HomeMy WebLinkAboutProject Information' n Job: Lot 8 Block 1 Watersto... - wrightsoft® Manual S Compliance Report Date: 06.07.12 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phom:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Project• • For: ADAMS HOMES 5428 Lugo Street, Fort Pierce, FL 34951 Cooling Equipment Design Conditions Outdoor design DB: 90.4OF Sensible gain: 20199 Btuh Outdoor design W B: 77.4 OF Latent gain: 4018 Btuh Indoor design DB: 75.0 OF Total gain: 24217 Btuh Indoor RH: 50% Estimated airflow: 947 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNB031 L00 Actual airflow: 947 cfm Sensible capacity: 20961 Btuh 104%of load Latent capacity: 6086 Btuh 151 % of load Total capacity: 27047 Btuh 112% of load SHR: 770/. Heating Equipment Design Conditions Outdoor design DB: 41.0 OF Heat loss: 23276 Btuh Indoor design DB: 70.0 cF Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNB031 L00 Actual airflow: 947 cfm Output capacity: 26646 Btuh 114% of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 947 cfm Output capacity: 6.6 kW 96%of load Temp. rise: 22 OF Meets all requirements ofACCA Manual S. Entering coil DB: 76.5OF Entering coil WB: 63.8cF Entering coil DB: 69.5OF Capacity balance: 36 OF Economic balance: -99 OF wrighttsoft- 2021-Mar-0816:13:42 ^.• „•w� ��m-m Right-Sute®Uriversal 2021 21.0.02 RSU23828 ACCK...Waterstorel780AGR\LotBBlklWaterstonel780AGR.np CaIc=MJ8 HOrsefaces:NW Page 1 Component Constructions Job: Lot 8 Block 1 Waterston ... -- wrightsoft® p Date: 06.07.12 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Prnne:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM •ject information For: ADAMS HOMES 5428 Lugo Street, Fort Pierce, FL 34951 Design Conditions Location: St Lucie Co Intl, FL, US Indoor: Indoor temperature (OF) Heating 70 Cooling 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 28 °N Relative humidity (%). 30 50 Outdoor: Heating Cooling Moisture difference (grib) 2.4 56.9 Dry bulb (T) 41 90 Infiltration: Daily range (OF) Wet bulb (OF) - 15 (L - 77 ) Method Simplified Wind speed -(mph) 15.0 7.5 Construction quality Fireplaces Average 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' BtutyftzIF ftz°FBtuh Btutff Btuh Btur✓ft2 Btuh Walls Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh 16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fnsh Partitions 12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2'k4" wood frm, 16" o.c. stud Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.21); 50% drapes, -medium; 1.3 ft overhang (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht 1 OC-m: 2 glazing, dr low-e outr, air gas, mtl no brk frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.70); 14.33 ft overhang (6.7 ft window ht, 0.8 ft sep.); 6.67 ft head ht n 17 0.201 4.1 5.83 99 4.06 69 ne 383 0.201 4.1 5.83 2232 4.06 1555 se 269 0.201 4.1 5.83 1571 4.06 1094 sw 291 0.201 4.1 5.83 1698 4.06 1183 w 17 0.201 4.1 5.83 99 4.06 69 nw 68 0.201 4.1 5.83 399 4.06 278 all 1046 0.201 4.1 5.83 6098 4.06 4247 ne 30 0.049 19.0 1.42 43 2.59 78 se 30 0.049 19.0 1.42 43 2.59 78 sw 30 0.049 19.0 1.42 43 2.59 78 nw 30 0.049 19.0 1.42 43 2.59 78 all 120 0.049 19.0 1.42 171 2.59 310 250 0.091 13.0 2.64 660 1.31 328 n 12 0.330 0 9.57 114 8.22 98 w 12 0.330 0 9.57 114 20.9 249 nw 23 0.330 0 9.57 224 16.6 389 all 47 0.330 0 9.57 452 15.6 736 ne 49 0.330 0 9.57 469 17.7 868 se 33 0.330 0 9.57 313 15.7 512 sw 33 0.330 0 9.57 313 15.7 512 all 114 0.330 0 9.57 1095 16.5 1892 se 18 0.550 0 16.0 285 16.2 289 a Doors 11J0: Door, mtl fbrgl type nw 20 0.600 6.3 17.4 350 17.6 353 11 DO: Door, wd sc type n 18 0.390 0 11.3 202 11.4 204 1 " wrightsc ft® 2021-Mar-0816:13:42 �� ,•k•,�.,eM1,.