HomeMy WebLinkAboutAPPROVED Manual JCalculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 1 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Load Short Form JUNE 18, 2021Date:Entire House Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Information InfiltrationClgHtg SimplifiedMethod9042Outside db (°F) AverageConstruction quality7570Inside db (°F) 1 (Average)Fireplaces1528Design TD (°F) M-Daily range 5030Inside humidity (%) 611Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make ALLIED Trade Trade ALLIED Model Cond 4AC16L36P-50A AHRI ref Coil BCE5E36M AHRI ref 202870272 Efficiency 100 EFF Efficiency 0 SEER Heating input kW4.6 Sensible cooling Btuh0 Heating output Btuh15764 Latent cooling Btuh0 Temperature rise °F13 Total cooling Btuh0 Actual air flow cfm1098 Actual air flow cfm1098 Air flow factor cfm/Btuh0.070 Air flow factor cfm/Btuh0.042 Static pressure in H2O0.50 Static pressure in H2O0.50 Space thermostat Load sensible heat ratio 0.85 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) KITCHEN 120 2759 5071 192 215 FAMILY 224 2843 3004 198 127 LIVING 210 1959 5960 136 252 BED1 144 2529 3817 176 162 BATH 84 739 630 51 27 BED2 144 1455 1931 101 82 BED3 144 3479 5515 242 233 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 2 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E Entire House 1070 15764 25929 1098 1098 Other equip loads 0 0 Equip. @ 0.95 RSM 24632 Latent cooling 4521 TOTALS 1070 15764 29154 1098 1098 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 1 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Building Analysis JUNE 18, 2021Date:Entire House Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) SimplifiedMethod)M(20-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 1 (Average)Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Doors Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 14.923552.5Walls 21.9346016.0Glazing 6.399410.9Doors 6.19590.9Ceilings 7.311501.11.1Floors 17.828112.3Infiltration 25.64036Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.015764Total Cooling Walls Glazing DoorsCeilings FloorsInfiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 7.018082.0Walls 35.3914142.2Glazing 3.694010.3Doors 6.617121.6Ceilings 2.46160.6Floors 2.46350.5Infiltration 22.75895Ducts 00Ventilation 20.05180Internal gains 00Blower 0Adjustments 100.025929Total Latent Cooling Load = 4521 Btuh Overall U-value = 0.098 Btuh/ft²-°F Data entries checked. 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 1 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Component Constructions JUNE 18, 2021Date:Entire House Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) SimplifiedMethod)M(20-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 1 (Average)Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 5401.967032.5513.00.091276n 3821.964982.5513.00.091196e 5261.966852.5513.00.091269s 3601.964692.5513.00.091184w 18081.9623552.5513.00.091924all Partitions (none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 67020.352716.000.57033n 258862.466216.000.57042e 169922.6120016.000.57075s 418462.4107116.000.57067w 914142.2346016.000.570217all Doors 11D0: Door, wd sc type 36210.338210.900.39035n 36210.338210.900.39035e 21710.322910.900.39021w 94010.399410.900.39091all Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 17121.609590.9030.00.0321070 Floors 19A-19cvcp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, leaky crwl ovr 6160.5811501.0819.00.0491070 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 2 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Component Constructions JUNE 18, 2021Date:KITCHEN Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) SimplifiedMethod)M(20-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 1 (Average)Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 2021.962642.5513.00.091104n 931.961212.5513.00.09148e 841.961102.5513.00.09143w 3801.964942.5513.00.091194all Partitions (none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 33520.326316.000.57017n 102962.426316.000.57017e 136441.352716.000.57033all Doors 11D0: Door, wd sc type 21710.322910.900.39021w Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 1921.601080.9030.00.032120 Floors 19A-19cvcp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, leaky crwl ovr 690.581291.0819.00.049120 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 3 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Component Constructions JUNE 18, 2021Date:FAMILY Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) SimplifiedMethod)M(20-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 1 (Average)Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 2181.962842.5513.00.091112n 1511.961962.5513.00.09177e 3691.964802.5513.00.091189all Partitions (none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 33520.326316.000.57017n Doors 11D0: Door, wd sc type 36210.338210.900.39035e Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 3581.602010.9030.00.032224 Floors 19A-19cvcp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, leaky crwl ovr 1290.582411.0819.00.049224 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 4 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Component Constructions JUNE 18, 2021Date:LIVING Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) SimplifiedMethod)M(20-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 1 (Average)Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1461.961902.5513.00.09175w Partitions (none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 233962.459916.000.57038w Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 3361.601880.9030.00.032210 Floors 19A-19cvcp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, leaky crwl ovr 1210.582261.0819.00.049210 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 5 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Component Constructions JUNE 18, 2021Date:BED1 Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) SimplifiedMethod)M(20-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 1 (Average)Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1391.961812.5513.00.09171e 1391.961812.5513.00.09171s 2781.963622.5513.00.091142all Partitions (none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 155962.439916.000.57025e 56522.639916.000.57025s 212442.579816.000.57050all Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2301.601290.9030.00.032144 Floors 19A-19cvcp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, leaky crwl ovr 830.581551.0819.00.049144 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 6 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Component Constructions JUNE 18, 2021Date:BATH Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) SimplifiedMethod)M(20-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 1 (Average)Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 931.961212.5513.00.09148s Partitions (none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 19222.613616.000.5709s Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 1341.60750.9030.00.03284 Floors 19A-19cvcp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, leaky crwl ovr 480.58901.0819.00.04984 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 7 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Component Constructions JUNE 18, 2021Date:BED2 Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) SimplifiedMethod)M(20-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 1 (Average)Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1391.961812.5513.00.09171s