- wrightsoft® Manual S Compliance Report Date: 06.07.12
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phom:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Project• •
For: ADAMS HOMES
5428 Lugo Street, Fort Pierce, FL 34951
Cooling Equipment
Design Conditions
Outdoor design DB:
90.4OF
Sensible gain: 20199
Btuh
Outdoor design W B: 77.4 OF
Latent gain: 4018
Btuh
Indoor design DB:
75.0 OF
Total gain: 24217
Btuh
Indoor RH:
50%
Estimated airflow: 947
cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type:
SpIitASHP
Manufacturer:
Carrier
Model: 25HBC530AP03+FX4DNB031 L00
Actual airflow:
947 cfm
Sensible capacity:
20961 Btuh
104%of load
Latent capacity:
6086 Btuh
151 % of load
Total capacity:
27047 Btuh
112% of load SHR: 770/.
Heating Equipment
Design Conditions
Outdoor design DB: 41.0 OF Heat loss: 23276 Btuh
Indoor design DB: 70.0 cF
Manufacturer's Performance Data at Actual Design Conditions
Equipmenttype: SpIitASHP
Manufacturer: Carrier Model: 25HBC530AP03+FX4DNB031 L00
Actual airflow: 947 cfm
Output capacity: 26646 Btuh 114% of load
Supplemental heat required: 0 Btuh
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 947 cfm
Output capacity: 6.6 kW 96%of load Temp. rise: 22 OF
Meets all requirements ofACCA Manual S.
Entering coil DB: 76.5OF
Entering coil WB: 63.8cF
Entering coil DB: 69.5OF
Capacity balance: 36 OF
Economic balance: -99 OF
wrighttsoft- 2021-Mar-0816:13:42
^.• „•w� ��m-m Right-Sute®Uriversal 2021 21.0.02 RSU23828 ACCK...Waterstorel780AGR\LotBBlklWaterstonel780AGR.np CaIc=MJ8 HOrsefaces:NW Page 1
Component Constructions Job: Lot 8 Block 1 Waterston ...
-- wrightsoft® p Date: 06.07.12
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY SANFORD, FL 32771 Prnne:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
•ject information
For:
ADAMS HOMES
5428 Lugo Street, Fort Pierce, FL 34951
Design
Conditions
Location:
St Lucie Co Intl, FL, US
Indoor:
Indoor temperature (OF)
Heating
70
Cooling
75
Elevation: 26 ft
Design TD (OF)
29
15
Latitude: 28 °N
Relative humidity (%).
30
50
Outdoor:
Heating Cooling
Moisture difference (grib)
2.4
56.9
Dry bulb (T)
41 90
Infiltration:
Daily range (OF)
Wet bulb (OF)
- 15 (L
- 77
) Method
Simplified
Wind speed -(mph)
15.0 7.5
Construction quality
Fireplaces
Average
0
Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain
ft' BtutyftzIF ftz°FBtuh Btutff Btuh Btur✓ft2 Btuh
Walls
Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh
16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum
board int fnsh
Partitions
12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int
fnsh, 2'k4" wood frm, 16" o.c. stud
Windows
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
thk; NFRC rated (SHGC=0.21); 50% drapes, -medium; 1.3 ft overhang
(5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht
2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang
(5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht
1 OC-m: 2 glazing, dr low-e outr, air gas, mtl no brk frm mat, clr innr, 1/4"
gap, 1/8" thk; NFRC rated (SHGC=0.70); 14.33 ft overhang (6.7 ft window
ht, 0.8 ft sep.); 6.67 ft head ht
n
17
0.201
4.1
5.83
99
4.06
69
ne
383
0.201
4.1
5.83
2232
4.06
1555
se
269
0.201
4.1
5.83
1571
4.06
1094
sw
291
0.201
4.1
5.83
1698
4.06
1183
w
17
0.201
4.1
5.83
99
4.06
69
nw
68
0.201
4.1
5.83
399
4.06
278
all
1046
0.201
4.1
5.83
6098
4.06
4247
ne
30
0.049
19.0
1.42
43
2.59
78
se
30
0.049
19.0
1.42
43
2.59
78
sw
30
0.049
19.0
1.42
43
2.59
78
nw
30
0.049
19.0
1.42
43
2.59
78
all
120
0.049
19.0
1.42
171
2.59
310
250
0.091
13.0
2.64
660
1.31
328
n
12
0.330
0
9.57
114
8.22
98
w
12
0.330
0
9.57
114
20.9
249
nw
23
0.330
0
9.57
224
16.6
389
all
47
0.330
0
9.57
452
15.6
736
ne
49
0.330
0
9.57
469
17.7
868
se
33
0.330
0
9.57
313
15.7
512
sw
33
0.330
0
9.57
313
15.7
512
all
114
0.330
0
9.57
1095
16.5
1892
se
18
0.550
0
16.0
285
16.2
289
a
Doors
11J0: Door, mtl fbrgl type nw 20 0.600 6.3 17.4 350 17.6 353
11 DO: Door, wd sc type n 18 0.390 0 11.3 202 11.4 204
1 " wrightsc ft® 2021-Mar-0816:13:42
�� ,•k•,�.,eM1,.„....,,.�m,.•, Right-SuteC5lUriversa12021 21.0.02 RSU23828 Page 1
Waterstone1780AGR\Lot8Blkl Waterstore1780AGR.rLp Calc= W8 Hotae faces: NW
41
Ceilings
16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1 /2"
gypsum board int fnsh
Floors
22A-tpl: Bg floor, light dry soil, on grade depth
1972
0.032
30.0
0.93
1830
1.69
3332
189
0.989
0
28.7
5425
0
0
-tz. -Pk- wrightsoft® 2021-Mar-0816:13:42
N,e h w•w�•.•.�m�m Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2
Waterstore1780AGR\Lot8BIklWaterstore1780AGR.rup Calc=MJ8 Hoisefaces:NW
wri htsoft Project Summary Job: Lot 8 Block 1 Waterston ...
