HomeMy WebLinkAboutProduct Approval; V3 Series & 70 Series Casement Windows?e19pjr-1'L -a
BUILDING DROPS
A Perfect Solution in Every Drop!
Certificate of Authorization: 29578
Silver Line Building Products
V3 Series/70 Series Casement Windows
(HVHZ) (IMPACT RATED)
for
Florida Product Approval
Current Florida Building Code
398 East Dania Beach Blvd.
Suite 338
Dania Beach, FL 33004
954.399.8478 PH
954.744.4738 FX
contact@buildingdrops.com
Method:
1— A (Certificate Method)
Category:
Windows
Sub — Category:
Casement
Product: V3 Series/70 Series Casement Windows
Material: PVC
Product Dimensions: See Installation Instructions, SWD046
Prepared for:
Silver Line Windo
.� .:
One Dr.
North Brunswick, NJ 08902
Prepared by:
Hermes F. Norero, P.E.
Florida Professional Engineer # 73778
Date:10/15/2020
Contents:
Evaluation Report Pages 1-3
Digitally signed by Hermes F Norero
Reason: I am approving this document
Date: 2020.12.1817:42:09-05'00'
`,�,e111111!/I/l��/
•°•• �'� E • `u' 'PO
7 7
- 3 A OF 4
.O� O
\
�r �4-MesF. Norero P.E.
Florida P.E. No. 73778
BUILDING DROPS
A Perfect Solution in Every Drop!
Certificate of Authorization: 29578
Manufacturer: Silver Line Windows & Doors
Product Category: Windows
Product Sub -Category: Casement
Compliance Method: State Product Approval Method (1)(a)
Product Name: V3 Series/70 Series Casement Windows
(HVHZ) (IMPACT RATED)
FL#: FL21335
Date: 10/15/20
Report No: 7302
Scope: This is a Product Evaluation Report issued by Hermes F. Norero, P.E. (FL # 73778) for Silver Line
Windows & Doors based on Method 1a of the State of Florida Product Approval, Florida Department
of Business and Professional Regulation - Florida Building Commission.
Limits of Use:
Hermes F. Norero, P.E. does not have nor will acquire financial interest in the company
manufacturing or distributing the product or in any other entity involved in the approval process of
the product named herein.
This product has been evaluated for use in locations adhering to the Current Florida Building
Code.
See Installation Instructions SWD046, signed and sealed by Hermes F. Norero, P.E. (FL # 73778) for
specific use parameters.
1. This product has been evaluated and is in compliance with the 5th Edition Florida Building
Code, includine the "High Velocity Hurricane Zone" (HVHZ).
2. Product anchors shall be as listed and spaced as shown on details. Anchor embedment into
substrate material shall be beyond wall dressing or stucco.
3. When used in areas requiring wind borne debris protection this product complies with
Chapter 16 of the Current Florida Building Code and does not require an impact resistant
covering.
4. Site conditions that deviate from the details of Installation Instructions SWD046 require
further engineering analysis by a licensed engineer or registered architect.
5. See Installation Instructions SWD046 for size and design pressure limitations.
Hermes F. Norero, P.E.
Florida P.E. No. 73778
Page 2of3
BUILDING DROPS FL#: FL21335
A Perfect Solution in Every Drop! Date: 10/15/20Report No: 7302
Certificate of Authorization: 29578
Certification Agency: The manufacturer has demonstrated compliance of products in accordance with the
Current Florida Building Code for manufacturing under a Certification Agency
through Window and Door Manufacturers Association (FBC Organization #:
CER1508).
Performance Standards: The product described herein has been evaluated per:
• AAMA/WDMA/CSA 101/I.S.2/A440-11
• TAS 201-94
• TAS 202-94
• TAS 203-94
• ASTM E1886-12
• ASTM E1996-17
Referenced Data:
1. Product Testing performed by Architectural Testing, Inc.
(FBC Organization # TST1558)
Report: Dated:
F1333.01-109-18 02/05/16
Signed and Sealed by: Joseph A. Reed, FL P.E. #58920, Date Sealed: 02/07/2016
F1333.04-109-44 02/05/16
F1333.05-109-44 02/05/16
2. Certification Agency
Window and Door Manufacturers Association
(FBC Organization #: CER1508)
3. Material Certification
PVC profiles meet requirements of WDMA/HallMark WD-61 in accordance with
AAMA 303
Installation Method: Please refer to installation instructions, SWD046, for anchor methods, selection, spacing,
edge distances, embedment's and further details of installation.