Partitions (none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 56522.639916.000.57025s Doors (none) Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2301.601290.9030.00.032144 Floors 19A-19cvcp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, leaky crwl ovr 830.581551.0819.00.049144 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 8 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Component Constructions JUNE 18, 2021Date:BED3 Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) SimplifiedMethod)M(20-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 1 (Average)Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls 12C-0sw: Frm wall, stucco ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2"x4" wood frm, 16" o.c. stud 1191.961552.5513.00.09161n 1551.962022.5513.00.09179s 1301.961692.5513.00.09166w 4041.965272.5513.00.091207all Partitions (none) Windows 1D-c2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/4" thk; 6.67 ft head ht 37722.626616.000.57017s 184662.447216.000.57030w 222348.073816.000.57046all Doors 11D0: Door, wd sc type 36210.338210.900.39035n Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1/2" gypsum board int fnsh 2301.601290.9030.00.032144 Floors 19A-19cvcp: Flr floor, frm flr, 8" thkns, carpet flr fnsh, r-19 cav ins, leaky crwl ovr 830.581551.0819.00.049144 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 1 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Project Summary JUNE 18, 2021Date:Entire House Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor:805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969Email: shafiq0123@yahoo.com Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15Daily range M Relative humidity %50Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh11728 Structure Btuh20033 Ducts Btuh4036 Ducts Btuh5895Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none) (none)Humidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh15764 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh24632 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average1 (Average)Fireplaces Structure Btuh2949 Ducts Btuh1572Central vent (0 cfm) Btuh0 CoolingHeating (none)10701070Area (ft²) Equipment latent load Btuh4521 85608560Volume (ft³)Air changes/hour 0.270.64 Equipment Total Load (Sen+Lat)Btuh29154 Equiv. AVF (cfm) 3991 Req. total capacity at 0.70 SHR ton2.9 Heating Equipment Summary Cooling Equipment Summary Make Make ALLIEDTrade Trade ALLIED Model Cond 4AC16L36P-50AAHRI ref Coil BCE5E36M AHRI ref 202870272Efficiency 100 EFF Efficiency 0 SEER Heating input kW4.6 Sensible cooling Btuh0Heating output Btuh15764 Latent cooling Btuh0 Temperature rise °F13 Total cooling Btuh0Actual air flow cfm1098 Actual air flow cfm1098 Air flow factor cfm/Btuh0.070 Air flow factor cfm/Btuh0.042Static pressure in H2O0.50 Static pressure in H2O0.50 Space thermostat Load sensible heat ratio 0.85 2021-Jun-22 13:02:45 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 1 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:AED Assessment JUNE 18, 2021Date:Entire House Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) )M(20-Daily range (°F) 78-Wet bulb (°F) 7.515.0Wind speed (mph) Test for Adequate Exposure Diversity Hourly Glazing Load Hourly Average AED limitGlazing load (Btuh)Hour of Day 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 8 9 10 11 12 13 14 15 16 17 18 19 20 Maximum hourly glazing load exceeds average by 28.9%. House has adequate exposure diversity (AED), based on AED limit of 30%. AED excursion: 0 Btuh Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:46Right-Suite® Universal 2021 21.0.07 RSU65124 Page 1...