Product Approval Menu > Product or Application Search > Application List > Application Detail
FL #
FL26000-RI
Application Type
Revision
Code Version
2020
Application Status
Approved
Comments
Archived
Product Manufacturer Tri County Metals
Address/Phone/Email 301 SE 16th Street
Trenton, FL 32693
(352)463-8400
testing@tricountymetals.com
Authorized Signature Jason Klinkenberg
testing@tricountymetals.com
Technical Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category Roofing
Subcategory Metal Roofing
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed Florida
Professional Engineer
Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed the Johnathan E. Green, P.E.
Evaluation Report
Florida License PE-88223
Quality Assurance Entity Keystone Certifications, Inc.
Quality Assurance Contract Expiration Date 02/12/2021
Validated By Brian Jaks, P.E.
Validation Checklist - Hardcopy Received
Certificate of Independence
Referenced Standard and Year (of Standard)
Equivalence of Product Standards
Certified By
Sections from the Code
FL26000 RI COI Letter of Certification- TO County Metals. sealed.pd
Standard Year
UL 1897 2012
UL 580 2006
Product Approval Method Method 1 Option D
https://floddabuilding.org/pr/pr app_dtl.aspx?param=wGEVXQwtDgsH88r2%2fJKYUkjsz6gYzRcJNDIWrfCoBfVfvL%2bcsxi6lg°/a3d%3d 1/2
6/3/2021 Florida Building Code Online
Date Submitted
10/13/2020
Date Validated
10/19/2020
Date Pending FBC Approval
10/26/2020
Date Approved
12/16/2020
Summary of Products
FL #
Model, Number or Name
Description
26000.1
5V Crimp
Min 26 ga., 24" wide through fastened panel over 15/32" thick
plywood
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL26000 Rl II FL26000.1 26 Ga. 5V Crimp Panel over
Plywood sealed.pdf
Approved for use outside HVHZ: Yes
Impact Resistant: N/A
Verified By: Johnathan E Green, P.E. 88223
Design Pressure: +N/A/-60
Created by Independent Third Party: Yes
Other: Uplift load of 60 psf @ fastener spacing of 16" D.C.
Evaluation Reports
FL26000 Rl AE FL26000.1 26 Ga. 5V Crimp Panel over
Plywood sealed.pdf
Created by Independent Third Party: Yes
Fack P9cxt
Contact Us :: 2601 Blair Stone Road, Tallahassee Fl. 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Co right 2007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public -records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section 455.275(i),
Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they have one. The emails
provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personal address, please
provide the Department with an email address which can be made available to the public. To determine if you are a licensee under Chapter 455, F.S., please click here .
Product Approval Accepts:
MWWORM
hftps:llfloridabuilding.org/prlpr app_dtl.aspx?param=wGEVXQwtDgsH88r2%2fJKYUkjsz6gYzRcJNDIWrfCoBfVfvL%2bcsxl6lg%3d%3d 2/2
------ ...... . .
Force Engineering & Testing
19530 Ramblewood Drive
Humble, Texas 77318
Phone: (281) 540-6603 FAX: (281) 540-"60
Website: w-,vw.foretenginecritigtestina,.com
Product Evaluation Report
TRI COUNTY METALS
Min. 26 Ga. 5V Crimp Roof Panel over 15132" Plywood
Florida Product Approval # 26000.1 R1
Florida Building Code 2020
Per Rule 61G20-3
Method: I —D
Category: Roofing
Subcategory: Metal Roofing
Compliance Method: 61G20-3.005(1)(d)
NON HVHZ
Product Manufacturer.
Tri County Metals
301 SE 16 th Street
Trenton, Florida 32693
Engineer Evaluator:
Johnathan Green, P.E. #88223
Florida Evaluation ANE ID: 12901
Validator:
Brian Jaks P.E. #70159
Contents:
Evaluation Report Pages 1 — 4
"VIC
"D
4
fj
10
OCT 01 2020
If I X0
THIS ITEM HAS BEEN
DIGITALLY SIGNED AND
SEALED BY JOHNATHAN
GREEN ON THE DATE
ADJACENT TO THE SEAL.
PRINTED COPIES OF THIS
DOCUMENT ARE NOT
CONSIDERED SIGNED AND
SEALED AND THE
SIGNATURE MUST BE
VERIFIED ON ANY
ELECTRONIC COPIES.
FL# 26000.1 R1
Force Engineering & Testing
19530 Ramblewood Drive
Humble, Texas 77318
Phone: (281) 540.6603 FAX: (28'1) 540-9966
Website: www.rorceenginceringtesting.com
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2020, Sections 1504.3.2, 1504.7.
Product Description: 5V Crimp Roof Panel, Min. 26 Ga. Steel, 24" coverage, through fastened roof panel
over Min. 15/32" APA Plywood decking. Non-structural Application.
Panel Material/Standards: Min. 26 Ga. Steel ASTM A792 AZ55, conforming to Florida Building Code 2020
Section 1507.4.3. Paint finish optional.
Yield Strength: Min. 80.0 KSI
Corrosion Resistance: Panel Material shall comply with Florida Building Code
2020, Section 1507.4.3.
Panel Dimension(s): Thickness: 0.019" min.
Width: 24" maximum coverage
Rib Height: 1/2" tall ribs
Panel Fastener: #9-15 x 1-1/2" Woodgrip HWH with sealing washing or approved equal
%" minimum penetration through plywood; @ 12" o.c. across panel through panel
ribs at interior locations; @ 6" o.c. across panel width through panel flat and rib at
panel ends.
