Loading...
HomeMy WebLinkAboutenergy Calc r Load Short Form Job: Date: Sep 14,2011 Entire House By: MAXINE SHAWVER DS AIR CONDITIONING INC PO BOX 197,JENSEN BEACH,FL 34957 Phone:772-335-4531 Fax:772-679-0103 Email:DSAIR09@HOTMAIL.COM Web:WVWV.DSAIRCONDITIONING.COM Project • • For: MIKE&SUZANNE RICHARDS 10701 S OCEAN ROAD, JENSEN BEACH, FL 34957 Design Information Htg Clg Infiltration Outside db(°F) 45 91 Method Simplified Inside db(°F) 70 75 Construction quality Average Design TD (°F) 25 16 Fireplaces 0 Daily range - L Inside humidity(%) 30 50 Moisture difference(gr/Ib) -3 57 HEATING EQUIPMENT COOLING EQUIPMENT Make Make Ruud Trade Trade RUUD UAPM SERIES Model Cond UAPM-042JEZ GAMA ID n/a Coil RCQD-4821+UGRM-09?ZAJ? ARI ref no. 3488440 Efficiency 100 EFF Efficiency 12.1 EER, 14 SEER Heating input 0 Btuh Sensible cooling 28000 Btuh Heating output 24313 Btuh Latent cooling 12000 Btuh Temperature rise 17 °F Total cooling 40000 Btuh Actual air flow 1333 cfm Actual air flow 1333 cfm Air flow factor 0.055 cfm/Btuh Air flow factor 0.041 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.88 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) Kitchen 213 1685 2115 92 87 Living 365 7439 12270 408 503 Stairs 43 487 297 27 12 Bath 1 29 559 472 31 19 Hall 78 1056 917 58 38 M Wic 135 1742 2215 96 91 M Bdrm 378 4154 4565 228 187 M Bath 140 750 1167 41 48 Study 137 1606 3743 88 153 Bath 3 60 1068 1251 59 51 - Bdrm 2 129 1886 1558 103 64 Hall Up 163 1879 1966 103 -81 Bold/italic values have been manually overridden Printout certified by ACCA to meet all requirements of Manual J 8th Ed. A wrightsoft Right-Suite®Universal 7.1.25 RSU08153 2011-Sep-1412:29:59 ...ir Conditioning\Documents\Wrightsofl HVAC\McCarty\Richards.rup Calc=MJ8 Orientation=SW Page 1 Entire House 1868 24313 32536 1333 1333 Other equip loads 0 0 Equip. @ 0.96 RSM 31235 Latent cooling 4425 TOTALS I 1868 l 24313 I 35659 l 1333 l 1333 • Bold/italic values have been manually overridden Printout certified by ACCA to meet all requirements of Manual J 8th Ed. wrightscft Right-Suite®Universal7.1.25RSU08153 2011-Sep-1412:29:59 A C4, ...ir Conditioning\Documents\Wrightsoft HVACkMcCarty\Richards.rup Calc=MJ8 Orientation=SW Page 2 Building Analysis Job. AS Date: Sep 14,2011 Entire House By: MAXINE SHAWVER DS AIR CONDITIONING INC PO BOX 197,JENSEN BEACH,FL 34957 Phone:772-335A531 Fax:772-679-0103 Email:DSAIR09@HOTMAIL.COM Web:W1MM.DSAIRCONDITIONING.COM • Project • • For: MIKE&SUZANNE RICHARDS 10701 S OCEAN ROAD, JENSEN BEACH, FL 34957 Design Conditions Location: Indoor: Heating Cooling West Palm Beach, FL, US Indoor temperature(°F) 70 75 Elevation: 20 ft Design TD(°F) 25 16 Latitude: 27°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/lb) -2.7 57.2 Dry bulb ff) 45 91 Infiltration: Dailyrange(°F) - 13 ( L ) Method Simplified Wet bulb(°F) - 78 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 • Component Btuh/ftz Btuh %of load Walls 3.0 6200 25.5 Glazing 26.4 7617 31.3 Doors 15.0 360 1.5 Ceilings 0.6 790 3.3 Floors 0.6 650 2.7 Infiltration 1.4 2919 12.0 Ducts 5777 23.8 Piping 0 0 Humidification 0 0 Ventilation 0 0 Adjustments 0 Total 1 24313 100.0 • • • Component Btuh/fl? Btuh %of load Walls 2.3 4807 14.8 Glazing 59.7 17222 '52.9 Doors 18.6 446 1.4 Ceilings 0 0 0 Floors 0.1 110 0.3 Infiltration 0.5 983 3.0 Ducts 8968 27.6 Ventilation 0 0 Internal