HomeMy WebLinkAboutStamped Joseph Hamel - As builtCOVER PAGEAUTHORITIES HAVING JURISDICTIONBUILDING: ST. LUCIE COUNTYZONING: ST. LUCIE COUNTYUTILITY: FLORIDA POWER & AMP; LIGHT CO NEW PHOTOVOLTAIC SYSTEM 14.85 KW DC4206 SUNRISE BLVD, FORT PIERCE, FL 34982, USAGENERAL NOTESVICINITY MAPSATELLITE VIEWSHEET INDEXCOVER PAGET-001G-001A-101SITE PLANATTACHMENT PLANRESOURCE DOCUMENT1.3.1 WORK INCLUDES:1.3.2 PV RACKING SYSTEM INSTALLATION - QUICK MOUNT PV1.3.3 PV MODULE AND INVERTER INSTALLATION - SILFABSIL-330W NL / SOLAREDGE SE11400H-US / SOLAREDGE POWEROPTIMIZER P3701.3.4 PV EQUIPMENT ROOF MOUNT1.3.5 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX1.3.6 PV LOAD CENTERS (IF INCLUDED)1.3.7 PV METERING/MONITORING (IF INCLUDED)1.3.8 PV DISCONNECTS1.3.9 PV GROUNDING ELECTRODE & BONDING TO (E) GEC1.3.10 PV FINAL COMMISSIONING1.3.11 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV1.3.12 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDINGCODESYSTEM SIZE: PTC: 45 x 307.56W = 13.84 kW DC(45) SILFAB SIL-330W NL ATTACHMENT TYPE: ROOF MOUNT MSP UPGRADE: NOPROJECT INFORMATIONOWNERNAME:ELECTRICAL PLANLINE DIAGRAMRESOURCE DOCUMENTA-102E-601R-001R-002A-103RESOURCE DOCUMENTE-602ELECTRICAL CALCULATIONSRESOURCE DOCUMENTR-003RESOURCE DOCUMENTR-004R-005REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY -T-001TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA TATIANA HAMELSTC:45 X 330W= 14.85 kW DC(1) SOLAREDGE SE11400H-USNOTESDESIGN SPECIFICATIONOCCUPANCY: R3/SINGLE FAMILY RESIDENTIALCONSTRUCTION TYPE / FIRE RATING: 5-BGROUND SNOW LOAD LOCAL: 0 PSFWIND EXPOSURE: BWIND SPEED : 150 MPH(45) SOLAREDGE POWER OPTIMIZER P370CONTRACTOR INFORMATION:CONTRACTOR NAME: PALMETTOCONTRACTOR ADDRESS: 1505 KING ST,CHARLESTON,SC 29405CONTRACTOR PHONE: (855) 339-1831PHONE: (904) 703-0170AC SIZE: 11.4 kW ACPLACARDE-603APPLICABLE CODES & STANDARDS: IBC 2015IFC 2015IRC 2015NEC 20172020 FLORIDA BUILDING CODE (7TH EDITION)SCOPE OF WORK1.1.1 PROJECT NOTES:1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONALELECTRIC CODE (NEC) ARTICLE 690, ALL MANUFACTURER LISTING ANDINSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THEAUTHORITY HAVING JURISDICTION’S (AHJ) APPLICABLE CODES.1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PVSYSTEM INSPECTED PRIOR TO PARALLEL OPERATION.1.1.4 ARC FAULT PROTECTION (AFCI) AND PHOTOVOLTAIC RAPID SHUTDOWNSYSTEM (PVRSS) IS INTEGRATED WITH THE POWER OPTIMIZER IN ACCORDANCEWITH NEC 210.12 & 690.12 RESPECTIVELY.1.1.5 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE ISINTEGRATED WITH THE INVERTER IN ACCORDANCE WITH NEC 690.41(B)1.1.6 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVEINVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED ANDLISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PVMODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIREINVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703OR UL 1741 ACCESSORY1.1.7 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMPCOEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATEDACCORDING TO NEC 690.7.1.1.8 ALL INVERTERS, PHOTOVOLTAIC MODULES,PHOTOVOLTAIC PANELS, ANDSOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWERSYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D).SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING ORLABELING [NEC 110.3].1.1.9 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE.IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES ANDSIGNAGE WILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.1.2.1 SCOPE OF WORK:1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN ANDSPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIMECONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTING ONSITEREQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THE EXTERIORROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMS DETAILED IN THISDOCUMENT
