HomeMy WebLinkAboutAPPROVED A1.10 Code RCODE REVIEW FOR D&D WELDING NEW BUILDING LOCATED AT 5300
SOUTH STEEL BLVD. FT. PIERCE, FLORIDA
ARCHITECTS PROJECT #2019-54/2
SEPTEMBER 28, 2020
The proposed Building is a Single-Story Pre-engineered Metal Structure clad with
Metal panels. The gross Floor area of the Building will be 39,504 sq. ft. This
consists of a Welding Shop with an area of 30,108 sq. ft., Offices, Toilet Rooms,
Storage etc. with an area of 2,900 sq. ft., and an exterior Roofed over space with an
area of 6,496 sq. ft. The Building height to the Roof eaves will be 29'-0" and 33'-0"
to the Roof ridge. There will be nine (9) overhead doors around the perimeter of the
Building. The Ancillary accommodation i.e. Breakroom, Offi ces etc. will be
constructed using CMU exterior Walls and Stucco, Steel Beams, Metal Deck, Rigid
insulation, and a modified bitumen Roofing system.
All Construction will be non-combustible and Parking is located North and East of
the proposed Building. The Building will be protected by an Automatic Fire Sprinkler
System.
CODE REFERENCES
Florida Building Code 2017 -Building
Florida Building Code 2017 -Accessibility
Florida Building Code 2017 -Plumbing
Florida Fire Prevention Code 6th Edition
CODE REVIEW
1)USE AND OCCUPANCY CLASSIFICATION:
FBC CH.3 FBC 306.2 Moderate-Hazard Factory/Industrial,
Group F-1; LSC 6.1.12.1; 40.1.2; Industr ial Occupancy
2)SPECIAL DETAILED REQUIREMENTS BASED ON USE AND
OCCUPANCY
FBC CH.4
N/A
3)GENERAL BUILDING HEIGHTS AND AREAS
FBC CH.5
i)Building Height and Number of Stories
FBC 504; FBC TABLE 504.3
Note: Construct ion Type; Type II (B); Sprinklered.
Maximum allowable Building height
ii)Allowable Number of Stories above Grade Plane
FBC TABLE 504.4
Maximum number of Stories allowed
(This is a Single-Story Structure)
iii)Building Area
FBC 506; FBC TABLE 506.2
Maximum Bu ilding area permitted
Actual Build ing area proposed
iv)Accessory Occupancies
FBC 508.2
Accessory Occupancies (Offices, Breakroom ,
Toilets & Storage)
10% of the Bu ilding area = 3,950 sq. ft. > 2,900 sq. ft.
No separation required.
v)Separation of Occupancies
FBC 508.2.4; FBC TABLE 508.4; LSC TABLE 6.1.14.4.1(b)
= 55'
= 2
= 62 ,000 sq . ft.
= 39 ,504 sq. ft.
= 2,900 sq. ft.
2 HR. separation re quired between F-1 Occupancy and
Assembly Occupancy (Breakroom) A-2.
vi)Incidental Uses
FBC TABLE 509
N/A
4)TYPES OF CONSTRUCTION
FBC CH.6; FBC 602.2; Type 11-B; Sprinklered ; LSC 40.1.6
i)Fire-Resistance Rating Requirements for Building Elements Hours
FBC TABLE 601
a)Primary Structural Frame = 0
b)Bearing Walls (Interior/ Exterior)= 0
c)Non -Bearing Interior Walls = 0
d)Floor Construction = 0
e)Roof Construction = 0
ii)Fire-Resistance Rating Requirements for Exterior Walls Based on Fire
Se_paration Distanc e.
N orth; distance to property li ne= 99' > 30' -No ra ting.
South; distance to property line= 52' > 30 ' -No rating.
East; distance to properly line= 148' > 30' -No rating.
West; distance to property line = 97' > 30 ' -No rating.
