APPROVED M Manual J
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Project Summary AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information FY 839 SPEC HOUSE, SYNERGY HOMESFor: 113 LIMA COURT, PORT ST LUCIE, FL 34983 Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18093 Struc ture Btuh18333 Ducts Btuh5651 Ducts Btuh8093 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh23744 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh25105 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh3908 Ducts Btuh2187 Central vent (0 cfm)Btuh0 CoolingHeating (none) 18091809Area (ft²)Equipment latent load Btuh6095 1729217292Volume (ft³) Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh31199 Equiv. AVF (cfm)58110 Req. total capacity at 0.70 SHR ton3.0 Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTR4036L1 AHRI ref Coil TEM4A0C37S31++TDR AHRI ref 201763661 Efficiency 100 EFF Efficiency 12.2 EER, 16 SEER Heating input kW6.0 Sensible cooling Btuh24500 Heating output Btuh20475 Latent cooling Btuh10500 Temperature rise °F16 Total cooling Btuh35000 Actual air flow cfm1167 Actual air flow cfm1167 Air flow factor cfm/Btuh0.049 Air flow factor cfm/Btuh0.044 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.81 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House M BATH 2 Exposed wall 167.0 ft 17.0 ft 3 Room height 9.6 ft 8.0 heat/coolft 4 Room dimensions ft11.0x6.0 5 Room area 1809.0 ft²66.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 568 497 1991 1088 48 48 192 105 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 30 0 252 317 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 41 0 343 432 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 280 280 1121 613 88 88 352 193 11 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 272 222 887 485 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 30 60 252 317 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 20 20 223 211 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 404 389 1558 851 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.1929.19 15 4 126 438 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 1809 1809 1621 2894 66 66 59 106 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 1809 167 6350 0 66 17 646 0 6 c) AED excursion 37 -9 Envelope loss/gain 14723 7683 1250 394 12 a) Infiltration 3370 950 301 85 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 9700 250 Subtotal (lines 6 to 13)18093 18333 1551 729 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 18093 18333 1551 729 15 Duct loads 31%44%5651 8093 31%44%484 322 Total room load 23744 26426 2035 1050 Air required (cfm)Air required (cfm)1167 1167 100 46 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name MASTER BEDROOM M WIC 2 Exposed wall 18.0 ft 8.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft248.0x1.0 ft69.0x1.0 5 Room area 248.0 ft²69.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 112 97 388 212 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 15 0 126 159 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 32 32 128 70 64 64 256 140 11 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.1929.19 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 248 248 222 397 69 69 62 110 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 248 18 684 0 69 8 304 0 6 c) AED excursion -37 -7 Envelope loss/gain 1549 801 622 244 12 a) Infiltration 318 90 142 40 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 2000 250 Subtotal (lines 6 to 13)1868 2891 764 534 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 6 10 0 0 14 Subtotal 1873 2900 764 534 15 Duct loads 31%44%585 1280 31%44%239 236 Total room load 2458 4181 1002 769 Air required (cfm)Air required (cfm)121 185 49 34 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name UTILITY RM ENTRY HALL 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft7.0x7.0 ft7.0x4.0 5 Room area 49.0 ft²28.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.1929.19 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 49 49 44 78 28 28 25 45 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 49 0 0 0 28 0 0 0 6 c) AED excursion -10 -1 Envelope loss/gain 44 69 25 44 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 700 0 Subtotal (lines 6 to 13)44 769 25 44 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 10 17 -25 -44 14 Subtotal 54 786 0 0 15 Duct loads 31%44%17 347 31%44%0 0 Total room load 70 1133 0 0 Air required (cfm)Air required (cfm)3 50 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name GREAT ROOM DINING 2 Exposed wall 20.0 ft 27.0 ft 3 Room height 12.0 heat/coolft 12.0 heat/coolft 4 Room dimensions ft13.0x20.0 ft13.0x14.0 5 Room area 260.0 ft²182.