Loading...
HomeMy WebLinkAboutAPPROVED, FL27499.12SPECIALIZING IN IMPACT RESISTANT CURTAINWALLS, STOREFRONTS, & WINDOWS Option #1 Option #2 Installation Installation Max. Design Pressure: -219 psf -219 psf Clip Anchor Spacing: 4" From Ends, 12" Max. O.C. 4" From Ends, 12" Max. O.C. Min Panel Fasteners: #10x1" Panclip Fasteners #10x1" Panclip Fasteners (2) Per Clip (2) Per Clip Panel Seam Sealant: Continuous bead of Bostik 915 on both sides of seam (at slopes < 2”/12” only) Continuous bead of Bostik 915 on both sides of seam (at slopes < 2”/12” only) Panels are Seamed to 90⁰ Panels are Seamed to 90⁰ Fire Barrier: Where required by code, install an approved fire barrier. Refer to a current fire directory listing for fire ratings of this roofing system assembly as well as the location of the fire barrier within the assembly. (See note #2 below) Note: Outside of the HVHZ, in areas with windspeeds < 170 mph, 1” round plastic caps meeting the requirements of FBC Section 1507.1.1.1, may be used to prevent galvanic reactions. Underlayment: Minimum ASTM D 226 Type II, installed and anchored per FBC Section 1507.1.1.1 (min). (or) Any underlayment with a valid FLPA or Miami-Dade NOA Note: Outside of the HVHZ, in areas with windspeeds < 170 mph, 1” round plastic caps meeting the requirements of FBC Section 1507.1.1.1 may be used to prevent galvanic reactions. Minimum Substrate: ½’ (15/32” min) 4-ply CDX Plywood or ¾” solid wood planks (S.G. = .42 min) nailed to 2x rafters spaced 24” max. on center with 8d ring-shank nails spaced 6” on center. Note: The ¾” wood planking must be installed as a solid deck and must be nailed or fastened in a manner equal to the deck above, or as specified by a Florida licensed Architect/Engineer