Design Pressure: Please refer to installation instructions, SWD046, for mull combination grouping,
configurations, and corresponding design pressures.
Hermes F. Norero, P.E.
Florida P.E. No. 73778
Page 3 of 3
. IA MHallmark@ Certificate of AXIS INC.
u Adminis=rive M3nWmmt
��: �� MConformance and License (CCL) srs,rn�.
iE
Silver Line Building Products Mfr ID: 440
One Silver Line Drive For more Information visit www.amscert.com
North Brunswick, NJ 08902 Website: https://www.andersenwindows.com/products/series/silver-line/
TEL: 800-234-4228 ext 4644
Product No. Product Name Standard Rating Wide High Test Report # CertDate ExpDate
440-H-085.29 70 Series/70NCW11MP-70RCW1IMP 101/I.S.2/A440-11
440-H-085.30 70 Series/70NCW11MP-70RCW1IMP ASTM E-1996-14/
ASTM E-1886-13
440-H-085.32 70 Series/70NCW11MP-70RCW1IMP TAS 201/202/203-94
WDMA and AMS HEREBY CERTIFY that the aforesaid Company ("Licensee"),
at its participating manufacturing plant(s), is licensed to use the WDMA
Registered Hallmark on product lines that have been manufactured in
accordance with the indicated standards. It is further certified that the plant(s),
facilities, quality control procedures, methods, and processes of Licensee have
been inspected, and are subject to regular follow-up inspection and test. It is
further certified that samples of the product set forth above were tested and
found to comply with the standards.
Class CW-PG50; (36 x 72)
Size Tested 914mm x 1829mm
Type-C; DP +50/-50 psf; Water
Test Press 360Pa (7.52psf)
DP +50/-50 psf, Missile D,
Wind Zone 4
(36" x 72") DP +50/-50 psf,
Missile D, Wind Zone 4
By:
By-
914mm 1829mm F1333.04-109-44
914mm 1829mm F1333.05-109-44
914mm 1829mm F1333.01-109-18
,-,f Lucas L_ tyenze.I; Authorized
2/19/2016 12/7/2025
2/19/2016 12/27/2025
8/22/2016 12/7/2025
Program Sponsor:
Program Administrator:
Window and Door Manufacturers Assoc
Administrative Management Systems, Inc.
330 N. Wabash Avenue, Suite 2000
PO Box 730, 205 West Main
Chicago, IL 60611
Sackets Harbor, NY 13685
TEL (312)673-4828 www.wdma.com
TEL (315)646-2234 staff@amscert.com
AIMS
ND-20 512612016 JGK Wednesday, December 2, 2020 Page 1
AM E RICAN CRAFTSMAN WINDOWS
SILVER LINE BUILDING PRODUCTS
V3 SERIES170 SERIES CASEMENT WINDOWS
(HVHZ) (IMPACT RATED
GENERAL NOTES:
I. THE PRODUCT SHOWN HEREIN IS DESIGNED AND
MANUFACTURED TO COMPLY WITH THE CURRENT
FLORIDA BUILDING CODE (FBC), INCLUDING HVHZ AND
HAS BEEN EVALUATED ACCORDING TO THE FOLLOWING:
• AAMA/WDMA/CSA 101/I.S.2/A440-11
• ASTM E1886-12
• ASTM E1996-17
• TAS 201-94
• TAS 202-94
• TAS 203-94
2. ADEQUACY OF THE EXISTING STRUCTURAL
CONCRETE/MASONRY, 2X FRAMING, AND METAL FRAMING
AS A MAIN WIND FORCE RESISTING SYSTEM CAPABLE OF
WITHSTANDING AND TRANSFERRING APPLIED PRODUCT
LOADS TO THE FOUNDATION IS THE RESPONSIBILITY OF
THE ENGINEER OR ARCHITECT OF RECORD FOR THE
PROJECT OF INSTALLATION.
