APPROVED 11 WYZSKOWSKI- MANUAL J
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-18 11:26:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Project Summary MARCH 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM Project Information WYZSKOWSKI RESIDENCE, PACE 2000, INC.For: 8004 HAMILTON AVEN UE, FORT PIERCE, FL 34951 Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F45 Outside db °F91 Inside db °F70 Inside db °F75 Design TD °F25 Design TD °F16 Daily range M Relative humidity %50 Moisture difference gr/lb60 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18695 Struc ture Btuh14712 Ducts Btuh6619 Ducts Btuh6775 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh25313 Use manufacturer's data n Rate/swing multiplier 0.96 Infiltration Equipment sensible load Btuh20628 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh2351 Ducts Btuh2882 Central vent (0 cfm)Btuh0 CoolingHeating (none) 17261726Area (ft²)Equipment latent load Btuh5233 1735117351Volume (ft³) Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh25861 Equiv. AVF (cfm)58110 Req. total capacity at 0.70 SHR ton2.5 Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1630AJ1 AHRI ref Coil RH1T3617STANJA AHRI ref 201281646 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW8.0 Sensible cooling Btuh20020 Heating output Btuh27297 Latent cooling Btuh8580 Temperature rise °F18 Total cooling Btuh28600 Actual air flow cfm1400 Actual air flow cfm1400 Air flow factor cfm/Btuh0.055 Air flow factor cfm/Btuh0.065 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.80 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-18 11:26:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Right-J® Worksheet MARCH 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House MASTER BEDROOM 2 Exposed wall 174.0 ft 30.0 ft 3 Room height 9.7 dft 9.3 heat/coolft 4 Room dimensions ft245.0x1.0 5 Room area 1794.0 ft²245.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 3.583.58 2.332.33 518 368 1317 859 121 87 311 203 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 13.9913.99 20 0 280 280 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 34 0 476 377 34 0 476 377 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 96 0 1344 1065 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 3.583.58 2.332.33 409 377 1348 879 158 138 494 322 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 24.0324.03 20 0 280 481 20 0 280 481 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 19.7719.77 12 0 168 237 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 3.583.58 2.332.33 321 224 802 523 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 13.9913.99 36 36 504 504 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 25 25 343 242 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 16 16 224 158 0 0 0 0 DD 11D011D0 0.3900.390 ss 9.759.75 10.7210.72 20 20 196 216 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 3.583.58 2.332.33 411 403 1439 938 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 14.0014.00 9.909.90 8 8 112 79 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.421.42 1.421.42 1794 1794 2540 2556 245 245 347 349 FF 22A-tpl22A-tpl 0.9890.989 --24.7324.73 0.000.00 1794 174 4302 0 245 30 742 0 6 c) AED excursion 0 -30 Envelope loss/gain 15676 9395 2649 1702 12 a) Infiltration 3019 1017 508 171 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 4300 500 Subtotal (lines 6 to 13)18695 14712 3157 2373 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 18695 14712 3157 2373 15 Duct loads 35%46%6619 6775 35%46%1118 1092 Total room load 25313 21487 4274 3464 Air required (cfm)Air required (cfm)1400 1400 236 226 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-18 11:26:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Right-J® Worksheet MARCH 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name M WIC 1 MASTER BATH 2 Exposed wall 6.0 ft 12.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft6.0x9.0 ft136.0x1.0 5 Room area 54.0 ft²136.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 3.583.58 2.332.33 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 3.583.58 2.332.33 56 56 199 130 112 100 356 232 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 24.0324.03 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 19.7719.77 0 0 0 0 12 0 168 237 WW 13A-4ocs13A-4ocs 0.1430.143 ss 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 9.759.75 10.7210.72 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.421.42 1.421.42 54 54 76 77 136 136 193 194 FF 22A-tpl22A-tpl 0.9890.989 --24.7324.73 0.000.00 54 6 148 0 136 12 297 0 6 c) AED excursion -4 78 Envelope loss/gain 424 203 1013 741 12 a) Infiltration 102 34 203 68 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 100 0 Subtotal (lines 6 to 13)526 337 1216 809 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 526 337 1216 809 15 Duct loads 35%46%186 155 35%46%431 372 Total room load 712 492 1647 1182 Air required (cfm)Air required (cfm)39 32 91 77 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-18 11:26:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Right-J® Worksheet MARCH 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name LAUNDRY DINING 2 Exposed wall 4.0 ft 14.0 ft 3 Room height 9.3 heat/coolft 10.0 heat/coolft 4 Room dimensions ft10.0x7.0 ft10.0x12.0 5 Room area 70.0 ft²120.