THIS CERTIFICATE SIGNIFIES
OLIVER FIBERGLASS
609 SWAN AVE
HOHENWALD. TN 38462
(CR# 6003)
IS IN CONFORMANCE WITH THE PROGRAM REQUIREMENTS
FOR THE FOLLOWING PLUMBING FIXTURES:
WHIRLPOOL BATHTUBS WITH PRESSURED SEALED DOORS
SHOWER BASES
MANUFACTURED IN ANY OF THE FOLLOWING APPROVED MATERIALS:
ACRYLIC FIBERGLASS REINFORCED PLASTIC
GELCOATED FIBERGLASS REINFORCED PLASTIC
THE LISTED PRODUCTS HAVE BEEN TESTED IN ACCORDANCE WITH THE APPROPRIATE
SECTIONS OF THE ASME A112.19.7/CSA B45.10; ASME A112.19.15; AND CSA B45.5/IAPMO Z124 STANDARDS
Deanna Seale. PE
Director Laboratory Services
Thr, cerfificbte becomes mvaFd upon °i/soenS�om camp..11at`on, r6'd:iration, rx expiration of Gertjftat,60
Home innovariw Research Labs 400 Pnnce Georges 6oukverd Upper Marlboro. MD 20774 1 Homelnnovarion.com
January 1 2021 December 31. 2021
Issuance Date Expiration Date
Manufactured By:
Report Number:
Date !unit Received:
Date Unit Tested:
Date off Report:
Home Innovation
RESEARCH LASS--.
Walk-in Bathtub.with Pressure Sealed Door and
Hydromassage System Certification Report
ANSI Z124.1.2, ASME Al 12.19.7, ASME Al 12.19.15.
Oliver Fiberglass
609 Swan Avenue
Hohenwald, TN 38462
60030514
05-02-14 Model Number: LP2851LWfoaded
05-09-14 Unit Serial Number: 125416
07-30-14 Date of Manufacture: 04-14-14
Tests perforated in accordance with ANSI Z124.1.2-200.5-Plastic Bathtub and Shower Urdts
2.0 GENERAL REQUIREMENTS
2.1 Materials Pass
Reinforcement — Resin/ Filler/ Fiberglass/ Metal Frame
Plastic — Resin
Filers —Calcium Carbonate
Surface .Finish — White Gel Coat
Unit Characteristics — Walk-in Bathtub with Pressure Sealed Door and Hydromassage
System
2-2 Dimensional Tolerances:: 59i x 28" x 36' Pass
The units finished trim measurements shall be within tolerance of
manufacturer's stated rough -in dimensions.
2.3 Unit for Testing Pass
Unit shall be randomly selected from manufacturers finished goods
inventory.
2.4 installation Instructions Pass
Written installation instructions shall be affixed to the unfit in a visible
location.
2.5 Care and Maintenance Instructions Pass
Written care and maintenance instructions shall be affixed to the unit in
a visible location.
2.6 Identification Pass
Manufacturers name and/or trade mark shall be permanentty .and
legibly marked on the unit in a visible location.
°1W i: :::1-.'•.'.e Ty���
WALK-IN BATHTUB TEST RESULTS
Manufactured by: Oliver Fiberglass Report #: 60€ W514
Hohenwald, TN
2.7 Grab Bars
Pass
2.g Raised Flanges and T'ding Beads N/A
Bathtub intended for use against a vertical wall shall incorporate a
raised flange or bead not less than 5116" above the rim at any poirti.
3.0 WORKMANSHIP AND FINISH
3.3 Surface Test Pass
Unit shall be free of cracks, chipped areas and blisters. The number of
molding and other defects or blemishes shall not exceed those given in
Table 1 of the referenced standard.
3.4 Subsurface Test Pass
No visual blemishes or voids larger than 1116 of an inch in diameter
shall be observed below the surface finish.
4.0 STRUCTURAL INTEGRITY
4.2 Drain Ruing Connection Test Pass.
During and after the application of 50 pounds by using a 24 inch lever
arm in three radial positions, no cracks shall be observed around the
drain opening. During the load application in the three positions, no
leaks shall be observed.