„....,,.�m,.•, Right-SuteC5lUriversa12021 21.0.02 RSU23828 Page 1 Waterstone1780AGR\Lot8Blkl Waterstore1780AGR.rLp Calc= W8 Hotae faces: NW 41 Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1 /2" gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 1972 0.032 30.0 0.93 1830 1.69 3332 189 0.989 0 28.7 5425 0 0 -tz. -Pk- wrightsoft® 2021-Mar-0816:13:42 N,e h w•w�•.•.�m�m Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 Waterstore1780AGR\Lot8BIklWaterstore1780AGR.rup Calc=MJ8 Hoisefaces:NW wri htsoft Project Summary Job: Lot 8 Block 1 Waterston ... g Date: 06.07.12 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Proiect Information For: ADAMS HOMES 5428 Lugo Street, Fort Pierce, FL 34951 Notes: L. S. 3-8-21 VWK Design • • Weather: St Lucie Co Infl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 Inside db 70 OF OF Outside db Inside db 90 75 OF OF Design TD 29 cF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19749 Ducts Btuh Structure 15302 Btuh 3528 Central vent (0 cfm) 0 Btuh Btuh Ducts Central vent (0 cfm) 4897 0 Btuh Btuh none e) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 23276 Btuh Use manufacturer's data y Infiltration Rate/swin multipplier EquipmenKensible load 1.00 20199 Btuh Method Simplified Construction quality Average Latent Cooling Equipment Load Sizing Fireplaces 0 Structure 2830 Btuh Ducts 1188 Btuh Central vent (0 cfm) 0 Btuh Heatingg Area (ft2) 1780 Coolingg 1780 (none) Equipment latent load 4018 Btuh Volume (ft3) 15760 15760 Air Changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 24217 Btuh Equiv. AVF (cfm) 100 53 Req. total capacity at 0.75 SHR 2.2 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Trade CARRIER Make Carrier Trade CARRIER Model 25HBC530AP03 AHRlref 204840289 Cond 25HBC530AP03 Coil FX4DNB031L00 Efficiency 8.5 HSPF AHRI ref 204840289 Efficiency 12.5 EER, 15 SEER Heating input Heating, output 28200 Btuh@47°F Sensible cooling Latentcooling 21300 7100 Btuh Btuh Temperature rise 27 Actual airflow 947 OF cfm Total cooling Actual airflow 28400 947 Btuh cfm Air flow factor 0.041 Static pressure 0.40 cfm/Btuh in H2O Air flow factor Static pressure 0.047 0.40 cfm/Btuh in H2O Space thermostat . Capacity balance point = 36 OF Load sensible heat ratio 0.83 Backup: Input = 7 kW, Output = 22460 Btuh,100 AFUE Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -* wrigl�tsoft' ^- •^ •° - Right-SuteOUriversal 2021 21.0.02 RSU23828 2021-Mar-0816:13:42 ACC`...Waterstone1780AGRIot6BIklWaterstore1780AGR.rip Calc=W8 Housefaces:NW Page 1 - wrightsoftRight-M Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531CODISCOWAY, SANFORD,FL32771. Phone: 407-333-2665Fax: 407-333-3853 Web:WWW.DEL-AIR.COM Job: Lot 8 Block 1 Waterston 178... Date: 06.07.12 By: FLETCH 1 Room name Entire House LAU 2 E)qcosedvall 1892 It 7.0 ft 3 Room height 8B It 8.0 ft heat/cool 4 Room dimensions 7.0 x 7.0 ft 5 Room area 1792.0 ftz 49.0 ftz Ty Construction U-value Or HTM Area (ft') Load Area (ftz) Load number (Btuh/ft-19 (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blkwall stu000eM0201 n 583 4.06 29 1G57 997777PC9 0 x D, 77777Q°;.0: W 161319ad 0049 ne 1.42 259 30 30 43 78 0 0 0 0 Blkvl stu000ext,; 0201 ne" 583, �4062 383 2232 1555 0 „00 -r0 11 ?A2ov Apr _ Q330 _fie 9,57177Q 49 - , .U- 0469 �_-.' 868 s 4 0 m0,`0 ".Q W 161319ad (k wall stucco ext r 0049 0 20) se se : 1.42 5 83 2.59 4 06 30 32076 30 43 1285 _ 78 1289 0 0 0 0 10C m 0550 ,use' 1595 1620 i 18i8 0 0 U `,R0 .33 .1 a� i5 1222&12 W 166 19ad 0.049 sw 1.42 2.59 30 30 43 78 .0 - 0 0 w 0 0 I`Blkwall stUcooext 0201 dsw; 583 40Q a 324 291 1698 1183 0 0� ;0 0` t 2A2ov,x._ ;, r_»xw0330 .sw 957 15:67_.