3. IX AND 2X BUCKS (WHEN USED) SHALL BE DESIGNED AND
ANCHORED TO PROPERLY TRANSFER ALL LOADS TO THE
STRUCTURE. BUCK DESIGN AND INSTALLATION IS THE
RESPONSIBILITY OF THE ENGINEER OR ARCHITECT OF
RECORD FOR THE PROJECT OF INSTALLATION.
4. THE INSTALLATION DETAILS DESCRIBED HEREIN ARE
GENERIC AND MAY NOT REFLECT ACTUAL CONDITIONS
FOR A SPECIFIC SITE. IF SITE CONDITIONS CAUSE
INSTALLATION TO DEVIATE FROM THE REQUIREMENTS
DETAILED HEREIN, A LICENSED ENGINEER OR ARCHITECT
SHALL PREPARE SITE SPECIFIC DOCUMENTS FOR USE
WITH THIS DOCUMENT IN NON-HVHZ AREAS. IN HVHZ
AREAS, ONE TIME PRODUCT APPROVAL TO BE OBTAINED
FROM MIAMI-DADE RER OR AHJ.
5. APPROVED IMPACT PROTECTIVE SYSTEM IS NOT
REQUIRED ON THIS PRODUCT IN AREAS REQUIRING IMPACT
RESISTANCE.
6. WINDOW FRAME MATERIAL: PVC
7. GLASS MEETS THE REQUIREMENTS OF ASTM E 1300 GLASS
CHARTS. SEE SHEET 1 FOR GLAZING DETAILS.
TABLE OF CONTENTS
SHEET
REVISION
SHEET DESCRIPTION
I
-
GENERAL NOTES 6 GLAZING DETAIL
2
-
ELEVATION 8. ANCHOR LAYOUTS
3
-
VERTICAL SECTIONS
4
-
HORIZONTAL SECTIONS
5
-
INSTALLATION NOTES AND ANCHOR DETAILS
6
-
BILL OF MATERIALS B COMPONENTS
OVERALL SIZE
PRODUCT
DESIGN
INSTALLATION
MISSILE IMPACT
WIDTH
HEIGHT
MODEL
PRESSURE
METHOD
RATING
70NCWIIMP
36'
72'
+50 / -50 PSF
NAIL FIN
LARGE 6 SMALL
MISSILE IMPACT
70RCWIIMP
36'
72'
+50 / -50 PSF
THROUGH
LARGE 9 SMALLFRAME
MISSILE IMPACT
314' O.A. I.G. LAMINATED GLASS
CONSISTING OF:
I/8' ANNEALED GLASS.
AIR SPACE,
r3132- ANNEALED GLASS
0.090BUTACITE BY KURARAY AMERICA INC
3/32- ANNEALED GLASS
I EXTERIOR \ INTERIOR
4 I 5
1
TIN COATED STEEL
INTERCEPT SPACER MIN. GLASS
SETTING BLOCK � BITE I/2'
GLAZING DETAIL TREMCO S700 OR DOW 995
NOTE:
I. ALL GLAZING CONFIGURATIONS SHALL COMPLY WITH
SAFETY GLAZING REQUIREMENTS OUTLINED IN
CURRENT FBC AND ASTM E 1300 GLASS LOAD
RESISTANCE.
2. SETTING BLOCK SHOULD BE 10-90 DUROMETER AS PER
CH 24 OF THE CURRENT FBC.
3. GLASS LITES THAT EXCEED 38• IN WIDTH SHALL USE
SETTING BLOCKS AT} SPAN FROM CORNERS.
4. FOR INSTALLATION ABOVE 30 FT. ABOVE GRADE IN
AREAS REQUIRING IMPACT RESISTANCE. ALL
I UNITS MUST BE SAFETY GLAZED OR COVERED BY AN
IMPACT PROTECTIVE SYSTEM PER FBC CHAPTER 24.