5) FIRE AND SMOKE PROTECTION FEATURES
FBC CH.7
6)
i)Exterior Walls
FBC 705; 705.2
There are no eaves ov erhangs from the Exterior Walls.
ii)Maximum Area of Exterior Wall Openings Based on Fire Separation
Distance and Degree of Opening Protec tion
FBC TABLE 705.8
All sides> 30'
iii)Fire Partitions
FBC 708
= No Limit
The Fire partition separating the Shop (F-1) from the Break room (A-2)
will be 2 HR. Fire rated. The CMU Wall will be conslructed full height
to separate both Occupancies.
iv)Penetrations
FBC 714; 714.3.1.1; 714.3.1.2
All through penetrations in the 2 HR rated CMU Wall to be protected
by an approved penetration firestop system installed and tested in
accordance with ASTM E814 or U.L. 1479.
v)Opening Protectives
FBC 716
The two (2) Doors connecting the Shop with the Breakroom will be 1 ½
HR rated with a maximum vision panel of 100 sq. inches.
vi)Concealed Spaces
FBC 718
Fire blocking and Draft stopping in concealed spaces not required.
All construction is non-combustible. Draft stopping in the Roof is not
required as the Building will be protected by a fully Automatic Fire
Sprinkler System.
INTERIOR FINISHES
FBC CH. 8; Table 803.11; LSC 10.2; 40.3.3.2
All interior wall and ceiling finishes to conform to the following Table:
INTERIOR WALL & CEILING FINISH REQUIREMENTS BY OCCUPANCY
Group "A-2"; Group F-1; Sprinklered
INTERIOR EXIT CORRIDOR, ENCLOSURES FOR EXIT STAIRWAYS RAMPS AND
EXIT PASSAGEWAYS ACCESS STAIRWAYS AND RAMP
--
CLASS C -Flame Spread Index; 76-200
Smoke Developed; 0-450
I)Interior Floor Finish
FBC 804; 804.4.2; LSC 40.3.3.3
ROOMS AND ENCLOSED SPACES
C
The minimum Critical Radiant Flux for all finishes shall not be less than
Class II.
7)FIRE PROTECTIO N SYSTEMS
FBC CH. 9; 903.2.4; LSC 40.3.5
An Automatic Fire Sprinkler System installed in accordance with NFPA 13
will be provided throughout the Building.
i)Portable Fire Extinguishers
FBC 906; 906.1
ii)
See Life Safety Plan for location of Portable Fire extinguishers.
Fire Alarm and Detection Systems
FBC 907; 907.2.4; LSC 9.6; 40.3.4.1
Provide a manual Fire Alarm System throughout the Building initiated by
the Automatic Fire Sprinkler System.
8)MEANS OF EGRESS
FBC CH. 1 O; LSC 40.2
i)General Means of Egress
FBC 1003; 1003.2
All Means of Egress shall have a minimum Ceiling height of 7'-6".
ii)Oc cupant Load
iii)
iv)
i)
ii)
FBC 1004; FBC TABLE 1004.1.2; LSC 7.3.1.2; 40.1.7
a)Shop; 30,108 sq. ft.+ 100 = 301 Occupants
b)Breakroom; 896 sq. ft+ 15 = 60 Occupants
c)Offices; 461 sq. ft. .. 100 = 5 Occupants
d)Storage/Electrical Room etc. 1,000 sq. ft.+ 300 = 4 Occupants
Total Occupant Load = 370 Occupants
Means of Egress Sizing
FBC 1005; 1005.3.2; LSC 40.2.3
Egress Capacity required
a)Shop; 301 x 0.2"
Egress capacity provided
b)Breakroom; 60 x 0.2"
Egress capacity provided
Number of Exits and Exit Access Doorways
FBC 1006; 1006.2.1; LSC 7.4; 40.2.4.1
a)Minimum Number of Exits required
b)Number of Exits provided
Exit and Exit Access Doorway Configuration
FBC 1007; 1007.1.1; LSC 7.5; 40.2.5
a)Building Diagonal
Maximum Building diagonal
Maximum Door separation
50% x 318' = 159' < 306' -o.k.