•X w33, �`t$'�313512.,� Q,�QI, Q� 0 Blk wall, stucco e)d 0.201 w 5.83 4.06 29 17 99 69 0 0 .� 0 0 2A 2ov 0230 w 9.57 20.92 12 1 114 249 0 0 0 0 y11 1619ad c >s. 0049 ;.OW..�,i,42 ,.k 259 s 30 ,, 30. f3 f Blk wall, stucco ext 2A-2ov 0.201 0,330 nw nw 5.83 9.57 4.06 16.61 112 23 68 0 399 224 �78 ' 278 389 w` 0 0 0' 0 0 0 0 11JO 0.600 nw 1740 1758 20 20 350 353 0 0 0 0 0 w 12C Osw a' j a ,0091 r 264 1 268 s 250 660 328 i 56 38 "'' 1 Ol a 50 „11D.O s �,0390. �n _ 1]31.3 ii,g3' 18 18 ux «202 �2041$,s.: J8' H C 161330ad 0.032 0.93 1.69 1972 1972 1830 3332 49 49 ,202 45 �.c204 83 .F 22A Vl, w w 0 989 r.. ZM..«.3:r;.9` 11 ............. u.uS'.,,,,,.... -.k�. ,w..� „a Y�.-.7'.fiC........ ,.w ......,�..uuf .a. �� �.mus....t d .0 .....w. { '"'.9. :;Y7 •?^ S^` .."^G^`^ `�,Fe..,o-. -..;ram wa p .,.-«. .e. ....... .........-,.. ...z w ,«..2:..a .......:.. .,..,= _ ... .. ......... .o..-.J «-.,. z '.4.�..sa,., c...«�.. � .�m,....o...o�. ,...�...,:.,,,d,w..T..... ,.,.C,,,....,. : -..,.xr.�..sx,_s.. = p,_,€a.......s...r. � ,".�.,w -..... .__......y..� _...,e,...... •- � °_....,.ram,^ ..�...-.wFu... ..+n,.e� ,....„. 22 m.,_.....xu.. ,µ t E,..-x.,.,a„a 2....,u...vr ....c. s: r¢Su ...Z....a� �u.aY":3 r^.1r...:' ...o ...,....= v...::a w...,..v....ti .........-A._���� ies....w.:. 2a.w.w...,.,....ub 1-VT F ......t , ..J ...�,w::........ -.s4 '.,.-.w�.... » tfr-,....s v.ww.+.a .,,....., ....-vs..1....1:....- qm.=- ,m,.�y• , tw '4"°5'"'2'3, .w..+..gfi n1 '�" .. $ �" ,. "'F .,� �. ..,.s. � � .'1..i:.,C-...n.. -i.sx,....a42.c..raw�.:w...u�� dk.-t".,c::t � °w: � "�'-.,.L..a ..av,...:.m,.....: sS.� ;wixa...dr3.m.� ...41�;✓.u,.sw .w.z.n......� 0 -46 6 c) AED excursion Envelope loss/gain 16568 11693 549 291 12 a) Infiltration 3181 889 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 4 920 0 0 Applianoes/other 1800 600 Subtotal (lines 6 to 13) 19749 15302 549 891 Less external load 0 0 0 Less transfer 0 0 0 0 0 Redistribution 0 0 0 14 Subtotal 19749 15302 549 0 891 15 Duct loads 1806 32 / 3528 4897 18 % 32 % 98 285 Total room load 23276 20199 647 1177 Air required (cfm) 1 1 947 947 26 55 Calculations approved byACCAto meet all requirements of Manual J 8th Ed �}�- wrigF�#soft^ 2021-Mar-0816:13:42 Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1 Waterstonel780AGRIotBBlklWaterstonel780AGR.rup Calc=WS Housetaces:NW -- wrightsofta Right-JO Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax: 407-333-3853 Web: W W W.DEL-AIR.COM Job: . Lot 8 Block 1 Waterston 178... Date: 06.07.12 By: FLETCH 1 Room name BR3 BATH2 2 E)posed wall 26.0 It 0 It 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 146.5 ft 9.0 x 6.0 It 5 Room area 146.5 ftz 54.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuht-T-) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PPS Heat Cool 6 = Blkwall siuocoext ! ; 0207 n ,583 4.06 ; ' 0 0 7: 0 -,_0 __ 0 0 �G 2Q 2ov-, 7 w. 16B-19ad � rs0.330 __n _ _ _z957 822 0 . �0 0 0 0 _ =� 0 -•0 , . 0 .0 Blk wall shioro e R 0.049 '" 0201 ne ne 1.42 5;83 2.59 4;06 0 0 �0 0 0 0 0 0 0 ; 0 0 0 0 0 -0.W 0 0 2ov _ne� _ 9.57 17Z0 _ _0 . .. 0 0 ;_ 0 , �0 ,� L_10 W 16B 19ad Blkwall stucooext 0 049 0550 se se 1 42 1595 2 59 1620 _0 0 _0 0 0 0 p 0 psN' ~ 0 0 0 h 0 0,7777767 �0 W 1 {.Pp 0. 16B 19ad "'wall 0049 sw 1.42 2.59 0 0 0 0 0 0 0 �.0. Blk sticao eM U 201 sw 5.83 4 06 104 88 ", 4 511 1' 356 0 7,7 07 0 p 2Atoy 0330 _sw _9R 15.67' 16 v... 4 156 256 ,0 0 W L-C Blk wall slucoo ext 0201 w 5.83 4.06 0 0 0 0 0 0 0 0 2A 2ov 0.330 w 9.57 20,92 0 0 0 0 0 0 0 W� f6_B-195d,, _ . 