HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: Lot51 Block Waterston wrightsof® ... Date: Entire House By: Dcs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIRCOM Project• • For: ADAMS HOMES 5379 Lugo Street, Fort Pierce, FL 34951 Cooling Equipment Design Conditions design DB: 90.4 OF Sensible gain: 25151 Btuh Outdoor design WB: 77.4 OF, Latent gain: 4767 Btuh _Indoor design DB: 75.0 OF Total gain: 29918 Btuh Indoor RH: 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Sensible capacity: 28188 Btuh 112%of load Latent capacity: 5115 Btuh 1071/6 of load Total capacity: 33303 Btuh 111%of load SHR: 85% Heating Equipment Design Conditions design DB: 41.0 OF Heat loss: 28559 Btuh Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Output capacity. 31708 Btuh 111 % of load Supplemental heat required. 0 .Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.9 kW 94%of load Temp. rise- 21 OF Meets all requirements ofACCA Manual S. Entering coil DB: 76.4°F Entering coil WB: 63.2°F Entering coil DB: 69.5OF G.00 Capacity balance: 36 °F Economic balance: -99 cF wrightsoft® 2021-Mar-2310:32:10 A 5rtek./0.A hmN Newry omp ry Right Sute@Uriversal2021 2l.O.O2 RSU23828 Page 1 aterstore1820DGL\Lot5lBlklWaterstonel82ODGL.rLp Calc=10J8 FrortDoorfaoes: W - wrightsoft® Component Constructions o e. Lot51 Block Waterston... Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM • • .. ... .. .. ... .. .. For: ADAMS HOMES 5379 Lugo Street, Fort Pierce, FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lucie -Co Inti, FL, US Indoor temperature (T) 70 75 Elevation: 26 .ft Design TD (OF) 29 15 Latitude: 28 °N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb (T) -- 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area U-value Insul R Htg HTM Loss Cig HTM Gain fF Btut✓ftz F ftz°FBtuh Btuwft� Btuh BtuW t� Btuh Walls 1613-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum n 20 0.049 19.0 1.42 28 2.59 52 board int fnsh a 20 0.049 19.0 1.42 28 2.59 52 s 20 0.049 19.0 1.42 28 2.59 52 W 20 0.049. 19.0 .1.42 28 2.59 52 all 80 0.049 19.0 1.42 114 2.59 207 Blkwall, stucco ext, r-4 ext bd ins, 8"thk, 1/2" gypsum board int fnsh n 534 0.201 4.1 5.83 3113 4.06 2168 e 317 0.201 4.1 5.83 1846 4.06 1286 s 611 0.201 4.1 5.83 3561 4.06 2481 W 129 0.201 4.1 5.83 751 4.06 523 all 1591 0.201 4.1 5.83 9272 4.06 6458 Partitions 12C-Osw. Frm Wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int 270 0.091 13.0 2.64 713 1.31 354 fnsh, 2W" wood frm, 16" o.c. stud Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" n 7 0.330 0 9.57 66 8.52 59 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (3.2 ft window ht, 0.8 ft sep.); 6.67 it head ht 2A-2ov: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" n 49 0.330 0 9.57 469 8.52 418 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang a 33 0.330 0 9.57 313 22.4 730 (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht s 49 0.330 0 9.57 469 8.52 418 all 131 0.330 0 9.57 1251 12.0 1566 1 OC-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" a 18 0.550 0 16.0 285 16.2 289 thk; NFRC rated (SHGC=0.70); 12 ft overhang (6.7 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, dr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" a 33 0.330 0 9.57 313 8.52 279 thk; NFRC rated (SHGC=0'.23); 50% drapes, medium; 12 ft overhang (5.3 ft wind owht, 0.25 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" w 33 6.330 0 9.57 313 21.0 686 thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.3 ft overhang (5.3 ft window ht, 0.83 ft sep.); 6.67 ft head ht wrightsoft® 2021 -Mar-23 1032:10 .MO.N/9..6hImHY.w C.mP Y R1g1t-Sdte®Uriversal202121.0.02RSU23828 Page 1 aterstorel820DGLL.ot5lBlklWaterstore1820DGL.nQ Calc=W8 FrortDoorfaces: W 2B'2fv: 2 glazing, clr lowe outr, air gas, vnl fnn-mat, dr innr, 1/4" gap, 1/8" w 5 0.330 0 9.57 48 11.6 58 thk; NFRC rated (SHGC=0.31); 9 ft overhang (1 ft Wndowht, 0.5 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, clr lowe outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" w 13 0.330 0 9.57 128 13.4 179 thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 9 ft overhang (6.7. ft window ht, 2 ft sep.); 6.67 ft head ht Doors 11JO: Door, mtl fbrgl type w 20 0.600 6.3 17.4 350 17.6 353 Ceilings 1613-30ad: Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1/2" 1835 0.032 30:0 0.93 1703 1.69 3100 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 212 0.989 0 28.7 6080 0 0 - i-: wrightsc ft- 2021 -Mar-23 10:32:10 aM,*••, �„w��.