gains 0 0 Blower 0 0 Adjustments 0 Total 325361 100.0 latent Cooling Load=4425 Btuh 6verall U-value=0.135 Btuh/ft2--°F Data entries checked. . Bold/italic values have been manually overridden t *T+ wricjtviLs .rft Right-Suite®Universal 7.1.25 RSU08153 2011-Sep-1412:29:59 !1C:CN, ...ir Conditioning\Documents\Wrightsoft HVAC\McCarty\Richards.rup Calc=MJ8 Orientation=SW Page 1 SIR Component Constructions Job: Date: Sep 14,2011 Entire House By: MAXINE SHAWVER DS AIR CONDITIONING INC PO BOX 197,JENSEN BEACH,FL 34957 Phone:772-335-4531 Fax:772-679-0103 Email:DSAIR09@HOTMAIL.COM Web:WWW.DSAIRCONDITIONING.COM Project • • For: MIKE&SUZANNE RICHARDS 10701 S OCEAN ROAD, JENSEN BEACH, FL 34957 Design Conditions Location: Indoor: Heating Cooling West Palm Beach, FL, US Indoor temperature(TF) 70 75 Elevation: 20 ft Design TD(TF) 25 16 Latitude: 27°N Relative humidity(%) 30 50 Outdoor: Heating Cooling Moisture difference(gr/lb) -2.7 57.2 Dry bulb(°F) 45 91 Infiltration: Daily range(T) - 13 ( L ) Method Simplified Wet bulb(°F) - 78 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft Muhlft'-°F ft'-°F/Btuh Btuh/R' Btuh Btuh/W Bluh Walls 13A-5ocs:Blk wall,stucco ext,r-5 ext bd ins,8"thk,5/8"gypsum ne 135 0.125 5.0 3.13 422 2.47 334 board int fish se 674 0.125 5.0 3.13 2106 2.47 1664 s 37 0.125 5.0 3.13 117 2.47 92 sw 348 0.125 5.0 3.12 1087 2.47 859 w 54 0.125 5.0 3.13 170 2.47 134 nw 539 0.125 5.0 3.13 1684 2.47 1330 all 1788 0.125 5.0 3.12 5586 2.47 4413 Partitions 12C-Osw:Frm wall,stucco ext,r-13 cav ins,2"x4"wood frm 270 0.091 13.0 2.27 614 1.46 394 Windows 1A-c1ob: 1 glazing,clr glz,mtl/w brk frm mat, 1/8"thk;2.5 ft overhang se 6 1.080 0 27.0 162 33.0 198 (3 ft window ht,0 ft sep.) 1A-c1ob:1 glazing,clr glz,mtl/w brk frm mat,1/8"thk;2.5 ft overhang se 22 1.080 0 27.0 594 38.1 838 (5.5 ft window ht,0 ft Sep.) se 22 1.070 0 26.8 589 38.8 853 s 11 1.070 0 26.8 294 33.5 368 sw 26 1.070 0 26.8 687 38.8 995 all 81 1.070 0 26.8 2163 37.9 3055 1 B-clfb: 1 glazing,clr glz,mtl/w brk frrn mat, 1/8"thk;2.5 ft overhang se 12 1.070 0 26.8 321 41.5 498 (6 ft window ht,0 ft sep.) s 12 1.070 0 26.8 321 33.5 402 sw 51 1.070 0 26.8 1364 41.5 2115 all 75 1.070 0 26.8 2006 40.2 3014 1 OA-b:1 glazing,clr glz,mtl/w brk frm mat,1/8"thk;2.5 ft overhang(8 sw 48 0.970 0 24.3 1164 26.0 1246 ft window ht,0 ft Sep.) 1A-clob:1 glazing,clr glz,mtl/w brk frm mat,1/8"thk;4 ft overhang(2 nw 8 1.080 0 27.0 207 68.7 526 ft window ht,0 ft sep.) 1A-clob:1 glazing,clr glz,mtl/w brk frm mat,1/8"thk;4 ft overhang(3 nw 6 1.080 0 27.0 155 68.7 395 ft window ht,0 ft sep.) 1A-clob:1 glazing,clr glz,mtl/w brk frm mat,1/8"thk;4 ft overhang nw 27 1.080 0 27.0 718 68.7 1825 (5.5 ft window ht,0 ft sep.) nw 11 1.070 0 26.8 282 70.6 744 all 37 1.070 0 26.9 1000 69.2 2569 1 B-clfb: 1 glazing,clr giz,mtl/w brk frm mat, 1/8"thk;4 ft overhang nw 11 1.070 0 26.8 291 70.6 767 (4.5 ft window ht,0 ft sep.) Bold/italic values have been manually overridden .