HomeMy WebLinkAboutAPPROVED HVAC Plans - 6903 Salerno Rd INSTALLATION OF CONDENSING UNIT SPLIT SYSTEM SCHEDULE revisions
GENERAL AIR CONDITIONING NOTES MECHANICAL EQUIPMENT NOTES: SHALL COMPLY WITH FBC-2017 UNIT NUMBER AHU-1 no. date
Mc.
1. THESE DRAWINGS ARE RESULTING INSTALLATION ARE INTENDED TO COMPLY WITH: 1. ALL MECHANICAL EQUIPMENT SHALL BE ARI & U.L. LISTED WHERE APPLICABLE MIN. 2"+0 OF FLEX DUCT MANUFACTURER RHEEM
SEE ADDITIONAL COMPLIANCE NOTES. AND RATED FOR THE REQUIRED SERVICE, PRESSURES, TEMPERATURES, AND MODEL NUMBER RHIT3624STANJA
2. THE DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC, NOT NECESSARILY SHOWING SHALL BE PROVIDED WITH ALL NECESSARY TRANSFORMERS, SEALS, VALVES,
IN DETAIL OR TO SCALE ALL OF THE MINOR ITEMS. UNLESS SPECIFIC DIMENSIONS CONNECTIONS, ETC. TO FUNCTION PROPERLY.
ARE SHOWN, THE STRUCTURAL, ARCHITECTURAL AND SITE CONDITIONS SHALL 2. PROVIDE SMOKE DETECTORS WITH ACCESS DOORS IN ALL SUPPLY AIR DUCTS RIGID BOARD CABINET VERTICAL
GOVERN THE EXACT LOCATIONS. CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING FOR FANS AND AHU'S ABOVE 2000 CFM. ALL SMOKE DETECTORS SHALL BE BY FIBERGLASS ISOMODE PADS REFRIGERANT
OUT WORK, CHECK DRAWINGS OF ALL TRADES TO VERIFY SPACES IN WHICH WORK �ONTRACTORAANDRFIREC�LARMASYST�MTBEFORE ORDERINGLECUPIONLDETECTION, PLENUM BOX. I O�G� 4" CONCRETE PAD LINES z TOTAL AIRFLOW (cfm) / EXT. STATIC PRESSURE (iwc) 1200/0.25
WILL BE INSTALLED AND MAINTAIN MAXIMUM HEADROOM, AND SPACE CONDITIONS /
SMOKE DETECTORS SHALL SHUT DOWN ASSOCIATED AIR MOVING EQUIPMENT Q��� 0 A CFM 60
AT ALL POIN.T.S.. WHERE HEAD ROOM, OR SPACE CONDITIONS APPEAR � ��
AND ALL AIR MOVING EQUIPMENT SERVING THAT COMMON AREA. �� a ° °°° o °� o -• oo °° o FINISHED GRADE
INADEQUATE, ARCHITECT/ENGINEER SHALL BE NOTIFIED BEFORE PROCEEDING WITH
3. PROVIDE TYPE "B" FIRE DAMPERS IN ALL DUCTS OR OPENINGS PENETRATING � E.A.T. (db/wb °F) 76/63.8
INSTALLATION. THIS CONTRACTOR SHALL, WITHOUT EXTRA CHARGE, MAKE FIELD \, \, \>\\\\ \\ \\ \\ \\ \\\\ \\\\�\\\\�\\\\�\\\\ \ \\ \\\\
MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF FIRE RATED WALLS, PARTITIONS, FLOORS OR ROOF SLABS AND AT FRESH AIR
INTAKES IF REQUIRED (SEE ARCHITECTS PLANS FOR RATINGS). PROVIDE / J SENSIBLE COOLING CAPACITY (mbh) 26.1 designed VARIOUS TRADES OF FOR PROPER EXECUTION OF THE WORK. g 3. EXAMINE ALL DRAWINGS CAREFULLY PRIOR TO SUBMITTING A BID. CONTRACTOR RADIATION DAMPERS IN RATED CEILINGS FOR ALL CEILING OPENINGS, CEILING � MIN.2"+Qf OF FLEX DUCT FASTEN COND UNIT BASE PAN TO ___
FANS, DIFFUSERS OR GRILLES RATED FOR USE IN THE CEILING ASSEMBLY AS 4" CONC. PAD WITH (4) 1/4" TOTAL COOLING CAPACITY (mbh) 34.0
WILL BE REQUIRED TO FURNISH, INSTALL AND/OR CONNECT WITH APPROPRIATE SPECIFIED BY ARCHITECT. /, TAPCON CONCRETE SCREWS. 0 drawn LTH
SERVICES ALL AIR CONDITIONING ITEMS SHOWN ON ANY OF THE ARCHITECTURAL, 4. PROVIDE BACKDRAFT DAMPERS ON ALL EXHAUST FANS AND/OR INLINE FANS. SCREWS TO PENETRATE CONCRETE z BLOWER MOTOR HP / F.L.A. 1/2 / 2.7
p p
PLUMBING, ELECTRICAL AND SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENSE 5. PROVIDE VIBRATION ISOLATORS ON ALL MECHANICAL EQUIPMENT AS SPECIFIED / Q checked SBD
TO THE OWNER. IF DISCREPANCIES, CONFLICTS, INTERFERENCES OR OMISSIONS IN THE DRAWINGS. IF NOT SPECIFIED, AS RECOMMENDED BY MANUFACTURER / 1.5" MINIMUM, PLACE SCREWS AS VOLTAGE 230-1-60
OCCUR BETWEEN DRAWINGS, NOTIFY IN WRITING THE ARCHITECT/ENGINEER IN FOR QUIET OPERATION (WITH 99 % ISOLATION EFFICIENCY). / INDICATED IN THE BASE PAN.