��m�m Rigtrt-Sute®Uriversal202121.0.02RSU23828 Paget aterstone1820DGL\Lot5lBlklWaterstorel82ODGL.rLp Calc=W8 FrortDoorfaces: W Project Summary Job: Lot 51 Block 1 Waterston... wrightsof , Entire House ry Byte: ncs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAYSANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Project• • For: ADAMS HOMES 5379 Lugo Street, Fort Pierce, FL 34951 Notes: JA8-18-15 Change to 3.0 ton 2/16/16 S. Finch RVSD 12/7/16 JA L. S. 3-23-21 VWK Design • • Weather: St Lucie Co Inti, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 T Inside db 70 cF Inside db 75 cF Design TD 29 OF Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 grub Heating Summary Sensible Cooling Equipment Load Sizing Structure 24339 Btuh Structure 19374 Btuh Ducts 4220 Btuh Ducts 5777 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping, 0 Btuh Equipment load 28559 Btuh Use manufacturer's data y Rate/swin multipplier 1.00 Infiltration Equipmenqsensbleload 25151 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3364 Btuh Ducts 1403 Btuh Central vent (0 cfm) 0 Btuh Area He a'Coolingg ' (none) (f12) 1820 1820 Equipment latent load 4767 Btuh Volume (ft3) 18350 18350 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 29918 Btuh Equiv. AVF (cfm) 116 61 Req. total capacity at 0.75 SHR 2.8 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC537AP03 Cond 25HBC537AP03 AHRI ref 204837926 Coil FX4DNF037L00 AHRI ref 204837926 Efficiency 8.5 HSPF Efficiency 12.5 EER,16 SEER Heating input Sensible cooling 26250 Btuh Heating output 34600 Btuh @a 47°F Latent cooling 8750 Btuh Temperature rise 27 OF Total cooling 35000 Btuh Actual airflow 1167 cfm Actual airflow 1167 cfm Airflowfactor 0.041 cfm/Btuh Air flow factor 0.046 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.84 Capacity balance point = 36 OF Backup: Input = 8 kW, Output = 26788 Btuh,100 AFUE Calculations approved byACCAto meet all requirements of Manual J 8th Ed. wr7gf�tsoft® 2021-Mar-2310:32:10 Right-SL&O Uriversal 202121.0.02 PIS U23828 Pagel ...atLrstorel820DGL\Lot51BlklWaterstorel82ODGL.rLp Calc=MJB FrortDoorfaces: W -�- wrightsoftRight-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Pln66:407-333-2665 Fax:407-333-3653 Web: W W W:DELAIR.COM' Job: Lot 51 Block 1 Waterston 18... Date: By: DCS . 1 Room name Entire House BDRM2 2 Elposed waall 212.0 It 36.0 It 3 Room height 10.0 It d 10.0 ft heaftol 4 Room dimensions 13.0 x 13.0 It 5 Room area 1835.0 ftz 169.0 ftz Ty Construction U-value Or HTM Area (ft2)) Load Area (ftz) Load number (BtuW F) (Btuhl" or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk wall, stu000 e)d 0201 n 5.83 4.06 590 534 3113 2168 100 100 583 406 2A 2ov 0.330 n 9.57 8.52 7 0 66 59 0 0 0 0 2A 2ov 0.330 n '9 57 8.52 49 0 469 418 0 0 0 0 NOR.19ad, . r :,0.049 eti ? 59 20 {;; 20 =128 = k % = =0 ZMMO z Uy :_O VVjj✓✓ Blk wall, stucco e)d 0201 a -142 5.83 .tt.`..2 4.06 400 ,"<. 317 1846 , _ 1286 130 . 114 663 461 I-G 10C-v 0.550 a 15.95 1620 18 18 285 289 0 0 0 0 2A 2ov 0.330 e 9.57 22.35 33 2 313 730 16 1 156 365 II�-G 2A 2ov 0.330 e 9.57 8.52 33 33 313 279 0 0 0 0 W 1:6819ad, A049 s `. 