HomeMy WebLinkAboutAPPROVED Generac 100 amp Smart Managemnet ModuleGENERAL'
Smart Management GENERAL° LOAD MANAGEMENT
Module (SMM) 100_Amp Smart Management Module (SMM)
0 0 c, O�T�_
FEATURES
Model: G007006-0
UPC:696471077520
Generac's Smart Power Management System is designed to optimize the performance of a standby generator. The system can consist of up to eight individual Smart
Management Modules (SMM). Unlike other load management systems that depend on another control device, the SMM is self -aware and operates autonomously.
Frequency is the true measure of generator engine performance, and does not need to factor in increased ambient temperatures, elevation changes, or generator fuel
type. The SMM monitors the frequency (Hz) of the power being produced by Generac's standby generators. If frequency falls below a certain threshold of a correctly
sized system, the SMM will automatically shed the managed loads to allow the generator to recover.
The SMM can be set to a load priority between 1-8, or be set in a lock -out only mode for loads that do not need to run in an outage. This reduces the minimum size of
generator required for a more cost-effective solution*.
* It is recommended to size the generator with appropriate excess capacity to allow starting of the largest managed loads (i.e. loads with highest starting currents). Each
managed load of the SACM and SMM must be assigned a unique priority setting, so no two managed loads attempt to start simultaneously. See owner's manual for
more information.
SMM SPECIFICATIONS
Powersupply source..................................................................................................................................................................................
240 VAC (from Line input)
Contactvoltages.............................................................................................................................................................................................................220/240
VAC
Contactorcoil voltage............................................................................................................................................................................................................240
VAC
CoilVA inrush...............................................................................................................................................................................................................................300
CoilVA sealed.................................................................................................................................................................................................................................35
Poles.................................................................................................................................................................................................................................................2
Resistiveamps..............................................................................................................................................................................................................................100
F/L inductive amps..........................................................................................................................................................................................................................90
Lockedrotor amps.........................................................................................................................................................................................................................540
NEMA.............................................................................................................................................................................................................................................
3R
Enclosure rating.......
UL 50
Frequencyselectability...................................................................................................................................................................................................50
Hz / 60 Hz
Wiregauge range box lugs..............................................................................................................................................................................................1/0
to 8 AWG
Wirematerial..................................................................................................................................................................................................................................
Cu
Coilpick up voltage......................................................................................................................................................................................................................80%
Coildrop out voltage....................................................................................................................................................................................................................20%
Maximumcontact voltage.......................................................................................................................................................................................................
600VAC
Ambienttemperature maximum....................................................................................................................................................................................149
°F (65 °C)
Coilterminals.........................................................................................................................................................................................................................18
AWG
GENERAC'
Smart Management Module (SMM) Dimensions and UPC
—VV1
Model
G007006-0
Height (in mm)
H1
7.0/178.5
H2
2.4/61
Width (in mm)
W1
11.39 / 289.4
W2
7.8/200
Depth (in mm)
5.3/136.9
Weight (lb / kg)
5.3/2.4
Shipping weight (1b / kg)
j 5.8/3.62
UPC
1 696471077520
SMM Controls
Kr
PRIORITY 'LOA ON
5 \ GENERATOR
TEST
0 LOCKOUT
DISABLED
LED ON = LOAD CONNECTED
LED FLASH 1 S = LOAD SHED
LED FLASH 3S = 30 MIN LOCKOUT
LED FLASH BS = GEN LOAD LOCKOUT
LED OFF = NO MODULE POWER
6���j D
Priority Dial (A) Sets module priority
Lockout Switch (B) Prevents load from operating when system is operating under generator power.
Test Button (C) Disables contactor output for a specified time.
LED (0) Provides module status with easy viewing through the external viewing window
located in the upper right corner of the module.
GENERACGenerac Power Systems, Inc. - S45 W29290 HWY. 59, Waukesha, WI 53189 - generac.com
(02019 Generac: Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Part No. 10000041878 Rey C 09/25/19