Digitally signed by Hermes F Norem
Reason: I am approving this document
Date: 2020.12.17 18:58:18 -05'00'
AMERICAN CRAFTSMAN
WINDOWS
SILVER LINE WINDOWS AND
DOORS
ONE SILVERLINE DRIVE
NORTH BRUNSWICK, NJ 08902
PH: (888) 741-0354
U W N
a a o
� p N
N =
2J Do
Di
2a J
vw
0
Z
w?
u
COLD o
U 0 1-
rn w rL
W I_ (r U
W= N ILL.
V7� o 0
� N
1\Z O N
Ww _
� H O
rx > F
LLL W
V3 w
•1 n
W 1- Do CO Z LU rN
~ D Z 3,U_ a~
0 0 3 =_ w Z
p U
N 7 7
o SA OF 0:
Zi7/� �/,p�BYirr(l�plGodG�-irocR�lo��
304 E. DLVD.'d M
oAxu eEAcx, mmo"
FHPE CENT.OF AU1310RQATION N0.283T4
4 BUILDING DROPS, INC.
l� 398 E. DANIA BEACH BLVD.. 033E
U DANIA BEACH, FL 33004
FH:(954)399-8478 FX:(954)744-4738
FL*: 21335
DWG #:
SWD046
SHEET: 1 OF C
FRAME MAX.
WIDTH 36'
AMERICAN CRAFTSMAN
VENT MAX.
WINDOWS
SILVER LINEWINDOWS AND
WIDTH 34'
DLO MAX.
ONE SILVERLI DRIVE
WIDTH 29'
NORTH BRUNSWICK, NJ 08902
PH: (880) 74I-0554
A B
Ci
S 3
Q
�
F
Q
N
O
E
O
N_
rm
=
FRAME MAX.
N
HEIGHT 72'
>
B
= h
v H
J
n
VENT MAX.
Z
4
�X•
HEIGHT 70'
yo
Z
=
O
D.L.O. MAX.
u z
h
HEIGHT 65'
W CO
Fx
U
wrr o
ti
Lu
m
LL.
c
Z
N
J
w
Lu
H
O
0C
y
W
DC
~
w
Lu
m
J
F
O
Z
Q
N
j
8' MAX. 8' MAX.
FROM CORNER FROM CORNER
5.5' MAX.
1' MAX. O.C.
W
o 0
m
3
0
m Z
m =
u
J N
4a) Z
rn
FROM CORNER
``,��� •, 077�''','
i
Pp
N : 7 7
11.25' MAX.
5.5' MAX.'-
D.C.
O S A OF a
O.c
.X.
-X•
�T O IOP:' 40
328E E. µLVD�.�BfE`m
DANIA BEADN. FL S
FB PE DERS. OP AMORRATION N0. 2M
� BU LDING DROPS, INC.
(,yy 329E E. DANIA BEACH BLVD.. #338
UU DANIA BEACH. FL 33004
PH:(954)399-8478 FX:(954)744-4738
FL#: 21335
ANCHOR LAYOUT ANCHOR LAYOUT
FINLESS
FIN
DWG #:
SWD046
SHEET: 2 OF 6
AMERICAN CRAFTSMAN
WINDOWS
SILVER LINE WINDOWS AND
DOORS
ONE SILVERLINE DRIVE
NORTH BRUNSWICK, NJ 08902
PH: (888) 74I-0354
9
I-
o
Q
F
6 3
5 2
K
o
a
6
4
N
SEE GLAZING \ 5
SEE GLAZING \
=
m
SHEET I DETAIL, SHEET 1
Z
s,DETAIL,
NOTE:
w
I. NAIL FIN INSTALLATION MAY
�N
Z
0
USE OPTIONAL J-CHANNEL
cai o
SUCH THAT TYPICAL
y u
INSTALLATION METHODS AND
u
m
ANCHOR REQUIREMENTS ARE
i2
a
w
LL
MAX. FRAME
MET.
MAX. FRAME
w
p
N
HEIGHT
2. THROUGH FRAME
HEIGHT
n�
Z
N
MAX. PANEL
INSTALLATION MAY USE AN
M
0
HEIGHT
OPTIONAL SNAP ON FLANGE_E
HEIGHTEL
w
p
MAX. D.L.O.