- wri«hR r�fR Right-Suite®Universal 7.1.25 R SU08153 2011-Sep-1412:29.59 $�GA ...ir Conditioning\Documents\Wrightsoft HVAC\McCarty\Richards.rup Calc=MJ8 Orientation=SW Page 1 16-clfb: 1 glazing,clr glz,mtl/w brk frm mat, 1/8"thk;4 ft overhang(6 nw 18 1.070 0 26.8 468 70.6 1235 ft window ht,0 ft sep.) Doors ` 11J0'Door,mtl fbrgl type se 24 0.600 6.3 15.0 360 18.6 446 Ceilings IcyR-20:Icynene Spray Foam Insualtion R-20 1216 0.026 20.0 0.65 790 0 0 Floors 19C-19cscp:Flr ,floor,frm flr,6"thkns,carpet flr fish,r-2 ext ins,r-19 406 0.049 30.0 0.42 172 0.27 110 cav ins,tight crwl ovr,r-11 wall insul Icy R-20 CS:Crawlspace Icynene R-20 734 0.026 20.0 0.65 477 0 0 Bold/italic values have been manually overridden wrk5j"*+cr>ft Right-Suite®Universal7.1.25 RSU08153 2011-Sep-14 12:29:59 ACC,.A ...ir Conditioning\Documents\Wrightsoft HVAC\McCarty\Richards.rup Calc=MJ8 Orientation=SW Page 2 'w - Job:�Ins Date: Sep 14,2011 Entire House By: MAXINESHAWVER DS AIR CONDITIONING INC PO BOX 197,JENSEN BEACH,FL 34957 Phone:772-335-4531 Fax:772-679-0103 Email:DSAIR09@HOTMAIL.COM Web.WWW.DSAIRCONDITIONING.COM Project • • For: MIKE&SUZANNE RICHARDS 10701 S OCEAN ROAD, JENSEN BEACH, FL 34957 Notes: Design Information Weather: West Palm Beach, FL, US Winter Design Conditions Summer Design Conditions Outside db 45 °F Outside db 91 °F Inside db 70 °F Inside db 75 °F Design TD 25 °F Design TD 16 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 18536 Btuh Structure 23568 Btuh Ducts 5777 Btuh Ducts 8968 Btuh Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24313 Btuh Use manufacturer's data n Rate/swing multiplier 0.96 Infiltration Equipment sensible load 31235 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2172 Btuh Ducts 2252 Btuh Heating Cooling Central vent(0 cfm) 0 Btuh Area(ft') 1868 1868 Equipment latent load 4425 Btuh Volume (ft3) 16769 16769 Air changes/hour 0.38 0.20 Equipment total load 35659 Btuh Equiv.AVF (cfm) 106 56 Req.total capacity at 0.70 SHR 3.7 ton Heating Equipment Summary Cooling Equipment Summary Make Make Ruud Trade Trade RUUD UAPM SERIES Model Cond UAPM-042JEZ GAMA ID n/a Coil RCQD-4821+UGRM-09?ZAJ? ARI ref no. 3488440 Efficiency 100 EFF Efficiency 12.1 EER, 14 SEER Heating input 0 Btuh Sensible cooling 28000 Btuh Heating output 24313 Btuh Latent cooling 12000 Btuh • Temperature rise 17 °F Total cooling 40000 Btuh Actual air flow 1333 cfm Actual air flow 1333 cfm Air flow factor 0.055 cfm/Btuh Air flow factor 0.041 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.88 Bold/italic values have been manually overridden Printout certified by ACCA to meet all requirements of Manual J 8th Ed. ti -+4- wrighxsofT Right-Suite@ Universal 7.1.25RSU08153 2011-Sep-1412:29:59 ,C 01, .Ar Conditioning\Documents\Wrightsoft HVAC\McCarty\Richards.rup Calc=MJ8 Orientation=SW Page 1 i FORM 1100A-08 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Community Affairs Residential Performance Method A ProjectName: Richards BuilderName: Street: 10701 S OCEAN ROAD Permit Office: City,State,Zip: JENSEN BEACH,FL,34957 Permit Number: Owner: MIKE&SUZANNE RICHARDS Jurisdiction: V Design Location: FL,West Palm Beach 1. New construction or existing New(From Plans) 9. Wall Types(2369.3 sgft.) Insulation Area 2. Single family or multiple family Single-family a.Concrete Block-Ext Insul,Exterior R=5.0 2099.30 ft2 b.Frame-Wood,Exterior R=13.0 270.00 ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 2 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types (1216.1 sgft.) Insulation Area 6. Conditioned floor area(ft2) 1868 a.UnderAttic(Unvented) R=20.0 1216.10 ft2 b.N/A R= ft2 7. Windows(336.6 sgft.) Description Area c.N/A R= ft2 a. U-Factor: Sgl,U=0.60 336.59 ft2 SHGC: SHGC=0.27 11.Ducts b. U-Factor: N/A ft2 a. Sup:Attic