142 2.59 2020 m 28 k 52 0ZM,0 VIJ _ Blk wall stu000 e)d 0.201 s 5.83 _ 4.06 660 611 3561 2481 130 130 . _ 758 528 �G 2A 2ov 0330 s 957 852 49 49 469 418 0 0 0 0 Blk wall, stuom e)d 0201 w 5.83 4.06 200 129 751 523 .w 0 0 0 0 2A-2ov 0.330 w 9.57 20.99 .33 2 313 .686 0 0 0 0 2B-2fv 0.330 w 9.57 11.58 5 5 48 58 0 0 0 0 2B-2fv 0.330 w 9.57 13.35 13 11 128 179 0 0 0 0 11,10 0.600 w 1740 1768 20 20 350 353 0 0 0 0 sP C iti&30ad 0.032 0 93 1 69 1835 1835 1703 3100 169 xz 169 157 286. 2 ";,; 1835 1� �. , ,a.,...0989 _x2868 ,t)QQ w - ; m6080 Q 25 1 ., ,rN L.+.,+-a. ,*..,.._.� .,. { .o,.9 ,fi _.. r.«x., ..,' ...,.r, _ 4 Y F sr..wM1,xia M...ry M _. .{w- a. L.. i.....w,. ,.a»._._... x Y' ^S ^� a t* w,a.._§S .x.n,. nl7l .x...x..S.,. �Jdk......� u..«...,,;_.6,... ..1,.-'.r..`.k..'�..... ✓ ,�.`..... g... s.. .o-.......+..,:". .. _ f.., �.._ �_aS..t�.,. t � .. ,�., ... ,, ,....>�'� f .........,. .W «. �`:.. .. «i;.a ..p ..... . .-..A..w t� ..a ......,._., .. ,w.....,> ........,ek.. ,..., s �..�..,. ,. r ..,.."......_ -+e M au.., ... � � § ... .... 1f. A a" ...�N a �.1'.- , "�' T. ' 'S .s.,uw. M1...r+ fi }� Y .. }�, .sza . ,,.3 ,.. d.. �.,-........ i= ,....+.w.,,-.,. �' t '4i 5 � h A"^ r' �..sE:.�Aa ' 4. }. x^^ W �,.,..,..., ,xfi .,....« .:-......s <..m.. �.,.. a „x;.„.S� .,..�.. a...,,,,,... i«,..,,.Y „, ..r,+oi.ixY. ..-,'L'....:..,a.1, 3,�.,k.t..exSya .� n �. a.n.. o.rv.,.., S.c .t,.. ,-.�, ash u<.._. ..M�i'Y ,.x ..tu, FI- .rbY....xvE- uM a. .._ ..H� a< ,�, a..�a. h« '�. t .f, ._ rv..-ta.,. . .m . , m ., a..,.. i . ,-.. ..,.,,._.,. „✓„ i.. �e .,. x.e _ .U....m.u, .., _ s..aw,... ..-..- ."a«, ........, ..._,..,,,*5. 6 c) AED exairsion 0 -3 Envelope losstgain 20635 13589 3349 2043 12 a) Infiltration 3704 1035 691 193 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupants @ 230 5 1150 0 0 Appliances/other 3660 300 Subtotal(lines 6to13) 24339 19374 4040 2536 Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 24339 19374, 4040 2536 15 Duct loads 17% 30% 4220 5777 17°/a 30% 700 756 Total room load 28559 25151 4740 3292 Airrequired(dm) 1167 1167 194 153 Calculations approved bvACCAto meet all retauirements of Manual J 8th Ed. wrigtits4M- 2021-Mar-2310.32:10 " """ Right-.SUte®Uriversal 2021 21.0.02 RSU23828 Page 1 aterstone1820DGLNLot5lBlklWaterstorL-182ODGL.rtp "Calc=W8 FrortDoorfaces: W ? - wrightsoft® Right-J® WorkSheet" Job: . Lot51 Block 1 Waterston 18... Entire HoW;e Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY SANFORD, FL 32771 Pho . 407-333-2665 Fax:407-333-3853 ' Web: W W W.DELAIR.COM 1 Room name BATH 2 BDRM3 2 Exposedlwall 6.0 ft 13.0 ft 3 Room height 10.0 It heat/mol 10.0 it heat/000l 4 Room dimensions 13.0 x 6.0 It 13.0 x 13.0 It 5 Room area 78.0 fF 169.0 ,fF Ty Construction U-value Or HTM Area (P) Load Area (f e) Load number (BhrhHtiT) (BtuW) or perimeter (ft) (Btuh) or perimeter (ft) (Bluh) Heat Cool Gross N/P/S Heat Cool Gross N/P/5 Heat Cool 6 W W V)1 Blk wall, stucco eA 2A-2ov 0201 0.330 n n 5.83 '9.57 4.06 8.52 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 W ,. 2A 2ov 16619ad .-- 0.330 n e""',1A? 9.57 8.52 r 258 0 0 0 �. �,.�.��0 0 z 0 0 . -� 0 0 � -0 Z,. 0 =5: 0 0; =Q; Blk vidl, sfucoc e)d 10C-0 2A-2ov ._0:049 0:201 0:550 a a 5,83 15.95 4.06 1620 s .„.�..,� 0 0 . 0 0 .>�t .;.�'.ce, .0 0 ��..x, ,if�.�. 0 0 . �� ..A 0 0 sM.nQ 0 0 .,. 0 0 0 0 0.330 a 9.57 22.35 0 0 0 0. 0 0 0 0 2A 2ov 0.330 e 9.57, 8.52 0 0 0 0 0 0 0 �0 Blk wall stucoo ext 0.201 s 5.83 4.06 60 60 350 244 130 114 663 461 2A 2ov _ 0.330 s 9.57 8.52 0 0 0 0 16 16 156 139, N► .... , Js -1' 3,tl r-,.U;049 Blk wall, stu000 exi 2A-2ov 0201 0.330 w .w 5.83 9.57 4.06 20.99 0 0 0 0 0 0 01 .0 0 0 0 0 0 0 0 0 213-21v 0.330 w 9.57 11.5E 0 0 0 0 0 0 0 0 213-21v 0.330 w 9.57 13.35 0 0 6 0 0 0 0 0 11J0 0.600 w 1740 17.58 0 0 0 0 0 0 0 0 C 16B 30ad 0 032 0.93 169 78 78 72 132 169 169 157 286 F :22A �I 10000 EM10 Mlq6 =(72 M`.0 M r� MjE@03 =2�0. _9�989 �X -_ .169 ., -" M.,,uokw,:;:., yk,.... r. «w ..^ .xv,M .w,mz.,z.::... ,..F.w..'.i -,s m_.x:+s LY . .. ..s., ..._...a ..-_.'.s„xn,�,.. .. „.o-s..,-..a ..ir...>... +... ,e.. r cr.'.:.�". +,."1.....«.. /..... .......... G.. �...... Ka<.. ,S„.