Compliance statement: This product as described has demonstrated compliance with
Florida Building Code 2020, Section 1504.3.2, as required by Rule
61G20-3, method 1D
Manufacturer: Integrity Metals, LLC | 2640 Piper Dr, Ste. B, Vero Beach, FL
32960 | 772-584-2654 | www.intregritymetalsfl.com
Product: IntegriLok IM100 is a nailstrip panel with a 16” maximum panel
width, and nominal rib height of 1.”
Material: This product is manufactured from 26ga or thicker steel with yield
strength of at least 50ksi, and corrosion resistance per FBC
1507.4.3.
Fastener: #10 x 1” low-profile style fastener compliant with FBC 1506.6.
Larger diameter and longer length fasteners are acceptable.
Stainless steel fasteners may be used.
Substrate/Deck: Minimum 15/32” thick plywood.
Underlayment: Comply with FBC 1507.1.1 where applicable.
Slope: Comply with FBC 1507.4.2 where applicable.
Technical Documentation: This product has been tested to the UL 580-06 standard by
Intertek Testing (TST-1527), report I7726.05-450-44 R0. This test
report is used with permission.
This product has also been tested to UL 580-06 and UL 1897-15
by Intertek, report K4846.01-450-44 R0.
Max. Allowable Loads & Method A: 78.5psf | Install fasteners every other hole (±10” o.c.).
Installation Requirements: Method B: 108.5psf | Use self-adhering underlayment and install
fasteners in every hole (±5” o.c.).
Factor of Safety of 2.0 applied to calculate allowable loads.
Evaluated By: David Eng, PE
Timberlake Cove, LLC
3324 W Univ. Ave # 206, Gainesville FL 32607
PE Lic. No: 81377
CA Lic. No: 33344
www.timberlakecove.com
IM100 IntegriLok
26 gauge (min) 16” wide nail strip panel over 15/32” plywood
Florida Product Approval Number 28113.1
2604 Piper St Ste B
Vero Beach FL 32609
(772) 584-2654
FL28113.1 www.IntegrityMetalsFl.com Page 2
Panel Accessories: The manufacturer does not require the use of closures,
sealants, butyl, or other similar accessories between bottom
edge of panel and drip edge, or in other locations. The use
of closures and sealants may be advisable in some cases,
however that decision is the discretion of the project owner
and the installer.
Certification of Independence: David Eng, PE and Timberlake Cove, LLC do not have, nor
will acquire a financial interest in any company
manufacturing or distributing products under this evaluation.
The same entities do not have, nor will acquire, a financial
interest in any other entity involved in the approval process
of the product.
Exclusions & Limitations: Design of deck and roof structure (to include attachment of
plywood or wood plank) shall be completed by others. Fire
classification and shear diaphragm design are outside the
scope of this evaluation.
This report is limited to compliance with structural wind load
requirements of FBC 1504.3.2, as required by Rule 61G20-
3. Neither Timberlake Cove nor the manufacturer shall be
responsible for any conclusions, interpretations, or designs
made by others based on this evaluation report. This report
is limited solely to documenting compliance with Rule
61G20-3, and makes no express or implied warranty
regarding performance of this product.
Design Process: The load tables in this report provides one prescriptive
option for the fastening requirement for the applicable wind
loads for roofs within the parameters described. For roofs
outside of the listed parameters, design wind loads shall be
determined as required by FBC 1609, ASCE 7, or other
design code in force, using allowable stress. These load
tables are based on ASCE 7-16. Use of these tables
assumes that the structure is:
Enclosed and conforms to wind-borne debris provisions
and is a regular shaped building
Is not subject to across-wind loading, vortex shedding, or
instability; nor does it have a site location for which
channeling or buffeting warrant consideration
Engineering analysis may be completed by other licensed
engineers for project specific approval by local authorities
having jurisdiction.
2604 Piper St Ste B
Vero Beach FL 32609
(772) 584-2654
FL28113.1 www.IntegrityMetalsFl.com Page 3
Design Load Tables:
Select the appropriate load table that applies to the
structure in question.
Determine the design wind speed for the project
location.
Use the attachment method indicated for that
windspeed within each roof zone.
NOTE: ASCE 7-16 and FBC 2020 adopt a 7-zone
concept. For the load tables below, the worst case
was taken for each zone and reported using the
standard zones 1-2-3:
Zone 1 includes zones 1 and 1’
Zone 2 includes zones 2e, 2r, and 2n
Zone 3 includes zones 3e and 3r
Combining these zones creates a clear, simple scheme, at the expense of some design efficiency.
Contact the manufacturer for further information, or consult a licensed design professional.
Method A: (1) #10 x 1” (min) fastener every other
hole (±10” o.c.)
Method B: (1) #10 x 1” (min) fastener every hole
(±5” o.c.) with self-adhering underlayment
NR: Consult a design professional to assess the
proposed installation
Use this load table for structures which meet the following criteria:
Are located in Exposure B area
Have either a flat roof, or gable/hip roof with max slope of 45°
Have a mean roof height of 30 feet or less
Wind 120 130 140 150 160 170 180 190 200
Zone 1:A A A A A A A A B
Zone 2:A A A A A B B B NR
Zone 3:A A A A B B NR NR NR
Use this load table for structures which meet the following criteria:
Are located in Exposure B area
Have either a flat roof less than 7°, hip roof with
max slope of 45°, or gable roof with slope between 20° and 45°
Have a mean roof height of 30 feet or less
Wind 120 130 140 150 160 170 180 190 200
Zone 1:A A A A A A A A A
Zone 2:A A A A A A B B B
Zone 3:A A A A B B B NR NR
FL28813.1: 26ga IM100 1" nail strip on 15/32" plywood
FL28813.1: 26ga IM100 1" nail strip on 15/32" plywood
Use this load table for structures which meet the following criteria:
Are located in B, C, or D exposure area
Have either a flat roof, or gable/hip roof with max slope of 45°
Have a mean roof height of 30 feet or less
Wind 120 130 140 150 160 170 180 190 200
Zone 1:A A A A B B NR NR NR
Zone 2:A B B NR NR NR NR NR NR
Zone 3:B B NR NR NR NR NR NR NR
Use this load table for structures which meet the following criteria:
Are located in B, C, or D exposure area
Have either a flat roof less than 7°, hip roof with
max slope of 45°, or gable roof with slope between 20° and 45°
Have a mean roof height of 30 feet or less
Wind 120 130 140 150 160 170 180 190 200
Zone 1:A A A A A B B NR NR
Zone 2:A A B B B NR NR NR NR
Zone 3:A B B NR NR NR NR NR NR
FL28813.1: 26ga IM100 1" nail strip on 15/32" plywood