Ret:Attic AH:Garage Sup.R=6,150 ft2 SHGC: 12.Cooling systems c. U-Factor: N/A ft2 a.Central Unit Cap:40.0 kBtu/hr SHGC: SEER:14 d. U-Factor: N/A ft2 13.Heating systems SHGC: a.Electric Strip Heat Cap:24.3 kBtu/hr e. U-Factor: N/A ft2 COP:1 SHGC: 14.Hot water systems 8. Floor Types (1139.7 sgft.) Insulation Area a.Electric Cap:50gallons a.Raised Floor R=0.0 734.40 ft2 EF:0.ns b.Crawlspace R=20.0 405.27 ft2 b.Conservation features 97 c.N/A R= ft2 None 15.Credits None Glass/Floor Area: 0.180 Total As-Built Modified Loads: 46.70 PASS Total Baseline Loads: 59.44 I hereby certify that the plans and specifications covered by Review of the plans and 04�tiE STAl� this calculation are in co Ian ith the Florida Energy specifications covered by this All O Code. calculation indicates compliance �wP b�^ ` 3 with the Florida Energy Code. PREPARED BY: - Before construction is completed DATE: this building will be inspected for : 01. „ compliance with Section 553.908 I hereby certify that this b Ode as designe is in compliance Florida Statutes.with the Florida Energy C C0D WE t�-S OWNER/AGENT: BUILDING OFFICIAL: DATE: DATE: 9/14/2011 12:29 PM EnergyGauge@USA-FlaRes2008 Page 1 of PROJECT Title:• Richards Bedrooms: 2 AdressType: Street Address Building Type: FLAsBuilt ConditionedArea: 1868 Lot# Owner: MIKE 8 SUZANNE RICHARD TotalStories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: BuilderName: RotateAngle: 0 Street: 10701 S OCEAN ROAD Permit Office: CrossVentilation: No County: MARTIN Jurisdiction: Whole House Fan: No City,State,Zip: JENSEN BEACH , FamilyType: Single-family FL. 34957 New/Existing: New(From Plans) Comment: CLIMATE / IECC Design Temp Int Design Temp Heating Design Daily Temp DesignLocation TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,West Palm Beach FL_WEST_PALM_BEAC 2 44 90 75 70 316 60 Medium FLOORS # FloorType Perimeter PerimeterR-Value Area Joist R-Value Tile Wood Carpet 1 Crawlspace 57.2 ft 0 405.27 ft2 20 0 0 1 2 Raised Floor 734.4 ft2 0 0 0 1 ROOF / Roof Gable Roof Solar Deck # Type Materials Area Area Color Absor. Tested Insul. Pitch 1 Flat Composition shingles 1220 ft2 52 ft' Medium 0.8 N 0 4.8 deg / ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 No attic Unvented 0 1216 ft2 N N CEILING # Ceiling Type R-Value Area Framing Frac Truss Type 1 Under Attic(Unvented) 20 1216.1 ft2 0 Wood WALLS Cavity Sheathing Framing Solar # Omt Adjacent To Wall Type R-Value Area R-Value Fraction Absor. 1 NE Exterior Concrete Block-Ext Insul 5 135 ft2 0 0 0.8 • 2 SE Exterior Concrete Block-Ext Insul 5 759.75 ft2 0 0 0.8 3 S Exterior Concrete Block-Ext Insul 5 60 ft2 0 0 0.8 4 SW Exterior Concrete Block-Ext Insul 5 472.5 ft2 0 0 0.8 5 W Exterior Concrete Block-Ext Insul 5 54 ft2 0 0 0.8 6 NW Exterior Concrete Block-Ext Insul 5 618 ft2 0 0 0.8 • 7 Exterior Frame-Wood 13 270 ft2 0 0.25 0.8 9/14/2011 12:29 PM EnergyGaugeO USA-Fla Res2008 Page 2 of 5 ~~ DOORS # Ornt DoorType Storms U-Value Area 1 SE Wood None 0.6 24 ft2 WINDOWS Orientation shown is the entered,asBuilt orientation. / Overhang # Ornt Frame Panes NFRC U-Factor SHGC Storms Area Depth Separation IntShade Screening 1 SE TIM Single(Clear) Yes 0.6 0.27 N 6 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 2 SE TIM Single(Clear) Yes 0.6 0.27 N 22 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 3 SE TIM Single(Clear) Yes 0.6 