SUCH THAT TYPICAL
MAX. D.L.O.
w
>
CK
~
HEIGHT
INSTALLATION AND ANCHOR
HEIGHT EXTERIOR INTERIOR
ti
w
EXTERIOR INTERIOR
REQUIREMENTS ARE MET.
>
_
F
Iii
NOTE: IX WOOD BUCK
J
Z
Q
BY OTHERS IS OPTIONAL
w n
CO>
m
w
FOR MASONRY APPLICATIONS.
F .D
z
to
Q
0 0
3_=
N Z
p
U
EXTERIOR INTERIOR
SEE GLAZING
SEE GLAZING
ETAIL, SHEET I
:° \• E.•S•'• 'P ��
ETAIL, SHEET 1 \ 5
B
\
O
N
B
.;
7 7
4
4' S A OF F
5
��T O IDP:'• ���
6
3
7
```��
T
77
�1p pNOPEBo\,.`
]Y8 E DAMR ��AC}173LW1A.' m m
DANIA BEACH, FLA008
9
MPE CERT.OFAUTHORQA7gN 103.3i3T8
� BUILDING DROPS, INC.
q.al` 3D8 E. OANIA BEACH BLVD.,.M
LLJJ DANIA BEACH, FL 330"
VERTICAL SECTION
B VERTICAL SECTION
FX:(954)7444738
3 THROUGH FRAME INSTALLATION
3 NAIL FIN INSTALLATION
FL#L)399-B47B
21335
DWG #:
SWD046
SHEET: 3 OF 6
5
5
3
3
AMERICAI CRAFTSMAN
SEE GLAZING
INTERIOR
SEE GLAZING
WINDOWS
DETAIL, SEE SHEET I
DETAIL, SEE SHEET I
SILVER LINE WINDOWS AND
DOORS
_
ONE SILVERLINE DRIVE
NORTH BRUNSWICK, NJ 08902
PH: (888) 741-0354
\�
\1 /
EXTERIOR
/
Q
LU
cell
9 7 6
6 7 q
c
o
4
4
N_
2
MAX. D.L.O.
_
m
�
WIDTH
H
Z
MAX. PANEL
z
�
WIDTH
U) u
Z
2
MAX.FRAME
UN
WIDTH
w i
F,
m
A
HORIZONTAL SECTION
1. NAIL FIN INSTALLATION MAY
y m
o
LL
N
4
THROUGH FRAME INSTALLATION
USE OPTIONAL J-CHANNEL
o x
o
o
SUCH THAT TYPICAL
INSTALLATION METHODS AND
w
N
z
p
ANCHOR REQUIREMENTS ARE
rx
>
LU
F
MET.
co
fe
o
2. THROUGH FRAME
n
w
-
INSTALLATION MAY USE AN
(_-
OPTIONAL SNAP ON FLANGE
SUCH THAT TYPICAL
J
-
INSTALLATION AND ANCHOR
F-
Z
REQUIREMENTS ARE MET.
Lil^
DO>
}
m Z
J U)
H .C1
Q_
Z
Y=
N Z
2 5
I
NOTE: IX WOOD BUCK
o
(_)
SEE GLAZING
INTERIOR
SEE GLAZING
BY OTHERS IS OPTIONAL
'If
DETAIL, SHEET I
DETAIL, SEE SHEET I
FOR MASONRY APPLICATIONS.
` %
"I
� "I''
N 7 7
/
\
o• SA OF r0;
Q
6 q
EXTERIOR
4 5
, 'O
]9!E'��9�AE11V 9i�w� ax
MAX. D.L.O.
GAH. REACH, FL Um
WIDTH
POPE CERT. OF AMORPAMN NO.]Y37D
SIX DING DROPS. INC.