AMPLE TIME TO PERMIT REVISIONS BEFORE THE BIDS ARE SUBMITTED. 6. PROVIDE A MIN. OF 10' CLEARANCE BETWEEN O/A INTAKES AND VTR OR = date 10/24119(PERMIT SET)
4. INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE EXHAUST OPENINGS. p p UNIT WEIGHT 125
MANNER. THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT 7. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE scale 114"=1'4-(U.O.N.)
OF ITEMS, WHICH, IN HIS OPINION, DO NOT PRESENT A NEAT AND WORKMANLIKE INSTALLATION (48" A.F.F.). SIZE AS REQUIRED MATCHING CONDENSING UNIT CU-1
APPEARANCE. REMOVAL AND REPLACEMENT IS TO BE DONE IMMEDIATELY WHEN 8. RUN INSULATED CONDENSATE DRAINS AS PER PLUMBING DRAWINGS. Q job no. 190627_SF 21.Ih
DIRECTED BY THE OWNER IN WRITING, AT THE SOLE EXPENSE OF CONTRACTOR. 9. MOUNT ALL ROOFTOP EQUIPMENT FOR WIND LOADS AND MOUNTING HEIGHTS AS APPROXIMATE SIZE (LxWxH) (in) 22 x 241 x 35
5. START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM REQUIRED BY LOCAL CODES, ALL CURBS SHALL EXTEND 8" MIN. ABOVE CUT PLENUM BOX PER GRILLE REQUIREMENT,
OF ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER FINISHED ROOF. (VERT OR HORZ)SEE PLANS FOR MODELS&SIZES KW 9.6
10. ALL PIPING AND DUCTWORK SHALL BE SLEEVED THRU WALLS, BEAMS, SLABS, CONDENSING UNIT FASTENING DETAIL
TRADES OTHER CONTRACTORS TO RECEIVE HIS WORK. THIS CONTRACTOR ETC, AS REQUIRED AND COORDINATED WITH THE STRUCTURAL ENGINEER. REWORK ELECTRIC HEAT ER
SHALL REMOVE AND REPLACE, AT HIS EXPENSE, ALL AIR CONDITIONING WORK BAR JOIST CROSS BRACING AND PROVIDE NECESSARY TRANSITIONS AS ALL FLEX DUCT TO BE FULL CIRCLE INTO GRILLE BOOTS(TYPICAL) N.T.S. CAPACITY (mbh) 32.7
WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCE WITH OTHER REQUIRED FOR DUCTWORK INSTALLATION.
TRADES. 11. ALL INSULATION WILL HAVE FIRE/SMOKE RATING LESS THAN 25/50. CU NUMBER CU-1
6. THE CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE, FEES, PERMITS 12. PROVIDE MOTOR STARTERS AS FOLLOWS (UNLESS OTHERWISE RECOMMENDED BY
ASSOCIATION DUES, ROYALTIES, AND TAXES OF WHATEVER NATURE SHALL APPLY TO MOTOR MANUFACTURER): FLEX-DUCT/PLENUM BOX DETAIL MANUFACTURER RHEEM
THIS WORK. HE SHALL ALSO PAY ALL INSPECTION FEES AS MAY BE REQUIRED BY A. PROVIDE OVERLOAD PROTECTION - 1/3 HP AND ABOVE (ALL PHASES). N.T.S.
