 128 513 280 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 12 1 188 352 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 190 190 301 260 24 24 38 33 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 190 25 951 0 24 3 114 0 6 c) AED excursion 3 -10 Envelope loss/gain 2626 1360 272 89 12 a) Infiltration 464 124 56 15 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)3091 1484 328 104 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 3091 1484 328 104 15 Duct loads 22%20%682 297 22%20%72 21 Total room load 3773 1781 400 125 Air required (cfm)Air required (cfm)122 80 13 6 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 11 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC MASTER BEDROOM 2 Exposed wall 8.0 ft 41.0 ft 3 Room height 10.0 heat/coolft 11.0 heat/coolft 4 Room dimensions ft8.0x8.0 ft311.0x1.0 5 Room area 64.0 ft²311.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 80 80 320 175 209 169 677 370 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 40 0 627 537 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 165 129 517 282 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 26.0526.05 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 30.3830.38 0 0 0 0 36 2 564 1094 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 16.3116.31 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.6818.68 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 15.6815.68 18.8318.83 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 66 66 264 144 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 15.6815.68 13.4313.43 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 11 11 44 24 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 29.3029.30 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.3830.38 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 15.6815.68 30.6530.65 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 64 64 101 88 311 311 493 426 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 64 8 304 0 311 41 1559 0 6 c) AED excursion -25 -323 Envelope loss/gain 726 237 4745 2554 12 a) Infiltration 149 40 837 224 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 750 Subtotal (lines 6 to 13)874 277 5582 3528 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 874 277 5582 3528 15 Duct loads 22%20%193 55 22%20%1232 706 Total room load 1067 332 6814 4233 Air required (cfm)Air required (cfm)35 15 221 189 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-11 10:51:45 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 12 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet MARCH 11, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name PANTRY 2 Exposed wall 0 ft 3 Room height 10.0 heat/coolft 4 Room dimensions ft4.0x4.0 5 Room area 16.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 .G 2 glazing, clr low-e 0.560 n 15.68 13.43 0 0 0 0 .G 2 glazing, clr low-e 0.560 n 15.68 13.43 0 0 0 0 .D 11D0 0.390 n 10.92 10.34 0 0 0 0 11 W 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.560 e 15.68 26.05 0 0 0 0 G 2 glazing, clr low-e 0.560 e 15.68 30.38 0 0 0 0 G 2 glazing, clr low-e 0.560 e 15.68 16.31 0 0 0 0 G 2 glazing, clr low-e 0.560 e 15.68 18.68 0 0 0 0 G 2 glazing, clr low-e 0.560 e 15.68 18.83 0 0 0 0 W 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.560 s 15.68 13.43 0 0 0 0 G 2 glazing, clr low-e 0.560 s 15.68 13.43 0 0 0 0 W 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.560 w 15.68 29.30 0 0 0 0 G 2 glazing, clr low-e 0.560 w 15.68 30.38 0 0 0 0 G 2 glazing, clr low-e 0.560 w 15.68 30.65 0 0 0 0 C 16X19-0md 0.408 -1.59 1.37 16 16 25 22 F 22A-tph 1.358 -38.02 0.00 16 0 0 0 6 c) AED excursion -2 Envelope loss/gain 25 20 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)25 20 Less external load 0 0 Less transfer 0 0 Redistribution 40 15 14 Subtotal 65 35 15 Duct loads 22%42%14 15 Total room load 79 50 Air required (cfm)3 2 2021-Mar-11 10:51:53 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Duct System Summary MARCH 11, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information CHRISTOPHER AND DIANE BOBO, PACE 2000, INC.For: 4955 S. INDIAN RIVER DRIVE, FORT PIERCE, FL 34982 CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1383cfm1383 Total effective length (TEL)ft184 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3115.07.7VlFx0x05.01.00023411256hBATH 2 st4135.033.6VlFx0x04.01.00056181hBATH 3 st3115.08.1VlFx0x07.01.0001051484568hBEDROOM 2 st1115.019.2VlFx0x07.01.000104642319cBEDROOM 3 st4135.036.2VlFx0x07.01.000961023153hBEDROOM 4 st2115.030.1VlFx0x07.01.0001091193688hDINING RM st1115.022.4VlFx0x05.01.000101112254cKITCHEN st5135.049.5VlFx0x08.01.000139813107cLIVING RM st5135.045.9VlFx0x08.01.000139813107cLIVING RM-A st5135.048.5VlFx0x06.01.000801223773hM BATH st5135.046.5VlFx0x04.01.000613400hM TOILET st5135.047.8VlFx0x04.01.00015351067hM WIC st2115.035.4VlFx0x07.01.000951103407hMASTER BEDROOM st2115.034.6VlFx0x07.01.000941103407hMASTER BEDROOM-A st4135.036.2VlFx0x05.01.0001001133480hNOOK st1115.017.0VlFx0x04.01.0002379hPANTRY st2115.030.2VlFx0x07.01.000108912428cSTUDY st4135.040.2VlFx0x06.01.000591263903hUTILITY st1115.017.3VlFx0x04.01.00034126hWIC 3 st4135.033.2VlFx0x04.01.0003256cWIC 4 2021-Mar-11 10:51:53 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\BOBO RESIDENCE.rup Calc = MJ8 Front Door faces: E Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st5 Peak AVF 332 377 1.000 692 10.0 0x0 VinlFlx st2 st2 Peak AVF 763 783 1.000 733 14.0 0x0 VinlFlx st4 Peak AVF 349 262 1.000 790 9.0 0x0 VinlFlx st1 st1 Peak AVF 431 472 1.000 601 12.0 0x0 VinlFlx st3 Peak AVF 188 128 1.000 540 8.0 0x0 VinlFlx Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 13830 1383 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������