0049 0.riw m�0 _ �0 0 Blk wall, stuoao eM 2A-2ov 0.201 0,330 nw nw 5.83 9.57 4.06 16.61 0 0 0 0 0�0 0 11,10 0 0 0 0 0 0 0 0.600 nw 17.40 17.58 0 0 0 0 0 0 0 0 12C Osw 0 091 . 2.64 131 77 104 7. 104 ; 274 136 ' -; 0 0 0 0 C 111J0_ - 0390 n:_ 11.31, 1:43 _ _ u 0 �;....a,_r0 0 ',� _0. �0 168-30ad 22A tpl. - 0.032 0 989 136 746• 54 .� -0 54 F" 0.93 2868 1.69 0^OA 147 147 147 26' 248 `.-- -0 50 91 �_ 54 _ p77-17 :✓'t-..wL.w.:.n'.:,...�..:u 6 c) AED excursion 71 -4 Envelopeloss/gain 1823 1066 50 87 12 a) Infiltration 242 68 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Oavpantspa 230 0 0 0 Appliancestother 0 0 0 Subtotal (lines 6 to 13) 2066 1134 50 87 Less external load 0 0 Lesstransfer 0 0 Redistribution 0 0 0 0 14 Subtotal 0 0 0 02066 15 Duct loads 18% 32% 369 1134 363 18% 32% 50 9 87 28 Total room load Air required (dm) 2435 1497 59 115 99 70 2 5 Calculations approved byACCA to meet all requirements of Manual J 8th Ed Aft- wriq!?! 7Ft- 2021-Mar-0816:13:42 Right-Suite®Unversal 2021 21.0.02 RSU23828 Waterstonel780AGRV_otBBlklWaterstanel780AGR.np Calc=W8 Hoisefaces:NW Page 2 wrightsoft® Right-M Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 8 Block 1 Waterston 178... Date: 06.07.12 By. FLETCH 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BR2 MBq 13.0 It 32.5 ft 8.0 ft heat/cool 8.0 It heat/cool 1.0 x 137.5 8 1.0 x 270.5 ft 137.5 ft2 270.5 ftz Ty Construction number U-value (Btuhftt29 Or HTM (Btuh/ft2 Area s ft or perimeter (ft) z (ft) (13 h) o eaperimeter (ft) Load (Btuh) Heat Coal Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W W Vl/ W W v- -r C F Blk v�all stu000 ext 29 2ov 16B-19ad Blk wall stucco ext 2A2ov v 161319ad Blkwall siuocoext 2A2oX1 `..__,� ¢ 16B 19ad blkwall stu000�ext ;2A,2ov w r _t _ Blk wall, stucco ext 2A 2ov ai6B-19ad �4�4 00 20T «= 0:330 0.049 0201 �0330 0.049 0201 0550 %z.'_.> A.330 0 049 0201 - t'0330 0201 0 330 ,"0049. 0201 0.330 0.600 091 0 `., ri �n� ne ne" -ne_; se se se' see sw sw, _s/V w w 6, nw nw nw . 5:83' A9 57 1.42 5.83 ,,_-� 957 142 583 1695 "�957 1 42 583 w 957= 5.83 9.57 � - 5.83 9.57 17.40 2.64 0.93 a >28 68; 4:06 822 2.59 406 1770 2.59 406 1620 �w. 1567 2 59 � 406 1567 4.06 20.92 4.06 16.61 17.58 13] 1.69 :. 0 0 - 0 _ "� 0 0 �` 0 _0 0 _. " z 0 p 0 : w , -0 0 0 0 0 w 0 ' s Y9: _ . ; p ,p' ,7 -_-- 0 0 7 0 p 0 0- 0 0 :' 0 0 0 0 A 0 �0 �.0 � . a.Q 0 x" 104 a `a16 0 0 0 0 0 p ',� 0 0 88 3 4 0 0 0 0 0 �i0. 0 511 156 0 0 0 0 ` 0 144 0 0 0 33 0 0 356 ✓' 116 256 : :. . 0 0 0 0 _ 0 11-1' ' 0 ° � s � :$ 0 ; 11(i 0 0 0 649 0 � u�313. 0 67.6 7 0 0 0 452 al Y 512, 0 471' 0 0 Bik wall, stucco ext 2A-2ov 11J0 12C Osw 1tD0_,. 16B-30ad _ 229 fi1� . 0 0 0 0 138 0 0 0 .. 0 138 0 0 0 0""` 0 0 0 0 0 0 "'0 0 0 0 0 " 0 0 0 0 :•0,' 9 0 0 .0 ;.0 =0. 0.032 _�. _ a u .0 989 128 232 271 271 252 q5g R 7271' :33JQ3 2 ` • 0. -�^: '^s -xr<^'^.va- _ ,-: .....,.�.,c.... .. ✓ >� one -^ rP.n--,-:ate '..r.= x ,.,.....x.sc.,:*.: .�.,.�..w... -.-.... ».wy,,,a•;,..,..c�own.W.a - o..-...-.�..,.>.. ,ay � +a,H%.rwa. ....wu........ �+,..3�.k,.a....,. .M,.....s.1Lr»..�.> ....>,,.a.......-.iY... �>...-,.:rwa.:..k �wF,... ,wSZ?+...-s.,... -..e..�..� ....-,,x...x,�,..,.W �..,..... 7. .-...-,..,-..,. ..._ ...e... "�...«n., u a�.m+ad...,....m ."Jd..A.:+L`,w+a.T.c. �,..,v.1«a' `............: .......�...a.r.....x :µ °"',:.r. ." .',< «....�-.x...-.... y.,..,,uw, 4,w. ✓ws'"X"x°`R*�T`t Y^5?^ »-. ... .... �.�ia+ .w.. `...e'. ' A+ ,..'',....w.: 7�"......J"' .,Y.,t-t.,,✓ rt ✓y4+, ...[..is� :eE.: "> (� ✓.t �� ' . ..ria_.'+1�'„' "n'M ^^^ r �- , t.^ .-[..,.•--1--"--`;. 