g Date: 06.07.12
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Proiect Information
For: ADAMS HOMES
5428 Lugo Street, Fort Pierce, FL 34951
Notes: L. S. 3-8-21 VWK
Design • •
Weather: St Lucie Co Infl, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 41
Inside db 70
OF
OF
Outside db
Inside db
90
75
OF
OF
Design TD 29
cF
Design TD
15
OF
Daily range
L
Relative humidity
50
%
Moisture difference
57
grAb
Heating Summary
Sensible Cooling Equipment Load
Sizing
Structure 19749
Ducts
Btuh
Structure
15302
Btuh
3528
Central vent (0 cfm) 0
Btuh
Btuh
Ducts
Central vent (0 cfm)
4897
0
Btuh
Btuh
none
e)
Humidification 0
Btuh
Blower
0
Btuh
Piping 0
Btuh
Equipment load 23276
Btuh
Use manufacturer's data
y
Infiltration
Rate/swin multipplier
EquipmenKensible load
1.00
20199
Btuh
Method Simplified
Construction quality Average
Latent Cooling Equipment Load Sizing
Fireplaces
0
Structure
2830
Btuh
Ducts
1188
Btuh
Central vent (0 cfm)
0
Btuh
Heatingg
Area (ft2) 1780
Coolingg
1780
(none)
Equipment latent load
4018
Btuh
Volume (ft3) 15760
15760
Air Changes/hour 0.38
0.20
Equipment Total Load (Sen+Lat)
24217
Btuh
Equiv. AVF (cfm) 100
53
Req. total capacity at 0.75 SHR
2.2
ton
Heating Equipment Summary
Cooling Equipment Summary
Make Carrier
Trade CARRIER
Make Carrier
Trade CARRIER
Model 25HBC530AP03
AHRlref 204840289
Cond 25HBC530AP03
Coil FX4DNB031L00
Efficiency 8.5 HSPF
AHRI ref 204840289
Efficiency 12.5 EER,
15 SEER
Heating input
Heating, output 28200
Btuh@47°F
Sensible cooling
Latentcooling
21300
7100
Btuh
Btuh
Temperature rise 27
Actual airflow 947
OF
cfm
Total cooling
Actual airflow
28400
947
Btuh
cfm
Air flow factor 0.041
Static pressure 0.40
cfm/Btuh
in H2O
Air flow factor
Static pressure
0.047
0.40
cfm/Btuh
in H2O
Space thermostat .
Capacity balance point = 36 OF
Load sensible heat ratio
0.83
Backup:
Input = 7 kW, Output = 22460 Btuh,100 AFUE
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-* wrigl�tsoft' ^- •^ •° - Right-SuteOUriversal 2021 21.0.02 RSU23828 2021-Mar-0816:13:42
ACC`...Waterstone1780AGRIot6BIklWaterstore1780AGR.rip Calc=W8 Housefaces:NW Page 1
- wrightsoftRight-M Worksheet
Entire House
DEL -AIR HEATING &AIR CONDITIONING
531CODISCOWAY, SANFORD,FL32771. Phone: 407-333-2665Fax: 407-333-3853 Web:WWW.DEL-AIR.COM
Job: Lot 8 Block 1 Waterston 178...
Date: 06.07.12
By: FLETCH
1
Room name
Entire House
LAU
2
E)qcosedvall
1892 It
7.0 ft
3
Room height
8B It
8.0 ft heat/cool
4
Room dimensions
7.0 x 7.0 ft
5
Room area
1792.0 ftz
49.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ft')
Load
Area (ftz)
Load
number
(Btuh/ft-19
(Btuh/ft2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
Blkwall stu000eM0201
n
583
4.06
29
1G57
997777PC9
0
x D,
77777Q°;.0:
W
161319ad
0049
ne
1.42
259
30
30
43
78
0
0
0
0
Blkvl stu000ext,;
0201
ne"
583,
�4062
383
2232
1555
0
„00
-r0
11
?A2ov Apr
_ Q330
_fie
9,57177Q
49
- , .U- 0469
�_-.' 868
s 4 0
m0,`0
".Q
W
161319ad
(k wall stucco ext
r
0049
0 20)
se
se :
1.42
5 83
2.59
4 06
30
32076
30
43
1285
_ 78
1289
0
0
0
0
10C m
0550
,use'
1595
1620
i 18i8
0
0
U
`,R0
.33
.1
a� i5
1222&12
W
166 19ad
0.049
sw
1.42
2.59
30
30
43
78
.0 -
0
0
w
0
0
I`Blkwall
stUcooext
0201
dsw;
583
40Q
a 324
291
1698
1183
0
0�
;0
0`
t
2A2ov,x._ ;,
r_»xw0330
.sw
957
15:67_.•X
w33,
�`t$'�313512.,�
Q,�QI,
Q�
0
Blk wall, stucco e)d
0.201
w
5.83
4.06
29
17
99
69
0
0
.�
0
0
2A 2ov
0230
w
9.57
20.92
12
1
114
249
0
0
0
0
y11
1619ad c >s.
0049
;.OW..�,i,42
,.k 259
s 30
,, 30.
f3
f
Blk wall, stucco ext
2A-2ov
0.201
0,330
nw
nw
5.83
9.57
4.06
16.61
112
23
68
0
399
224
�78
' 278
389
w`
0
0
0'
0
0
0
0
11JO
0.600
nw
1740
1758
20
20
350
353
0
0
0
0
0
w
12C Osw a' j
a ,0091
r 264
1
268
s 250
660
328
i 56
38
"'' 1 Ol
a 50
„11D.O s
�,0390.