LAW OR ORDINANCE AND SHALL KEEP THE OWNER HARMLESS FROM ANY DAMAGE B. PROVIDE ACROSS THE LINE VOLTAGE STARTING BELOW 25 HP. MODEL NUMBER RA1436AJINA
AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS, RULES OR C. REDUCED VOLTAGE MOTOR STARTER FOR 25 HP AND ABOVE.
ORDINANCES. 13. ALL OUTDOOR EQUIPMENT SHALL COMPLY WITH LOCAL ZONING NOISE NOMINAL TONS 3.0
7. THE WORD "AIR CONDITIONING" MEANS HEATING, VENTILATION, AIR CONDITIONING, ORDINANCES. MIN. REQUIREMENT SHALL NOT EXCEED A NOISE LEVEL OF 65 DB
DUCTWORK, PIPING, REFRIGERANT LINES, CONTROLS, SMOKE AND FIRE DAMPERS AS MEASURED RADIALLY 30 FT FROM THE EQUIPMENT IN ALL DIRECTIONS. O F CONDENSER AIR ENTERING TEMP 95°F
ETC. 14. FILTERS SHALL BE IN PLACE DURING CONSTRUCTION. PROVIDE A NEW SET. (° )
8. PROVIDE MEANS "FURNISH AND INSTALL". 15. PROVIDE FLEXIBLE CONNECTION FOR (RUBBER EXPANSION JOINT) FOR THE No. OF COMPRESSORS 1
9. DO A COMPLETE JOB, EVERYTHING CONNECTED, READY FOR USE. CONDENSER WATER PIPE ON THE SUCTION AND DISCHARGE SIDE OF THE PUMP,
10. SHOP DRAWINGS: THE CONTRACTOR SHALL FURNISH THE ENGINEER WITH SHOP HEAT EXCHANGER AND COOLING TOWER. FLEXIBLE CONNECTION TO BE TWIN O O ri
C7 O O O Z
SPHERE FROM API INTERNATIONAL TZT SERIES. R.L.A. ea 14.1
DRAWINGS OF EQUIPMENT PRIOR TO PURCHASE FOR APPROVAL. 1 1/2", 26 GAGE
11. AT COMPLETION OF JOB THE HVAC CONTRACTOR SHALL GIVE THE OWNER AN 16. PROVIDE 1' ISOLATION PAD UNDER CLAMP AT ALL PIPE PENETRATION ON THE HANGER BAND
AS-BUILT SET OF REPRODUCIBLE DRAWINGS SHOWING THE EXACT AND COMPLETE SLAB. /� L.R.A. ea 77
INSTALLATION. 17. PROVIDE 10" INERTIA BLOCK "MASON BMK" FOR ALL PUMPS. CLAMP WITH BAND V
12. ALL DUCT SIZES ARE IN INCHES AND REPRESENT CLEAR INSIDE DIMENSIONS. 18. ALL PIPE ABOVE 12" IN DIAMETER RUNNING HORIZONTALLY MUST BE HANGED LANAI DINING STRAP z No. OF CONDENSER FANS 1
13. THE HVAC CONTRACTOR SHALL WARRANT ALL WORKMANSHIP AND MATERIALS FOR FROM ADJUSTABLES STEEL YOKE PIPE ROLL WITH SPRING ISOLATORS. PIPES 12" 1"MIN.ONE YEAR FROM THE DATE OF FINAL WORK ACCEPTANCE BY OWNER. ANY AND LESS RUNNING HORIZONTALLY MAY BE HANG FROM STANDARD CLEVIS 5-0" F.L.A. ea 0.8
BREAKDOWN OCCURRING IN FIRST YEAR SHALL BE REPAIRED AT NO EXPENSE TO HANGERS, WITH ISOLATION PAD BETWEEN PIPE & HANGER AND SPRING O Z
ISOLATORS. O VOLTAGE 230-1-60
THE OWNER. THE COMPRESSOR (S) SHALL HAVE A FIVE YEAR WARRANTY. 19. UPON INSTALLATION OF DRYER EXHAUST DUCT, BECAUSE OF FIELD 8x8 CG-4W f W
14. MOUNT ALL EQUIPMENT FOR WIND LOADS AND MOUNTING HEIGHTS AS REQUIRED BY COORDINATION DRYER EXHAUST EXCEED MANUFACTURER RECOMMENDED LENGTH 150 CFM CU MAX BREAKER SIZE 30
LOCAL CODES. (INCLUDING ELBOWS). f NOTE:
15. ALL LOUVERS, GRILLES, PIPING, ETC. SHALL BE PAINTED TO MATCH SURROUNDING 20. PROVIDE PROOF OF AIR FLOW TO ALL AIR MOVING EQUIPMENT USE IN THE p 1 1/2" HANGER BAND CLAMP Z SYSTEM SEER 15.0
COLOR AND TEXTURES AS REQUIRED BY ARCHITECT. VERIFY COLOR AND TEXTURE SMOKE CONTROL SYSTEM, CURRENT SENSORS FOR ALL DIRECT DRIVE FANS I WITH WIRE IS OPTIONAL.