NOTESREV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-2.1.1 SITE NOTES:2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITHOSHA REGULATIONS.2.1.3 THE PV MODULESARECONSIDERED NON-COMBUSTIBLE AND THISSYSTEM IS A UTILITY INTERACTIVE SYSTEM WITHOUT STORAGEBATTERIES.2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING,MECHANICAL, OR BUILDING ROOF VENTS.2.1.5 PROPERACCESS AND WORKING CLEARANCE AROUND EXISTINGAND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED ASPERSECTION NEC 110.26.2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, ANDMAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVEDMANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERINGSERVES TO PROTECT THE BUILDING OR STRUCTURE.2.2.1 EQUIPMENT LOCATIONS:2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BYNEC 110.26.2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATEDFOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31(A),(C) AND NEC TABLES 310.15 (B)(2)(A) AND 310.15 (B)(3)(C).2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PVMODULES ACCORDING TO NEC 690.34.2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THEINVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT.2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIEDPERSONNEL ACCORDING TO NEC APPLICABLE CODES.2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATEDFOR OUTDOOR USAGE WHEN APPROPRIATE.2.3.1 STRUCTURAL NOTES:2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TOCODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE ADESIGNATED SPACE BETWEEN MODULES, AND RAILS MUSTALSOEXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THEARRAY/SUBARRAY, ACCORDING TO RAI MANUFACTURER’SINSTRUCTIONS.2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERSPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED &SEALED PER LOCAL REQUIREMENTS.2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETEDAND SEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY ALICENSED CONTRACTOR.2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATERTHAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BESTAGGERED AMONGST THE ROOF FRAMING MEMBERS.2.7.1 INTERCONNECTION NOTES:2.7.2 LOAD-SIDE INTERCONNECTION SHALL BE INACCORDANCE WITH [NEC 705.12 (B)]2.7.3 THE SUM OF THE UTILITY OCPD AND INVERTERCONTINUOUS OUTPUT MAY NOT EXCEED 120% OF BUSBARRATING [NEC 705.12(D)(2)(3)].2.7.4 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S)OUTPUT CIRCUIT CURRENT AND THE RATING OF THEOVERCURRENT DEVICE PROTECTING THE BUSBAR SHALLNOT EXCEED 120 PERCENT OF THE AMPACITY OF THEBUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BELOCATED OPPOSITE END OF THE BUS FROM THE UTILITYSOURCE OCPD [NEC 705.12(B)(2)(3)].2.7.5 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUTCOMBINER PANEL, TOTAL RATING OF ALL OVERCURRENTDEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR.HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BEEXCLUDED ACCORDING TO NEC 705.12 (B)(2)(3)(C).2.7.6 FEEDER TAP INTERCONECTION (LOADSIDE) ACCORDINGTO NEC 705.12 (B)(2)(1)2.7.7 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TONEC 705.12 (A) WITH SERVICE ENTRANCE CONDUCTORS INACCORDANCE WITH NEC 230.42 2.7.8 BACK FEEDINGBREAKER FOR ELECTRIC POWER SOURCES OUTPUT ISEXEMPT FROM ADDITIONAL FASTENING [NEC 705.12 (B)(5)].G-001TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA 2.4.1 WIRING & CONDUIT NOTES:2.4.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FORTHEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS AREBASED ONMINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMITUP-SIZING.2.4.3 CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.2.4.4 VOLTAGE DROP LIMITED TO 3.0%.2.4.5 DC WIRING LIMITED TO INVERTER FOOTPRINT. OPTIMIZER WIRINGSYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/SUITABLE WIRING CLIPS.2.4.6 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE AOR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREEPHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHERCONVENTION NEUTRAL- WHITE OR GREY IN 4-WIRE DELTA CONNECTEDSYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE[NEC 110.15].2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTIONNOTES:2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCHTHAT WHEN THE SWITCH IS OPENED THE CONDUCTORSREMAINING ENERGIZED ARE CONNECTED TO THE TERMINALSMARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS).2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITYPERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH2.6.4 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGSSHALL INCLUDE A RAPID SHUTDOWN FUNCTION TO REDUCESHOCK HAZARD FOR EMERGENCY RESPONDERS INACCORDANCE WITH 690.12(A) THROUGH (D).2.6.5 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDINGTO NEC 690.8, 690.9, AND 240.2.6.6 OPTIMIZER BRANCHES CONNECTED TO A SINGLEBREAKER OR GROUPED FUSES IN ACCORDANCE WITH NEC110.3(B).2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULTCIRCUIT PROTECTION ACCORDING TO NEC 690.11 ANDUL1699B.2.5.1 GROUNDING NOTES:2.5.