�n
_ 1]31.3
ii,g3'
18
18
ux «202
�2041$,s.:
J8'
H
C
161330ad
0.032
0.93
1.69
1972
1972
1830
3332
49
49
,202
45
�.c204
83
.F
22A Vl, w w
0 989
r..
ZM..«.3:r;.9`
11
.............
u.uS'.,,,,,.... -.k�. ,w..� „a
Y�.-.7'.fiC........
,.w
......,�..uuf
.a. ��
�.mus....t d
.0 .....w.
{
'"'.9.
:;Y7
•?^
S^` .."^G^`^
`�,Fe..,o-.
-..;ram
wa p .,.-«.
.e. .......
.........-,..
...z w ,«..2:..a
.......:..
.,..,= _
...
.. .........
.o..-.J
«-.,.
z '.4.�..sa,.,
c...«�.. � .�m,....o...o�.
,...�...,:.,,,d,w..T.....
,.,.C,,,....,. :
-..,.xr.�..sx,_s.. =
p,_,€a.......s...r.
� ,".�.,w
-.....
.__......y..�
_...,e,......
•- �
°_....,.ram,^
..�...-.wFu...
..+n,.e�
,....„.
22
m.,_.....xu.. ,µ
t
E,..-x.,.,a„a
2....,u...vr
....c.
s: r¢Su
...Z....a� �u.aY":3
r^.1r...:' ...o
...,....=
v...::a w...,..v....ti
.........-A._����
ies....w.:.
2a.w.w...,.,....ub
1-VT
F
......t ,
..J ...�,w::........
-.s4 '.,.-.w�.... »
tfr-,....s v.ww.+.a
.,,.....,
....-vs..1....1:....-
qm.=-
,m,.�y•
,
tw '4"°5'"'2'3,
.w..+..gfi
n1
'�" .. $
�" ,. "'F
.,� �.
..,.s.
�
�
.'1..i:.,C-...n..
-i.sx,....a42.c..raw�.:w...u��
dk.-t".,c::t
�
°w:
�
"�'-.,.L..a
..av,...:.m,.....:
sS.�
;wixa...dr3.m.�
...41�;✓.u,.sw
.w.z.n......�
0
-46
6
c) AED
excursion
Envelope loss/gain
16568
11693
549
291
12
a) Infiltration
3181
889
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Occupants@ 230
4
920
0
0
Applianoes/other
1800
600
Subtotal (lines 6 to 13)
19749
15302
549
891
Less external load
0
0
0
Less transfer
0
0
0
0
0
Redistribution
0
0
0
14
Subtotal
19749
15302
549
0
891
15
Duct loads
1806
32 /
3528
4897
18 %
32 %
98
285
Total room load
23276
20199
647
1177
Air required (cfm)
1
1 947
947
26
55
Calculations approved byACCAto meet all requirements of Manual J 8th Ed
�}�- wrigF�#soft^ 2021-Mar-0816:13:42
Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1
Waterstonel780AGRIotBBlklWaterstonel780AGR.rup Calc=WS Housetaces:NW
-- wrightsofta Right-JO Worksheet
Entire House
DEL -AIR HEATING &AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax: 407-333-3853 Web: W W W.DEL-AIR.COM
Job: . Lot 8 Block 1 Waterston 178...
Date: 06.07.12
By: FLETCH
1
Room
name
BR3
BATH2
2
E)posed
wall
26.0
It
0 It
3
Room
height
8.0 ft
heat/cool
8.0 ft heat/cool
4
Room
dimensions
1.0
x 146.5 ft
9.0 x 6.0 It
5
Room
area
146.5 ftz
54.0 ftz
Ty
Construction
U-value
Or
HTM
Area (ftz)
Load
Area (ftz) Load
number
(Btuht-T-)
(Btuh/ftz)
or perimeter (ft)
(Btuh)
or perimeter (ft) (Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/PPS
Heat
Cool
6
=
Blkwall siuocoext !
; 0207
n
,583
4.06
; '
0 0
7:
0 -,_0
__
0
0
�G
2Q 2ov-, 7 w.
16B-19ad
� rs0.330
__n _
_ _z957
822
0 . �0
0
0
0
_ =� 0
-•0
, . 0
.0
Blk wall shioro e R
0.049
'" 0201
ne
ne
1.42
5;83
2.59
4;06
0
0 �0
0
0
0
0
0
0
; 0
0
0
0
0
-0.W
0
0
2ov
_ne�
_ 9.57
17Z0
_ _0
. .. 0
0
;_ 0
, �0
,� L_10
W
16B 19ad
Blkwall stucooext
0 049
0550
se
se
1 42
1595
2 59
1620
_0
0
_0
0
0
0
p
0
psN'
~ 0
0
0
h 0
0,7777767
�0
W
1
{.Pp
0.
16B 19ad
"'wall
0049
sw
1.42
2.59
0
0
0
0
0
0
0
�.0.
Blk sticao eM
U 201
sw
5.83
4 06
104
88
", 4 511
1' 356
0
7,7 07
0
p
2Atoy
0330
_sw
_9R
15.67'
16
v... 4
156
256
,0
0
W
L-C
Blk wall slucoo ext
0201
w
5.83
4.06
0
0
0
0
0
0
0
0
2A 2ov
0.330
w
9.57
20,92
0
0
0
0
0
0
0
W�
f6_B-195d,,
_ . 0049
0.riw
m�0
_
�0
0
Blk wall, stuoao eM
2A-2ov
0.201
0,330
nw
nw
5.83
9.57
4.06
16.61
0
0
0
0
0�0
0
11,10
0
0
0
0
0
0
0
0.600
nw
17.40
17.58
0
0
0
0
0
0
0
0
12C Osw
0 091
.