WITH ARCHITECT. PAINT ALL EXPOSED MECHANICAL EQUIPMENT WITH BENJAMIN AND SAIL SWITCHES FOR ALL BELT DRIVING FANS. II r0, LIQUID LINE (in) 3/8
MOORE EPDXY ENAMEL 182. 21. ALL VALVES AND FITTINGS RATED TO 175 PSI. O O O v
16. ALL CUTTING, PATCHING, STRUCTURAL STEEL, WEATHER PROOFING, PAINTING, AND 22. PROVIDE 1" VIBRATION ISOLATION PAD (NEOPRENE PAD) FOR ALL AHU AND A/C FLEXIBLE DUCT 24"0 MAX. TO BE INSTALLED SUCTION LINE (in) 7/8
WALL OPENINGS SHALL BE BY THE GENERAL CONTRACTOR. UNITS. IN ACCORDANCE W MANUFACTURES
23. SEAL ALL DUCTS, JOIN.T.S. AND SEAMS AN AN APPROVED MANNER TO INSURE
17. ALL OPENINGS IN BUILDING STRUCTURE, FOR DUCTWORK, PIPING, ETC. TO BE 1/2" AGAINST LEAKAGE. � 10"0 INSTALLATION INSTRUCTION. USE UNIT WEIGHT (Ibs) 171
LARGER (ON ALL SIDES) THEN THE OUTSIDE DIMENSIONS. FILL VOIDS WITH FIRE ONLY). 16�16 16x16 DUCT SEALER & BANDING DEVICE. I UJ
RETARDANT SILICONE FOAM (I.E. CHASE-FOAM CTC PR-855 BY CHASE TECHNOLOGY 24. PROVIDE CIRCUIT SETTERS FOR ALL HEAT PUMPS (DIRECT RETURN SYSTEM RAG\ RAG ' `
CORP.). 25. ALL HORIZONTAL EXHAUST DUCTWORK INSIDE APARTMEN.T.S. SHALL HAVE PITCH , FLEXIBLE DUCT SUPPORT AREA SERVED SEE DWG. v
18. ALL STORAGE ROOMS, TOILETS, ETC. (COMMON AREAS), WILL HAVE 3/4" UNDERCUT OF 1/16" PER LINEAR FOOT TOWARD THE WALL CAP.
DOORS TO PROVIDE VENTILATION REQUIRED WHEN DOOR OR TRANSFER GRILLES 26. RETURN AIR PLENUMS SHALL BE CONSTRUCTED AIR TIGHT TO AVOID AIR FAMILYROOM 6"0 O N.T.S. Z
ARE NOT SHOWN. EXHAUST DUOCTWRKU STHALL BELE TERIALS IN INSTALLED WED IN INRETURN PLENUMS.M SPACE. NO
19. ALL BEDROOMS AND BATHROOMS. (APARTMEN.T.S.), WILL HAVE 1" UNDERCUT DOORS w
TO PROVIDE VENTILATION REQUIRED. ACCESSORIES: Q
20. PROVIDE FLEXIBLE DUCT CONNECTORS, RATED AS REQUIRED, TO ALL FANS, A/C
UNITS, OR MECHANICAL EQUIPMENT. 1. BUILT IN CONDENSATE PAN FLOAT SWITCH.
21. PROVIDE MAINTENANCE AND OPERATION MANUAL ON ALL MECHANICAL EQUIPMENT O 2. FACTORY PROGRAMMABLE THERMOSTAT WITH COLOR TOUCH SCREEN. V)
OR SYSTEMS. PROVIDE 5 SETS OF SUBMITTALS ON ALL HVAC EQUIPMENT. ADDITIONAL COMPLIANCE NOTES: O 3. NON COMBUSTIBLE FLOOR STAND FOR AHU.
