10007 S Indian River
HVAC Load Calculations
for
Residence
10007 S Indian River Drive
Fort Pierce, Florida 34982
Prepared By:
Karen Oliver
KO Energy Design
1470 N Congress Ave, Suite 106A
West Palm Beach, Florida 33409
(561) 327-7272
Wednesday, May 19, 2021
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
KO Energy Design LLC 10007 S Indian River
West Palm Beach, FL 33411 Page 2
Project Report
General Project Information
Project Title:10007 S Indian River
Designed By:Karen Oliver
Project Date:Monday, May 03, 2021
Client Name:Residence
Client Address:10007 S Indian River Drive
Client City:Fort Pierce, Florida 34982
Company Name:KO Energy Design
Company Representative:Karen Oliver
Company Address:1470 N Congress Ave, Suite 106A
Company City:West Palm Beach, Florida 33409
Company Phone:(561) 327-7272
Company E-Mail Address:info@koenergydesign.com
Company Website:www.koenergydesign.com
Permit Number(s):ww
Design Data
Reference City:Vero Beach, Florida
Building Orientation:House faces East
Daily Temperature Range:Medium
Latitude:27 Degrees
Elevation:13 ft.
Altitude Factor:1.000
Outdoor Outdoor Outdoor Indoor Indoor Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference
Winter:43 40.34 n/a n/a 70 n/a
Summer:90 78 59%55%75 54
Check Figures
Total Building Supply CFM:1,000 CFM Per Square ft.:1.176
Square ft. of Room Area:850 Square ft. Per Ton:404
Volume (ft³):6,870
Building Loads
Total Heating Required Including Ventilation Air:20,270 Btuh 20.270 MBH
Total Sensible Gain:21,640 Btuh 86 %
Total Latent Gain:3,619 Btuh 14 %
Total Cooling Required Including Ventilation Air:25,259 Btuh 2.10 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ...\10007 Indian River MJ wh low e.rh9 Wednesday, May 19, 2021, 1:21 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
KO Energy Design LLC 10007 S Indian River
West Palm Beach, FL 33411 Page 3
Load Preview Report
Scope
Net
Ton
ft.²
/Ton Area
Sen
Gain
Lat
Gain
Net
Gain
Sen
Loss
Sys
Htg
CFM
Sys
Clg
CFM
Sys
Act
CFM
Duct
Size
Building 2.10 404 850 21,640 3,619 25,259 20,270 1,000 1,000 1,000
System 1 2.10 404 850 21,640 3,619 25,259 20,270 1,000 1,000 1,000 16
Supply Duct Latent 303 303
Return Duct 1,308 597 1,905 408
Zone 1 850 20,332 2,719 23,051 19,862 1,000 1,000 1,000 16
1-Living / Kitchen 339 7,289 1,318 8,607 5,854 295 359 359 2--7
2-Bath 60 427 0 427 282 14 21 21 1--4
3-Florida Room 153 6,658 598 7,256 7,458 376 327 327 2--7
4-Bedroom 2 149 3,366 393 3,759 3,323 167 166 166 1--7
5-Bedroom 1 149 2,591 410 3,001 2,944 148 127 127 1--6
C:\ ...\10007 Indian River MJ wh low e.rh9 Wednesday, May 19, 2021, 1:21 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
KO Energy Design LLC 10007 S Indian River
West Palm Beach, FL 33411 Page 4
Duct Size Preview
Room or
Duct Name Source Minimum
Velocity
Maximum
Velocity
Rough.
Factor
Design
L/100
SP
Loss
Duct
Velocity
Duct
Length
Htg
Flow
Clg
Flow
Act.