2.64
131
77 104
7. 104
; 274
136
' -; 0
0
0
0
C
111J0_
- 0390
n:_
11.31,
1:43
_ _ u 0
�;....a,_r0
0
',� _0.
�0
168-30ad
22A tpl. -
0.032
0 989
136
746•
54
.�
-0
54
F"
0.93
2868
1.69
0^OA
147
147
147
26'
248
`.-- -0
50
91
�_ 54
_
p77-17
:✓'t-..wL.w.:.n'.:,...�..:u
6
c) AED excursion
71
-4
Envelopeloss/gain
1823
1066
50
87
12
a) Infiltration
242
68
0
0
b) Room ventilation
0
0
0
0
13
Internal gains: Oavpantspa 230
0
0
0
Appliancestother
0
0
0
Subtotal (lines 6 to 13)
2066
1134
50
87
Less external load
0
0
Lesstransfer
0
0
Redistribution
0
0
0
0
14
Subtotal
0
0
0
02066
15
Duct loads
18%
32%
369
1134
363
18%
32%
50
9
87
28
Total room load
Air required (dm)
2435
1497
59
115
99
70
2
5
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
Aft- wriq!?! 7Ft- 2021-Mar-0816:13:42
Right-Suite®Unversal 2021 21.0.02 RSU23828
Waterstonel780AGRV_otBBlklWaterstanel780AGR.np Calc=W8 Hoisefaces:NW Page 2
wrightsoft® Right-M Worksheet
Entire House
DEL -AIR HEATING &AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WWW.DEL-AIR.COM
Job: Lot 8 Block 1 Waterston 178...
Date: 06.07.12
By. FLETCH
1
2
3
4
5
Room name
Exposed wall
Room height
Room dimensions
Room area
BR2 MBq
13.0 It 32.5 ft
8.0 ft heat/cool 8.0 It heat/cool
1.0 x 137.5 8 1.0 x 270.5 ft
137.5 ft2 270.5 ftz
Ty
Construction
number
U-value
(Btuhftt29
Or
HTM
(Btuh/ft2
Area s
ft
or perimeter (ft)
z
(ft)
(13 h) o eaperimeter (ft)
Load
(Btuh)
Heat
Coal
Gross
N/P/S
Heat
Cool Gross
N/P/S
Heat
Cool
6
11
W
W
Vl/
W
W v-
-r
C
F
Blk v�all stu000 ext
29 2ov
16B-19ad
Blk wall stucco ext
2A2ov v
161319ad
Blkwall siuocoext
2A2oX1 `..__,� ¢
16B 19ad
blkwall stu000�ext
;2A,2ov w r _t _
Blk wall, stucco ext
2A 2ov
ai6B-19ad �4�4
00 20T
«= 0:330
0.049
0201
�0330
0.049
0201
0550
%z.'_.> A.330
0 049
0201
- t'0330
0201
0 330
,"0049.
0201
0.330
0.600
091 0
`., ri
�n�
ne
ne"
-ne_;
se
se
se'
see
sw
sw,
_s/V
w
w
6,
nw
nw
nw
.
5:83'
A9 57
1.42
5.83
,,_-� 957
142
583
1695
"�957
1 42
583
w 957=
5.83
9.57
� -
5.83
9.57
17.40
2.64
0.93
a >28 68;
4:06
822
2.59
406
1770
2.59
406
1620
�w. 1567
2 59
� 406
1567
4.06
20.92
4.06
16.61
17.58
13]
1.69
:. 0
0
- 0
_ "� 0
0
�` 0
_0
0
_. " z 0
p 0
: w , -0 0
0 0
0 w 0
' s Y9:
_ . ; p
,p'
,7 -_-- 0
0
7 0
p
0
0-
0
0
:' 0
0
0
0
A
0
�0
�.0
� . a.Q
0
x" 104
a `a16
0
0
0
0
0
p ',� 0
0
88
3 4
0
0
0
0
0
�i0.
0
511
156
0
0
0 0
` 0 144
0 0
0 33
0 0
356 ✓' 116
256 : :. .
0 0
0 0
_
0
11-1'
' 0
° � s � :$
0
; 11(i
0
0
0
649
0
� u�313.
0
67.6
7
0
0
0
452
al
Y 512,
0
471'
0
0
Bik wall, stucco ext
2A-2ov
11J0
12C Osw
1tD0_,.
16B-30ad
_
229 fi1� .
0
0
0
0
138
0
0
0
.. 0
138
0
0
0
0""`
0 0
0 0
0 0
"'0 0
0
0
0
" 0
0
0
0
:•0,'
9
0
0
.0
;.0
=0.
0.032
_�.
_ a u .0 989
128
232 271
271
252
q5g
R
7271'
:33JQ3
2
` • 0.
-�^: '^s
-xr<^'^.va-
_
,-:
.....,.�.,c.... .. ✓ >�
one
-^
rP.n--,-:ate
'..r.=
x ,.,.....x.sc.,:*.:
.�.,.�..w...
-.-....
».wy,,,a•;,..,..c�own.W.a -
o..-...-.�..,.>..
,ay
�
+a,H%.rwa.
....wu........
�+,..3�.k,.a....,.
.M,.....s.1Lr»..�.>
....>,,.a.......-.iY... �>...-,.:rwa.:..k
�wF,...
,wSZ?+...-s.,...
-..e..�..�
....-,,x...x,�,..,.W
�..,.....
7.
.-...-,..,-..,.