SUBMITTALS SHALL HAVE A SUMMARY SHEET SHOWING ALL SCHEDULED 4. 3/4" SLIP ON ARMAFLEX INSULATION FOR ENTIRE LENGTH OF RE W
INFORMATION. OWNERS
22. CONTRACTOR TO PROVIDE A COMPLETE SET OF SHOP DRAWINGS FOR ALL DUCT 1. THESE ENGINEERING DOCUMEN.T.S. AND THE RESULTING INSTALLATION OF THE SUITE 8x8 CG-4W
LAYOUT INCLUDING APARTMENT. CONTRACTOR TO VERIFY FIELD CONDITIONS AND DEPICTED HVAC SYSTEMS FOR THIS PROJECT ARE INTENDED TO CONFORM TO THE 150 CFM K
MECHANICAL VENTILATION CALCULATION:
23. CONTRACTORNOTE ANY S S TO PROVIDE SHOP DRAWINGS AND SUBMITTA SON THE SHOP DRAWING FOR ENGINEER O BASED ON THE FOLLOWING CODES AND STANDARDS: 3 BEDROOMS X (1 PERSON/BEDROOM + 1) X 15 CFM/PERSON = 60 CFM
APPROVED SET OF DRAWINGS. ANY DEVIATION FROM THE ORIGINAL DESIGN MUST BE . FLORIDA BUILDING CODE 6TH EDITION (2017) W
BROUGHT UP TO THE ATTENTION OF THE ENGINEER OF RECORD FOR REVIEW AND FAN SCHEDULE
COMMEN.T.S.. FLORIDA BUILDING CODE RESIDENTIAL 6TH EDITION (2017) „
• FLORIDA BUILDING CODE MECHANICAL 6TH EDITION (2017) t _ _ _ _6 0 _ O FAN No MFG MODEL No FAN TYPE CFM S.P. FAN RPM MOTOR VOLTS DRIVE SONES LOCATION SERVICE ACCESSORIES
• FLORIDA ENERGY CONSERVATION CODE 6TH EDITION (2017) 10x10 CG-1W 8"0 - - - i
� HP• FLORIDA FIRE PREVENTION CODE 6TH EDITION (2017) 200 CFM CHEN REF./ EF-1 GREENHECK SPA-70 CEILING FAN 50 0.25 850 13W 120-1-60 DIRECT 0.30 SEE DWS RES BATH 1FXH ,2O
MATERIALS• ACCA MANUAL D 2009 - RESIDENTIAL DUCT SYSTEMS DBL. SI K FREE . C L0
• ASHRAE 2009 FUNDAMENTALS HANDBOOK c
ASHRAE STD 62.1 2010 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY w DISP D ACCESSORIES:
A. AIR CONDITIONING RIGID DUCTWORK SHALL BE CONSTRUCTED OF 1.5-INCH THICK �
FIBERGLASS DUCT BOARD AS MANUFACTURED BY CERTAINTEED OR EQUAL. DUCT NAIMA AH116-2009 FIBROUS GLASS DUCT CONSTRUCTION STANDARDS p 8x8 CG-1W��T A. BACK DRAFTDAMPER M
WORK TO BE FABRICATED AND INSTALLED PER LATEST SMACNA STANDARDS. NFPA 90A - STANDARD FOR AIR CONDITIONING AND VENTILATION SYSTEMS O 125 CFM -► 60 B. DECORATIVE CEILING GRILLE Q
• NFPA 101 - LIFE SAFETY CODE // J
B. FLEXIBLE DUCTWORK SHALL BE CLASS I AIR DUCT, U.L. 181 LISTED AS
• SMACNA 2005 HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE 6x6 - W ° \ �_
MANUFACTURED BY ATCO FLEXAIRE OR APPROVED EQUAL AND OF R=6.0. SMACNA 010 FIBROUS GLASS CONSTRUCTION STANDARDS 50 CFM PLENUM ATTACHMENT PER SMACNA FIBROUS GLASS DUCT Q 0 J
• UL181 2005 FACTORY MADE AIR DUCTS AND AIR CONNECTORS J
INSTALL PER LATEST S.M.A.C.N.A. STANDARDS AND MANUFACTURER'S CONSTRUCTION STANDARDS. - PAGE 2.14 (FIG 2-25) O O
RECOMMENDATIONS. FLEXIBLE DUCTS SHALL BE CONFIGURED AND SUPPORTED SO 4"0 ❑O
IF WORK AS LAID OUT, INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS RECIRC. RANGE J J
AS TO PREVENT THE USE OF EXCESS DUCT MATERIAL, PREVENT DUCT ff-1 MICRO