Flow
Duct
Size
Reg
Size
System 1
Supply Runouts
Zone 1
1-Living / Kitchen Built-In 0 0 0.0003 0.1 670.7 295 359 359 2--7
2-Bath Built-In 0 0 0.0003 0.1 240.8 14 21 21 1--4
3-Florida Room Built-In 0 0 0.0003 0.1 612.7 376 327 327 2--7
4-Bedroom 2 Built-In 0 0 0.0003 0.1 619.5 167 166 166 1--7
5-Bedroom 1 Built-In 0 0 0.0003 0.1 649.1 148 127 127 1--6
Other Ducts in System 1
Supply Main Trunk Built-In 0 0 0.01 0.12 716.2 1,000 1,000 1,000 16
SummarySummarySummarySummarySummarySummarySummarySummary
System 1
Heating Flow:1000
Cooling Flow:1000
C:\ ...\10007 Indian River MJ wh low e.rh9 Wednesday, May 19, 2021, 1:21 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
KO Energy Design LLC 10007 S Indian River
West Palm Beach, FL 33411 Page 5
Total Building Summary Loads
Component
Description
Area
Quan
Sen
Loss
Lat
Gain
Sen
Gain
Total
Gain
Low E .99 UF SHG: Glazing-Standard Low E 1.10 UF .29
SHGC, U-value 1.1, SHGC 0.29
10 298 0 284 284
Low E .99 UF SHG: Glazing-Standard Low E 1.10 UF .29
SHGC, U-value 1.06, SHGC 0.25
178.9 5,120 0 4,870 4,870
Low E .99 UF SHG: Glazing-Standard Low E 1.10 UF .29
SHGC, U-value 0.99, SHGC 0.27
14.6 391 0 301 301
Low E .99 UF SHG: Glazing-Standard Low E 1.10 UF .29
SHGC, U-value 1.04, SHGC 0.32
70.4 1,975 0 2,498 2,498
11D: Door-Wood - Solid Core, U-value 0.39 19.1 201 0 194 194
12B-0sw: Wall-Frame, R-11 insulation in 2 x 4 stud cavity,
no board insulation, siding finish, wood studs, U-value
0.097
709.2 1,858 0 1,659 1,659
16C-30-ml: Roof/Ceiling-Under Attic with Insulation on
Attic Floor (also use for Knee Walls and Partition
Ceilings), vented attic, no radiant barrier, R-30
insulation, light metal, U-value 0.032
850 735 0 1,089 1,089
19A-0cp-h: Floor-Over enclosed crawl space, No
insulation on exposed walls, sealed or vented space,
passive, no floor insulation, hardwood covering, U-
value 0.295
850 2,544 0 1,414 1,414
Subtotals for structure:13,122 0 12,309 12,309
People:3 600 690 1,290
Equipment:0 4,000 4,000
Lighting:0 0 0
Ductwork:3,919 900 3,415 4,315
Infiltration: Winter CFM: 109, Summer CFM: 57 3,229 2,119 945 3,064
Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
AED Excursion:0 0 281 281
Total Building Load Totals:20,270 3,619 21,640 25,259
Check Figures
Total Building Supply CFM:1,000 CFM Per Square ft.:1.176
Square ft. of Room Area:850 Square ft. Per Ton:404
Volume (ft³):6,870
Building Loads
Total Heating Required Including Ventilation Air:20,270 Btuh 20.270 MBH
Total Sensible Gain:21,640 Btuh 86 %
Total Latent Gain:3,619 Btuh 14 %
Total Cooling Required Including Ventilation Air:25,259 Btuh 2.10 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ...\10007 Indian River MJ wh low e.rh9 Wednesday, May 19, 2021, 1:21 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
KO Energy Design LLC 10007 S Indian River
West Palm Beach, FL 33411 Page 6
Building Pie Chart
Building
Loss
20,270
Btuh
Floor 13%
Roof 4%
Wall 9%
Glass 38%
Door 1%
Ductwork 19%
Infiltration 16%
Building
Gain
25,259
Btuh
Floor 6%
Roof 4%
Wall 7%
Glass 31%
Door 1%People 5%
Equipment 16%
Ductwork 17%
Infiltration 12%
AED Excursion 1%
C:\ ...\10007 Indian River MJ wh low e.rh9 Wednesday, May 19, 2021, 1:21 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
KO Energy Design LLC 10007 S Indian River
West Palm Beach, FL 33411 Page 7
System 1 System #1 Summary Loads
Component
Description
Area
Quan
Sen
Loss
Lat
Gain
Sen
Gain
Total
Gain
Low E .99 UF SHG: Glazing-Standard Low E 1.10 UF .29
SHGC, U-value 1.1, SHGC 0.29
10 298 0 284 284
Low E .99 UF SHG: Glazing-Standard Low E 1.10 UF .29
SHGC, U-value 1.06, SHGC 0.25
178.9 5,120 0 4,870 4,870
Low E .99 UF SHG: Glazing-Standard Low E 1.10 UF .29
SHGC, U-value 0.99, SHGC 0.27
14.6 391 0 301 301
Low E .99 UF SHG: Glazing-Standard Low E 1.10 UF .29
SHGC, U-value 1.04, SHGC 0.32
70.4 1,975 0 2,498 2,498
11D: Door-Wood - Solid Core, U-value 0.39 19.1 201 0 194 194
12B-0sw: Wall-Frame, R-11 insulation in 2 x 4 stud cavity,
no board insulation, siding finish, wood studs, U-value
0.097
709.2 1,858 0 1,659 1,659
16C-30-ml: Roof/Ceiling-Under Attic with Insulation on
Attic Floor (also use for Knee Walls and Partition
Ceilings), vented attic, no radiant barrier, R-30
insulation, light metal, U-value 0.032
850 735 0 1,089 1,089
19A-0cp-h: Floor-Over enclosed crawl space, No
insulation on exposed walls, sealed or vented space,
passive, no floor insulation, hardwood covering, U-
value 0.295
850 2,544 0 1,414 1,414
Subtotals for structure:13,122 0 12,309 12,309
People:3 600 690 1,290
Equipment:0 4,000 4,000
Lighting:0 0 0
Ductwork:3,919 900 3,415 4,315
Infiltration: Winter CFM: 109, Summer CFM: 57 3,229 2,119 945 3,064
Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0
AED Excursion:0 0 281 281
System 1 System #1 Load Totals:20,270 3,619 21,640 25,259
Check Figures
Supply CFM:1,000 CFM Per Square ft.:1.176
Square ft. of Room Area:850 Square ft. Per Ton:404
Volume (ft³):6,870
System Loads
Total Heating Required Including Ventilation Air:20,270 Btuh 20.270 MBH
Total Sensible Gain:21,640 Btuh 86 %
Total Latent Gain:3,619 Btuh 14 %
Total Cooling Required Including Ventilation Air:25,259 Btuh 2.10 Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\ ...\10007 Indian River MJ wh low e.rh9 Wednesday, May 19, 2021, 1:21 PM
Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc.