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Right-J® Worksheet JUNE 18, 2021Date:Entire House Mustafa TurkBy:TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co 1 Room name Entire House KITCHEN 2 Exposed wall 154.0 ft 31.0 ft 3 Room height 8.0 ft 8.0 heat/coolft 4 Room dimensions ft8.0x15.0 5 Room area 1070.0 ft²120.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 2.552.55 1.961.96 344 276 703 540 120 104 264 202 .GG 1D-c2ov1D-c2ov 0.5700.570 nn 15.9615.96 20.2920.29 33 0 527 670 17 0 263 335 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 35 35 382 362 0 0 0 0 .WW 12C-0sw12C-0sw 0.0910.091 ee 2.552.55 1.961.96 272 196 498 382 64 48 121 93 11 GG 1D-c2ov1D-c2ov 0.5700.570 ee 15.9615.96 62.3662.36 42 0 662 2588 17 0 263 1029 DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 35 35 382 362 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ss 2.552.55 1.961.96 344 269 685 526 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ss 15.9615.96 22.6122.61 75 0 1200 1699 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 2.552.55 1.961.96 272 184 469 360 64 43 110 84 GG 1D-c2ov1D-c2ov 0.5700.570 ww 15.9615.96 62.3662.36 67 0 1071 4184 0 0 0 0 DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 21 21 229 217 21 21 229 217 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 1070 1070 959 1712 120 120 108 192 FF 19A-19cvcp19A-19cvcp 0.0490.049 --1.081.08 0.580.58 1070 1070 1150 616 120 120 129 69 6 c) AED excursion 0 -432 Envelope loss/gain 8917 14218 1487 1790 12 a) Infiltration 2811 635 566 128 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 6 1380 0 0 Appliances/other 3800 2000 Subtotal (lines 6 to 13)11728 20033 2053 3918 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 11728 20033 2053 3918 15 Duct loads 34%29%4036 5895 34%29%706 1153 Total room load 15764 25929 2759 5071 Air required (cfm)Air required (cfm)1098 1098 192 215 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:46Right-Suite® Universal 2021 21.0.07 RSU65124 Page 2...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Right-J® Worksheet JUNE 18, 2021Date:Entire House Mustafa TurkBy:TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co 1 Room name FAMILY LIVING 2 Exposed wall 30.0 ft 14.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft14.0x16.0 ft14.0x15.0 5 Room area 224.0 ft²210.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 2.552.55 1.961.96 128 112 284 218 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 nn 15.9615.96 20.2920.29 17 0 263 335 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 .WW 12C-0sw12C-0sw 0.0910.091 ee 2.552.55 1.961.96 112 77 196 151 0 0 0 0 11 GG 1D-c2ov1D-c2ov 0.5700.570 ee 15.9615.96 62.3662.36 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 35 35 382 362 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ss 2.552.55 1.961.96 0 0 0 0 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ss 15.9615.96 22.6122.61 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ww 2.552.55 1.961.96 0 0 0 0 112 75 190 146 GG 1D-c2ov1D-c2ov 0.5700.570 ww 15.9615.96 62.3662.36 0 0 0 0 38 0 599 2339 DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 224 224 201 358 210 210 188 336 FF 19A-19cvcp19A-19cvcp 0.0490.049 --1.081.08 0.580.58 224 224 241 129 210 210 226 121 6 c) AED excursion -256 706 Envelope loss/gain 1567 1297 1202 3648 12 a) Infiltration 548 124 256 58 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 900 900 Subtotal (lines 6 to 13)2115 2321 1458 4605 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2115 2321 1458 4605 15 Duct loads 34%29%728 683 34%29%502 1355 Total room load 2843 3004 1959 5960 Air required (cfm)Air required (cfm)198 127 136 252 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:46Right-Suite® Universal 2021 21.0.07 RSU65124 Page 3...