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 240 199 798 436 168 153 613 335 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 15 0 126 159 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 41 0 343 432 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 156 156 625 341 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.1929.19 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 260 260 233 416 182 182 163 291 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 260 20 760 0 182 27 1027 0 6 c) AED excursion -22 -23 Envelope loss/gain 2134 1262 2553 1103 12 a) Infiltration 531 150 716 202 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 300 500 Subtotal (lines 6 to 13)2664 1711 3269 1805 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 1 3 14 Subtotal 2664 1711 3271 1808 15 Duct loads 31%44%832 755 31%44%1022 798 Total room load 3497 2467 4292 2605 Air required (cfm)Air required (cfm)172 109 211 115 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name KITCHEN FOYER 2 Exposed wall 0 ft 6.0 ft 3 Room height 12.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft263.0x1.0 ft9.0x6.0 5 Room area 263.0 ft²54.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 48 28 111 60 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 20 20 223 211 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.1929.19 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 263 263 236 421 54 54 48 86 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 263 0 0 0 54 6 228 0 6 c) AED excursion -38 -20 Envelope loss/gain 236 383 610 338 12 a) Infiltration 0 0 106 30 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 2600 1200 Subtotal (lines 6 to 13)236 2983 716 1568 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 29 51 1 3 14 Subtotal 265 3034 717 1570 15 Duct loads 31%44%83 1339 31%44%224 693 Total room load 348 4374 941 2263 Air required (cfm)Air required (cfm)17 193 46 100 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 2 BEDROOM 2 2 Exposed wall 0 ft 20.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft2.0x9.0 ft151.0x1.0 5 Room area 18.0 ft²151.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 56 56 224 123 11 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 104 89 356 195 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 15 15 126 159 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.1929.19 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 18 18 16 29 151 151 135 242 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 18 0 0 0 151 20 760 0 6 c) AED excursion 0 -19 Envelope loss/gain 16 28 1602 698 12 a) Infiltration 0 0 354 100 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 700 Subtotal (lines 6 to 13)16 28 1956 1498 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -16 -28 15 27 14 Subtotal 0 0 1971 1525 15 Duct loads 31%44%0 0 31%44%616 673 Total room load 0 0 2587 2198 Air required (cfm)Air required (cfm)0 0 127 97 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALL BATH 2 2 Exposed wall 0 ft 5.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x4.0 ft5.0x11.0 5 Room area 24.0 ft²55.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 40 40 160 88 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.1929.19 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 24 24 22 38 55 55 49 88 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 24 0 0 0 55 5 190 0 6 c) AED excursion 0 -6 Envelope loss/gain 22 38 400 170 12 a) Infiltration 0 0 88 25 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 250 Subtotal (lines 6 to 13)22 38 488 445 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -22 -38 102 48 14 Subtotal 0 0 590 493 15 Duct loads 31%44%0 0 31%44%184 218 Total room load 0 0 775 710 Air required (cfm)Air required (cfm)0 0 38 31 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 3.AHU CLST 2 Exposed wall 2.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft2.0x8.0 ft2.0x3.0 5 Room area 16.0 ft²6.