WITH THE LISTED CODES AND STANDARDS, THE CONTRACTOR SHALL REPORT IN 4"0 UJI
DISLOCATION OR DAMAGE, AND PREVENT THE CONSTRICTION OF THE DUCT BELOW O O O O -�
THE RATED DUCT DIAMETER IN ACCORDANCE WITH THE FOLLOWING WRITING TO THE ARCHITECT/ENGINEER BEFORE SUBMITTING A BID. THE ABV. PANTRY FIBROUS GLASS PLENUM L LJJ LU
REQUIREMENTS: ARCHITECT/ENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED. N DUCT 0
1. DUCTS SHALL BE INSTALLED FULLY EXTENDED. DUCT SHALL NOT EXCEED 4"0 10110 DISCONNECT W L
8'-0" IN LENGTH THE TOTAL EXTENDED LENGTH OF DUCT MATERIAL SHALL 2. ALL EQUIPMENT IS TO BE INSTALLED PER THE MANUFACTURER'S INSTRUCTIONS, \ 16x6 �1W SWITCH LJJ
NOT EXCEED 5 PERCENT OF THE MINIMUM REQUIRED LENGTH FOR THAT SPECIFICATIONS, AND RECOMMENDATIONS FOR SAFE AND EFFICIENT OPERATIONS. ALL 25 CFM 22' SQ. WASHERS J W
MANUFACTURER OPERATION AND MAINTENANCE GUIDES SHALL BE ISSUED TO THE � 6x6 CG-1W BEDROOM 3 12" MAX O.C. AUX. OVERFLOW rn Q - �
RUN. q7N 25 CFM 22 GAUGE S.M. MICRO-SWITCH V Cn
2. BENDS SHALL MAINTAIN A CENTERLINE RADIUS OF NOT LESS THAN ONE BUILDING OPERATOR AFTER SUCCESSFUL COMPLETION OF MAINTENANCE AND/OR _ 4"0 f MIN. 2 PER SIDE Cn
/ „ 1"x3" COLLAR
DUCT DIAMETER. PREVENTATIVE MAINTENANCE PROCEDURES TRAINING OF THE BUILDING OPERATORS. EF-1 10 0
z M N
3. TERMINAL DEVICES SHALL BE SUPPORTED INDEPENDENTLY OF THE FLEXIBLE WIC " O AHU O
DUCT. 3. DESIGN CRITERIA INCLUDES BUT NOT LIMITED TO: 6xf CG-1W 8 CG-1W 4 # 1Ox1J" SHEET �^^ O7 C)
4. HORIZONTAL DUCT SHALL BE SUPPORTED AT INTERVALS NOT GREATER THAN INSIDE DESIGN CONDITIONS - 75°F/63'F COOLING, 70'F HEATING O II 25 CFM CFM METAL SCREWS
5 FEET. DUCT SAG BETWEEN SUPPORTS SHALL NOT EXCEED 1/2 INCH PER OUTSIDE DESIGN CONDITIONS - 91•F/79'F 1/7 _ _ WIC /I
FOOT OF LENGTH. SUPPORTS SHALL BE PROVIDED WITHIN 1.5 FEET OF • EXTERIOR CBS WALL INSULATION - FI-FOIL R=4.1 GLASS FABRIC & MASTIC REFRIG. LINES UP
INTERMEDIATE FITTINGS AND BETWEEN INTERMEDIATE FITTINGS AND BENDS. ATTIC BATT INSULATION - R=30.0 ATTIC GAL ERY LINEN 6"0 CLOSURE OR UL LISTED SUPPLY AIR TO CU AT ROOF project
CEILING JOISTS AND RIGID DUCT OR EQUIPMENT MAY BE CONSIDERED TO BE SLAB ON GRADE INSULATION - NONE PRESSURE SENSITIVE ALUM. DISCHARGE
SUPPORTS. ELEVATED FLOOR OVER UNCONDITIONED SPACE - NONE �ACCESS� COF . CLG. TAPE (SEE EXCEPTIONS) FLANGE
5. HANGERS, SADDLES AND OTHER SUPPORTS SHALL MEET THE DUCT GARAGE PARTITION - WOOD FRAME PARTITION R-11 6"0 TX T DUCT- J 202
MANUFACTURER'S RECOMMENDATIONS AND SHALL BE NOT LESS THAN 1-1/2 EXTERIOR GLAZED FENESTRATION SUMMER DAYTIME U VALUE = 1.07, SHGC=0.35 TO ROOF CAP \ RAG „ REF. LINES
8„ 12 0 DOWN IN UNE EQUIP. TOP
INCHES WIDE AND SHALL BE OF SUFFICIENT WIDTH TO PREVENT RESTRICTION 12x12 COVER
OF THE INTERNAL DUCT DIAMETER.
