Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: Permit #:
Job Information
Builder: I< Hovnanian Community: `rr✓Lot: j
Address: Ai v�Ir`� 0 Unit.
City: ,P CC��-� State: FL Zip: 13Lf G, j
House S.F: �
Avg. Ceiling Height:, .
Total Volume:
All' Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ER1 Method
0PRESCRIPTIVE METHOD The building or dwelling unit shall be tested and verified as having an air leakage rate or not exceeding 7 air
change per hour at a pressure of 0.2-inch w.g. (50 pascals) in climate zones 1 and 2.
&ERFORMANCE OR ERl METHOD � The building or dwelling unit shall be tested and verified as having an air leakage rate of not
exceeding the selected ACH(50) value, as shown on FORM 14445-2017 (performance) or R40&2017 (FRI), section labeled as infiltration, sub"
section ACH,
ACH(50) specified on Form R4052017�Fnergy Calc (Performance) or R406�2017 (ERI):
Pressure & Flow Data (For Single Point)
Test #
House Pressure: Pascals
Flow: CFM (50)
Ring Used
ACH50 = CFM (50) _. 60 / House Volume = `- Method for calculating building volume:
0 Retrieved from architectural plans
PASS ❑ FAIL
Code Software calculated
❑ When ACH(50) is less than 3, Mechanical Ventilation installation must
be verified by building department. 0 Field measured and calculated
Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure or 0.2 inch w.g. (50 pascals). Testing shall be
conducted by either Individual as defined in Section 553.993(5) or (7), Florida Statues, or individuals licensed as set forth in Section 489-105(9)(f), (g), or (1) or
an approved third parry, A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing
shall be performed at any time after creation of all penetrations of the building thermal envelope.
Testing Company
Company Name: RunBrook, LLC Phone: 561-S10-5715
I hereby verify that the above Air Leak g results are in accordance with the 2017 61h Edition Florida Building Code
Energy Conservation requiremen a c ding e compliance method selected above.
Signature of Tester: Date of Test: `�l
Printed Name of Tester:/fif*oank' Costagliola
License/Certification #: 3243649 Issuing Authority: RESNET
RUNBROOK
Duct Leakage Test Report
GREEN BUILDING& ENERGY TESTING
Residential Prescriptive, Performance or ERI Method Compliance
2U I /Florida Building Code, Energy Conservation, 6th Edition
jurisdiction: Permit #:
Job Information
Builder: K Hovnanian Community: Lot: ID
Address: o Atol,Unit:
City: State: FL Zip: 'y
Duct Leakage Test Results
d
S stem 1 =' Prescriptive Method cfm25 (Total)
Y I
cfm25 E To qualify as "substantially leak free" Qn must be less than or equal to
System 2 " 0.04 if air handier unit is installed. If air handler unit is not installed,
cfm25 Qn Total must be less than or equal to 0.03. This testing method
System 3 cfm25 meets the requirements in accordance with Section R403.3.3.
Sum of any
additional systems cfm25
ME Performance / ERI Method cfm25 (Out or Total)
Total of all ? ^'
systems cfm25 To qualify using this method, Qn must not be greater than the
proposed duct leakage Qn specified on Form R405=2017 or R406-2017.
60 g3;L 01 z _
T .Qn Leakage Type selected on Form Qn specified on Form R405=2014
Total of all jotal Conditioned
systems Square Footage 1?405-2017 (Energy Calc) or R406-2017 (Energy Calc) or 406-2017
PASS FAIL
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section
553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(01 (g) or (i), Florida Statutes,
Testing Company
Company Name: RunBrook, LLC Phone: 561-510-5715
I hereby verify that the above duct leakage testing results are in accordance with the 2017 6th Edition Florida Building Code Energy
Conservation requirements according to the com liance method selected above. Signature of Tester: Date of Test: 7dL I
Printed Name of Tester:
Frank Costagliola