Means of Egress Illumination
FBC 1008.; LSC 7.8; 40.2.8
a)Illumination Required
FBC 1008.2; LSC 7.8; 40.2.8
= 60.2"
= 180" =
=
= =
12"
36"
2
7
= 318' = 306'
The Means of Egress, including Exit Discharge will be
illuminated at all times during Building Occupancy.
b)Illumination Level Under Normal Power
FBC 1008.2.1
Means of Egress Illumination Level shall not be less than 1
Footcandle (11 LUX) at the walking surface.
c)Emergency Power for Illumination
FBC 1008.36; LSC 7.9; 40.2.9
An Emergency Power Supply will be provided to illuminate at
Means of Egress components. The emergency supply will
provide power for a minimum of 90 minutes and will consist of
storage batteries, unit equipment or on-site generator.
vii)Accessible Means of Egress
FBC 1009; FBC 2017-Accessibility
a)Accessible Routes
FBC 206
An Accessible Route from the Accessible Parking is provided to
the Facility Entrances.
b)Accessible Means of Egress
FBC 207
All required Means of Egress comply with Accessibility Standards.
c)Parking Spaces
FBC 208; FBC 502.5
Accessible Parking Spaces are located adjacent the Facility
Entrance.
d)Drinking Fountains
FBC 211
Combination "Hi-Lo" Drinking Fountain provi ded (See Floor Plan).
e)Kitchens, Kitchenettes and Sinks
FBC 212; 606 and 604
The Breakroom Sink is to be 34" (maximum) above FFL, the
Work surface ( counter) to be ad j ustable for varying heights
between 29" (minimum) and 36" (maximum).
f)Toilet Facilities and Bathing Facilities
FBC 212; FBC 603
All Toilets Facilities are on an Accessible Route, meet all
necessary Door clearances and Turning Circle and Clear Floor
Space Fixture requirements.
viii)Doors, Gates and Turnstiles
FBC 1010; 1010.1.1; LSC 7-2.1; 40.2.2.2
All Egress doors are 36" x 80" (minimum), swing in the direction of
travel and are side hinged.
All interior side-swinging doors (without closers) to comply with
the following prescribed forces:
1)A maximum 51b (22N) force shall swing door fully open.
2)A 151b (67N) force shall release a latch.
3)A 301b (133N) force shall set door in motion.
IX)Exit Access
FBC 1016; LSC 40.2.5
All exit access locations are on an accessible route and do not pass
through any intervening spaces.
X)Exit Access Travel Distance
FBC 1017; FBC TABLE 1017.2; LSC 7.6; FBC TABLE 40.2.6.1
a)Maximum Travel distance to an Exit = 250'
b)Actual maximum Travel distance to an Exit = 234'
XI)Corridors
FBC 1020; LSC 40.3.6
N/A
XII)Exit Discharge
FBC 1028; LSC 7.7; 40.2.7
All Exits Discharge directly to the Building exterior.
MINIMUM PLUMBING FIXTURE COUNT
FBC 2017 -PLUMBING
a)Oc cupant Load
Maximum Occupant Load = 370 Occupants
50% I 50% Male/Female Ratio = 185 Male and 185 Female
Water Closets; 1/100; Male/Female;
Lavatories; 1/100 Male/Female;
Drinking Fountains; 1 per 400
Service Sink; 1
MINIMUM PLUMBING FIXTURE COUNT
Industrial/Factory F-1; Assembly A-2
WATER CLOSETS LAVATORIES DRINKING SERVICE SINKS
FOUNTAINS
Required Provided Required Provided Required Provided Required Provided
Male 2 2 + 2 3 1 1 1 1 2 Urinals
Female 2 3 2 3
Project:
PROPOSED
BUILDING
FOR D&D WELDING
5300 SOUTH STEEL BLVD.
FT. PIERCE, FLORIDA
Key Plan:
Issues:
No.:
A,
Architect:
Date: Descrip_tion:
02/10/21 PERMIT SET DONADIO & Associates, Architects P.A.
Consultant:
Drawing Title:
2001 9th Avimue, Sultl!I 303
Vero Bea:::h, FL 32960
Tel.m.794292.9
Fax.m.562.8600
Lii::en5e .\lo. AA0002'2:33
www.olonadio-arch.wm
CODE REVIEW
Re-forence Noreh
�
Drn: Dwg. File:
MT Chd, XREF File,
AJD Project No.: Plot File:
2019-54
Sheet No.:
Cert. No.: 12456
Date Signed: A1.10
Co�le,frt;(Q 2020, Donadio & A,:100::l;rtai, Ar-chttecte. P.A.
02/16/2021