�..._...,�..„t ..»�.....+w = = =M2i .� h v>w.r= x.= .. a .:n u x'w'7 ;.. -. }ZZ. "E joz P I., 3.`i:i t C "-Mu. ixa.,.. e5 .+ter;:..• _.+,.n....,..:im.,..:,;wn�'e.. ..,, .:e. ,.., ..,.tt .. ..Nf„ 6 c) AED excursion -18 -56 Envelope loss/gain 594 357 1349 831 12 a) Infiltration 115 32 249 70 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 300 Subtotal (lines 6 to 13) 709 389 1598 1200 Less e)demal load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 709 389 1598 1200 15 Dud loads 171/6 30% 123 116 171/6 30% 277 358, Total room load 832 506 1 at 1558 Air required (dm) 34 23 77 72 Calculations approved byACCAto meet all requirements of Manual J 8th Ed A- 2021-Mar-2310:32:10 Right Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 aterstorel820DGLIot5lBlklWaterstorel82ODGL.rup Calc=MJ8 Front Door faces W wrightsoft' RiOW@ Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job:: Lot 51 Block 1 Waterston 18... Date: By: DCS 1 Room name DININCvMYER DENBDRM4 2 Exposed wall 25.0 It 31.0 It 3 Room height 10.0 It heat/cool 10.0 It heat/cool 4 Room dimensions 1.0 x 276.0 ft 13.0 x 13.0 It 5 Room area 276.0 V 169.0 fte Ty Construction U-value Or HTM Area (fly) Load Area (fq Load number or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 .„W fi16B 19ad. ' nzs {0201 ' » Blk wall, stuom ext n 5.83 4.06 0 0 0 0 50 50 ' 291 203 :. 2A-2ov 0.330 n 9.57 8.52 0 0 0 0 0 0 0 0 _ 2A 2ov _ 0330 n 9.57 852 0 0 0 0 0 0 0. 0 11 ;N1, 16619ad' �, rn..0;049 , e.: _ 142 .. 2,59 _0 M�O __ 0 _. 0 _r :__ w0 • 0 M »0 v . a__ �0. ::. "_ w*U Blk wall, stu000 erd 0201 a 5.83 4.06 0 0 0 0 0 0 _ 0 10C-v 0.550 a 1525 1620 0 0 0 0 0 0 0 0 2A 2ov 0.330 e 9.57 22.35 0 0 0 0 0 0 0 0 2A 2ov 0 330 e, 9 57 8 52 0 0 0 0 0 0 0 0 1.42 259_ ,, 0 ... ..':, _0 w„> - ."0 . _ ... 0 V+/ Blk wall, stuom ext 0201 s 5.83 4.06 110 77 451 314 130 130 758 528 2A 2ov 0;330 9.57 8.52 33 313 279 0 0 0 0 »Blk ws �33 < _ ._ _ v _- � � wall, stu000 ext 0201 w 5.83 4.06 70 32 184 128 130 97 567 395 2A-2ov 0.330 w 9.57 20.99 0 0 0 0 33 2 313 686 213-2fy 0.330 w 9.57 11.58 5 5 48 58 0 0 0 0 28-2fv 0.330 w 9.57 13.35 13 '11 in 179 0 0 0 0 11J0 0.600 w 17AO 17.58 20 20 350 353 0 0 0 0 .P 12C 168 30ad 0.032 0.93 1.69 276 276 256 466 169 1,69 286 ;C F .. _ 31`_0 r157 ,...u. ......,.., .....,.a.v..._y ..iw,,.....e a ....._....,. ...... ,-..w ,..-t.aw�,.�i..,-...,E_4sl st,ti.�.,...._ ia++.r;aw.. ,,.... w a.vms.... ... .........«r.,.....t .._.a ,,..J..,..,. ....F.._w.ac.w_ _..._,.,.._ {.-.._» .�.._..,...._.,. Y .,,_...-..,.......V..r.....,vw1.... .,c, .., a..k4. ,,,..�,... .. ....re. ,,. ,a.d. ....... ....._..:..�.3,_,. .,,_.-.._._. ,[6 :.s. __ .-...,.._,._ _..._...,.. .,..._..., ��: ....9_... 5........«,,,,.,-».......w�,d.,,..a... .... e,....,..:..:dt. \.. L..w w......)., r v.....•*.. .-.a..i'4..ah .h...,.., t ., ..„..,.[_..,. .......... ...:. ,.,. „w ..., .,. .._.w..,. .:-......... _..... _.>.-t _.a�..it�' Yr ,..w-T. ..t .,.K.... �x..,....s..,,.,_,.+dm,. _ ......, i .... ............. _..`u. +i-r�" ,xwa, r .,.._,'4..-... ,_.+.en o-M ' .u..._,..t� .t- ..,.,...» u.........»,.. ,.._ ..-.,,,.... «_...... :..w°... r .. _...n..._.,-..,._r.N.._ik:...:.... _ .._.n..._.a._.. _._ cur- c,.�,W.,-..__ .............. -w--.._ _._. v_--rv_„ i..- ........_.,...._. ....._....w.. _ .,...... ,.......' ..._-- ..»vw_.. r 6 0) AED excursion 236 : 279 Envelopeloss/gain 2631 2104 2975 2377 12 a) Infiltration 345 97 595 166 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupants @ 230 1 230 0 0 ApplianoWother 0 300 Subtotal (lines6to13) 2976 2431 3570 2843 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2976 2431 3570 2843 15 Duct loads 17% 30% 516 725 17% 30% 619 848 Total room load 3492 3156 4189 3691 Air required ((*m) 143 146 171 171 _ Calculations approved byACCAto meet all requirements of Manual J 8th Ed. . - wrogFetsoft� 2021 -Mar-23 10:32:10 Right SLAe®Uriversal 2021 21.0.02 RSU23828 Page 3 .