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Right-J® Worksheet JUNE 18, 2021Date:Entire House Mustafa TurkBy:TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co 1 Room name BED1 BATH 2 Exposed wall 24.0 ft 7.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft12.0x12.0 ft12.0x7.0 5 Room area 144.0 ft²84.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 2.552.55 1.961.96 0 0 0 0 0 0 0 0 .GG 1D-c2ov1D-c2ov 0.5700.570 nn 15.9615.96 20.2920.29 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 .WW 12C-0sw12C-0sw 0.0910.091 ee 2.552.55 1.961.96 96 71 181 139 0 0 0 0 11 GG 1D-c2ov1D-c2ov 0.5700.570 ee 15.9615.96 62.3662.36 25 0 399 1559 0 0 0 0 DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ss 2.552.55 1.961.96 96 71 181 139 56 48 121 93 GG 1D-c2ov1D-c2ov 0.5700.570 ss 15.9615.96 22.6122.61 25 0 399 565 9 0 136 192 WW 12C-0sw12C-0sw 0.0910.091 ww 2.552.55 1.961.96 0 0 0 0 0 0 0 0 GG 1D-c2ov1D-c2ov 0.5700.570 ww 15.9615.96 62.3662.36 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 144 144 129 230 84 84 75 134 FF 19A-19cvcp19A-19cvcp 0.0490.049 --1.081.08 0.580.58 144 144 155 83 84 84 90 48 6 c) AED excursion -325 -10 Envelope loss/gain 1444 2391 422 458 12 a) Infiltration 438 99 128 29 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1882 2949 550 487 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1882 2949 550 487 15 Duct loads 34%29%648 868 34%29%189 143 Total room load 2529 3817 739 630 Air required (cfm)Air required (cfm)176 162 51 27 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:46Right-Suite® Universal 2021 21.0.07 RSU65124 Page 4...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Right-J® Worksheet JUNE 18, 2021Date:Entire House Mustafa TurkBy:TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co 1 Room name BED2 BED3 2 Exposed wall 12.0 ft 36.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft12.0x12.0 ft12.0x12.0 5 Room area 144.0 ft²144.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 12C-0sw12C-0sw 0.0910.091 nn 2.552.55 1.961.96 0 0 0 0 96 61 155 119 .GG 1D-c2ov1D-c2ov 0.5700.570 nn 15.9615.96 20.2920.29 0 0 0 0 0 0 0 0 .DD 11D011D0 0.3900.390 nn 10.9210.92 10.3410.34 0 0 0 0 35 35 382 362 .WW 12C-0sw12C-0sw 0.0910.091 ee 2.552.55 1.961.96 0 0 0 0 0 0 0 0 11 GG 1D-c2ov1D-c2ov 0.5700.570 ee 15.9615.96 62.3662.36 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 12C-0sw12C-0sw 0.0910.091 ss 2.552.55 1.961.96 96 71 181 139 96 79 202 155 GG 1D-c2ov1D-c2ov 0.5700.570 ss 15.9615.96 22.6122.61 25 0 399 565 17 0 266 377 WW 12C-0sw12C-0sw 0.0910.091 ww 2.552.55 1.961.96 0 0 0 0 96 66 169 130 GG 1D-c2ov1D-c2ov 0.5700.570 ww 15.9615.96 62.3662.36 0 0 0 0 30 0 472 1846 DD 11D011D0 0.3900.390 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 144 144 129 230 144 144 129 230 FF 19A-19cvcp19A-19cvcp 0.0490.049 --1.081.08 0.580.58 144 144 155 83 144 144 155 83 6 c) AED excursion -35 350 Envelope loss/gain 864 983 1931 3653 12 a) Infiltration 219 49 657 148 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 2 460 Appliances/other 0 0 Subtotal (lines 6 to 13)1083 1492 2588 4261 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 1083 1492 2588 4261 15 Duct loads 34%29%373 439 34%29%891 1254 Total room load 1455 1931 3479 5515 Air required (cfm)Air required (cfm)101 82 242 233 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:46Right-Suite® Universal 2021 21.0.07 RSU65124 Page 1...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Right-J8® Form J1 JUNE 18, 2021Date:Entire House Mustafa TurkBy:TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co 1 Name of Room Entire House KITCHEN 2 Running Feet of Exposed Wall 154.0 ft 31.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²2424.0ft 8.0 ft²336.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)ft²1070.0 15.0 x 8.0 ft ft²120.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²1070.0°0 ft²120.