6 c) AED excursion 78 166 Envelope loss/gain 1168 922 2822 2059 12 a) Infiltration b) Room ventilation 242 0 68 0 606 0 169 0 13 Internal gains: Oocupants@ 230 Appliances/other 0 0 1 p 230 0 Subtotal (lines 6 to 13) 1410 990 3427 P458 14 15 Less extemalload Less transfer Redistribution Subtotal Duct loads 18% 32% 0 0 0 1410 252 0 0 0 990 317 18% 32% 0 0 0 34270 612 0 0 0 2458 787 Total room load Air required (cfm) 1662 68 1307 61 4040 164 3245 152 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed . P. - war➢gl�tsofe" 0816:13:42r- Right-Sute®Uriversal 202121.0.02 RSU23828 2021-MaPage 3 Waterstone1780AGR\LotBBlki Waterstone1780AGR.np Calc= W8 House faces: NW - wrightsoft Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 8 Block 1 Waterstone 178... Date: 06.07.12 By: FLETCH 1 Room name MBATH WIC 2 3 Exposed wall Room height 21.0 It 7.5 ft 4 Room dimensions 8.0 8 heatbool 8.1 ft heat/cool 5 Room area 1.0 116.0 ftz x 116.0 ft 1.0 87.0 ftz x 87.0 ft Ty Construction U-value Or HTM Area (ft) Load Area (ftz) Load number (Btuh/ft-`-) (13tuh/R2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 �f Blk wall; stu000 ext F 01 `._ M:n'. , 5:83 406 0 7 0 777 0 0 0 .. 0 !-C ,2A 2ov - .e.;.--._._0330 W 16B 19ad 0049 n: _'957 -822 s_ "0 ... _ 0 - ' % 0 � 'Q 0 =Q � 0. �__ 0. 2S9 - ' b6 0 0 56 0 0 227 : "' y! Blk wall sti000 ext 0201 ne ne 1 42 5 837 326 0 - 60 0 .0 350 0 " `244 4 W 161319ad 0.049 Blkvuall stuocoext A201 ;b550 se se se. 142 58340f'� 1595 2.59 1620 0 112 t 0 0 112 0 0 653455 0 0 0 0' 0 0 0 0 0 p .2A.2ov r 0 0 0 0 0 .a 0339. W 161319ad o°�000, _ 0.049 sw 1.42 2.59 0 0 0 0_ 0 0 0 0 77.77702Y �15 _ _ W� _ -.` ..,..1%57 : 6 , 0 , �=v 0 o wall stucco e W 5.83 o o o _ .00 o W 16B-19ad_ -�� �- •.,0 049 :_ � 9.57 ter,=„_1.42 20.92 0 0 - 0 _ 0 0 �0 0 ���0 0 �0 L ^J �0 LBlk wall, stucco eM 0.201 --G 2A-2ov 0.330 nw nw 5.83 9.57 4.06 16.61 0 0 .0 0 0 11J0 0 0 0 0 0 0 0 0 -- 0.600 "" nw 17.40 17.58 0 0 0 0 0 0 0. 0 091 12C Osw µ 0 2.64 131. 0 0 0 - a0 0: r- �0 00 1 0390 C L161330ad n r 1131e 11 43 _0 0 .0 0 L:____.0 0 0032 0.93 1.69 116 88 88 116 108 196 81 148 7'V 0 ...,..w 4; ,.,_ra �...r........�,,.. uc..a. '. `�c?ss w"•C`f..,.i .. "' a H-- - z.,..u. i,....ca...� � -... �_.�,...t...� ...... ..w4.+e' w...:u✓S.s;.a..*.re.... u....-- -.-ax � M*+C w.vM132i'..rr.,h v'.:d "� v6'+»wYts^..- . t� � >v��'�f, .isv.t..1.r'.-.s. m... ...iir-A,.X., Mf.w s''• ........... ?".'^.�i:'" .Wfi.... .w.....x......,,A orb1✓ i �.a.c.ua..m& rL+v�aa. .....�..,.e-.- �� _ �....-,�,.e."^ _.w...✓` .rr.-.d:+-w..-r 'wi..,..'t' .-:. Tom-.+' %,.^..�.� �i ....�..>-.++...-, ..m..-•--.-,.rt..--u _ -._..+........+wd 5,. kv....m..- �'�`�'A^'T-+.- ..�,.«� .d.^.a...e».. �„S. s.....�.- +wrp'"',-^y +., .,ae.-`m �..,....r - 1.:.^^.:.-. _va. - w_..�.-.. .•....a... snsL"w.lr" .e...«w...� 'TP'..T„A','^� 6 c) AED excursion -48 21 Envelopeloss/gain 1689 830 646 371 12 a) Infiltration b) Room ventilation 391 109 140 39 0 0 0 0 13 internal gains: Occupants pa 230 0 0 0 Appliances/other 0 0 0 Subtotal (lines 6 to 13) 2081 939 786 410 Less eMemalload Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 'Subtotal 0 0 0 0 15 Ductloads 18% 32% 2081 372 939 301 18% 32% 786 140 410 131 room load Air r ir required (d 2452 1240m) 928 541 100 58 38 25 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. A wr7gF�tsof!- Right-Su2021-Mar-0816:13:42 te®Uriversal 2021 21.0.02 RSU23828 Waterstonel780AGR\Lot8BlklWaterstonel780AGR.nis p Calc=MJB Hoefaces:NW Page 4 wrightsoftm Right-M Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WWW.DEL-AIR.COM Job: Lot 8 Block 1 Waterston 178... Date: 06.07.12 By: FLIETCH 1 Room name FAMIHALL(S) KIT 2 ENposed wall 24.0 ft 30.5 ft 3 Room height 9.5 ft heat/cool 9.5 ft heaV000l 4 Room dimensions 1.0 x 451.0 8 1.0 x 290.0 It 5 Room area 451.0 ftz 290.