398E. DANIA BEACH BLVD.. #338
MAX. PANEL
DANIA BEACH, FL 33DD4
WIDTH
PH:(954)399-B47B FX:(954)744-4738
FL*:
21335
MAX. FRAME
WIDTH
DWG #:
HORIZONTAL SECTION
SWD046
4
NAIL FIN INSTALLATION
SHEET: 4
OF 6
MIN. SUBSTRATE
EDGE DISTANCE BY OTHERS
•••�P / FTEMIN.MBS a SILL HAVE SIMILAR DETAILS 1
EMBEDMENT
1/4' MAX.
SHIM SPACE
EXTERIOR w INTERIOR
VERTICAL SECTION
S THROUGH FRAME (HEAD)
INSTALLATION NOTES:
I. ONE (1) INSTALLATION ANCHOR IS REQUIRED AT EACH ANCHOR
LOCATION SHOWN.
2. THE NUMBER OF INSTALLATION ANCHORS DEPICTED IS THE MINIMUM
NUMBER OF ANCHORS TO BE USED FOR PRODUCT INSTALLATION OF THE
MAXIMUM SIZE LISTED.
3. INSTALL INDIVIDUAL INSTALLATION ANCHORS WITHIN A TOLERANCE OF
31/2 INCH THE DEPICTED LOCATION B SPACING IN THE ANCHOR LAYOUT
DETAILS (I.E., WITHOUT CONSIDERATION OF TOLERANCES). TOLERANCES
ARE NOT CUMULATIVE FROM ONE INSTALLATION ANCHOR TO THE NEXT.
4. SHIM AS REQUIRED AT EACH INSTALLATION ANCHOR WITH LOAD
BEARING SHIM(S). MAXIMUM ALLOWABLE SHIM STACK TO BE 1/4 INCH.
SHIM WHERE SPACE OF 1/16 INCH OR GREATER OCCURS. SHIM(S) SHALL
BE CONSTRUCTED OF HIGH DENSITY PLASTIC OR BETTER.
5. FOR MASONRY OR CONCRETE OPENINGS, A IX WOOD BUCK MAY BE USED
(OPTIONAL) AS LONG AS THE MINIMUM EMBEDMENT AND EDGE DISTANCE
REQUIREMENTS ARE STILL MET WITHIN THE CORRESPONDING HOST
SUBSTRATE. SEE GENERAL NOTE #3 ON SHEET I FOR MORE
INFORMATION.
6. MINIMUM EMBEDMENT AND EDGE DISTANCE EXCLUDE WALL FINISHES,
INCLUDING BUT NOT LIMITED TO STUCCO, FOAM, BRICK VENEER, AND
SIDING.
7. INSTALLATION ANCHORS AND ASSOCIATED HARDWARE MUST BE MADE OF
- CORROSION RESISTANT MATERIAL OR HAVE A CORROSION RESISTANT
COATING.
8. FOR HOLLOW BLOCK AND GROUT FILLED BLOCK, DO NOT INSTALL
INSTALLATION ANCHORS INTO MORTAR JOINTS. EDGE DISTANCE IS
MEASURED FROM FREE EDGE OF BLOCK OR EDGE OF MORTAR JOINT
INTO FACE SHELL OF BLOCK.
9. INSTALLATION ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH
ANCHOR MANUFACTURER'S INSTALLATION INSTRUCTIONS, AND ANCHORS
SHALL NOT BE USED IN SUBSTRATES WITH STRENGTHS LESS THAN THE
MINIMUM STRENGTH SPECIFIED BY THE ANCHOR MANUFACTURER.
AMERICAN CRAFTSMAN
WINDOWS
SILVER LINE WINDOWS AND
DOORS
MIN. SUBSTRATE ONE SILVERLINE DRIVE
EMBEDMENT BY OTHERS NORTH BRUNSWICK, NJ 08902
PH: (888) 741-0354
EDGE
DISTANCE
1/4' MAX.