-at:rstore1820DGLtLot51Blk1Waterston1820DGL.rip CaIc--WB Frort Doorfaces: W - wrightsoft, RiOW@ Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAYSANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 51 Block 1 Water§tone 18... Date: By: DCS 1 Room name FAMILY RM MSTR BDRM 2 EVosedwall 13.0 It 41.0 It 3 Room height 10.0 It heaV000l 10.0 It heaUcool 4 Room dimensions 13D x 22.0 It 14.0 x 17.0 ft 5 Room area 286.0 ftz 238.0 ftz Ty Construction U-value Or HTM Area (ft2) Load (ft2) number (BWh� (Btuhfttz) or perimeterLoad) (ft) (BWh or perimeter (ft) (Btuh Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W _ : 16B 19adU _ tiw __:0,049 n . 142 2,59 w: _ 2.0 .:_:T�20 28 Blk vvall, stu000 e)d 0201 n 5.83 4.06 0 0 0 0 170 ~ 154 896 624 2A 2ov 0.330 n 9.57 852 0 0 0 0 0 0 0 0 2A 2ov 0.330 n 9.57 8.52 0 0 0 0 16 0 156 139 11 11V ,__ 6B lad-2.1 _ .,. M. h _ 0:049 r Blk vvl, stuom ext 10C-v 2A 2ov 0201 0.550 a a 5.83 15.95 4.06 1620 130 18 79 18 463 285 323 289 140 0 124 0 721 0 502 0 0.330 e 9.57 22,35 0 0 0 0 16 1 156 365 2A 2ov 0 330 e 9 57 8.52 33 33 313 279 0 0 0 0 1N. 10619ad 7 0049 _. S SM,y, 1,42 , w 20 ;, 20 :.a.28. € 0 0 e t Y !.., ;0,. VIJ Blk wall stu000 eM 0.201 s 5.83 ,. ,_259 4.06 .u„_. 0 .._.w..�. 0 -__ , 0 , .t52 0 E .,.,... 100 100 583 , n._::.fo 406 2A2ov 0.330 s„ 957 852 0 0 0 0 0 0 0 0 _ 0,049 ._w-' 1A2 w Blk wall, stucco ext 2A-2ov 0201 0.330 w w 5.83 9.57 4.06 20.99 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 213-2ty 0.330 w 9.57 -11.58 0 0 0 0 0 0 0 0 213-21`v 0.330 w 9.57 13.35 0 0 0 0 0 0 0 0 11J0 0.600 w 17.40 17.58 0 0 0 0 0 0 0_0 P 12GOsw 0:091 _ 264 131' '0 0 0 0 _ D C 1613-30ad 0,032 093 169 286 286 265 483 238 238 221 402 ,,: ,0 _ .238 =.41.. n+ ..,n.. .. ,...... - .,.,....,:.,.. ..... ...3._.,a.,. ,.a..._..� _. ............:... ....... .. v-.... X.t ,-.,J.; ,L .,. .,.,:.. ., ...,...-,u.., -3, �'v.n,,... .,..t", �'i d. ....._..1,:.. .... .,.x�..;.--.Y +.,. .0.. ..,..:'...... .....t o.._.. __.._ ....._._ _..a..w .�.:.,56 {... d.,. ,.:.., .:. 71 7-1 s , 6 c) AED excursion -119 -130 Envelope loss!gain 1813 1462 3909 2308 12 a) Infiltration 403 113 787 220 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupants@ 230 3 690 1 230 Appliancesrother '300 600 Subtotal (lines 6 to 13) 2216 2564 4696 M58 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2216 2564 4696 3358 15 Dud loads 170/6 30% 384 765 17% 30% 814 1001 Total roam load 2600 3329 5510 4359 Air required (dm) 1061 1541 225 1 202 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed A -* wrYgF�tsofta 2021-Mar-2310:32:10 Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 4 aterstorel820DGL\Lot5lBlklWaterstorel82ODGL.rLp Calc=W8 FrortDoorfaces: W wrightsoft® Right-J® Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phone: 407r333-2665 Fax:4Q7-333-3B53 Web': W W W.DELAIR.COM Jobs: Lot 51 Block 1 Waterston 18... Date: By: DCS 1 Room name M BATH M WIC 2 Exposed wall 12.0 .ft 0 ft 3 Room height 10.0 It heaU000l 10.0 'ft heat/mol 4 Room dimensions 1.0 x 119.0 It 7.0 x 7.0 it 5 Room area 119.0 ft2 49.0 fF Ty Construction U-value Or HTM Area( Load Area (P) Load number (Bluhlftz� (Btuh/fl�) or perimeter (ft) (BWh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 IIV. a 16B 1,9ad .' ; w 0,049 n .. W uu. Blk wall stucco ext 0.201 n 5.83 4.06 120 113 659 459 0 0 0 0 2A 2ov 0.330 n 9.57 8 52 7 0 66 59 0 0 0 0 2A 2ov 0.330 n 9,57 8 52 0 0 0 0 0 0 0 0, 11 W -... a,.:..,. ,< 16&19ad,: M ZEE" _�. 0.049 e , ;a<i.. «e , „ds„i n42• 2.59 � 0 .�, x x 0 � p " ' 1 Q �� ,i' ,ate... ._.. ....,d.�: .' � w � +, ., c,.>es,;0 � _.a>_.acmO s<,. 3' Blk %dl, stucco ext 10C-v . 0201 0.550 a 5.83 15.95 4.06 1620 0 0 0 0 :0 0 0 0 0 0 0 0 0 0 ,.»..4:,uu'Q: 0 0 2A 2ov 0.330 e 9.57 22.35 0 0 0 0 0 0 0 0 2A2ov 0330 a 957 8.52 0 0 0 0 0 0 0 0 1 42 2:59 Q r 0 0 0 06 r 0 Q; Blk Yell stucco ext 0.201 s 5.83 4.06 0 0 0 0 6 0 0 0 2A 2ov 0.330 s 9 57 8 52 0 0 0 0 0 0 0 0 W 16B-f90'' O'049 w n „142 , ,w,,259 S Ma a =- Zo 3. = : Q j= q %N Blk wall, stucco ext 2A-2ov 0201 0.330 w w 5.83 9.57 4.06 20.99 0 0 0 0 __O 0 0 _ .0 0 0 .. _,,, 0 0 .3 0 0 w...