C. TOILET EXHAUST DUCTWORK SHALL BE GALVANIZED SHEET METAL DUCT INSTALLED O RAG VIBRATION
°
IN ACCORDANCE WITH THE LATEST SMACNA AND ASHRAE STANDARDS AND LEGEND I I SCREW, POP RIVET OR ISOLATION
MANUFACTURERS RECOMMENDATIONS. EF_ SPOT WELD TO EQUIP. PADS METAL
D. DRYER EXHAUST DUCTWORK SHALL BE 26 GAGE ROUND SHEET METAL SNAP LOCK FLID FLANGE STAND
PIPE OR EQUAL. DRYER EXHAUST DUCTWORK SHALL BE INSTALLED IN STRAIGHT / 10"0 / FILTER
RIGID DUCTWORK, R=6.0 6x6 CG-1W „ 6x CG-1W EWH 1 RACK
LINE FASHION AND IN COORDINATION WITH OTHER TRADES IN ORDER TO AVOID / 4 0
TRAPS AND DIPS IN THE DUCTWORK. 50 CFM 50 ` CU
E. DRYER EXHAUST DUCTWORK SHALL BE AS FOLLOWS: O / M
1. 4"0, AND CONSTRUCTED OF 26 GAGE GALVANIZED SHEET METAL AND OF 4XDO�O�D�D�D� FLEXIBLE DUCT, CLASS I, R=6.0 + - AHU-1 @ \ ,,FLOOR- STRUCTURE
SMOOTH INTERIOR FINISH. O
2. SUPPORTED EVERY 4FT. LAUNDRY 12x12 DOOR 4„0
3. INSERT END OF THE DUCT SHALL EXTEND INTO THE ADJOINING END. � RETURN AIR REGISTER/GRILLE \ GRILLE 4"b 0/A INTAKE AHU PLENUM DUCT ATTACHMENT
4. NO SCREWS OR FASTENERS THAT PROTRUDE INTO THE SIDE OF THE DUCT f
ARE ALLOWED. 6x6 CG-1W
5. THE EQUIVALENT LENGTH OF DUCT SHALL BE IDENTIFIED ON A PERMANENT 50 CFM g"� UP TO ROOF CAP N.T.S.
LABEL OR TAG. THE LABEL OR TAG SHALL BE LOCATED WITHIN 6FT OF THE 7 PANEL 'A' METER &
EXHAUST DUCT CONNECTION. CURVED BLADE CEILING GRILLE - 1,2, OR 4-WAY. O AIR GUIDE MODEL CB WITH OPPOSED BLADE DAMPER. F 7
DISC
- -
6. TRANSITION DUCTS USED TO CONNECT THE DRYER TO THE EXHAUST DUCT 5„� ATTIC
SHALL BE A SINGLE LENGTH THAT IS LISTED AND LABELED IN ACCORDANCE (OR EQUAL) DRYER ASHER
WITH UL 2158A. TRANSITION DUCTS SHALL BE A MAXIMUM OF 8FT LONG RETURN AIR GRILLE - AIR GUIDE MODEL RH (OR ACCESS
AND SHALL NOT BE CONCEALED WITHIN CONSTRUCTION. TRANSITION DUCT TO FFOYER
EQUAL). 4 C G. \111111111//
O
BE DRYER FLEX DRYER EXHAUST DUCT BY IN-OVATE DRYER PRODUCTS OR 12x1 9- Digitally signed by � S
EQUAL. DRYER BOX AND TRANSITION DUCT TO BE PURCHASED SEPARATELY } _ _ _ _ _
cL RAG Albert S. Shub PE g��
FROM APPLIANCE. MOTORIZED CONTROL DAMPER W/ACCESS PANEL. DRYER EXH DRYER 8"� �/
7. ALL FLOOR SLAB PENETRATIONS OF THE DRYER DUCT SHALL BE SEALED DAMPER OPEN WHEN AHU IS ON; CLOSED WHEN WALL CqP BOX 1 �y """""" A,,z 43414 Q \ SF
WITH APPROVED FIRE-STOPPING MATERIAL. AHU IS OFF. \ 6"� ��� ART S•12
�' ii ;
F. ALL AIR DISTRIBUTION DEVICES SHALL BE OF ALUMINUM CONSTRUCTION, PAINTRAG .� �Q>............•.,,�G DN: c=US, st=Florida, No. 43414 - -_
