HomeMy WebLinkAboutAPPROVED, 2106-0334 - Bldg 1 - 5150 Oleander DATE: 6/23/21 JOB ORDER #: 21-3881 CLIENT: St. Lucie Roofing Permit # 2106-0334 ADDRESS: 1919 SW South Macedo Blvd. Pt. St. Lucie, FL 34984 PROJECT: Covenant Presbyterian Church 26ga 5V Crimp Roof Panels ADDRESS: Bld. 1 - 5150 Oleander Avenue Fort Pierce, FL 2020 FBC/ASCE 7-16 DESIGN PRESSURE CALCULATIONS Project Information: Mean Roof Heights = 10' Exposure: C Basic/Ultimate Wind Speed: Vult=170 mph Length = 100' Category: II Nominal Wind Speed: Vasd=Vult*√0.6 Width = 50' Slope: 5/12 = 22.6° (asd = allowable strength design) Gable Roof For multiple deck condition, the most conservative dimensions were utilized for design calcs. Width of Pressure Coefficient: 0.1(50') = 5.0' or 0.4(10') = 4.0' } use: 4'0" Proposed Roof Replacement Load Table Per Product Approval Roof Zones for Generic Bld. Per Product Approval Bld. 1 Bld. 2 50' 50' 125' 100' Page 2, 6/23/21; Job Order # 21-3881 St. Lucie Roofing - 26ga 5V Crimp Roof Panels Covenant Presbyterian Church Permit # 2106-0334 Bld. 1 - 5150 Oleander Avenue; Fort Pierce, FL: Attachment Requirements: Based on the requirements of Florida Product Approval # FL17022.01-R19, Load Table for Structures in Exposure C, Gable Roofs with Max. Slope of 12/12 and Max. Mean Roof Height of 30', with Maximum Design Pressure of -228PSF; the following are the recommended fastening method to attach the Extreme Metal Fabricators' 26ga 5V Crimp Roof Panels to the minimum 15/32" plywood or 3/4" thick wood plank deck: Roof Zones Zone 1 (1 & 1') Zone 2 (2e, 2r, & 2n) Zone 3 (3e and 3r) Max. Design Pressure -101psf -228psf -228psf Attachment Method C D D Fastener #10 x 1.5" Fasteners with Sealing Washer #10 x 1.5" Fasteners with Sealing Washer #10 x 1.5" Fasteners with Sealing Washer Fastener Spacing at 8" o.c. (12"-12" Pattern) at 6" o.c. (12"-12" Pattern) at 6" o.c. (12"-12" Pattern) Notes: • Corners and perimeter (edge, hip, & ridge) area dimension shall not be less than a = 4'0" (Zone 2: Perimeter is a 4'0" wide strip, Zone 3: Corners are 4'0" x 4'0") • Our engineering attachment analysis is limited to uplift resistance only, therefore, it does t0 include waterproofing or aesthetic concerns as applicable. • Contractor to verify that the fastening patterns meet manufacturer’s requirements for issuance of a warranty (as applicable). • All work shall be in compliance with the local building code product control notice of acceptance and manufacturer specifications and Florida Building Code 2020 Edition. • Wind load calculations based on ASCE 7-16, 2020 FBC, and information provided by client. Client is responsible for verifying existing/proposed conditions/decks as it pertains to the above provided product approval. • All work shall be inspected by our field engineer (or authorized representative) or a building department inspector to verify compliance with specifications. Sincerely, ______________________________ Reza Javidan, P.E. Florida Engineering & Testing, Inc. Florida Reg. No. 60223 Certificate of Authorization No. 6923