..._
...e...
"�...«n.,
u
a�.m+ad...,....m
."Jd..A.:+L`,w+a.T.c.
�,..,v.1«a' `............: .......�...a.r.....x
:µ °"',:.r.
." .',<
«....�-.x...-....
y.,..,,uw,
4,w. ✓ws'"X"x°`R*�T`t Y^5?^
»-. ... .... �.�ia+
.w.. `...e'. ' A+
,..'',....w.:
7�"......J"'
.,Y.,t-t.,,✓ rt
✓y4+,
...[..is� :eE.:
">
(� ✓.t
��
' .
..ria_.'+1�'„' "n'M ^^^
r
�- , t.^
.-[..,.•--1--"--`;.
6
c) AED excursion
78
166
Envelope loss/gain
1168
922
2822
2059
12
a) Infiltration
b) Room ventilation
242
0
68
0
606
0
169
0
13
Internal gains: Oocupants@ 230
Appliances/other
0
0 1
p
230
0
Subtotal (lines 6 to 13)
1410
990
3427
P458
14
15
Less extemalload
Less transfer
Redistribution
Subtotal
Duct loads
18%
32%
0
0
0
1410
252
0
0
0
990
317 18%
32%
0
0
0
34270
612
0
0
0
2458
787
Total room load
Air required (cfm)
1662
68
1307
61
4040
164
3245
152
Calculations approved bVACCA to meet all requirements of Manual J 8th Ed
. P. - war➢gl�tsofe" 0816:13:42r-
Right-Sute®Uriversal 202121.0.02 RSU23828 2021-MaPage 3
Waterstone1780AGR\LotBBlki Waterstone1780AGR.np Calc= W8 House faces: NW
- wrightsoft Right-JO Worksheet
Entire House
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM
Job: Lot 8 Block 1 Waterstone 178...
Date: 06.07.12
By: FLETCH
1
Room name
MBATH
WIC
2
3
Exposed wall
Room height
21.0
It
7.5 ft
4
Room dimensions
8.0 8
heatbool
8.1 ft
heat/cool
5
Room area
1.0
116.0 ftz
x 116.0 ft
1.0
87.0 ftz
x 87.0 ft
Ty Construction U-value
Or
HTM
Area (ft)
Load
Area (ftz)
Load
number (Btuh/ft-`-)
(13tuh/R2)
or perimeter (ft)
(Btuh)
or perimeter (ft)
(Btuh)
Heat
Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
6
�f Blk wall; stu000 ext F 01
`._
M:n'.
, 5:83
406
0 7 0
777
0 0
0 ..
0
!-C ,2A 2ov - .e.;.--._._0330
W 16B 19ad 0049
n:
_'957
-822
s_ "0
... _
0 - ' %
0 � 'Q
0 =Q
� 0.
�__ 0.
2S9
-
' b6
0 0
56
0 0
227
:
"'
y! Blk wall sti000 ext 0201
ne
ne
1 42
5 837
326
0
- 60
0 .0
350
0
" `244
4
W 161319ad 0.049
Blkvuall stuocoext A201
;b550
se
se
se.
142
58340f'�
1595
2.59
1620
0
112
t 0
0
112
0
0
653455
0
0
0
0'
0
0
0
0
0
p
.2A.2ov r
0
0
0
0
0
.a 0339.
W 161319ad
o°�000,
_ 0.049
sw
1.42
2.59
0
0
0
0_
0
0
0
0
77.77702Y
�15
_
_
W�
_ -.`
..,..1%57
:
6
, 0
,
�=v
0
o
wall stucco e
W
5.83
o
o
o
_ .00
o
W 16B-19ad_ -�� �-
•.,0 049
:_ �
9.57
ter,=„_1.42
20.92
0
0
- 0
_ 0
0
�0
0
���0
0
�0
L ^J �0
LBlk wall, stucco eM 0.201
--G 2A-2ov 0.330
nw
nw
5.83
9.57
4.06
16.61
0
0
.0
0
0
11J0
0
0
0
0
0
0
0
0
-- 0.600
""
nw
17.40
17.58
0
0
0
0
0
0
0.
0
091
12C Osw µ 0
2.64
131.
0
0
0
- a0
0:
r- �0
00
1 0390
C L161330ad
n r
1131e
11 43
_0
0
.0
0
L:____.0
0
0032
0.93
1.69
116
88
88
116
108
196
81
148
7'V
0
...,..w 4; ,.,_ra �...r........�,,..
uc..a.
'. `�c?ss
w"•C`f..,.i ..
"'
a
H--
- z.,..u. i,....ca...�
�
-...
�_.�,...t...�
......
..w4.+e'
w...:u✓S.s;.a..*.re....
u....--
-.-ax
� M*+C w.vM132i'..rr.,h v'.:d "�
v6'+»wYts^..-
.
t� �
>v��'�f,
.isv.t..1.r'.-.s.
m... ...iir-A,.X.,
Mf.w
s''•
...........
?".'^.�i:'" .Wfi....
.w.....x......,,A
orb1✓ i
�.a.c.ua..m&
rL+v�aa.
.....�..,.e-.-
��
_
�....-,�,.e."^
_.w...✓` .rr.-.d:+-w..-r 'wi..,..'t'
.-:. Tom-.+' %,.^..�.�
�i ....�..>-.++...-,
..m..-•--.-,.rt..--u
_
-._..+........+wd
5,. kv....m..- �'�`�'A^'T-+.-
..�,.«�
.d.^.a...e».. �„S.
s.....�.-
+wrp'"',-^y
+., .,ae.-`m
�..,....r
-
1.:.^^.:.-.
_va. -
w_..�.-..