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ft- (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V� Blkwall stu000ext a. ;0201 n` 593 406 0 0 0 - p p p p U . B. , _. ,. 0.57_ L_ 822 _ 0 , w -0 W V�! 1613-19ad Blk wall stucco eM 0.049 0201 ne ne . 1.42 5.83 2.59 30 4.66 i28 30 ; 95 43 . 556 78 - 387 0 96 0 96 0 560 0 390 2A 2ov _ _ =0330 Re, _ 9,57_ 1,7_.7Q 33 ..� 0 . �a 313 =_, _ _57_9 _ 0 :1_ . z_0 W 161319ad � 0.049 se 1.42 2.59 30 30 43 78 0 0 0 0 Blk wall stuaoo ext ;10C`m� �0550 'se: 7W 1595 77706 7 64 1620 18 777746 18 =7269 285 T7 18 289 ', 0 r ; - 0 0 `0 2g,2ov,> A 0 0 0.0, +�'Q 9 W 168 19ad 0.049 sw 1.42 2.59 30 30 43 78 0 0 0 0 PBlkwall sticooexC x 0201 sw 5.83 406 0 0 r 0 0 0` 0 $ 0 2A 2ov ; _ M 0 330 ,,rsnf W 9.57; 15 67: _ '0 _ 0 , n 0 ° 0 . ` _ w0 .` 0 �0 w0 0 Blk wall, stucco e)d 0201 w 5.83 4.06 0 0 0 0 0 0 0 Wa 2A 2ov 39ad :, .-." 6B y 0330 J , 049 0 w _ riw: 9.57 ir42: 20.92 0 v 2S9 =:: 30 0 _ �� 30 0 0 0 0 0 0 Blk wall, stucco ext 2A-2ov 0201 0.330 nw nw 5.83 9.57 4.06 0 16.61 0 0 0 0 0 0 0 40 20 116 81 11J0 92C Osnr 0600 0091 nw 17.40 264; 17.58 0 1.3]i A 0 � 0 .0 0 0 0 0 20 108 0 20 " 108 0 350 285;=.142 0 353 11D0 _ v -0390 �n 1131 _ 1J.43. °0 0 ��0 0. :v �0 ,,.. ".�0 C _F...w.>= 166 30ad 22A1p1�;;_,',..sx.... 0.032 0989 0.93 1.69 538 909 _� _ 346 w= 346 321 584 �." 538 � 499 «___2868 •0,00 _451, . ;�24 688.;« _ 0 � ,_-_290 �.�,...:"31. �,, ,�875 0; k-«...,..« u' F Z atl] v .ur..� 7,-.- .i....se...t e+L-.v.. wwa« re=`�P .j-a+.rv.5 .r^ •e.. "c"i"-+'q., +eyy..o.«., -..zz. '.t »q, y k .,._.. ..,._..,..,„.�......r....«,,.+,�....._ .d..�..�..� M a.,. .�. #...,s.--n..'J,cak'? kf ........0 -c.....�. -.....B,.Y �r.....�.. .. wa.�.� 1 i'piµ+'..v.+J.wu..��v,.,Lu..-.«..m6'�. X...Ns..wo-:.�.P�«L . .:`. µ� � tiT .wlJ" " .A.._.w..b �% t. •Lz�m iM'8sS�1 i9.«3 { V �'..^"'u"' W;.'- ^^�+-^-.0 _ q' .- .. .. a' :.. ]=-_7= 6 c) AED excursion -162 -138 Envelope loss(gain 2780 2500 2506 1412 12 a) Infiltration 727 203 317 89 b) Room ventilation 0 0 0 0 13 Internal gains: OocupantsCa 230 2 460 0 0 Appliances/other p 1200 Subtotal (lines 6 to 13) 3507 3163 2823 2700 Less external load 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 15 Subtotal Duct loads 3507 3163 0 2823 0 2700 18% 32% 626 1012 18% 32% 504 864 Total room load Air required (cfm) 4133 4175 3327 3564 168 196 135 167 Calculations approved byACCA to meet all requirements of Manual J 8th Ed A - - wrigF�tsoR� Right-Sute®Uriversal 2021 21.0.02 RSU23828 2021-Mar-0816:13:42 Waterstone1780AGR\Lot8BlkiWaterstone1780AGR.np Calc=MJ8 Hoisefaces:NW Page 5 -- wrightsoft® Right-JO Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone: 407-333-2665 Fax: 407-333-3853 Web: W W W.DEL-AIR.COM 1 Room name 2 Exposed wall 3 Room height 4 Room dimensions 5 Room area Ty Construction U-value Or number (Btuh/ft-f) 6 11 Blk stuccoext 1- 02011 w I 6 c) AED excursion Envelope loss/gain 12 a) Infiltration b) Room ventilation 13 Internal gains: Subtotal (lines 6 to 13) Less external load Less transfer Redistribution 14 Subtotal 15 Ductloads Total room load Air required (cfm) Md 0.2011 riw, 0.330 nw 0.600 nw Occupants pa Job: Lot 8 Block 1 Waterston 178... Date: 06.07.12 By: FLIETCH HTM (Btuh/ftz) DIN/FOY 27.7 It 9.5 ft heatbool 1.0 x 190.5 It 190.5 ftz Area (ftz) Load or perimeter '(ft) (Btuh) Area Load or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 5,83 4:06 297 - �`17 �- g99 S 1.42 2.59 0 0 �{ 0 0 " 583 �406 76 44 307" a957'10,4x16 r'0- 156 289i> g 7 1 42 2.59 0 0 0 0 ,x 583 4Q6 X ' fia v T ,0 � 0 7 r 0{7 ax �1595 11620 " 1.42 2.59 0 0 0 0 583 '"406ct0 , XO 0 re�0 P 5.83 4.06 29 17 99 69 9.57 20.92 12 1 114 249 42 259 Tom— 0 A 0 . ? ci0 , "0_ 5.83 4.06 72 49 283 197 9.57 16'61 23 0 224 389 1740 1758 0 0 0 0 264 131 0A`, 0 '00k: a`r 11,31 ,j1:43a�0.0. ,001'u .