KO Energy Design LLC 10007 S Indian River
West Palm Beach, FL 33411 Page 8
System 1 Room Load Summary
No
Room
Name
Area
SF
Htg
Sens
Btuh
Min
Htg
CFM
Run
Duct
Size
Run
Duct
Vel
Clg
Sens
Btuh
Clg
Lat
Btuh
Min
Clg
CFM
Act
Sys
CFM
---Zone 1---
1 Living / Kitchen 339 5,854 76 2-7 671 7,289 1,318 331 359
2 Bath 60 282 4 1-4 241 427 0 19 21
3 Florida Room 153 7,458 97 2-7 613 6,658 598 303 327
4 Bedroom 2 149 3,323 43 1-7 620 3,366 393 153 166
5 Bedroom 1 149 2,944 38 1-6 649 2,591 410 118 127
Duct Latent 303
Return Duct 408 1,308 597
System 1 total 850 20,270 258 21,640 3,619 925 1,000
System 1 Main Trunk Size:16 in.
Velocity:716 ft./min
Loss per 100 ft.:0.087 in.wg
Cooling System Summary
Cooling
Tons
Sensible/Latent
Split
Sensible
Btuh
Latent
Btuh
Total
Btuh
Net Required:2.10 86% / 14%21,640 3,619 25,259
Actual:2.38 75% / 25%21,450 7,150 28,600
Equipment Data
Heating System Cooling System
Type:Air Source Heat Pump Air Source Heat Pump
Model:4TWR6030H1 4TWR6030H1
Indoor Model:TEM6A0B30H21+TDR
Brand:TRANE TRANE
Description:Air Source Heat Pump Air Source Heat Pump
Efficiency:9 HSPF 16 SEER
Sound:0 0
Capacity:27,800 Btuh 28,600 Btuh
Sensible Capacity:n/a 21,450 Btuh
Latent Capacity:n/a 7,150 Btuh
AHRI Reference No.:n/a 7562380
This system's equipment was selected in accordance with ACCA Manual S.
Manual S equipment sizing data: SODB: 90F, SOWB: 78F, WODB: 43F, SIDB: 75F, SIRH: 55%, WIDB: 70F, Sen. gain:
21,640 Btuh, Lat. gain: 3,619 Btuh, Sen. loss: 20,270 Btuh, Entering clg. coil DB: 76.2F, Entering clg. coil WB: 64.3F,
Entering htg. coil DB: 69.6F, Clg. coil TD: 20F, Htg. coil TD: 70F, Req. clg. airflow: 925 CFM, Req. htg. airflow: 258 CFM
C:\ ...\10007 Indian River MJ wh low e.rh9 Wednesday, May 19, 2021, 1:21 PM
Field Verification Requirement
Project Information
Designed by:Karen Oliver
Project date:Monday, May 03, 2021
Client name:Residence
Client address:10007 S Indian River Drive
Client city:Fort Pierce, Florida 34982
Company name:KO Energy Design
Company phone:(561) 327-7272
In Field Verification
All inputs/defaults/building characteristics used for the Manual J Residential Load Calculation (8th Edition - Full)
[ANSI/ACCA 2 Manual J - 2016]. Calculations must be verified by the HVAC contractor in the field and/or must be verified
by the builder/owner verifying that what is being built is consistent with the builders/owners project components in this
report. Test and balance reports if performed are to reflect Manual J system actual CFM for each individual unit. K.O.
Energy Design must be notified in writing of any said changes.
Equipment Selection
Equipment selected below was carefully chosen to meet or exceed the FL Energy Efficiency Code. Alternate equivalent
equipment selection shall also meet the attached Energy Code Requirements. Any change in SEER or size of equipment
will require approval and plan revision. K.O. Energy Design must be notified in writing of any said changes.
Item System 1
Air Handler Name System #1
Cooling Description Air Source Heat Pump
Cooling Model Type Air Source Heat Pump
Cooling Model Number 4TWR6030H1+TEM6A0B30H21+TDR
Cooling Capacity 28600
Cooling Efficiency 16 SEER
AHRI Reference No.7562380
Heating Description Air Source Heat Pump
Heating Model Type Air Source Heat Pump
Heating Model Number 4TWR6030H1
Heating Capacity 27800
Heating Efficiency 9 HSPF
Manual D Duct Sizing
Duct sizing has been carefully engineered at the stated s.p. Any deviance in duct sizing could impact the performance and
efficiency of selected equipment. Any change or alteration in duct sizing will require approval and possible plan revision.
K.O. Energy Design must be notified in writing of any said changes. Duct sealing Air Distribution System Test to be
performed and made available for Rough Duct Inspection, if required.