4.3 Point impact Load Test Pass
After the impact of a 1'A inch, half -pound steel ball from a height of 36
inches and 24 inches, no cracks or chips shall be observed in any of the
surface.areas tested.
4.4 Seat Load Test
Pass
4.5 Bottom and Threshold Load Test Pass
Bottom Load
Measurements recorded under the applied loading of 300 pounds on
three: different bottom surface areas shah not exceed the maximum
allowable deflection of 0.150 inches. After removal, the unit shall not
exceed the maximum allowable residual deflection of 0.008 inches. No
cracks shall be observed in the surface finish.
Position
Number
Deflection
inches
Residual
Deflection
inches
1
0.:043
0.000-
2
0.027
0.000
3
E051
1 0 000
Home Innovation Research Labs: Z124.1.2, ASME At 12.19.7, ASME At 12:1.9.15 Test. Repoli Page 2. of 9
WALK-IN BATHTUB TEST RESULTS
Manufactured by: Oliver Fiberglass Report # 60030514
Hohenwald, TN
Rim Load
A 300 pound load shall be applied to the end and mid sections of the
rim. No cracks shall be observed in the surface finish.
Rim Load.
A = Pass
B = Pass
4.6 Area Impact on Wall Surrounds Test
4.7 Wall Surround Load Test
WA
4.8 Radii Load Test Pass
Surface shall :show no cracks, chips, or voids under the applied load of
10 pounds with a half -inch diameter nylon rod on the units radial
surface areas.
4.9 Unsupported Area Load Test Pass
Under the application of 10 pounds on three different tub wail areas, the
measured deflection shall not exceed 0.125 inches at any individual
load point. No cracks or chips shall be observed in the surface finish of
the areas tested.
Position
Number
Deflection
inches
1
0.014
2
0.092
3
Ci.065
5.j Colorfastness Test Pass
The test sample shall show no significant change in color or surface
texture after 200 hours of exposure to a xenon arc -type light -
exposure apparatus in accordance with ASTM D2565.
Home Innovation Research Labs: Z124.1.2, ASME A'l1:2.19.7, ASIME Al 12.19.15 Test Report Page 3 of 9
WALK-IN BATHTUB TEST RESULTS
Manufactured by: Oliver Fiberglass Report #: 60030514
Hohenwald, TN
5.2
5.3.
Stain Resistance Test
Ratings for removal of the seven stains listed in the referenced
standard are as follows:
. REAI:GENT
COVEREi3
.UNCOVERED
1. Black crayon
1
1
2. Black liquid shoe polish
1
1
3. Bluewashable ink
2
2
4. Gentian Violet solution
2
2
5. Lipstick
1
1
8. Hair dye
1
1
7, iodine solution
1
1
TOTALS
9
19
Thickness of.rnaterial Iost =
1----inches
Stain resistance rating = 18
The stain resistance rating shall not exceed 50. The maximum
allowable: thickness of material removal to eliminate the stain shalt be
0.005 inches.
Wear & Cleanability Test
A. Wear
The surface finish of the three test samples shall not wear
through to the supporting subsurfaces after 10,000 scrub
cycles with an abrasive slurry solution.
Cleanability
The average absolute loss of white light reflectance after
application and removal of standard dirt with liquid detergent
shall not exceed 5Z percent. The average absolute loss of
white -light reflectance after additional cleaning with an
abrasive slurry solution shall not exceed 2.0 percent.
B.
Loss after liquid detergent application = 0.9%
Loss after abrasive slurry application = ---%
5A Cigarette Test
After contact with three lighted cigarettes, the test sample shall show
no ignition, progressive glow, or unrepairable damage.. Damage to
the surface shall be easily repairable by using abrasive and./or
polishing compounds.
5.5 Chemical Resistance. Test
The surface finish shall be unaffected by the 12 reagents used. Any
superFicial surface change shall be easily repairable by using
abrasive and/or polishing compounds.
5.6 Ignition Test
Pass.
Pass
Pass
=
Pass
Pass
Hone Innovation Research Labs: Z124.1.2, ASME A112.1:9.7, A$ME A112.1.9.15 Test Report Page 40 9
WALK4N BATHTUB TEST RESULTS
Manufactured by. Oliver Fiberglass Report #: 60030514
Hohenwald, TN
5.7 Thermal Shock Resistance - Types 2,3;4,5 and 6 Pass
No cracking, crazing, blistering, spalling or delamination shall be
observed at the coriclusion of testing. The unit shall pass the ANSI
requirement of 250 cycles.