%y evekrx 0.93 1.69 227 227 210 383 ' y 28,68y 0 gQ191'28w x' 794 O N r Fr .w:,.[....�..,.F.;aix �.� _.,»xas»s.C.».".w, ,».s..w"ta.. L.�:aa.Nbu-'f„�, �.,, ems-. oS r�"'2�:1�,.. 'C...:. ��w..vrssu«.s +. b...,.v.» 5" S -• "A�"+ 72 �.,... sc ua 3,ySw n ..e.tur..,.c.....es'e MIKE .......w.. ....�..-.,-..�,-...sue .,»Fw.i...»v.� X«,1.-.,. a +.» ,....-r`:.�..s,.++`»>:.ew�... �� a, w......xrw:.✓w».. -.,.+...m +ahli.>Fiam.»".�^�.'. : "'^n ,,- '"Gwaa�d �`t _...,v.a.s_u... � esoox.,.iw .g"..+..sv.'..3.? U. zaza 4, Mn.....2-L3"'-.[iiu...a4.- v5a...e�.,�e ...y 'Y 1'..^`*ai,'�'•` ..3M... s u`a+'vr._'Y$a.,w ":'� 104 2534 2154 516 144 0 0 230 1 230 0 3050 2529 0 0 0 0 0 0 3050 2529 18 % 32 % 545 809 3595 3338 146 156 Calculations approved byACCAto meet all requirements of Manual J 8th Ed G`A - wrigFitsofe- 0816:13:42Mar- Rigk-SuteOUriversal 202121.0.02 RSU23828 2021- ...Waterstone1780AGR\LotBBlkiWaterstone1780AGR.rrp Calc=W8 Housefaces:NW Page 6 wrightsoft® stem Duct S Summary Job: Lot 8Block 1 Watersto... y nDate: 06.07.12 Entire House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: WWW.DEL-AIR.COM Project• • For: ADAMS HOMES 5428 Lugo Street, Fort Pierce, FL 34951 External static pressure Pressure losses Available static pressure Supply/return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.312 in/100ft 947 cfm 109 ft Supply Branch Detail Table Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.312 in/100ft 947 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH2 c 115 2 5 0.460 4.0 Ox 0 VI Fx 3.9 70.0 BR2 h 1662 68 61 0.420 6.0 Ox 0 VIFx 11.0 70.0 BR3 h 2435 99 70 0.443 6.0 Ox 0 VIFx 6.7 70.0 DIWFOY c 3338 146 156 0.374 7.0 Ox0 MFx 20.9 70.0 FAMMALL(S) c 4175 168 196 0.434 8.0 Ox0 VIFx 8.3 70.0 KIT c 3564 135 167 0.381 7.0 Ox 0 VI Fx 19.1 70.0 I.AU c 1177 26 55 0.456 4.0 Ox 0 VIFx 4.5 70.0 MBATH h 2452 100 58 0.312 6.0 Ox 0 VIFx 24.0 85.0 st1 MBR h 4040 164 152 0.322 7.0 Ox0 VIFx 20.7 85.0 sti WIC h 926 38 25 0.333 4.0 Ox0 VIFx 17.1 85.0 st1 Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st1 PeakAVF 302 236 0.312 553 10.0 0 x 0 VinlFlx Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rb2 Ox 0 947 947 0 0 0 0 Ox 0 VI Fx ' Wrlghtsoftm 2021-Mar-0816:13.43 Right-Sute®Uriversal202121.0.02RSU23828ACCk Pagel Waterstore1780AGR\Lot8BIklWaterstone1780AGR.rLp Calc=MJ8 Hoisefaoes:NW 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA a Project Name: Lot 8 Block 1 Waterstone 1780 AGR Builder Name: ADAMS HOMES Street: 5428 Lugo Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST LUCIE CO INTL = COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall The exterior thermal envelope contains a continuous air barrier. not be used as a sealingmaterial. requirements Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access'openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered floors) shall be permitted to be in contact with the top side of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned s ace shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind poping and wirmno Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids a. In addition, inspection of log walls shall be in accordance with the provisions of IC6-400. 