0.27 N 22 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 4 SE TIM Single(Clear) Yes 0.6 0.27 N 12 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 5 S TIM Single(Clear) Yes 0.6 0.27 N 11 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 6 S TIM Single(Clear) Yes 0.6 0.27 N 12 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 7 SW TIM Single(Clear) Yes 0.6 0.27 N 96 ft2 15 ft 6 in 0 ft 0 in HERS 2006 None 8 SW TIM Single(Clear) Yes 0.6 0.27 N 25.67 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 9 SW TIM Single(Clear) Yes 0.6 0.27 N 17.5 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 10 SW TIM Single(Clear) Yes 0.6 0.27 N 17 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 11 SW TIM Single(Clear) Yes 0.6 0.27 N 16.5 ft2 2 ft 6 in 0 ft 0 in HERS 2006 None 12 NW TIM Single(Clear) Yes 0.6 0.27 N 7.67 ft2 4 ft 0 in 0 ft 0 in HERS 2006 None 13 NW TIM Single(Clear) Yes 0.6 0.27 N 5.75 ft2 4 ft 0 in 0 ft 0 in HERS 2006 None 14 NW TIM Single(Clear) Yes 0.6 0.27 N 26.58333 4 ft 0 in 0 ft 0 in HERS 2006 None 15 NW TIM Single(Clear) Yes 0.6 0.27 N 10.88 ft2 4 ft 0 in 0 ft 0 in HERS 2006 None 16 NW TIM Single(Clear) Yes 0.6 0.27 N 10.54 ft2 4 ft 0 in 0 ft 0 in HERS 2006 None 17 NW TIM Single(Clear) Yes 0.6 0.27 N 17.5 ft2 4 ft 0 in 0 ft 0 in HERS 2006 None INFILTRATION &VENTING / ---Forced Ventilation--- Run Time Fan �/ Method SLA CFM 50 ACH 50 ELA EgLA SupplyCFM ExhaustCFM Fraction Wafts Default 0.00036 1764 7.08 96.8 182.1 0 cfm 0 cfm 0 0 GARAGE # FloorArea Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 256 ft2 256 ft2 64 ft 8 ft 1 COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Ducts 1 Central Unit None SEER:14 40 kBtu/hr cfm 0.7 sys#1 9/14/2011 12:29 PM EnergyGauge®USA-FlaRes2008 Page 3 of 5 HEATING SYSTEM # System Type Subtype Efficiency Capacity Ducts 1 Electric Strip Heat None COP: 1 24.31 kBtu/hr sys#1 HOT WATER SYSTEM # System Type EF Cap Use SetPnt Conservation 1 Electric 0.97 50 gal 50 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # CompanyName System Model# Collector Model# Area Volume FEF None None ft2 DUCTS ----Supply---- ---Return--- Air Percent V # Location R-Value Area Location Area LeakageType Handler CFM 25 Leakage QN RLF 1 Attic 6 150 ft2 Attic 25 ft2 DefaultLeakage Garage (Default)c (Default)% TEMPERATURES ProgramableThermostat: N Ceiling Fans: CoolingX Jan X Feb X Mar Apr X Ma X Jun X Jul X Aug ]Se Oct Nov DecHeatin f X�Jan f X�Feb fX�Mar IX�APr f X�May f XjJun f XJ Jl f Xj Auf X]SeP IX X�Oct JXJ X Nov JX Xj Dec VentingX Jan X Feb X Mar XAr X May X Jun X Jul X Aug X Se X Oct X Nov X Dec ThermostatSchedule: HERS 2006 Reference Hours ScheduleType 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 Heating(WEH) AM 68 68 68 68 68 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 9/14/2011 12:29 PM EnergyGauge®USA-FlaRes2008 Page 4 of 5 FORM 1100A-08 Code Compliance Checklist Residential Whole Building Performance Method A - Details ADDRESS: 10701 S OCEAN ROAD PERMIT#: JENSEN BEACH, FL, 34957 INFILTRATION REDUCTION COMPLIANCE CHECKLIST COMPONENTS SECTION REQUIREMENTS FOR EACH PRACTICE CHECK Exterior Windows& Doors N1106.AB.1.1 Maximum 3 cfm/s .ft. window area; .5 cfm/s .ft.door area. Exterior&Adjacent Walls N1106.AB.1.2 Caulk,gasket,weatherstrip or seal between:windows/doors& frames, surrounding wall;foundation&wall sole or sill