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 2.552.55 1.961.96 344 703 540 120 264 202 .GlazGlaz 1D-c2ov1D-c2ov nn 15.9615.96 20.2920.29 33 527 670 17 263 335 .DoorDoor 11D011D0 nn 10.9210.92 10.3410.34 35 382 362 0 0 0 .WallWall 12C-0sw12C-0sw ee 2.552.55 1.961.96 272 498 382 64 121 93 11 GlazGlaz 1D-c2ov1D-c2ov ee 15.9615.96 62.3662.36 42 662 2588 17 263 1029 DoorDoor 11D011D0 ee 10.9210.92 10.3410.34 35 382 362 0 0 0 WallWall 12C-0sw12C-0sw ss 2.552.55 1.961.96 344 685 526 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ss 15.9615.96 22.6122.61 75 1200 1699 0 0 0 WallWall 12C-0sw12C-0sw ww 2.552.55 1.961.96 272 469 360 64 110 84 GlazGlaz 1D-c2ov1D-c2ov ww 15.9615.96 62.3662.36 67 1071 4184 0 0 0 DoorDoor 11D011D0 ww 10.9210.92 10.3410.34 21 229 217 21 229 217 CeilCeil 16B-30ad16B-30ad --0.900.90 1.601.60 1070 959 1712 120 108 192 FlorFlor 19A-19cvcp19A-19cvcp --1.081.08 0.580.58 1070 1150 616 120 129 69 Infiltration Heating Load (Btuh)0.640.64 2811 566 Effect WAR WAR 12 Sensible Load (Btuh)ACH 1.00 635 0.20 128 0.270.27 Latent Load (Btuh)1609 Internal a Occupants at 230 and 200 Btuh 6 1380 1200 0 0 0 b Scenario number 3800 2000 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 140 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 11728 20033 2949 2053 3918 Duct EHLF & ESGF 0.3440.344 0.2940.294 4036 5895 706 1153 15 Loads ELG 1572 176 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 0 0 0 17 Winter Humidification Load Gal/Day 00 0 18 Piping Load 0 19 Blower Heat 0 20 AED Excursion & Latent Moisture Migration Load 0 -432 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 15764 25929 4521 2759 5071 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:46Right-Suite® Universal 2021 21.0.07 RSU65124 Page 2...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Right-J8® Form J1 JUNE 18, 2021Date:Entire House Mustafa TurkBy:TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co 1 Name of Room FAMILY LIVING 2 Running Feet of Exposed Wall 30.0 ft 14.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²360.0ft 8.0 ft²312.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)16.0 x 14.0 ft ft²224.0 15.0 x 14.0 ft ft²210.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²224.0°0 ft²210.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 2.552.55 1.961.96 128 284 218 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov nn 15.9615.96 20.2920.29 17 263 335 0 0 0 .DoorDoor 11D011D0 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 .WallWall 12C-0sw12C-0sw ee 2.552.55 1.961.96 112 196 151 0 0 0 11 GlazGlaz 1D-c2ov1D-c2ov ee 15.9615.96 62.3662.36 0 0 0 0 0 0 DoorDoor 11D011D0 ee 10.9210.92 10.3410.34 35 382 362 0 0 0 WallWall 12C-0sw12C-0sw ss 2.552.55 1.961.96 0 0 0 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ss 15.9615.96 22.6122.61 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ww 2.552.55 1.961.96 0 0 0 112 190 146 GlazGlaz 1D-c2ov1D-c2ov ww 15.9615.96 62.3662.36 0 0 0 38 599 2339 DoorDoor 11D011D0 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --0.900.90 1.601.60 224 201 358 210 188 336 FlorFlor 19A-19cvcp19A-19cvcp --1.081.08 0.580.58 224 241 129 210 226 121 Infiltration Heating Load (Btuh)0.640.64 548 256 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.19 124 0.09 58 0.270.27 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 0 0 0 0 0 0 b Scenario number 900 900 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 0 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 2115 2321 1458 4605 Duct EHLF & ESGF 0.3440.344 0.2940.294 728 683 502 1355 15 Loads ELG 329 309 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -256 706 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 2843 3004 1959 5960 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:46Right-Suite® Universal 2021 21.0.07 RSU65124 Page 3...