HomeMy WebLinkAboutAPPROVED, The House Of Winners Fire Alarm Plan Approved By SLCFPAZ AFAA NAC Voltage Drop Calculator for Audio / Visual devices FC901 Battery Calculations Worksheet Fixed Field Enter Numbers Here ver. 1.5 Calculated Field Choose a value 5-May-2021 Ref. No THE HOUSE OF WINNERS Submitted By LIFE SAFETY SYSTEMS INC. FC901 Panel Standby A Alarm A Main Board 0.178 0.203 Device Current Draw 0.0062 0.0062 NAC 1 0 0.79 NAC 2 0 0.984 Aux power external FCACi Tie FSD901 Remote Annun. Devices Clty smoke detector head heat detector head pull station dual point module HFP-1118713 HFPO-11/8710 HFPT-11 / 8712 OOHC941 0OH941 OH921 OP921 2 0.0006 0.00061 H1921 0 0 0 FDC10422 HMS / 8700-S/O/M 3 0.0042 0.0042 HTRI-S/M / 8701/8702 HTRI-D / 8703 1 0.0014 0,0014 HTRI-R / 8704 HZM / 8705 HCP / 8706 [LED / 8726 Total 61 0.0062 S stem OK 0.1842 1.9852 Total Current IStandby Time 24 4.421 Alarm Time 51 0.165 AH required no reserve 4.586 Battery Reserve 1 11071 AH Re uired with reserve : 5.044856667 S stem OK lBattery Provided I AH This calcu', for provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you "0"' what method is accepted by, and the results do not exceed the limits set by the respective ju Project Name HOUSE OF W frvrvcrco Date 5/5/2021 Circuit Number 1 Area Covered Nominal System Voltage 24 Minimum Device Voltage 16 Total Circuit Current 0.792 Wire Ohm's Gauge Per1000 Distance from source to 1st device 25 1 16 1 4.89 Wire Gauge for balance of circuit 1 16 4.89 Enter current in amps. Distance 150 = 150 ma from Voltage Device Device previousLavice At Drop from Percent rJ,,.. h- I r„^o.,r ,�o.n�o source Droo END Device 3 END END END END END END END END END END END END END END END END END Totals End of Dne Voltage ,urrent Distance Drop Current Distance Drop Current Distance Drop 0,792 115 0.54 0,792 115 0.891 0.792 I 115 0.445 End of Line Vottagel 23.461 End of Line Voltagel 23.11 1 End of Line Voltage 23.55 Percent Drop 2.26%1 Percent Dropi 3.71%1 Percent Drop] 1.86 End of Line and Load Centering Methods use only the wire guage for the first device to source Standard Wire Resistance in Ohms per 1000 feet. 18=7.77 16=4.89 14=3.07 12=1.98 10=1.24 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors tes: re resistance is doubled in the calculations for two wires (Positive and Negative) voltage calculated to the last device in any method must not be lower then manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). Ace Manufacturer ISIENIENS Device Manufacturer ISIEMENS itn�.rom a,rroor @Rated AZ AFAA NAC Voltage Drop Calculator for Audio I Visual devices This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jt Project Name HOUSE OF W INNt:Kb Date 5/5l2021 Circuit Number 2 Area Covered Nominal System Voltage 24 Minimum Device Voltage 16 Total Circuit Current 0.984 Wire Ohm's Gau a Per 1000 Distance from source to 1st device 45 167 6 4.89 Wire Gauge for balance of circuit L 16 1 4.89 Enter current in amps. Distance A! 0 = 150 ma from Voltage Device Device previous At Drop from Percent Number Current device DeVice source Drop Device 1 END Device 3 Device 4 Device Device 6 END END END END END END END END END END END END END END Totals 0.264 0.264 0.264 0.064 0.064 0.064 0.984 220 FIRE ALARM LEGEND PER