-My0 0 0. .b 0 0 28-21v 0.330 w 9.57 11.58 0 0 0 0 0 0 0 0 2B-2tv 0.330 w 9.57 ' 13..35 0 0 0 0 0 0 0 0 11J0 0600 w 17A0 17.58 0 0 0 0 0 0 0 0 U91 O 90264 i31 Z, 03 � 0Z ." 0 0 QZY EYRS:a b 1613-30ad 0.032 0 93 1 69 119 119 110 201 49 49 45 83 ", 11912 a 344 0 49 0 0 Q .266$0.00 - .a. ,w.. ,.�..:;,.�n va, .m,,..,�a „.�.c..<.. x w 9,n,.M N+' LOM MM fi Z Y . ..,K , ,, .. x. «.v,,... - .. ? 4 �. •av M.w.,.�.,. �. o.,,,,v....,x Res,s. ....=. „r,-..,. LS y., ,..-f .,.. .....x.. ,. ,....,u.« .i..HM :..............d..,,...>.s.w. a...zw.d,t.,.ri9,..i,nib. ,:w.l`ik.,.. 3w4.-<.^w. .w. .v,H .,,,.. ,:?N .,,�S,.k,.:.oa ,d.4. _,...,. ,. ,-. ,.0 u. Z+ .v... _.k".w 11 .sa,...,.._t.,.,. ,...t..a°.:.=.,..., + 3 Y Si,. .... ..M .. ,,, ak,. c., .« .,rv....,.,«, a . ............ <. .......vx .... ...> ,. ',n...c.,sw..... L-,.<.,.. +...<.. a...,..�i,$,.�.. ,...,,.� ,.. ..... .... &,.. �".>v,�... .a....,.rc.........+. =21, {.......,..a. }Ra { -• .l #....,...tx...�,.,. w. w ., ur.x. r: ;R..f �...�..rew... °.<. .. ✓ w„ a .....Tx,>..�s<._.. ,<. .,. i r , w =....< � s�,,....s� �' � ��'a. � �iw"4 �'4's' � 5w •• � tar,.. >...�. .. ,.. ... �...xri... .-..,."��..'." .a.., ..,u� .�. m, .. c..,.,. .. w.a,m..., u.N.�....s b_ ,u..._ s -;.n�.s...,,.. .,, i.. »..4 ....d..,w..+t..�. 6 c) AED excursion .35 -4 Envelope lose/gain 1180 684 45 79 12 a) Infiltration 230 64 0 0 b) Room ventilation. 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6to13) 1410 749 45 79 Less extemalload 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1410 749 45 79 15 Ductloads 17% 30% 245 223 17%a 30% 8 24 Total room load 1655 972 53 103 Air required (cfm) 68 45 2 5 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrigFvtsolFt- 2021 -Mar-23 10:32:10 A Right Suite®Uriversal 2021 21.0:02 RSU23828 Page 5 aterstore1820DGL\Lot5161k1Waterstore1820DGL.rup Catc=MJ8 FrortDoorfaces: W -- wrightsofe Right-J® Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 comscOWAY,SANFORD,FL32771 Phore:407-3332665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job:. Lot 51 Block 1 Waterston 18... Date: By. DCS 1 Room name KrrCHENMOOK LAUNDRY 2 Exposed wall 29.0 ft 6.0 ft 3 Room height 10.0 ft heat/cool 10.0 It heat/cool 4 Room dimensions 1.0 x 246.0 It 6.0 x 6.0 It 5 Room area 246.0 ft2 36.0 it' Ty Construction U-value Or HTM Area (M Load Area (ft2) Load number (Btuh/ft- fl (BtuhV) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 :W.rr=a,y 1 W Blk wall, stucco ext 2A 2ov 0201 0.330 n n 5.83 9.57 4.06 8.52 150 0 117 0 684 0 476 0 0 0 0 0 0 0 0 0 2A 2ov 0.330 n 9.57 8.52 33 0 313 279 0 0 0 0 t<..259 q ti0 z,. V[Al Blk wall, stucoo ext 100v 0201 0.550 a a 5.83 15.95 4.06 1620 .., _ 0 0 w,.1117 0_ 0 0 0 0 0 0 0 w 0 0 0 0 0 0 2A 2ov 0330 a 957 22.35 0 0 0 0 0 0 0 0 ,_ 2ov 0.330 e 9.57 8.52 0 0 0 0 0 0 0 0 M VI/ �--G talk v dl stuom ext 0201 s 5.83 4.06 0 0 0 0 0 0 0 0 <2A 2ov 0330 s 957 8.52 0 0 0 0 0 0 0 0, W,<, 16819ad,« ,. 0049 Blk wall, stucco ext 2A-2ov 0201 0.330 w.. w 5.83 9.57 '4.06 20.99 0 0. < < 0 0 0 0 0 -0 0 - 0 0 0- 0 0 0 0 26-21v 0.330 w 9.57 11.58 0 0 0 0 0 0 0 0 26-2N 0.330 w 9.57 13.35 0 0 0 0 0 0 0 0 11M 0.600 w 17AO 17.5E 0 0 0 0 0 0 0 0 `12C,Osw .<..tx ,. �w�:. �wvp, 1.3,1 xr�„�_•140 1.83 79 C 16B 30ad ,��,,40:Q91, 0 032 . .ra,���264.'"��,� 0 93 169 246 ...�_0 246 . _�,�.�369.,,>;.,:�»a 228 416 ,<e-�e" .t�.,w60 36 ....�„•�6Q. 36 � „�158 38 ,�� 61 F� M� ;22A 1pI (% 26 " z 29832 m 0 2.36 6 a72 .. •. e< .9.98.9 ..,. ��..2868 ri0 . . ... ° « «._0 P x 3E FSK ...... _. ��-c`,..w.._ +5:.,� w. ,. ,.. t r; , ...vim - .... ..s.+}.u:.:,,.. d ....,, L'.... �ti .,. _- ..Ue1 ....-<,3.a.a ,�,�.r., „�s. ba..«-.vk_....-.�'..-....«., c�ti_. ...a.�,+...a«.,.ce. �....«.�.:... w, ..2.�....>,✓,.«,..t., s..:na .,+...=.,�s�.,ax..k. w&�.. s-%.