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Right-J8® Form J1 JUNE 18, 2021Date:Entire House Mustafa TurkBy:TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co 1 Name of Room BED1 BATH 2 Running Feet of Exposed Wall 24.0 ft 7.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²384.0ft 8.0 ft²264.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)12.0 x 12.0 ft ft²144.0 7.0 x 12.0 ft ft²84.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²144.0°0 ft²84.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 2.552.55 1.961.96 0 0 0 0 0 0 .GlazGlaz 1D-c2ov1D-c2ov nn 15.9615.96 20.2920.29 0 0 0 0 0 0 .DoorDoor 11D011D0 nn 10.9210.92 10.3410.34 0 0 0 0 0 0 .WallWall 12C-0sw12C-0sw ee 2.552.55 1.961.96 96 181 139 0 0 0 11 GlazGlaz 1D-c2ov1D-c2ov ee 15.9615.96 62.3662.36 25 399 1559 0 0 0 DoorDoor 11D011D0 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ss 2.552.55 1.961.96 96 181 139 56 121 93 GlazGlaz 1D-c2ov1D-c2ov ss 15.9615.96 22.6122.61 25 399 565 9 136 192 WallWall 12C-0sw12C-0sw ww 2.552.55 1.961.96 0 0 0 0 0 0 GlazGlaz 1D-c2ov1D-c2ov ww 15.9615.96 62.3662.36 0 0 0 0 0 0 DoorDoor 11D011D0 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --0.900.90 1.601.60 144 129 230 84 75 134 FlorFlor 19A-19cvcp19A-19cvcp --1.081.08 0.580.58 144 155 83 84 90 48 Infiltration Heating Load (Btuh)0.640.64 438 128 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.16 99 0.05 29 0.270.27 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 2 460 400 0 0 0 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 40 0 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1882 2949 550 487 Duct EHLF & ESGF 0.3440.344 0.2940.294 648 868 189 143 15 Loads ELG 212 123 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -325 -10 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 2529 3817 739 630 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:46Right-Suite® Universal 2021 21.0.07 RSU65124 Page 4...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Right-J8® Form J1 JUNE 18, 2021Date:Entire House Mustafa TurkBy:TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co 1 Name of Room BED2 BED3 2 Running Feet of Exposed Wall 12.0 ft 36.0 ft 3 Ceiling Ht (Ft) and Gross Wall Area (SqFt)8.0 ft²384.0ft 8.0 ft²384.0ft 4 Room Dimensions (Ft) and Floor Plan Area (SqFt)12.0 x 12.0 ft ft²144.0 12.0 x 12.0 ft ft²144.0 5 Ceiling Slope (Deg.) and Gross Ceiling Area (SqFt)0 ft²144.0°0 ft²144.0° Type of Exposure Const., Number Type of Exposure Const., Number Panel Faces HTMPanel Faces HTM Area or Length BtuhArea or Length Btuh Area or Length BtuhArea or Length Btuh Htg.Htg.Clg.Clg.HeatingHeating S-ClgS-Clg L-ClgL-Clg HeatingHeating S-ClgS-Clg L-ClgL-Clg 6 WallWall 12C-0sw12C-0sw nn 2.552.55 1.961.96 0 0 0 96 155 119 .GlazGlaz 1D-c2ov1D-c2ov nn 15.9615.96 20.2920.29 0 0 0 0 0 0 .DoorDoor 11D011D0 nn 10.9210.92 10.3410.34 0 0 0 35 382 362 .WallWall 12C-0sw12C-0sw ee 2.552.55 1.961.96 0 0 0 0 0 0 11 GlazGlaz 1D-c2ov1D-c2ov ee 15.9615.96 62.3662.36 0 0 0 0 0 0 DoorDoor 11D011D0 ee 10.9210.92 10.3410.34 0 0 0 0 0 0 WallWall 12C-0sw12C-0sw ss 2.552.55 1.961.96 96 181 139 96 202 155 GlazGlaz 1D-c2ov1D-c2ov ss 15.9615.96 22.6122.61 25 399 565 17 266 377 WallWall 12C-0sw12C-0sw ww 2.552.55 1.961.96 0 0 0 96 169 130 GlazGlaz 1D-c2ov1D-c2ov ww 15.9615.96 62.3662.36 0 0 0 30 472 1846 DoorDoor 11D011D0 ww 10.9210.92 10.3410.34 0 0 0 0 0 0 CeilCeil 16B-30ad16B-30ad --0.900.90 1.601.60 144 129 230 144 129 230 FlorFlor 19A-19cvcp19A-19cvcp --1.081.08 0.580.58 144 155 83 144 155 83 Infiltration Heating Load (Btuh)0.640.64 219 657 Effect WAR WAR 12 Sensible Load (Btuh)ACH 0.08 49 0.23 148 0.270.27 Latent Load (Btuh) Internal a Occupants at 230 and 200 Btuh 2 460 400 2 460 400 