.•....a...
snsL"w.lr"
.e...«w...�
'TP'..T„A','^�
6
c) AED excursion
-48
21
Envelopeloss/gain
1689
830
646
371
12
a) Infiltration
b) Room ventilation
391
109
140
39
0
0
0
0
13
internal gains: Occupants pa 230
0
0
0
Appliances/other
0
0
0
Subtotal (lines 6 to 13)
2081
939
786
410
Less eMemalload
Less transfer
0
0
0
0
Redistribution
0
0
0
0
14
'Subtotal
0
0
0
0
15
Ductloads
18%
32%
2081
372
939
301
18%
32%
786
140
410
131
room load
Air r
ir required (d
2452
1240m)
928
541
100
58
38
25
Calculations approved bvACCA to meet all requirements of Manual J 8th Ed.
A wr7gF�tsof!- Right-Su2021-Mar-0816:13:42
te®Uriversal 2021 21.0.02 RSU23828 Waterstonel780AGR\Lot8BlklWaterstonel780AGR.nis
p Calc=MJB Hoefaces:NW Page 4
wrightsoftm Right-M Worksheet
Entire House
DEL -AIR HEATING &AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WWW.DEL-AIR.COM
Job: Lot 8 Block 1 Waterston 178...
Date: 06.07.12
By: FLIETCH
1
Room name FAMIHALL(S)
KIT
2
ENposed wall 24.0 ft
30.5 ft
3
Room height 9.5 ft heat/cool
9.5 ft heaV000l
4
Room dimensions 1.0 x 451.0 8
1.0 x 290.0 It
5
Room area 451.0 ftz
290.0 ftz
Ty Construction U-value Or HTM Area (ftz) Load
Area (ftz) Load
number (Btuh/ft- (Btuh/ftz) or perimeter (ft) (Btuh)
or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool
Gross
N/P/S
Heat
Cool
6
V�
Blkwall stu000ext a.
;0201
n`
593
406 0
0
0
- p
p
p
p
U
. B. ,
_. ,. 0.57_
L_ 822 _ 0
, w -0
W
V�!
1613-19ad
Blk wall stucco eM
0.049
0201
ne
ne .
1.42
5.83
2.59 30
4.66 i28
30
; 95
43
. 556
78
- 387
0
96
0
96
0
560
0
390
2A 2ov _
_ =0330
Re,
_ 9,57_
1,7_.7Q 33
..� 0
. �a 313
=_, _ _57_9
_ 0
:1_ . z_0
W
161319ad
�
0.049
se
1.42
2.59 30
30
43
78
0
0
0
0
Blk wall stuaoo ext
;10C`m�
�0550
'se:
7W
1595
77706 7 64
1620 18
777746
18
=7269
285
T7 18
289
',
0
r ; -
0
0
`0
2g,2ov,>
A
0
0
0.0,
+�'Q
9
W
168 19ad
0.049
sw
1.42
2.59 30
30
43
78
0
0
0
0
PBlkwall sticooexC x
0201
sw
5.83
406 0
0
r 0
0
0`
0
$
0
2A 2ov ; _
M 0 330
,,rsnf W
9.57;
15 67: _ '0
_ 0
, n 0
° 0
. ` _ w0
.` 0
�0
w0
0
Blk wall, stucco e)d
0201
w
5.83
4.06 0
0
0
0
0
0
0
Wa
2A 2ov
39ad :, .-."
6B y
0330
J , 049 0
w
_ riw:
9.57
ir42:
20.92 0
v 2S9 =:: 30
0
_ �� 30
0
0
0
0
0
0
Blk wall, stucco ext
2A-2ov
0201
0.330
nw
nw
5.83
9.57
4.06 0
16.61 0
0
0
0
0
0
0
40
20
116
81
11J0
92C Osnr
0600
0091
nw
17.40
264;
17.58 0
1.3]i A
0
� 0
.0
0
0
0
0
20
108
0
20
" 108
0
350
285;=.142
0
353
11D0 _ v
-0390
�n
1131
_ 1J.43. °0
0
��0
0.
:v
�0
,,.. ".�0
C
_F...w.>=
166 30ad
22A1p1�;;_,',..sx....
0.032
0989
0.93
1.69 538
909
_�
_
346
w=
346
321
584
�."
538
�
499
«___2868
•0,00 _451,
. ;�24
688.;«
_ 0
� ,_-_290
�.�,...:"31.
�,, ,�875
0;
k-«...,..«
u' F Z atl] v .ur..�
7,-.- .i....se...t
e+L-.v..
wwa« re=`�P
.j-a+.rv.5 .r^ •e..
"c"i"-+'q.,
+eyy..o.«., -..zz.
'.t »q, y k
.,._..
..,._..,..,„.�......r....«,,.+,�....._
.d..�..�..� M
a.,.
.�.
#...,s.--n..'J,cak'? kf
........0
-c.....�.
-.....B,.Y
�r.....�..
..
wa.�.�
1
i'piµ+'..v.+J.wu..��v,.,Lu..-.«..m6'�.
X...Ns..wo-:.�.P�«L
. .:`.
µ� � tiT
.wlJ" "
.A.._.w..b
�% t. •Lz�m
iM'8sS�1 i9.«3 {
V �'..^"'u"' W;.'-
^^�+-^-.0
_
q'
.-
..
..
a' :..