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 16 16 64 35 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.1929.19 0 0 0 0 0 0 0 0 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 16 16 14 26 6 6 5 10 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 16 2 76 0 6 0 0 0 6 c) AED excursion -1 0 Envelope loss/gain 154 60 5 9 12 a) Infiltration 35 10 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)190 70 5 9 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -190 -70 -5 -9 14 Subtotal 0 0 0 0 15 Duct loads 31%44%0 0 31%44%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 9 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 BEDROOM 4 2 Exposed wall 32.0 ft 12.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft170.0x1.0 ft12.0x11.0 5 Room area 170.0 ft²132.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 nn 8.408.40 10.5810.58 0 0 0 0 0 0 0 0 .WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 40 40 160 88 0 0 0 0 11 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 120 105 420 230 0 0 0 0 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ss 8.408.40 10.5810.58 15 15 126 159 0 0 0 0 DD 11D011D0 0.3900.390 ss 10.9210.92 10.3410.34 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 96 96 384 210 96 81 324 177 GG 2 glazing, clr low-e 0.3002 glazing, clr low-e 0.300 ww 8.408.40 29.1929.19 0 0 0 0 15 2 126 438 CC 16B-30ad16B-30ad 0.0320.032 --0.900.90 1.601.60 170 170 152 272 132 132 118 211 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 170 32 1217 0 132 12 456 0 6 c) AED excursion -19 250 Envelope loss/gain 2460 939 1025 1076 12 a) Infiltration 566 160 212 60 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 400 550 Subtotal (lines 6 to 13)3026 1498 1237 1686 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 102 48 7 12 14 Subtotal 3129 1546 1244 1697 15 Duct loads 31%44%977 683 31%44%388 749 Total room load 4106 2229 1632 2446 Air required (cfm)Air required (cfm)202 98 80 108 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-29 14:43:47 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 10 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Right-J® Worksheet AUGUST 26, 2020Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name CLST 4 2 Exposed wall 0 ft 3 Room height 8.0 heat/coolft 4 Room dimensions ft9.0x2.0 5 Room area 18.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 .G 2 glazing, clr low-e 0.300 n 8.40 10.58 0 0 0 0 .G 2 glazing, clr low-e 0.300 n 8.40 10.58 0 0 0 0 .W 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 11 W 13A-4ocs 0.143 s 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.300 s 8.40 10.58 0 0 0 0 D 11D0 0.390 s 10.92 10.34 0 0 0 0 W 13A-4ocs 0.143 w 4.00 2.19 0 0 0 0 G 2 glazing, clr low-e 0.300 w 8.40 29.19 0 0 0 0 C 16B-30ad 0.032 -0.90 1.60 18 18 16 29 F 22A-tph 1.358 -38.02 0.00 18 0 0 0 6 c) AED excursion 0 Envelope loss/gain 16 28 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains:Occupants @ 230 0 0 Appliances/other 0 Subtotal (lines 6 to 13)16 28 Less external load 0 0 Less transfer 0 0 Redistribution -16 -28 14 Subtotal 0 0 15 Duct loads 31%44%0 0 Total room load 0 0 Air required (cfm)0 0 2021-Apr-29 14:43:51 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE GARAGE RIGHTJob:Duct System Summary AUGUST 26, 2020Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information FY 839 SPEC HOUSE, SYNERGY HOMESFor: 113 LIMA COURT, PORT ST LUCIE, FL 34983 CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1167cfm1167 Total effective length (TEL)ft163 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk 95.04.5VlFx0x05.01.0003138775hBATH 2-A 95.012.1VlFx0x07.01.000971272587hBEDROOM 2 95.09.2VlFx0x07.01.000982024106hBEDROOM 3-A st1115.029.8VlFx0x07.01.000108802446cBEDROOM 4 st1115.029.8VlFx0x07.01.0001152114292hDINING st2115.037.2VlFx0x07.01.000100462263cFOYER st1115.032.1VlFx0x07.01.0001091723497hGREAT ROOM st1115.034.3VlFx0x07.01.0009792187cKITCHEN st1115.026.2VlFx0x07.01.0009792187cKITCHEN-A st2115.048.3VlFx0x06.01.000461002035hM BATH st2115.037.0VlFx0x05.01.00034491002hM WIC st2115.047.5VlFx0x08.01.0001851214181cMASTER BEDROOM st2115.032.6VlFx0x06.01.0005031133cUTILITY RM Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 480 525 1.000 669 12.0 0x0 VinlFlx st2 Peak AVF 320 415 1.000 528 12.0 0x0 VinlFlx 2021-Apr-29 14:43:51 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 ...cumnets\Wrightsoft HVAC\FY 839 SPEC-LIMA CT.rup Calc = M J8 Front Door faces: NE Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 11670 1167 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������