6.1 Water Resistance Test -.Types 1,2 and 3 pass
The water resistance rating is determined by evaluating each test
sample, after 100 hours of exposure to elevated, water temperature,
(Types 1 & a-150°F, Type 2 - 2121,F), for color change,, blistering,
change in surface profile, cracks and loss of visible gloss.
The water resistance rating for each of the samples tested shalt not
exceed the maximum allowable water resistance rating of 9. Each of
the five types of failures shall not exceed the individual maximum
allowable, rating of 4.
MERGE
as
[tom t •
Water
Home Innovation, Research Labs: Z124.1.2, ASME Al 2.19.7, ASME Al12.19.15 Test Report Page 5 of 9
WALK-IN BATHTUB TEST RESULTS
Manufactured by: Oliver Fiberglass Report* 6003M14
Hohenwald, TN
Tests performed in accordance with AS1VIE All 2.19.7
2.1.1 Bathtub: Bathtub: shall conform to ANSI Z124.1.2 standard. Pass
Bathtub has been previously tested and listed by Home Innovation
Research Labs and conforms with the ANSI. Z124.1.2 standard.
2.1.2
Piping System:
Pass
A. Intake
Outer Dia.: 1 718"
Material Type: PVC
Label or Marking: ASTM D1785/2665
B. Jet Connections
Outer Dia.: 1 1/4" u
Material Type: White Flexible Plastic / PVC
Label or Marking: SP1099 / ASTM D17885
2.1.3
Joint Requirements:
Pass
2.1.4
Pump. Requirements:
Pass
Pump Motor
Make: NuWhid Make:
NuWhirl
Model No.: PXD7500 Model No:
PX.D7500
Serial No.: 011714 Serial No.:
011714
Horsepower.
1
GFCI Label Location: Top of Motor
Pump & Motor Listed By: UL / CSA
2.1.5
Suction Fittings:
Pass.
Quantity: 1
Material Type: Plastic
Make: NuWhirl
Model No.: SSCL
GPM Rating: 118 UL & IAPM0 Listed
2.2
Circulation System
Pass
a. Acceptable Drainage Slope
Complies with Section 5.0.
b. Pump Connection
Attached by removable fittings.
c. Self- or Non -Draining Pump
Provides drainage for pump volute.
d. Separation Between Muitiple Suction Fitting
Separation was not less than 12 inches.
e. System must be watertight.
Horne innovation :Research Labs: Z124.1.2, ASME A112.19.7, ASME A112.19.15 Test Report Page 6 of 9
WALK-IN BATHTUB- TEST RESULTS
Manufactured by: Oliver Fiberglass Report 8QO,';M 14
Hohenwald, TN
2.3 Installation Instructions Pass.
Roughing -in Reference Including Overall Dimensions
Service Access. Panel Requirement
Electrical Requirement
Reference to NEC Section 680G including reference
of GFCI protection.
Installation Precautions .(to the installer)
2.4 Operation, Use and Care Instructions Pass
Operating and Use Instructions
Flushing Instructions
3.0 WATER RETENTION REQUIREMENTS
3.1 Water Retention Requirements pass
The amount of water retained in each fitting must be no greater than
1.5 ounces. No leaking shall be allowed.
Number of .Suction Fittings: 1
Number of Jets: 11
Water retained per fitting: 1.1 oz.
3.3.2 Hair Entrapment Requirements (in Unit) pass
The force required to remove the hair from the suctionfitting shall be no greater
than 5 pounds in ail trials.