�.. ..... s...1.LE:S.L.�`, MUMY d, P.,r , a = =,P . v..-.✓m.� a., r......>. r,<ce. v,_ .«. r.w ., . .n,... .,. ..... ...f4<... fie. ..w� ... ... .v .,.... wr..ir.+i..a ...«.,....�..«,. 2.rwd"x+%R4 4 Qx, h �t,:.ym, t #i: ...v.1.'Tuu.. ,..w<v ..s.kk u.4_.,.- rut,s.3.,ii;'d;'4 v,r:+c r...w& .-...0 .>..... •., > .. J..i s....a.v.. .r... u8„n..,0 =,....sl .w :.4,i; ,. Yaa ad;_, ..*,= =X E ... e..• i= Mam ]1' " Max mom S 4�.�ut � 7.<Lea x.lW ,... <� .=....v ,. .e ...1+. w. •`.+.h, ...�„{.e ....rt.. NFy u.._. ,._w....s `N "`rM.,y.. 2120,..s, £ # �..-. �i..a ,*,.. <""".« s R: ,2,.,.....-..,..3.t s..«� .,.. moo... a,.i .. a... ` •.+ 6 c) AED excursion -117 33 Envelope loss/gain 2426 1237 364 107 12 a) Infiltration 288 80 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Applianoes(other 1200 600 Subtotal (lines 6to 13) 2714 2518 364 707 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2714 2518 364 707 15 Dudloads 17% 30% 471 751 17/° 30% 63 211 Total room load 8185 3268 427 917 Air required (dm) 1301 152 17 43 Calculations approved WACCA to meet all requirements of Manual J 8th Ed -•*- wrigFrrtsoft� Right-Sute®Uriversal 2021 21.0.02 RSU23828 2021-Mar-2310:32:10Page 6 atLrstorel820DGL\Lot5lB]klWaterstore182ODGL.rip CaIc=W8 Front Door faces: W wrightsoff® Duct System Summary o e. Lot51 Block Waterston... Entire House By- ocs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAYSANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM iLroject intormation For: ADAMS HOMES 5379 Lugo Street, Fort Pierce, FL 34951 External static pressure Pressure losses Available static pressure Supply/return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.300 in/100ft 1167 cfm Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.300 in/100ft 1167 cfm 113 ft - Name -Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln.(ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 832 34 23 0.304 4.0 Ox 0 VI Fx 16.3 70.0 BDRM2 h 4740 194 153 0.366 8.0 Ox0 VIFx 22.9 .70.0 BDRM 3 h 1875 77 72 0.433 6.0 Ox 0 . VI Fx 8.6 70.0 DENSDRM4 c 3691 171 171 0.409 7.0 Ox0 VIFx 13.2 70.0 DINING/FOYER c 3156 143 146 0.444 TO Ox 0 VIFx 6.5 70.0 FAMILYRM c 3329 106 154 0.330 8.0 Ox0 VIR 17.9 85.0 sti KITCHEN/NOOK c 3268 130 152 0.323 8.0 Ox 0 VIFx 20.1 85.0 st1 LAUNDRY c 917 17 43 0.316 4.0 Ox0 VIFx 22.7 85.0 sti M. BATH h 1655 68 45 0.317 5.0 Ox 0 VI Fx 22.2 85.0 sti M. W IC c 103 2 5 0.318 4.0 Ox 0 VI Fx 21.9 85.0 sti MSTR BDRM h 5510 225. 202 0.300 8.0 Ox 0 VIFx 28.2 85.0 st1 Supply Trunk Detail Table Name Trunk Type Htg (Cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk sti PeakAVF 549 601 0.300 562 14.0 0 x 0 VInlFlx wrightsoft® 2021-Mar-2310:32:11 •M*:�• �.� p� R gid-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1 aterstore1820DGL1Lot51BIk1Waterstore1820DGL.rLp CaIc=MJ8 Frort Door faces: W Return Branch Detail Table Name Grille Size (in) Htg {cfm) Clg (cfm) TEL (ft) Design FR veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rbi ox0 1167 1167 0 0 0 0 Ox 0 MFx - wrightsoft- TaN(BebNm HSNaxoytompam� Right-Sute®Uriversal2021 21.0.02 RSU23828 aterstore1820DGL\LotSlBlklWaterstorel820DGL.rLp CaIc=W8 FrortDooriaces: W 2021-Mar-2310:32:11 Page 2 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 51 Block 1 Waterstone 1820 DGL Builder Name: ADAMS HOMES Street: 5379 Lugo Street Permit Office: City, State, Zip: Fort Pierce, FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST LUCIE_CO_INTL 2 U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be, sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. . Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking,or floor framing cavity g insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be but neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind pip'nuand wwring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exteriorwalls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope, shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer, Caulking or other adhesive sealants shall not be used to fill voids nkler cover plates and walls or ceolongs. uVUuIun, 1110PO .uvn UI ,Uy waus 511411 Uc IS dt:UUrUahGe with the provjsions of iCG-400. 