NFPA 170 FACP FIRE ALARM CONTROL PANEL JEVAC 25 WATT VOICE EVACUATION PANEL DACT CEI 4G/LTE FIRE CELLULAR COMMUNICATOR SMOKE DETECTOR PHOTOELECTRIC a PULL STATION WATERFLOW DETECTOR FTI TAMPER SWITCH © STROBE cd as noted 15cd s SPEAKER STROBE cd as noted 95cd s CEILING SPEAKER STROBE cd as noted Current I Distance I Drop I Current I Distance I Drop I Current I Distance I Drop End of Line and Load Centenng Methods use only the wire guage for the tlrst device to source Standard Wire Resistance in Ohms per 1000 feet. 18=7.77 16=4.89 14=3.07 12=1.98 10=1.24 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors as: e resistance is doubled in the calculations for two wires (Positive and Negative) voltage calculated to the last device in any method must not be lower then manufactures listed minimum operating voltage (IE: rated operating voltage 20-32 VDC). ice Manufacturer ISIEMENS Device Manufacturer ISIEMENS Current Current 54KER STROBE @Rated Rated SIGNAL CIRCUIT 18 GAUGE SHIELDED FPL WIRE d1i/t 8191111 11119/I �9/1 SIGNAL CIRCUIT 18 GAUGE SHIELDED FPL WIRE slop ADDRESSABLE LOOP 18 GAUGE FPL WIRE ALL SPEAKERS TO BE TAPPED AT 2 WATTS FIRE LlARM SYSTEM HOO U E OO F WINNE' S ARCADE 7137 US- HWY. 1 PORT ST.LUCIE, FLOORIDDA PAUL WELCH INC. 1984 BILTMORE ST. #114 PORT ST LUCIE, FL 34984 PAUL WELCH P.E. LA REG NO.29945 MAY 0 5 2021 1, Power Connection - Power for FACP will be run from electrical panel located in Mechanical Room, Circuit will be dedicated with a 20 amp breaker as over current protection and no less than 14 AWG wire with 600 volt insulation will be used, 2, Per FBC Section 907,16 Acceptance tests, Upon completion of the installation of the fire alarm system, alarm notification appliances and circuits, alarm -initiating devices and circuits, supervisory -signal initiating devices and circuits, signaling line circuits, and primary and secondary power supplies shall be tested in accordance with NFPA 72 in the presence of the Building Official, 3, Per FBC Section 907,17 Record of Completion, A record of completion in accordance with NFPA 72 verifying that the system has been installed in accordance with the approved plans and specifications sha 1 1 be provided, 4, Per FBC Section 907,18 Instructions, Operating, testing and maintenance instructions, and record drawings ( a as bunts") and equipment specifications shall be provided at an approved Location. 5, Battery Calculations - See attached, 6, Conductor Type and Sizes - Initiating Circuits - Solid copper 2 conductor 18 AWG r Notification Circuits - Solid Copper 4 conductor 18 AWG SHIELDED 7. Voltage Drop Calculations - See attached, 8r FACP w i l l be mon i tored by a Ur L. l i steel centra l station via CELLULAR C❑MMUNICAT❑R PORT " �� t- ,. x :. 3 , its � " 95cd 95cd 95cd 8 g g EOL SIGNAL CIRCUIT #1 95cd 95cd 95cd V 15cd 15cd 15cd • .wa g g EOL SIGNAL CIRCUIT #2 U OP P & O IJ Q � � SIGNAL CIRCUIT 18 GAUGE FPL WIRE FACP __ ADDRESSABLE LOOP 18 GAUGE FPL WIRE EVAC I DACT C a L/C 12ov-A/C 120v 0 Op 0 F1 Fw] IT] ADDRESSABLE LOOP LEGEND 0 3 10 SEA k F ONVTE�rEI) Ly. '311 TT ALARM CONTRACTOR LIC. EF 0001037 Building -ARCADE Area - ALL System NFPA 72 File: Date: 5/5/21 SCALE: AS NOTED Revisions Drawn By: R.THOMPSON Contract No. Insurance Review - AIE Sheet No.