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 3.583.58 2.332.33 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 24.0324.03 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 19.7719.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 3.583.58 2.332.33 0 0 0 0 120 84 300 196 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 13.9913.99 0 0 0 0 36 36 504 504 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 9.759.75 10.7210.72 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 3.583.58 2.332.33 37 37 133 87 20 20 72 47 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.421.42 1.421.42 70 70 99 100 120 120 170 171 FF 22A-tpl22A-tpl 0.9890.989 --24.7324.73 0.000.00 70 4 99 0 120 14 346 0 6 c) AED excursion -10 -18 Envelope loss/gain 331 176 1392 899 12 a) Infiltration 68 23 255 86 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 600 500 Subtotal (lines 6 to 13)399 799 1647 1484 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 352 212 14 Subtotal 399 799 1998 1696 15 Duct loads 35%46%141 368 35%46%707 780 Total room load 540 1167 2706 2476 Air required (cfm)Air required (cfm)30 76 150 161 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-18 11:26:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Right-J® Worksheet MARCH 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name FOYER BEDROOM 3 2 Exposed wall 8.0 ft 30.0 ft 3 Room height 10.0 heat/coolft 9.3 heat/coolft 4 Room dimensions ft8.0x8.0 ft162.0x1.0 5 Room area 64.0 ft²162.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 3.583.58 2.332.33 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 3.583.58 2.332.33 0 0 0 0 47 47 166 108 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 24.0324.03 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 19.7719.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 3.583.58 2.332.33 80 44 157 102 121 96 345 225 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 25 25 343 242 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 16 16 224 158 0 0 0 0 DD 11D011D0 0.3900.390 ss 9.759.75 10.7210.72 20 20 196 216 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 3.583.58 2.332.33 0 0 0 0 112 112 399 260 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.421.42 1.421.42 64 64 91 91 162 162 229 231 FF 22A-tpl22A-tpl 0.9890.989 --24.7324.73 0.000.00 64 8 198 0 162 30 742 0 6 c) AED excursion -8 -3 Envelope loss/gain 865 560 2224 1064 12 a) Infiltration 146 49 508 171 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1011 609 2732 1235 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -1011 -609 407 235 14 Subtotal 0 0 3139 1470 15 Duct loads 35%46%0 0 35%46%1111 676 Total room load 0 0 4250 2146 Air required (cfm)Air required (cfm)0 0 235 140 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-18 11:26:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Right-J® Worksheet MARCH 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 3 BATH 2 2 Exposed wall 2.0 ft 6.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft16.0x1.0 ft6.0x9.0 5 Room area 16.0 ft²54.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 3.583.58 2.332.33 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 24.0324.03 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 19.7719.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 9.759.75 10.7210.72 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 3.583.58 2.332.33 19 19 66 43 56 48 171 111 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 14.0014.00 9.909.90 0 0 0 0 8 8 112 79 CC 16X19-0md16X19-0md 0.4080.408 --1.421.42 1.421.42 16 16 23 23 54 54 76 77 FF 22A-tpl22A-tpl 0.9890.989 --24.7324.73 0.000.00 16 2 49 0 54 6 148 0 6 c) AED excursion -1 78 Envelope loss/gain 139 65 508 345 12 a) Infiltration 34 11 102 34 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)172 77 609 380 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -172 -77 183 89 14 Subtotal 0 0 792 469 15 Duct loads 35%46%0 0 35%46%281 216 Total room load 0 0 1073 684 Air required (cfm)Air required (cfm)0 0 59 45 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-18 11:26:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Right-J® Worksheet MARCH 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 2 BEDROOM 2 2 Exposed wall 2.0 ft 25.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft2.0x9.0 ft12.0x13.0 5 Room area 18.0 ft²156.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 3.583.58 2.332.33 0 0 0 0 121 101 361 235 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 13.9913.99 0 0 0 0 20 0 280 280 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 24.0324.03 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 19.7719.