HomeMy WebLinkAboutCreekside Lot 7-digiA Universal
Sciences
snn c .tceCompany
UES Project No: 3360.1800067.0000
Workorder No: 236312-1
Report Date: 06/10/2021
607 Northwest Commodity Cove, Port St. Lucie, FL 34986 - P: 772-924-3575 - F: 772-924-3580
In -Place Density Test Report
Client: D.R. HORTON, INC. EAST FLORIDA DIVISION UES Technician: Russell Brause
1430 Culver Drive, NE Date Tested: 06/10/2021
Palm Bay, FL 32907
Project: CMT CREEKSIDE
Various Locations, Vero Beach, TBD County, FL 32967
Area Tested: Lot 7 / 3323 Homestead Dr, Ft Pierce -
House Pad
Material: Fill
Reference Datum: 0 = Top of Fill
The tests below meet the 95% minimum compaction requirement.
Type of Test:
Field: ASTM D-6938 Nuclear Gauge Method
Laboratory: ASTM D1557 Modified Proctor
Maximum
Optimum
Field Dry
Field
Soil
Pass
Test
Density
Moisture
Density
Moisture
Compaction
or
No.
Location of Test
Range
(pcf)
N
(pcf)
N
N
Fail
1
SE corner
0 to -1 ft
118.6
10.8
115.7
6.9
98
Pass
2
Middle.
0 to-1 ft
118.6
10.8
117.3
7.3
99
Pass
3
NW corner.
0 to -1 ft
118.E
10.8
116.5
7.7
98
Pass
Remarks: Permit 2104-0933.
Reviewed By
GFA International, Inc
FBPE Registry No.4930
JohnDigitally signed
by John Kent
Date:
Kent 24:58:1 -0
14:58:19-04'00'
John Kent
Senior Project Engineer
STATE OF FLORIDA
Professional Engineer No. 63218
This item has been digitally signed and sealed by John Kent on
the date adjacent to the seal. Printed copies of this document are
not considered signed and sealed and the signature must be
verified on any electronic copies.
To establish a mutual protection to Universal's clients, the Public and ourselves, all reports are submitted as confidential property of our clients and
authorization for publication of statements, conclusions or extracts from or regarding Universal's reports is reserved pending our written approval.
Page 1