Corrosion Resistance: Per Florida Building Code 2020, Section 1507.4.4.
Substrate Description: Min. 15/32" thick, CAT Exposure 1 CDX APA Rated plywood over supports at
maximum 24" O.C. Design of plywood and plywood supports are outside the
scope of this evaluation. Substrate must be designed in accordance w/ Florida
Building Code 2020.
Allowable Design Uplift Pressures:
Table "A"
Maximum Total Uplift Design Pressure:
60.0 psf
Fastener Pattern:
12"-12"
Fastener Spacing:
16" O.C.
*Design Pressure includes a Safety Factor = 2.0.
.fit 111111111
.+ a6
Sam
o
sP s i
1�}to
r
a
OCT 01 2020 r����`f/11i1 1 I11"��i@�������
THIS ITEM HAS BEEN
DIGITALLY SIGNED AND
SEALED BYJOHNATHAN
GREEN ON THE DATE
ADJACENT TO THE SEAL.
PRINTED COPIES OF THIS
DOCUMENT ARE NOT
CONSIDERED SIGNED AND
SEALED AND THE
SIGNATURE MUST BE
VERIFIED ON ANY
ELECTRONIC COPIES.
FL# 26000.1 Rl
}
Force Engineering & Testing
195-30 Ramblewood Drive
Humble, Texas 77338
Plume: (281) 5=40-6603 FAX: (281) 540-9966
Website: www.forecenginecringtesting.com
Code Compliance: The product described herein has demonstrated compliance with
The Florida Building Code 2020, Section 1504.3.2,1504.7.
Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2020, as relates to Rule 61G20-3.
Performance Standards: The product described herein has demonstrated compliance with:
■ UL 580-06 - Test for Uplift Resistance of Roof Assemblies
■ UL 1897-2012 - Uplift Test for Roof Covering Systems
Reference Data: 1. UL 580-06 / 1897-04 & -12 Uplift Test
PRI Construction Materials Technologies, LLC (FBC Organization # TST5878)
Project No. TCM-003-02-02 Dated 01/02/2018
3. Certificate of Independence
By Johnathan Green, P.E. (No. 88223) @ Force Engineering & Testing
(FBC Organization # ANE ID: 12901)
Test Standard Equivalency: The UL 1897-04 test standard is equivalent to the UL 1897-2012 test standard.
Quality Assurance Entity: The manufacturer has established compliance of roof panel products in
accordance with the Florida Building Code and Rule 61G20-3.005 (3) for
manufacturing under a quality assurance program audited by an approved
quality assurance entity.
Minimum Slope Range: Minimum Slope shall comply with Florida Building Code 2020, including Section
1507.4.2 and in accordance with Manufacturers recommendations. For slopes
less than 3:12, lap sealant must be used in the panel side laps.
Installation: Install per manufacturer's recommended details.
,i
aND 6=3
e� a i Ar m
OCT 01 2020 �f�fffit �11111100AL
THIS ITEM HAS BEEN
DIGITALLY SIGNED AND
SEALED BY JOHNATHAN
GREEN ON THE DATE
ADJACENT TO THE SEAL.
ITED COPIES OF THIS
�CUMENT ARE NOT
�NSIDERED SIGNED AND
ALED AND THE
'NATURE MUST BE
RIFTED ON ANY
CTRONIC COPIES.
FL# 26000.1 Rl
_-; Forte Engineering & Testing
19530 Ramblewood Drive
Humble, Texas 77338
Phone: (281) 540-6603 FAX: (281) 540A966
Website: vvvvvv.foreeengineeringtesting.com
Underlayment:
Per Florida Building Code 2020, Section 1507.1.1 and manufacturer's installation
guidelines.
Roof Panel Fire Classification:
Fire classification is not part of this acceptance.
Shear Diaphragm:
Shear diaphragm values are outside the scope of this report.
Design Procedure:
Based on the dimensions of the structure, appropriate wind loads are
determined using Chapter 16 of the Florida Building Code 2020 for roof cladding
wind loads. These component wind loads for roof cladding are compared to the
allowable pressure listed above. The design professional shall select the
appropriate erection details to reference in his drawings for proper fastener
attachment to his structure and analyze the panel fasteners for pullout and
pullover. Support framing must be in compliance with Florida Building Code 2020
Chapter 22 for steel, Chapter 23 for wood and Chapter 16 for structural loading.
a i38=3a
P
OCT 01 2020 (j019AtL11%
THIS ITEM HAS BEEN
DIGITALLY SIGNED AND
SEALED BY JOHNATHAN
GREEN ON THE DATE
ADJACENT TO THE SEAL.
NTED COPIES OF THIS
'UMENT ARE NOT
4SIDERED SIGNED AND
kLED AND THE
NATURE MUST BE
11FIED ON ANY
CTRONIC COPIES.
FL# 26000.1 R1
Force Engineering & Testing
19530 Ramblewood Drive
Hatable, Texas 77318
Phone: (281) 540-6603 FAX: (281) 540-9966
Website: www.forcLvnl_,iiiec-ringtesting.com
..4% -1 at —, SW13, AIW= PAL
alw z
41 to 4�-.
OCT 01 2020 !```�j��i� t1ia����~�
THIS ITEM HAS BEEN
DIGITALLY SIGNED AND
SEALED BY JOHNATHAN
GREEN ON THE DATE
ADJACENT TO THE SEAL.
PRINTED COPIES OF THIS
DOCUMENT ARE NOT
CONSIDERED SIGNED AND
SEALED AND THE
SIGNATURE MUST BE
VERIFIED ON ANY
ELECTRONIC COPIES.