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIRPURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTSSHALL BE RATED FOR SUCH USE.2.5.3 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43AND MINIMUM NEC TABLE 250.122.2.5.4 METAL PARTS OF MODULE FRAMES, MODULE RACKING, ANDENCLOSURES CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND250.136(A).2.5.5 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZEDACCORDING TO NEC 690.45 AND INVERTER MANUFACTURERINSTRUCTIONS.2.5.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPSAS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BYTHE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUSTBE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THEMANUFACTURER INSTALLATION REQUIREMENTS.2.5.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGEDSUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT AGROUNDING CONDUCTOR TO ANOTHER MODULE.2.5.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BECOLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC250.119]2.5.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47AND NEC 250.50 THROUGH 250.106. IF EXISTING SYSTEM ISINACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEMPROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ.2.5.10 GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690.41(B)(1)AND (2) TO REDUCE FIRE HAZARDS
JB
INVMSPUMACDSITE PLAN REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY -A-101TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA1SITE PLANSCALE:1/32" = 1'-0"LEGEND- JUNCTION BOXJB- VENT, ATTIC FAN (ROOF OBSTRUCTION)- PROPERTY LINE- FIRE SETBACK- CHIMNEY (ROOF OBSTRUCTION)- SKYLIGHT (ROOF OBSTRUCTION)NSEW(N) SOLAREDGE SE11400H-US INVERTER(E) UTILITY METER(E) MAIN SERVICE PANEL SUNRISE BLVD(N) VISIBLE LOCKABLE LABELED AND FUSED ACDISCONNECT (UTILITY DISCONNECT)DRIVEWAY106'-11"29'-0"46'-3"137'-10"191'-6"172'-2"60'-6"33'-8"42'-8"57'-11"AUSTRALIAN AVE1 MODULESILFAB SIL-330W NL2INVERTER SOLAREDGE SE11400H-US3OPTIMIZERSOLAREDGE POWER OPTIMIZERP3704 MOUNTSPROTEA BRACKET5 RAILQUICKMOUNT - QMR-RL: QRAILLIGHT
JB
INVMSPUMACD11 11 11 11 11 11 11 12 22 22 22 22
2
22
2
22
3 3
33 33
3 3
33 3
3 3
33
ELECTRICAL PLAN REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY -A-102TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA1ELECTRICAL PLANROOF SECTION(S)TILT - 18°AZIMUTH - 91°MODULE - 22TILT - 18°AZIMUTH - 91°MODULE - 23ROOF 1ROOF 21- MODULE STRING2- MODULE STRING3- MODULE STRINGSCALE:3/32" = 1'-0"LEGEND- JUNCTION BOXJB- VENT, ATTIC FAN (ROOF OBSTRUCTION)- PROPERTY LINE- FIRE SETBACK- CHIMNEY (ROOF OBSTRUCTION)- SKYLIGHT (ROOF OBSTRUCTION)NSEW(N) CONDUIT RUNIN THE ATTICROOF 1ROOF 2(N)SOLAREDGE SE11400H-US INVERTER(E) UTILITY METER(E) MAIN SERVICE PANEL(N) VISIBLE LOCKABLE LABELED AND FUSED ACDISCONNECT (UTILITY DISCONNECT)1 MODULESILFAB SIL-330W NL2INVERTERSOLAREDGE SE11400H-US3OPTIMIZERSOLAREDGE POWER OPTIMIZERP3704 MOUNTSPROTEA BRACKET5RAILQUICKMOUNT - QMR-RL: QRAILLIGHT
1'-10"11'-1"2'-9"37'-1"2'-9"1'-10"16'-7"1'-9"27'-0"4'-0"2'-3"ATTACHMENT PLAN REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-A-103TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA - CLAMP- RAIL1ATTACHMENT PLANSCALE:1/8" = 1'-0"ROOF 1TILT- 18 DEGAZIMUTH - 91 DEG- PROTEA BRACKET-TRAPEZOIDAL METALSEAM @ 12" O.C.ROOF 2TILT- 18 DEGAZIMUTH - 91 DEGROOF SECTION(S)ROOF MATERIAL -TRAPEZOIDAL METAL SEAMRAFTER SIZE - 2"X4"O.C. SPACING - 24"SEAM SPAN - 9"ROOF 1ROOF 2ROOF MATERIAL -TRAPEZOIDAL METAL SEAMRAFTER SIZE - 2"X4"O.C. SPACING - 24"SEAM SPAN - 9"MOUNTING PATTERN SAMPLEMAX. 27"MAXIMUM MOUNT SPACING: 27" MOUNT PATTERN:STAGGEREDALL HARDWARE, INCLUDING MOUNTINGAND RACKING, TO BE INSTALLED PERMANUFACTURER SPECIFICATIONS.