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 9.759.75 10.7210.72 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 3.583.58 2.332.33 19 19 66 43 112 112 399 260 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.421.42 1.421.42 18 18 25 26 156 156 221 222 FF 22A-tpl22A-tpl 0.9890.989 --24.7324.73 0.000.00 18 2 49 0 156 25 618 0 6 c) AED excursion -1 -18 Envelope loss/gain 141 68 1879 980 12 a) Infiltration 34 11 423 143 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 300 Subtotal (lines 6 to 13)175 79 2302 1422 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -175 -79 96 48 14 Subtotal 0 0 2398 1471 15 Duct loads 35%46%0 0 35%46%849 676 Total room load 0 0 3247 2147 Air required (cfm)Air required (cfm)0 0 180 140 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-18 11:26:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Right-J® Worksheet MARCH 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN HALL 2 Exposed wall 20.0 ft 0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft328.0x1.0 ft36.0x1.0 5 Room area 328.0 ft²36.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 3.583.58 2.332.33 112 112 399 260 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 3.583.58 2.332.33 37 37 133 87 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 24.0324.03 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 19.7719.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 9.759.75 10.7210.72 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 3.583.58 2.332.33 37 37 133 87 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.421.42 1.421.42 328 328 464 467 36 36 51 51 FF 22A-tpl22A-tpl 0.9890.989 --24.7324.73 0.000.00 328 20 495 0 36 0 0 0 6 c) AED excursion -40 -1 Envelope loss/gain 1624 861 51 51 12 a) Infiltration 338 114 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 2200 0 Subtotal (lines 6 to 13)1962 3175 51 51 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -51 -51 14 Subtotal 1962 3175 0 0 15 Duct loads 35%46%695 1461 35%46%0 0 Total room load 2657 4636 0 0 Air required (cfm)Air required (cfm)147 302 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-18 11:26:36 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Right-J® Worksheet MARCH 18, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM 1 Room name LIVING ROOM M TOILET 2 Exposed wall 15.0 ft 0 ft 3 Room height 11.0 heat/coolft 9.4 heat/coolft 4 Room dimensions ft21.0x15.0 ft4.0x5.0 5 Room area 315.0 ft²20.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 3.583.58 2.332.33 165 69 247 161 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 nn 14.0014.00 11.1011.10 96 0 1344 1065 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ee 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 24.0324.03 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ee 14.0014.00 19.7719.77 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 13.9913.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ss 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 9.759.75 10.7210.72 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 3.583.58 2.332.33 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.5602 glazing, clr low-e 0.560 ww 14.0014.00 9.909.90 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.421.42 1.421.42 315 315 446 449 20 20 28 28 FF 22A-tpl22A-tpl 0.9890.989 --24.7324.73 0.000.00 315 15 371 0 20 0 0 0 6 c) AED excursion -23 0 Envelope loss/gain 2407 1652 28 28 12 a) Infiltration 300 101 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 100 0 Subtotal (lines 6 to 13)2708 1853 28 28 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 371 231 0 0 14 Subtotal 3079 2084 28 28 15 Duct loads 35%46%1090 959 35%75%10 21 Total room load 4169 3043 38 49 Air required (cfm)Air required (cfm)231 198 2 3 2021-Mar-18 11:26:41 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N ESSEX MODEL GAR- RTJob:Duct System Summary MARCH 18, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., F ORT PIERCE, FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS@AOL.COM Project Information WYZSKOWSKI RESIDENCE, PACE 2000, INC.For: 8004 HAMILTON AVEN UE, FORT PIERCE, FL 34951 CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1400cfm1400 Total effective length (TEL)ft174 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3135.027.7VlFx0x06.01.00045591073hBATH 2 st3135.033.6VlFx0x07.01.0001401803247hBEDROOM 2 st3135.030.3VlFx0x07.01.0001402354250hBEDROOM 3 st1115.012.3VlFx0x08.01.0001611502476cDINING st1115.016.6VlFx0x08.01.000151732318cKITCHEN st1115.07.2VlFx0x08.01.000151732318cKITCHEN-A st2115.021.6VlFx0x06.01.00076301167cLAUNDRY st3135.038.6VlFx0x07.01.000991152084hLIVING ROOM st3135.027.5VlFx0x07.01.000991152084hLIVING ROOM-A st2115.019.2VlFx0x04.01.0003249cM TOILET st2115.015.1VlFx0x05.01.0003239712hM WIC 1 st2115.018.1VlFx0x06.01.00077911647hMASTER BATH st2115.019.1VlFx0x08.01.0002262364274hMASTER BEDROOM Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 399 414 1.000 527 12.0 0x0 VinlFlx st1 Peak AVF 1001 986 1.000 937 14.0 0x0 VinlFlx st3 Peak AVF 705 523 1.000 897 12.0 0x0 VinlFlx st1 2021-Mar-18 11:26:41 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...Wrightsoft HVAC\ESSEX MODEL- WYZSKOWSKI RES.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 14000 1400 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������