SHIM SPACE
EXTERIOR W INTERIOR
HORIZONTAL SECTION
5 THROUGH FIN (JAMB)
ANCHOR SCHEDULE
METHOD
SUBSTRATE
ANCHOR SCHEDULE
MIN EMBEDMENT
MIN. EDGE
DISTANCE
WOOD: MIN. SG =0.65
08 WOOD SCREW
1 5'
0.75'
FLAT HEAD
MAIL FIN ANCHOR
3 THREADS MIN
DETAIL
METAL: 18 GAUGE
#8 TEK SCREW
PENETRATION BEYOND
0.75'
Steel, MIN. Fy=33KS1
FLATHEAD
METAL
WOOD: MIN. SG = 0.55
#10 WOOD SCREW
1.51
0.75'
FLAT HEAD
METAL: 18 GAUGE
#10 TEK SCREW
3 THREADS MIN
Steel, MIN. Fy = 33KSI
FLAT HEAD
PENETRATION BEYOND
0.75'
THROUGHFRAME
METAL
ANCHOR DETAIL
CONCRETE:
3/16' ITW TAPCON
fc=3000PSI
FLATHEAD
1.2'^
1.75'
MASONRY: CMU per
3116' ITW TAPCON
ASTM C90 MIN. 2D00
FLATHEAD
1.25'
1.75'
PSI
LL
a
S
O
$
1
�
N
vJ
20
m
J
Fo
Zu
E�
wm
Q N
OF
O
�
�o
Z
LU00)
tJ
VW7 F
F
W
a
O_
N
W_ 2
cr
y
N
W
Of
p
~
C
w
M
>
Lll
=
F
r
H
F
O
Z
Q
r
Q
D o
Y
DO>
Z 2
G
Y
DO Z
Y=
ULL
J
a~
N Z
O�.
N 7 7
'OF
IDP
FBPECERT.OFA ORRA710NNO.Z
BLRLDING DROPS, INC.
Q398 E. DANIA BEACH eLVD.,
D4NIA BEACH. FL 33004
PH:(954)399-8478 FX:(954)744i7
FL#: 21335
DWG #:
SWD046
SHEET: 5 OF L
BILL OF MATERIALS NAIL FIN FRAME NAIL FIN FRAME WITH J-CHANNEL AMERICAN CRAFTSMAN
ITEM# DESCRIPTION MANUFACTURER MATERIAL O PVC O PVC WINDOWS
SILVER LINE WINDOWS AND
1 NAIL FIN FRAME SILVERLINE PVC 3 250• DOORS
2 NAIL FIN FRAME WITH J-CHANNEL SILVERLINE PVC ONE SILVERLINE DRIVE
T�t NORTH BRLVERLIK. NJ 08902
3 REPLACEMENT FRAME SILVERLINE PVC 3.250• 2 647' PH: (868) 74I-0354
4 GLAZING BEAD SILVERLINE PVC 0.075• 0.051' 4.397' o
2.633' c) w N
5 CASEMENT MAIN SASH SILVERLINE PVC CL c o
6 SASH REINFORCEMENT SILVERLINE ALUMINUM o.osl 0.065' N
7 TRACK REINFORCEMENT SILVERLINE ALUMINUM L=W m
8 ISS ENCORE DUAL ARM OPERATOR I SILVERLINE IALUMINUMI
3.500•
9 ISNAP ON FLANGE I SILVERLINE PVC 0.065• wo
I:U
OREPLACEMENT FRAME O GLAZING BEAD O CASEMENT MAIN SASH O SASH REINFORCEMENT aN o
PVC PVC PVC 6 ALUMINUM -:5 a
2.455' W w c9
w
3.244' 1 L N W o
0.879•� 0.075'
Lo.7I6• z N
2.647• 0.051 0.075'1 OD o
�yill Nm o Z
0.051 0.415' 2.434• Tr1lF 0 > ru F
TD.D75• 0.601' N w
0.069' 0.051' >
di
J
F O Q
F Z
W^ m m Z W U,
OTRACK REINFORCEMENT Oq SNAP ON FLANGE o S o Oc x Z
ALUMINUM PVC
0.427'
L �0
0.04 420• 1.020- r4o N.055'
T--4— 0.060• S A OF : a
�T 0
BUILDING DROPS. INC.
l� 398 E. DANIA BEACH BLVD.. 0
LJ DANIA BEACH. FL 330%
PH:(954)399-0478 F%:(954)744-47
FL#: 21335
DWG #:
SWD046
SHEET: 6
OF 6