3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 3/8/2021 4:27:52 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Duct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job,l`nformatidn . Builder: ADAMS HOMES Community: Lot: NA System 1 cfm25 System 2 cfm25 System 3 cfm25 Sum of others cfm25 Total of all cfm25 1780 Qn Total of all Total Conditioned systems Square Footage P`rescriptive Method cfm25 (Total), To qualify as "substantially'leakfreef On"Totalmust be less than or equal to 0.04 If air, handler unit is nstalled .lf air handler`uin is not , installed; Qn, Total must'be less4f6n or'equal .to'0.03. Th testing, method mb.otg,the requirements in accordance' with Section 13403.3;3. ' ls; the air ha»dlerunit, installed during tes`ting� 0 YES, (Sod? ,0 NO Q Performance/ERI Method cfm25,(out or TO a[)' <= To qualify using;this.method;'Qmmust not bgreater,than the; e ' •proposed duct'leakage Qn'specified on•rorm'11405-2020 or R406-2020 Leakage Type,selected on Forcri Qri. specified on Form R405-2020' R405-2020 (EnergyCalc), or R406 2020 (En ; • ergyCalc) or'R406-2020." PASS FAIL Proposed I 0.05 Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. Tesfing Company Company Name: Phone: I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 3/8/2021 4:28:56 PM EnergyGauge@ USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 66i 000 Permit #: Job Information Builder: ADAMS HOMES Community: Lot: NA Address: 5428 Lugo Street City: Fort Pierce State: FL Zip: 34951 Air Leakage'., Resuits Passing results must meet either the Perfdhmapce, Prescriptive, or ERl Method y, Q PRESCRIPTIVE METHOD The building or.dwellm'g unit shall be ested'and verified as having an air leakage rate of not exceeding 7 air changes per hour at a pressure of 0 2 inchw:g. (50 Pascals) m�.Climate Zones 1 and 2 ', - t Q PERFORMANCE or ERl METHOD The building or dwelling unitshall be;tested and uenfied:as hayi , an air leakage rate,of •nof:exceeding ahe selected ACH(50) value, as shown on Form R405=2020.(P. ertormance) or R406 2020 (ERI) (alieled section as infiltration, $ub-section ACH50: ACH(50) specified on.Form I?4Q5 2020 Energy,Ca/c (1?4ormanceJ'or R406 2020 (ERIJ 7.000 x 60 _ 15664 — Method for calculating building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans 1-1 PASS 0 Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. .4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing .Company` Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 3/8/2021 4:28:44 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance,. Prescriptive and ERI Methods ADDRESS: 5428 Lugo street Permit Number: Fort Pierce, FL, 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (1) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Lis) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2'percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned Floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. El R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'Y2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 600C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. I Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods In -line fan Any Any 2.8 cfm/watt 2.8 cfm/watt Any Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) oR403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized_ in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that'can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 ❑R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. ❑R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. ❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. ❑ R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. ❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. ❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 3/8/2021 4:28 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5