Trial 1
1.0 'Ibs
Trial #2
1.0lbs
Trial 43
1.0 Ibs
Trial #4
10 Ibs
Trial #5
1.0 lbs
Trial 416
1.0 Ibs
Trial #7
1.0 lbs
Trial #8
1.0 lbs
Trial #9
1.0 lbs
Trial #10
1.0 lbs
Home Innovation Research Labs: Z124.1.2, ASME All2.19.7, ASME Al 12.19.15 Test Report Page 7 of$
WALK-IN BATHTUB TEST RESULTS
Manufactured by: Oliver Fiberglass Report #: 60030514
Hohenwald, TN
4.0 MARKING AND LABELING
4.1 Factory Assembled Units Pass
Label shall be affixed to the exterior and adjacent. to the waste and
overflow which states, in 3/16 inch high letters:
TUB SHALL BE TESTED FILL THE TUB WITH WATER TO
OVERFLOW DURING ROUGH INSPECTION AND INSPECT FOR
LEAKS.
Tests performed in accordance with ASMF All 12.19.15
2.1 Materials pass
Materials used in the construction of the unit shall be suitable for
application in a plumbing fixture. The unit shall also comply with the
requirements of ANSI Z124.1.2 and ASMF Al 12.19.7 if applicable.
2.2 Door Pass
The bathtub door shall meet .the per ormance criteria detailed in
section 3.
2.3 Electrical Components Pass
Electrical components shall comply with the applicable sections of
UL1795.
2.4 Door & Seals
Pass
The door shah have either a primary and secondary seal or a primary
seal with adequate means for drainage.
2.5 Primary Seal Materials Pass
Materials used for the primary seal shall conform with the following
requirements from ASTM D2000. Heat Aged for 70 hours at 257`F.
Shall have a maximum water absorption of no more than 5% when
exposed to 212°F water for 70 hours. Shall have a minimum tear
resistance of 14 kN/m.
3.i Secondary Seal N/S
The secondary seal, if used, shall have a leakage of not more than 0.5
gal in 20 minutes when the unit is filled to the overflow and the primary
seal has been disabled.
3.2 Door Load Test Pass
The door shall withstand a 300 pound load with a deflection of less
than 0.625". No cracking is permitted.
Home Innovation Research Labs: Z124.1.2, ASMF A112.19.7, ASMF A112,1...15 Test Report Rage<8 of 9
WALK-IN BATHTUB TEST RESULTS
Manufactured by. Oliver Fiberglass Report #: 6OW05.1.4
Hohenwald, TN
3.3 Door Cycle Test on Primary Seal Pass
The door shalt be cycled 20,000 times and, then the unit filled with
water. No leaking of the primary seal is permitted.
3.4 Door Cycle Test on Secondary Seal NIA
With the primary seal disabled, the door shall be cycled 20,.000 times
and then the unit filled with water. The secondary seal shall have a
leakage rate of no more than 0.5 gallons in 20 minutes.
4. Marking'Pass
The unit shall be marked with the manufacturer's name or trademark,
model number, and markings as required by other standards.
The unit was not damaged during shipping and it did not appear that the unit was tampered
with prior to arrival. These tests were performed under the direct and continuous supervision
of laboratory personnel. The plastic walk-in bathtub unit with hydromassage system; as
tested, passed all the sections of the ANSI Z1.24.1.2, ASME A112.19.7, and ASME
Al 12.19.15 standards as detailed in. this report..
Charles Arnold
Project Manager
Horne innovation Research Labs, is accredited by IAS in accordance with ISO 17025 and the tests
contained within this report are included in the scope of accreditation. This report shall not be Wed
to claim product endorsement by Home Innovation Research Labs or IAS. This Certificationreport
may be distributed in its entirety, but excerpted portions shall not be distributed without prior written
approval of Home Innovation Research Labs.
Home Innovation Research -Labs., Z124.1.2. ASME A1t2'.y9.7, ASM.E A112.:1�9.15 Test Report Page 9 of 9
* * * * * All weights are approximates * * * * *
Model
Empty
Water Cap.
Filled
LP2848
175lbs
73gal/609lbs
7781bs
LP2851
200lbs
75gal/626lbs
8011bs
LP2853
200lbs
90gal/7521bs
952lbs
LP3153
200lbs
105ga1/877lbs
1077lbs
LP3255
200lbs
105ga1/877lbs
1077lbs
LP5116
200lbs
85 gal/710 lbs
910 lbs
***All tub models take 30-35 gallons of water to fill the foot well***
SRecificadons for all components:
Heater 5.1 amps
Pump 4.7 amps
Air Blower 3.4 amps
Light.5 amps
Surface Heater .8 amps
Ozone .5 amps
Total amps 15.0 amps
In most cases this would require 1 dedicated 20 amp GFIC circuit.