3/23/2021 10:41 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 3/23/2021 10:41:04 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report, (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: � JQb Information q� � 4� ��� Builder: ADAMS HOMES Community: Lot: NA Address: 5379 Lugo Street City: Fort Pierce State: FL Zip: 34981 AIr Leakage Test Resu Its ; �Pass�ng results rnvst meet ertber fhe Performance, Prescriptive, orhERl Nlefhod ' � , O PRESCRIPTIVE METHOD The`buildmg or dwelling urnt shall be tested and venfied'as having an air leakage rate of not exceeding 7 airy changes per Hour ai a pressure of 0 2,irach w g (50 Pascals) m Climate Zo�nes1 Fond 2 g Q PERFORIil1ANCE or�ERl METt�OD The buildmg,or dwelling umt°shall be�tested and verrfied es having an air (eakage rate of noteexceedug;° the selected ACH(50)walue as shown on Form R405 2020 (Performance) or R�06 2020 (ERI) section labeled as irfiltratlonsub section ACH50. , = �� ` ACH(50) specifretl on Form�R4Q5"2020 Energy Calc "(Performance)zor F)4062020 (ERI) � T.000 - �`� x 60 _ 18200 = Method for calculating building volume: CFM(50) Building Volume ACH(50) O Retrieved from architectural plans F-1 PASS Code 40 software calculated When ACH(50) is less than 3, Mechanical Ventilation installation 0 Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. � s Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 3/23/2021 10:42:01 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 5379 Lugo Street Permit Number: Fort Pierce, FL, 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory).The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory =built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 3/23/2021 10:41 AM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All.ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handier. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct airleakage Qn to the outside ofless than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping Insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41 °C) or below 55°F (13°C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping Insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall ❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. ❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply .with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 3/23/2021 10:41 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'Yz inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). ❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the -horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means �of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems.'New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916 3/23/2021 10:41 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the.procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric bumers shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections ❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is failing and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40oF (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be.instalied for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 3/23/2021 10:41 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5 ❑R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. ❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. ❑ R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. ❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. ❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS ❑ R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 3/23/2021 10:41 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5