Loading...
HomeMy WebLinkAboutProject infoutility transformer 120/208v meter can location two 2" pvc conduits will be installed from the meter can to the transformer. 3 phase 4 wire. four 3/0 copper wires will be installed into each 2" conduit the existing service was fed by a single 2" conduit with utility pulled in wire. the existing utility wire had a downsized neutral that burned up in the transformer through the conduit into the meter can. it appears the AIRY wire may have been 1/0 aluminum with a downsized neutral wire. picture to the left is existing service 120/208v, 3 ph, 4 wire with two 200 amp, 3 ph, 4 wire disconnects to each side of the meter. Job: Plus One 3190 Airmans Way Ft Pierce, FL CO NTRACTOP: RICHMOND ELECTRIC INC 3086 ENTERPRISE ROAD FT PIERCE FL 34983 772-461-1951