Decibels of installed tub
78 decibels with all components running
Which is slightly louder than a dishwasher that runs at 50 decibels
IMPORTANT INFORMATION:
It is strongly recommended you use a qualified electrician that is familiar with ALL
local codes including National, State, City and County agencies as there are different
requirements across the nation.
Huntington Brass Installation Instructions for:
S7424701, S7424702, S7424703 - Thermostatic Roman Tub Filler Faucet
temperature
valve
Hand shower
re Valve Installation
Spout Installation
5" )
511 )
1 3/4 „ `
1 1 /4;.-' O
1 3/4"
1 /AII
-9 Align handle
button with
indicator mark
on cartridge,
and arrow on
plastic cartridge
retainer.
'k
DiverterValve Installation
1.
Huntington Brass Installation Instructions for:
S7424701, S7424702, S7424703 - Thermostatic Roman Tub Filler Faucet
Hand shower Installation
Please contact Huntinb on Brass
* Please flush the system before using the new faucet and hand shower.
Technical department
ifyou have any questions with the
We recommend removing the aerator and hand shower and let water
installation orfunction ofthisfaucer.
flush through the new faucet and hose to make sure that no contaminates
1-800-888-6604
will be present to cause blockage or damage to the system.
leaning & Care:
luntington Brass recommends cleaning your faucet with only mild soap and warm water. The use of any abrasive
leaners or chemicals will void* the finish warranty of you HB product.
roubleshooting:
The desired temperature cannot be reached, water is not hot enough.
Make sure the inlet temperature is within the specifications of this valve.
Make sure handle on temperature valve aligns with mark on the cartridge (see #11 on installation instructions)
Water temperature is either hot to cold. Will not maintain temperatures. Will not mix.
Hot and cold water inlet are reversed.
Flow rate reduced or fluctuating at the tub spout.
One way check valves at the hot and cold water inlet are blocked or restricted.
Flow rate reduced or fluctuating at the hand shower.
Check the two one way check valves in the hose and hand shower for blockage or restriction.
www.huntingtonbrass.com
H U NTI NGTON
B R A S S
SPECIFICATION 1 BREAK DOWN
S7424801 - Thermostatic Roman Tub Filler With Shower
scription
• Thermostatic Roman Tub Filler with Shower
Two way diverter with stop
• Brass tub spout
Single setting handshower with pause function.
• 2.D GPM @ 60 PSI handshower
• 5 " Metal shower hose
Ai Ijustable height shower with rain shower head
Standards
• C omplies with IAPMO UPC/cUPC
ME Al12.18.1
• C )mplies with B125.1
• A A Accessibility Guidelines for
uildings and Facilities - 4.27.4
Controls and Mechanisms
-ASSE 1016 Certified and listed
Colors / Finishes
B
- Chrome
oes
�a�
r
• 57424801
BEEN
0
3 _
E7E
060063 Qj 51
[2.36"]
[2.4.48"] � � [2.03"]
0 30-0 32
[1.18--1.26"]
13
[0.51"] Max
600
[23.6]
3/4-14NPgM-2B— \-3/4-14NPSM-2B
Inches marked in parentheses[
Item Number I Type I Date
S7424701 I Thermostatic Roman Tub Filler 1 12/28/2017
Inches
3
T R!
7
.[29
ou
0
.»^
o
tg6ae-t
YdzwcwQ
76
yas
sao-ax
°"
mze a�
[3.00"]
4NPSM-25
in parentheses ( j
6.0-305
[2:37-12"]
Cut to length
335
[13.20"]
200
[7.88"]
901-1363
[35.48-53.6E
766-1228
[30.2-48.34"]
Adjustable Height
178
i 126 [7.01 "]
-- [4.95"] 1
1"-- 154
[6.05"]
Item Number
Type
Date
S7424801
Thermostatic Roman Tub Filler 1
12/29/2017
50
IAPMO RESEARCH AND TESTING, INC.