]=-_7=
6
c) AED excursion
-162
-138
Envelope loss(gain
2780
2500
2506
1412
12
a) Infiltration
727
203
317
89
b) Room ventilation
0
0
0
0
13
Internal gains: OocupantsCa 230 2
460
0
0
Appliances/other
p
1200
Subtotal (lines 6 to 13)
3507
3163
2823
2700
Less external load
0
0
Lesstransfer
0
0
0
0
Redistribution
0
0
0
0
14
15
Subtotal
Duct loads
3507
3163
0
2823
0
2700
18%
32%
626
1012
18%
32%
504
864
Total room load
Air required (cfm)
4133
4175
3327
3564
168
196
135
167
Calculations approved byACCA to meet all requirements of Manual J 8th Ed
A - - wrigF�tsoR� Right-Sute®Uriversal 2021 21.0.02 RSU23828 2021-Mar-0816:13:42
Waterstone1780AGR\Lot8BlkiWaterstone1780AGR.np Calc=MJ8 Hoisefaces:NW Page 5
-- wrightsoft® Right-JO Worksheet
Entire House
DEL -AIR HEATING &AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: W W W.DEL-AIR.COM
1 Room name
2 Exposed wall
3 Room height
4 Room dimensions
5 Room area
Ty Construction U-value Or
number (Btuh/ft-f)
6
11
Blk
stuccoext 1- 02011 w I
6 c) AED excursion
Envelope loss/gain
12 a) Infiltration
b) Room ventilation
13 Internal gains:
Subtotal (lines 6 to 13)
Less external load
Less transfer
Redistribution
14 Subtotal
15 Ductloads
Total room load
Air required (cfm)
Md 0.2011 riw,
0.330 nw
0.600 nw
Occupants pa
Job: Lot 8 Block 1 Waterston 178...
Date: 06.07.12
By: FLIETCH
HTM
(Btuh/ftz)
DIN/FOY
27.7 It
9.5 ft heatbool
1.0 x 190.5 It
190.5 ftz
Area (ftz) Load
or perimeter '(ft) (Btuh)
Area Load
or perimeter
Heat Cool
Gross
N/P/S
Heat
Cool
Gross
N/P/S
Heat
Cool
5,83 4:06
297
- �`17
�-
g99
S
1.42 2.59
0
0
�{ 0
0
" 583 �406
76
44
307"
a957'10,4x16
r'0-
156
289i>
g
7
1 42 2.59
0
0
0
0
,x
583 4Q6
X ' fia
v T ,0
� 0
7 r 0{7
ax �1595 11620
"
1.42 2.59
0
0
0
0
583 '"406ct0
, XO
0
re�0
P
5.83 4.06
29
17
99
69
9.57 20.92
12
1
114
249
42 259
Tom— 0
A 0
. ? ci0
, "0_
5.83 4.06
72
49
283
197
9.57 16'61
23
0
224
389
1740 1758
0
0
0
0
264 131
0A`,
0
'00k:
a`r
11,31 ,j1:43a�0.0.
,001'u
.%y evekrx
0.93 1.69
227
227
210
383
'
y 28,68y 0 gQ191'28w
x' 794
O
N
r
Fr
.w:,.[....�..,.F.;aix �.�
_.,»xas»s.C.».".w,
,».s..w"ta..
L.�:aa.Nbu-'f„�, �.,,
ems-. oS
r�"'2�:1�,.. 'C...:.
��w..vrssu«.s
+. b...,.v.»
5" S -• "A�"+
72 �.,... sc
ua
3,ySw n
..e.tur..,.c.....es'e
MIKE
.......w..
....�..-.,-..�,-...sue
.,»Fw.i...»v.�
X«,1.-.,. a +.» ,....-r`:.�..s,.++`»>:.ew�...
�� a,
w......xrw:.✓w»..
-.,.+...m
+ahli.>Fiam.»".�^�.'.
: "'^n ,,-
'"Gwaa�d �`t
_...,v.a.s_u...
�
esoox.,.iw .g"..+..sv.'..3.?
U.
zaza 4,
Mn.....2-L3"'-.[iiu...a4.-
v5a...e�.,�e
...y
'Y 1'..^`*ai,'�'•`
..3M... s
u`a+'vr._'Y$a.,w
":'�
104
2534
2154
516
144
0
0
230
1
230
0
3050
2529
0
0
0
0
0
0
3050
2529
18 %
32 %
545
809
3595
3338
146
156
Calculations approved byACCAto meet all requirements of Manual J 8th Ed
G`A - wrigFitsofe- 0816:13:42Mar-
Rigk-SuteOUriversal 202121.0.02 RSU23828 2021-
...Waterstone1780AGR\LotBBlkiWaterstone1780AGR.rrp Calc=W8 Housefaces:NW Page 6
wrightsoft® stem Duct S Summary Job: Lot 8Block 1 Watersto...
