In -Place Density Test Report
Client: D.R. HORTON, INC. EAST FLORIDA DIVISION UES Technician: Russell Brause
1430 Culver Drive, NE Date Tested: 06/10/2021
Palm Bay, FL 32907
Project: CMT CREEKSIDE
Various Locations, Vero Beach, TBD County, FL 32967
Area Tested: Lot 90 / 3328 Homestead Dr, Ft Pierce -
House Pads
Material: Fill
Reference Datum: 0 = Top of Fill
The tests below meet the 95% minimum compaction requirement.
Type of Test:
Field: ASTM D-6938 Nuclear Gauge Method
Laboratory: ASTM D1557 Modified Proctor
Maximum
Optimum
Field Dry
Field
Soil
Pass
Test
Density
Moisture
Density
Moisture
Compaction
or
No.
Location of Test
Range
(pcf)
N
(pcf)
N
N
Fail
1
SW corner.
0 to -1 ft
118.6
10.8
116.2
6.8
98
Pass
2
Middle.
0 to -1 ft
118.6
10.8
118.4
7.2
100
Pass
3
NE corner.
0 to -1 ft
118.E
10.8
116.7
6.6
98
Pass
Remarks: Permit 2104-1014.
Reviewed By
GFA International, Inc
FBPE Registry No.4930
John.Digitally signed
by John Kent
John Kent
Senior Project Engineer
STATE OF FLORIDA
Professional Engineer No. 63218
This item has been digitally signed and sealed by John Kent on the
date adjacent to the seal. Printed copies of this document are not
considered signed and sealed and the signature must be verified on
any electronic copies.