WITH WHITE ENAMEL (COORDINATE WITH ARCHITECT) MANUFACTURED BY TITUS OR T SINGLE STAGE HEAT/COOL PROGRAMMABLE 2 CAR GARAGE Q,�,�GENSF.,� _ I=North Miami Beach,
APPROVED. O THERMOSTAT MOUNTED AT 46" A.F.F. 8x8 CG-1W N0.43414 =
G. FILTERS SHALL BE OF DISPOSABLE TYPE AND HAVE CLEAN PRESSURE DROP OF 150 CFM _* * _*_ o= STATE OF
F.E.S. INC., a S 'REFRIGERANT PIPING - SEE SPLIT SYSTEM SCHEDULE �'a= STATE OF :Q �O
0.15" PROVIDE TWO SETS, ONE DURING CONSTRUCTION AND ONE FOR USE ?y; cn=Albert S. Shub PE ,r OR
FOR SIZES %�.c`'.;�(OR10P.• 43414
AFTER OCCUPANCY. Q
H. COUNTERBALANCED BACKDRAFT DAMPERS SHALL BE HEAVY DUTY EXTRUDED S ,
ALUMINUM RUSKIN MODEL CBD2 OR APPROVED EQUAL. BEDROOM 2 O ����A ���NQ�����`��p emdll=Alberts fe51nC '/ ���� V���
uumnmu�p @ //// VGA drawing
I. ALL DUCT ACCESS DOORS TO BE SMACNA STANDARD LOW LEAKAGE DOUBLE SKIN 0111 lll\
MANUFACTURED BY RUSKIN. MINIMUM SIZE 10"x10". NOT ALL APPLY .biz
sealABBREVIATIONS ( ) \ � This item has been electronically signed and
J. ALL SUPPLY, RETURN, AND EXHAUST DUCT WORK SHALL BE SEALED TIGHT PER totedealusi by rgaSHbuh on hedateoncodet Date: 2021.03.24 JOB NUMBER: 20011
SMACNA STANDARDS. A/C AIR CONDITIONING UNIT FB FLOW BAR DIFFUSER tone copies
of
this
document
authentication code.
Printed copies of this document are not 17.14:56-04'00' FLORIDA ENGINEERING SERVICES, INC.
K. FIRE DAMPERS SHALL BE STYLE "B", U.L. 555 LISTED, 265 F FUSIBLE LINK AD ACCESS DOOR FLD FULL LOUVER DOOR considered signed and sealed and the SHA
RUSKIN MODEL DIBD20 OR APPROVED EQUAL AND SHALL BE INSTALLED IN AFF ABOVE FINISHED FLOOR GD GRAVITY DAMPER authentication code must be verified on any Adobe Acrobat
ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. PORCH electronic copies.
AHU AIR HANDLING UNIT MVD MANUAL VOLUME DAMPER
version:
AP ACCESS PANEL MCD MOTORIZED CONTROL DAMPER
BDD BACK DRAFT DAMPER OBD OPPOSED BLADE DAMPER 2021.001.20145
BFC BELOW FINISHED CEILING OAI OUTSIDE AIR INTAKE
CFM CUBIC FEET PER MINUTE OAL OUTSIDE AIR LOUVER engineering for the future
FE
!m
CG CEILING GRILLE RAG RETURN AIR GRILLE O =434 N.W. 168`h Street
CLG CEILING SD SMOKE DETECTOR O O O O North Miami Beach, FL 33169
CM CEILING MOUNTED SF SUPPLY FAN Tel.: (305)653-0212 sheet
CU CONDENSING UNIT SR SIDEWALL REGISTER E-Mail:AlbertS@fesinc.biz AC-1
DG DOOR GRILLE TG TRANSFER GRILLE Albert Shub, P.E., LEED AP
EF EXHAUST FAN TV TURNING VANES
EG EXHAUST GRILLE LID UNDERCUT DOOR HVAC FLOOR PLAN P.E.#: 0043414-Mechanical
EAL EXHAUST AIR LOUVER WM WALL MOUNTED
C.O.A.: EB0003862
ER EXHAUST REGISTER WMS WIRE MESH SCREEN _ SCALE: 1/4" = 1'-0"