y nDate: 06.07.12
Entire House By: FLETCH
DEL -AIR HEATING & AIR CONDITIONING
531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WWW.DEL-AIR.COM
Project• •
For: ADAMS HOMES
5428 Lugo Street, Fort Pierce, FL 34951
External static pressure
Pressure losses
Available static pressure
Supply/return available pressure
Lowest friction rate
Actual airflow
Total effective length (TEL)
Heating
0.40
in H2O
0.06
in H2O
0.34
in H2O
0.170 / 0.170
in H2O
0.312
in/100ft
947
cfm
109 ft
Supply Branch Detail Table
Cooling
0.40 in H2O
0.06 in H2O
0.34 in H2O
0.170 / 0.170 in H2O
0.312 in/100ft
947 cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FIR
Diam
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BATH2
c 115
2
5
0.460
4.0
Ox 0
VI Fx
3.9
70.0
BR2
h 1662
68
61
0.420
6.0
Ox 0
VIFx
11.0
70.0
BR3
h 2435
99
70
0.443
6.0
Ox 0
VIFx
6.7
70.0
DIWFOY
c 3338
146
156
0.374
7.0
Ox0
MFx
20.9
70.0
FAMMALL(S)
c 4175
168
196
0.434
8.0
Ox0
VIFx
8.3
70.0
KIT
c 3564
135
167
0.381
7.0
Ox 0
VI Fx
19.1
70.0
I.AU
c 1177
26
55
0.456
4.0
Ox 0
VIFx
4.5
70.0
MBATH
h 2452
100
58
0.312
6.0
Ox 0
VIFx
24.0
85.0
st1
MBR
h 4040
164
152
0.322
7.0
Ox0
VIFx
20.7
85.0
sti
WIC
h 926
38
25
0.333
4.0
Ox0
VIFx
17.1
85.0
st1
Supply Trunk Detail Table
Name
Trunk
Type
Htg
(cfm)
Clg
(cfm)
Design
FR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Duct
Material
Trunk
st1
PeakAVF
302
236
0.312
553
10.0
0 x 0
VinlFlx
Return Branch Detail Table
Name
Grille
Size (in)
Htg
(cfm)
Clg
(cfm)
TEL
(ft)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Stud/Joist
Opening (in)
Duct
Mat
Trunk
rb2
Ox 0
947
947
0
0
0
0
Ox 0
VI Fx
' Wrlghtsoftm 2021-Mar-0816:13.43
Right-Sute®Uriversal202121.0.02RSU23828ACCk Pagel
Waterstore1780AGR\Lot8BIklWaterstone1780AGR.rLp Calc=MJ8 Hoisefaoes:NW
2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a
Project Name: Lot 8 Block 1 Waterstone 1780 AGR Builder Name: ADAMS HOMES
Street: 5428 Lugo Street Permit Office:
City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y
Owner: Jurisdiction: 661000 w
Design Location: FL, ST LUCIE CO INTL =
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealingmaterial.
requirements
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier.
Access'openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity
sealed. with a material having a thermal resistance of R-3
Knee walls shall be sealed. per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/doorjambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to
(including
insulation. maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
floors)
shall be permitted to be in contact with the top side
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned s ace shall be sealed.
Batts in narrow cavities shall be cut to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spac as.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building
shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind poping and wirmno
Shower/tub
The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs. be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
a. In addition, inspection of log walls shall be in accordance with the provisions of IC6-400.
3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
FORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
3/8/2021 4:27:52 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Duct Leakage Test Report
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: 661000 Permit #:
Job,l`nformatidn .
Builder: ADAMS HOMES Community: Lot: NA
System 1
cfm25
System 2
cfm25
System 3
cfm25
Sum of others
cfm25
Total of all
cfm25
1780 Qn
Total of all Total Conditioned
systems Square Footage
P`rescriptive Method cfm25 (Total),
To qualify as "substantially'leakfreef On"Totalmust be less than or
equal to 0.04 If air, handler unit is nstalled .lf air handler`uin is not ,
installed; Qn, Total must'be less4f6n or'equal .to'0.03. Th testing,
method mb.otg,the requirements in accordance' with Section 13403.3;3. '
ls; the air ha»dlerunit, installed during tes`ting� 0 YES, (Sod? ,0 NO
Q Performance/ERI Method cfm25,(out or TO a[)' <=
To qualify using;this.method;'Qmmust not bgreater,than the;
e '
•proposed duct'leakage Qn'specified on•rorm'11405-2020 or R406-2020
Leakage Type,selected on Forcri Qri. specified on Form R405-2020'
R405-2020 (EnergyCalc), or R406 2020 (En ; • ergyCalc) or'R406-2020."
PASS FAIL Proposed I 0.05
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section
553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes.
Tesfing Company
Company Name: Phone:
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the
selected compliance path as stated above, either the Prescriptive Method or Performance Method.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #:
Issuing Authority:
3/8/2021 4:28:56 PM EnergyGauge@ USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: 66i 000 Permit #:
Job Information
Builder: ADAMS HOMES Community: Lot: NA
Address: 5428 Lugo Street
City: Fort Pierce State: FL Zip: 34951
Air Leakage'., Resuits Passing results must meet either the Perfdhmapce, Prescriptive, or ERl Method
y,
Q PRESCRIPTIVE METHOD The building or.dwellm'g unit shall be ested'and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0 2 inchw:g. (50 Pascals) m�.Climate Zones 1 and 2 ',
- t
Q PERFORMANCE or ERl METHOD The building or dwelling unitshall be;tested and uenfied:as hayi , an air leakage rate,of •nof:exceeding
ahe selected ACH(50) value, as shown on Form R405=2020.(P. ertormance) or R406 2020 (ERI) (alieled
section as infiltration, $ub-section ACH50:
ACH(50) specified on.Form I?4Q5 2020 Energy,Ca/c (1?4ormanceJ'or R406 2020 (ERIJ 7.000
x 60 _ 15664 — Method for calculating building volume:
CFM(50) Building Volume ACH(50)
Q Retrieved from architectural plans
1-1 PASS
0 Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
.4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing .Company`
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
3/8/2021 4:28:44 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
Mandatory Requirements for Residential Performance,. Prescriptive and ERI Methods
ADDRESS: 5428 Lugo street Permit Number:
Fort Pierce, FL, 34951
MANDATORY REQUIREMENTS - See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (1) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Lis) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R403.1 Controls.
SECTION R403 SYSTEMS
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2'percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned Floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
El R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'Y2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 600C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
R403.5.6.2 Water -heating equipment. I Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMU
(CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
In -line fan
Any
Any
2.8 cfm/watt
2.8 cfm/watt
Any
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916
3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
oR403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
2. calculated total sensible load but not less than 80 percent of that load.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized_ in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF (4.8°C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches. Time switches or other control methods that'can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5
❑R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
❑R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
❑ R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5