b Scenario number 0 0 13 c Default Adjustments d Custom Appliances 0 0 0 0 e Plants 40 60 14 Subtotals Sum lines 6 through 12Sum lines 6 through 12 1083 1492 2588 4261 Duct EHLF & ESGF 0.3440.344 0.2940.294 373 439 891 1254 15 Loads ELG 212 212 Vent CfmVent Cfm16Ventilation Loads 00 E CfmE Cfm 00 17 Winter Humidification Load Gal/Day 00 18 Piping Load 19 Blower Heat 20 AED Excursion & Latent Moisture Migration Load -35 350 21 Total Load Sum lines 13 through 19Sum lines 13 through 19 1455 1931 3479 5515 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:47 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 1 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:Loads for Multiple Orientations JUNE 18, 2021Date:Entire House Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Project Information COORONA LLCFor: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone: 772-468-6969 Email: shafiq0123@yahoo.com Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)Fort Pierce, FL, US 1528Design TD (°F)ft25Elevation: 5030Relative humidity (%)°N27Latitude: Outdoor:61.51.1Moisture difference (gr/lb)CoolingHeating Infiltration:9042Dry bulb (°F) )M(20-Daily range (°F) 78-Wet bulb (°F) 7.515.0Wind speed (mph) Front Door North Northeast East Southeast South Southwest West Northwest Sensible Load (Btuh) 24597 26093 24632 26849 25101 26069 24521 26078 Latent Load (Btuh) 4521 4656 4521 4659 4521 4656 4516 4656 Total Load (Btuh) 29118 30749 29154 31508 29622 30724 29038 30734 Heating AVF (cfm) 1096 1165 1098 1202 1122 1164 1093 1164 Cooling AVF (cfm) 1096 1165 1098 1202 1122 1164 1093 1164 Building Orientation Cooling Load Total Cooling Load (Btuh)Direction Front Door faces 0 10000 20000 30000 40000 N NE E SE S SW W NW Front Door faces EastCurrent Orientation: Front Door faces SoutheastHighest Cooling Load: Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Jun-22 13:02:48 Right-Suite® Universal 2021 21.0.07 RSU65124 Page 1 ...Drive\Documents\Wrightsoft HVAC\Coorona LLC.rup Calc = MJ8 Front Door faces: E 1001Job:J1 Form - Worksheet A JUNE 18, 2021Date:Entire House Mustafa TurkBy: TURKS A/C INC 3338 ENTERPRISE RD BAY1, FORT PIERCE, FL 34982 Phone: 772-519-0147 Email: mturk2001@aol.com License: CAC1820815, co Supporting Detail Project Name:JUNE 18, 2021Coorona LLC Date: Address: 805 VIRGINIA AVE STE 16, FORT PIERCE, FL 34982 Phone:1001772-468-6969 Job ID: Worksheet A Location and Design Conditions Weather Location: Fort Pierce, FL, US 2725 Latitude =Elevation = Indoor Conditions, Heating: 70 °FDB = %50°F75%30 RH =DB =Indoor Conditions, Cooling:RH = Table 1 Conditions 99% DB = 42 °F Mgr/lb61°F90 Daily Range =Grains Difference =1% DB = Design Temperature Differences °F15°F28 CTD =HTD = Job #: 1001 Performed by Mustafa Turk for: COORONA LLC 805 VIRGINIA AVE STE 16 FORT PIERCE, FL 34982 Phone: 772-468-6969 shafiq0123@yahoo.com TURKS A/C INC 3338 ENTERPRISE RD BAY1 FORT PIERCE, FL 34982 Phone: 772-519-0147 mturk2001@aol.com Scale: 1 : 98 Page 1 Right-Suite® Universal 2021 21.0.07 RSU65124 2021-Jun-22 13:03:09 ...\Wrightsoft HVAC\Coorona LLC.rup N Level 1 KITCHEN FAMILYLIVING BED1BATHBED2BED3 UTILITY ENTRANCE PATIO 3'0"W x 7'0"H H/W 126 cfm 126 cfm 2'6"W x 5'0"H 2'6"W x 5'0"H 2'6"W x 5'0"H 3'4"W x 5'0"H 2'6"W x 5'0"H 2'6"W x 5'0"H 2'6"W x 3'5"H 2'6"W x 5'0"H 2'6"W x 5'0"H 2'6"W x 5'0"H 2'6"W x 5'0"H 2'6"W x 3'4"H 2'6"W x 3'4"H 2'6"W x 3'4"H 2'6"W x 3'4"H 5'0"W x 7'0"H 5'0"W x 7'0"H 2'6"W x 3'4"H 2'6"W x 3'4"H 3'0"W x 7'0"H 8'0"W x 3'8"H 12 " 12 " 12 " 12 " 8 " 12 " 12'-0"12'-0"7'-0"12'-0" 43'-0" 8'-0" 14'-0" 12'-0" 34'-0" 16'-0"15'-0"12'-0" 43'-0" 12'-0" 11'-0"34'-0"7 " 7 " 8'-0" 4'-0" 7'-0" 215 cfm 176 cfm 8 " A/H 6'-0" 198 cfm 8 "8 " 101 cfm 7 " 8 " 51 cfm 10'0"W x 8'0"H 4'0"W x 8'0"H 6 " 15 " 5'0"W x 8'0"H 1098 cfm 12 " 8 " 242 cfm 8 "