plate;joints between exterior wall panels at corners; utility penetrations; between wall panels&top/bottom plates;between walls and floor. EXCEPTION: Frame walls where a continuous infiltration barrier is installed that extends from,and is sealed to,the foundation to the top plate. Floors N1106.AB.1.2 Penetrations/openings> 1/8"sealed unless backed by truss or t joint members. EXCEPTION: Frame floors where a continuous infiltration barrier is installed that is sealed to the perimeter, penetrations and seams. Ceilings N1106.AB.1.2 Between walls&ceilings; penetrations of ceiling plane to top floor; around shafts,chases, soffits, chimneys, cabinets sealed to continuous air barrier;gaps in gyp board&top plate; attic access. EXCEPTION: Frame ceilings where a continuous infiltration barrier is installed that is sealed at the perimeter,at penetrations and seams. Recessed Lighting Fixtures N1106.AB.1.2 Type IC rated with no penetrations,sealed;or Type IC or non-IC rated, installed inside a sealed box with 1/2"clearance&3"from insulation;or Type IC with<2.0 cfm from conditioned space, tested. Multi-story Houses N1106.AB.1.2 Air barrier on perimeter of floor cavity between floors. Additional Infiltration reqts N1106.AB.1.3 Exhaust fans vented to outdoors, dampers;combustion space heaters comply with NFPA, have combustion air. OTHER PRESCRIPTIVE MEASURES (must be met or exceeded by all residences.) COMPONENTS SECTION REQUIREMENTS CHECK Water Heaters N1112.AB.3 Comply with efficiency requirements in Table N1112.ABC.3 Switch or clearly marked circuit breaker(electric)or cutoff(gas) must be provided. External or built-in heat trap required. _ Swimming Pools&Spas N1112.AB.2.3 Spas&heated pools must have covers(except solar heated). Non-commercial pools must have a pump timer. Gas spa&pool heaters must have a minimum thermal efficiency of 78%. Heat pump pool heaters shall have a minimum COP of 4.0. Shower heads N 1112.AB.2.4 Water flow must be restricted to no more than 2.5 gallons per minute at 80 PSIG. Air Distribution Systems N1110.AB All ducts,fittings, mechanical equipment and plenum chambers shall be mechanically attached,sealed, insulated and installed in accordance with the criteria of Section N1110.AB. Ducts in unconditioned attics: R-6 min. insulation. HVAC Controls N1107.AB.2 Separate readily accessible manual or automatic thermostat for each system. Insulation N1104.AB.1 Ceilings-Min. R-19. Common walls-frame R-11 or CBS R-3 both N1102.B.1.1 sides. Common ceiling&floors R-11. 9/14/2011 12:29 PM EnergyGauge®USA-RaRes2008 Page 5 of 5 _ ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 79 The lower the EnergyPerformance Index, the more efficient the home. 10701 S OCEAN ROAD, JENSEN BEACH, FL, 34957 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a.Concrete Block-Ext Insul,Exterior R=5.0 2099.30 ft2 b.Frame-Wood,Exterior R=13.0 270.00 ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Numberof Bedrooms 2 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types Insulation Area 6. Conditioned floor area(ft2) 1868 a.Under Attic(Unvented) R=20.0 1216.10 ft' b.N/A R= ft2 7. Windows" Description Area c.N/A R= ft2 a. U-Factor: Sgl,U=0.60 336.59 ft2 SHGC: SHGC=0.27 11.Ducts b. U-Factor: N/A ft2 a. Sup:Attic Ret:Attic AH:Garage Sup.R=6,150 ft2 SHGC: 12.Cooling systems c. U-Factor: N/A ft2 a.Central