=SOLAREDGE SE11400H-US (240V)RATED OUTPUT POWER 11400 WOUTPUT: 240 VAC, 47.5A99% CEC WEIGHTED EFFICIENCYNEMA 3R, UL LISTED, INTERNAL GFDIWITH INTEGRATED DC DISCONNECTACDC- +-++- ++++---2- +-13==========JUNCTION BOX600 V, NEMA 3UL LISTED- +-++- ++++---2- +-13==========SOLAREDGE POWER OPTIMIZER P370DC INPUT POWER - 370 WATTSMAXIMUM INPUT VOLTAGE -60 VDCMPPT RANGE - 8 TO 60 VDCMAXIMUM INPUT CURRENT - 11 ADCMAXIMUM OUTPUT CURRENT - 15 ADC STRINGLIMITATIONS - 8 TO 25 OPTIMIZERS,6000 WATTS STC PER STRING MAXIMUM214151415- +-++- ++++---2- +-13==========SILFAB SIL-330W NL14151(E) MAIN BREAKER TOHOUSE 240 V, 200A/2P(TOP FED)(E) MAIN SERVICE200A RATED, 240VNL2L1TO UTILITY GRIDGECEXISTING GROUNDINGELECTRODE SYSTEMTO EARTHREF. NEC 250.52,250.53(A)MLOAD/LINE SIDEINTERCONNECTIONAT MAIN PANELPER ART. 705.12(D)GN(E)BI-DIRECTIONALUTILITY METER1-PHASE, 3-W,120V/240VMETER NO.: 751853LOADLINEGL1L2NAC DISCONNECT:VISIBLE, LOCKABLE, LABELED60A FUSED, (2) 60A FUSES, 240VNEMA 3R, UL LISTED4SUPPLY SIDE TAPLINE DIAGRAMREV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY -E-601TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA (45)SILFAB SIL-330W NL MODULES(3) STRING OF 15 MODULES CONNECTED IN SERIESIDPHASE CONDUCTOR QTY, SIZEAND TYPE PER CONDUITGROUND CONDUCTOR QTY, SIZEAND TYPE PER CONDUITCONDUITSIZECONDUIT TYPE1 6 AWG #10PV-WIRE/USE-2,COPPER1 AWG #6 BARE COPPER EGCN/AFREE AIR2 6 AWG #10THWN-2,COPPER1 AWG #103/4"EMT32 AWG #61 AWG #103/4"4THWN-2,COPPERTHWN-2,COPPER EGCTHWN-2,COPPER EGCBARE,COPPER EGCAWG #61NAFREE AIRNEUTRALN/A1 AWG #6THWN-2,COPPERN/AEMT52 AWG #6THWN-2,COPPER1 AWG #6THWN-2,COPPERDC SYSTEM SIZE:14.85 kW DCAC SYSTEM SIZE: 11.4 kW AC1 MODULESILFAB SIL-330W NL2INVERTER SOLAREDGE SE11400H-US3OPTIMIZERSOLAREDGE POWER OPTIMIZERP3704 MOUNTSPROTEA BRACKET5RAILQUICKMOUNT - QMR-RL: QRAILLIGHT
ELECTRICALCALCULATIONSREV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY -E-602TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USA DC CONDUCTOR AMPACITY CALCULATIONS:ARRAY TO JUNCTION BOX :DC CONDUCTOR AMPACITY CALCULATIONS:FROM JUNCTION BOX TO INVERTER:AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUITPER NEC 310.15(B)(2)(c)NO. OF CURRENT CARRYING CONDUCTORSCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)CIRCUIT CONDUCTOR SIZE0.810 AWG622°TEMP. CORRECTION PER TABLE (310.16)0.76CIRCUIT CONDUCTOR AMPACITY40AREQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B) 1.25 X Isc18.75ADERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.1624.32ARESULT SHOULD BE GREATER THAN (18.75A) OTHERWISE LESS THE ENTRY FORCIRCUIT CONDUCTOR SIZE AND AMPACITYEXPECTED WIRE TEMP (In Celsius)33°+22° = 55°AC CONDUCTOR AMPACITY CALCULATIONS:No. OF INVERTERNO. OF CURRENT CARRYING CONDUCTORSCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)CIRCUIT CONDUCTOR SIZE16 AWG31TEMP. CORRECTION PER TABLE (310.16)0.96CIRCUIT CONDUCTOR AMPACITY65AEXPECTED WIRE TEMP (In Celsius)33°REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B)1.25 X MAX INVERTER OUTPUT CURRENT59.38ADERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.16TEMP. CORRECTION PER TABLE (310.16) XCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) XCIRCUIT CONDUCTOR AMPACITY62.40AResult should be greater than (59.38A) otherwise less the entry for circuit conductor sizeand ampacityPOWER OPTIMIZER (OPTIMIZER P370) MAXIMUM INPUT POWER 370W MINIMUM INPUT VOLTAGE 8 VDC MAXIMUM INPUT VOLTAGE 60 VDC MAXIMUM MODULE ISC11 ADC MAXIMUM OUTPUT CURRENT 15 ADCPERCENT OFVALUESNUMBER OF CURRENTCARRYING CONDUCTORS IN EMT0.804-60.707-90.5010-20AMBIENT TEMPERATURE SPECS RECORD LOW TEMP0° AMBIENT TEMP (HIGH TEMP 2%)33° CONDUIT HEIGHT0.5" ROOF TOP TEMP55° CONDUCTOR TEMPERATURE RATE90° MODULE TEMPERATURE COEFFICIENT OF Voc-0.28%/°CTEMP. CORRECTION PER TABLE (310.16) XCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) XCIRCUIT CONDUCTOR AMPACITYSOLAR MODULE SPECIFICATIONS MANUFACTURER / MODEL # SILFAB SIL-330W NL VMP33.3V IMP9.92A VOC40.5V ISC10.42A TEMP. COEFF. VOC-0.28%/°C PTC RATING307.56W MODULE DIMENSION66.9"L x 39.4W x 1.5"D (In Inch)INVERTER SPECIFICATIONS MANUFACTURER / MODEL #SolarEdge SE11400H-US NOMINAL AC POWER11400 W NOMINAL OUTPUT VOLTAGE 240 VAC NOMINAL OUTPUT CURRENT 47.5EXPECTED WIRE TEMP (In Celsius)55°TEMP. CORRECTION PER TABLE (310.16)0.76NO. OF CURRENT CARRYING CONDUCTORS6CONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a)1CIRCUIT CONDUCTOR SIZE10AWGCIRCUIT CONDUCTOR AMPACITY40AREQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B)18.75A1.25 X IscDERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.1630.40ATEMP. CORRECTION PER TABLE (310.16) XCONDUIT FILL CORRECTION PER NEC 310.15(B)(2)(a) X CIRCUITCONDUCTOR AMPACITYRESULT SHOULD BE GREATER THAN (18.75A) OTHERWISE LESS THE ENTRY FORCIRCUIT CONDUCTOR SIZE AND AMPACITY
JB
INVMSPUMACDPV DISCONNECTMAIN SERVICE PANELUTILITY METERPV ARRAYPLACARDSPOWER TO THIS BUILDING IS ALSO SUPPLIEDFROM THE FOLLOWING SOURCES WITHDISCONNECTS LOCATED AS SHOWN:CAUTIONREV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY -E-603TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USANSOLAR CONNECTION LINE SIDE TAPWARNING: PHOTOVOLTAICPOWER SOURCESOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWNSOLAR ELECTRIC PV PANELSTURN RAPID SHUTDOWNSWITCH TO THE 'OFF'POSITION TO SHUTDOWN PV SYSTEM ANDREDUCE SHOCK HAZARDIN THE ARRAYAC DISCONNECTWARNINGELECTRIC SHOCK HAZARDDO NOT TOUCH TERMINALS.TERMINALS ON BOTH LINE ANDLOAD SIDES MAY BE ENERGIZED IN THEOPEN POSITION!!PHOTOVOLTAIC SYSTEM AC DISCONNECT!!OPERATING VOLTAGE:____VOLTSOPERATING CURRENT:____AMPSSOLARBREAKERAC COMBINER BOXPHOTOVOLTAICMICROINVERTERSLOCATED UNDEREACH PV MODULE INROOFTOP ARRAYPHOTOVOLTAIC SYSTEM EQUIPPED WITHRAPID SHUTDOWNRATED AC OUTPUT CURRENT:____NOM. OPERATING VOLTAGE:____DUAL POWER SUPPLYSOURCES: UTILITY GRID AND PVSOLAR ELECTRIC SYSTEMWARNING!!___________KW SOLARDISCONNECT LOCATEDFT___FT___INVERTER OUTPUT CONNECTION!DO NOT RELOCATE THISOVERCURRENT DEVICEWARNING!
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-001TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-002TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-003TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-004TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT
REV
SHEET TITLEDATEDESCRIPTION
REVISIONS SIGNATURE WITH SEAL PROJECT NAME & ADDRESSDRAWN DATEDRAWN BY01/18/2021WASSHEET NUMBERREVIEWED BY-R-005TATIANA HAMEL
4206 SUNRISE BLVD,
FORT PIERCE, FL 34982,
USARESOURCEDOCUMENT