D1 E. Philadelphia Streetr Ontario, CA 91761-2816 • (909) 472-4100 • Fax (909) 472-4244 • www.iapmort.org
CBd+15
tSO91EC 170" D
product Cer: ficat oe Sotly ry LAeerldai Ct.
IAPMO R&T Product Listing
This IAPMO R&T Listing is current as of 12/17/2019
M�
File No. 10921
Product: Water Temperature Limiting Devices
Issue ^o: NCIP INC.
5F-1, NO. 98, SEC.2
TUN HWA S.RD.
TAIPEI 10668, R.O.C.
TAIWAN
Identification: Each device shall have the following information permanently marked so the markings shall be
visible in the installed position: Name of manufacturer or trademark, model number, and hot and
cold indications on inlets along with the direction or means to change the outlet temperature
setting; product shall also bear the cUPC® certification mark or label.
Chara teristics:Water Temperature Limiting Devices to be installed using IAPMO listed fittings. Product to be
installed in accordance with the manufacturer's instruction and the latest edition of the Uniform
Plumbing Code.
Products listed on this certificate have been tested by an IAPMO R&T recognized laboratory. This
recognition has been granted based upon the laboratory's compliance to the applicable
requirements of ISO/IEC 17025.
Produ is are in compliance with the following code(s):
Uniform Plumbing Code (UPC®)
National Plumbing Code of Canada
Produ is are in compliance with the following standard(s):
ASSE 1070/ASME A112.1070/CSA B125.70-2015
T24771G*-**
T2487 G*-**
The 4ffix of "*" represents different types of finishes as follows:
Suffi* Description
O1
CHROME
02
SATIN NICKEL PVD
03
ANTIQUE BRONZE
13
POLISHED BRASS PVD
14
POLISHED NICKEL PVD
29
SATIN NICKEL
30
Matt Black Lacquering
35
Brushed Bronze
38
Matte Black
The sulffix of "**" represents different types of packages or trims as follows:
Suffix
Description:
AF
package 1
AQ
package 2
BC
package 3
BL
package 4
B1L
package 5
B2L
package 6
33L
package 7
CV
package 8
DH
package
9
DI
package
10
ET
package
11
KL
package
12
KT
package
13
NK
package
14
RE
package
15
SM
package
16
ST
package
17
TA
package
18
TM
package
19
VA
package
20
WB
package
21
WT
package
22
BG
package
23
IB
package
24
SP
package
25
AC
package
26
SS
package
27
WS
package
28
MB
package
29
HR
package
30
DV
package
31
PA
package
32
AT
package
33
FK
package
34
DW
package
35
AH
package
36
BT
package
37
WE
package
38
RB
package
39
AS
package
40
DB
package
41
SL
package
42
CF
package
43
MC
package
44
P.RM
package
45
PRB
package
46
PRA
package
47
SH
package
48
KP
package
49
FT
package
50
PS
package
51
PR
package
52
PH
package
53
MR
package
54
SW
package
55
SK
package
56
SB
package
57
LC
package
58
FA
package
59
SE
package
60
KE
package
61
ADDITI NAL COMPANY INFO:
Afeel orporation dba Huntington Brass
Model o. Description.
S7424 *-** 4-hole Roman Tub Filler faucet
S7424 *-** 4-hole Roman Tub Filler faucet
The sjffix of "*" represents different types of finishes as follows:
Suffix Description
01
CHROME
02
SATIN NICKEL PVD
03
ANTIQUE BRONZE
13
POLISHED BRASS PVD
14
POLISHED NICKEL PVD
29
SATIN NICKEL
30
Matt Black Lacquering
35
Brushed Bronze
38
Matte Black
The s ffix of "**" represents different types of packages
' or trms as follows:
Fe
SS800
SS900
Suffix Description
none for Huntington. Brass
AF1
packagel
AF2
package2
AF3
package3
AF4
package4
AF5
packages
AF6
package6
AF7
package?
AF8
package8
AF9
package9
AF10
packagel0
Enterprises Inc.
and its Proprietary Own Brands (for complete list of Ferguson brands, please refer to www.Ferguson..com)
Thermostatic Roman Tub Filler with hand shower
Thermostatic Roman Tub Filler with Shower Rail
This IAPMO R&T Listing is current as of 12/17/2019