Unit Cap:40.0 kBtu/hr SHGC: SEER:14 d. U-Factor: N/A ft2 13.Heating systems SHGC: a.Electric Strip Heat Cap:24.3 kBtu/hr e. U-Factor: N/A ft2 COP:1 SHGC: 14.Hot water systems 8. Floor Types Insulation Area a.Electric Cap:50 gallons a.Raised Floor R=0.0 734.40 ft2 EF:0.97 b.Crawlspace R=20.0 405.27 ft2 b.Conservation features c.N/A R= ft2 None 15.Credits None I certify that this home has complied with the Florida Energy Efficiency Code for Building "EKE sr " Construction through the above energy saving features which will be installed (or exceeded) o . in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code co nt features. Builder Signature: Date: Address of New Home: S 2 ,e, 33 City/FL Zip: TeX*7,; N. r4 G.=�A ��gAl 349s7 �oo:wE� Note: The home's estimated Energy Performance Index is only available through the EnergyGauge USA- FlaRes2008 computer program. This is not a Building Energy Rating. If your Index is below 100, your home may qualify for incentives if you obtain a Florida Energy Gauge Rating. Contact the Energy Gauge Hotline at (321)638-1492 or see the Energy Gauge web site at energygauge.com for information and a list of certified Raters. For information about Florida's Energy Efficiency Code for Building Construction, contact the **Label required by Section 13-104.4.5 of the Florida Building Code, Building, or Section B2.1.1 of Appendix G of the Florida Building Code, Residential, if not DEFAULT. EnergyGauge®USA-FlaRes2008 ENERGY PERFORMANCE LEVEL (EPL) ` DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 79 The lower the EnergyPerformance Index, the more efficient the home. 10701 S OCEAN ROAD, JENSEN BEACH, FL, 34957 1. New construction or existing New(From Plans) 9. Wall Types Insulation Area 2. Single family or multiple family Single-family a.Concrete Block-Ext Insul,Exterior R=5.0 2099.30 ft2 b.Frame-Wood,Exterior R=13.0 270.00 ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 4. Number of Bedrooms 2 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types Insulation Area 6. Conditioned floor area(ft2) 1868 a.UnderAttic(Unvented) R=20.0 1216.10 ft2 b.N/A R= ft2 7. Windows" Description Area c.N/A R= ft2 a. U-Factor: Sgl,U=0.60 336.59 ft2 SHGC: SHGC=0.27 11.Ducts b. U-Factor: N/A ft2 a. Sup:Attic Ret:Attic AH:Garage Sup.R=6,150 ft2 SHGC: 12.Cooling systems c. U-Factor: N/A ft2 a.Central Unit Cap:40.0 kBtu/hr SHGC: SEER:14 d. U-Factor: N/A ft2 13.Heating systems SHGC: a.Electric Strip Heat Cap:24.3 kBtu/hr e. U-Factor: N/A ft2 COP:1 SHGC: 14.Hot water systems 8. Floor Types Insulation Area a.Electric Cap:50 gallons a.Raised Floor R=0.0 734.40 ft2 EF:0.97 b.Crawlspace R=20.0 405.27 ft2 b.Conservation features c.N/A R= ft2 None 15.Credits None certify that this home has complied with the Florida Energy Efficiency Code for Building SHE sT Construction through the above energy saving features which will be installed (or exceeded) of 9rF in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code comp' t features. w . Builder Signature: k'v� Date: Address of New Home: 2(2 S ��?Y�I /32. Cyr 3?CIty/FL Zip: �f �� �•L f� ��g� wE 3�S 7 -Department of Community Affairs at (850)487-1824. **Label required by Section 13-104.4.5 of the Florida Building Code, Building, or Section B2.1.1 of Appendix G of the Florida Building Code, Residential, if not DEFAULT. EnergyGauge®USA-FlaRes2008