HomeMy WebLinkAboutFire sprinkler designSPRINKLER RISER
(SSE DETAIL THIS SHT.)
SPRINKLER PIPING PLAN 1st. FI.
SCALE: 3/16" = 1 °-011
GENERAL NOTES
1.) ALL WORK TO CONFORM TO NFPA-13R AND LOCAL AUTHORITIES HAVING JURISDICTION.
2.) SPRINKLER RISER PIPING TO BE SCH. 10 WITH GROOVED ENDS AND GROOVED
FITTINGS.
3.) ALL CONCEALED PIPING FEEDING UNITS SHALL BE CPVC WITH SLIP FITTINS AND
RESIDENTIAL SPRINKLERS.
4.) ALL AREAS SHALL BE SPRINKLED:
EXCEPTION-1.SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS UNDER 55sq.ft.
EXCEPTION-2.SPRINKLERS SHALL NOT BE REQUIRED IN CLO., LINEN CLO., OR PANTRIES
WITHIN THE DWELLING UNIT WHERE THE AREA DOES NOT EXCEED 24sq.ft.
EXCEPTION-3.SPRINKLERS SHALL NOT BE REQUIRED IN ANY GARAGES, PORCHES,
BALCONIES, CORK. AND OR STAIRS THAT ARE OPEN AND ATTACHED.
EXCEPTION-4.SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS OR CRAWL SPACES
THAT ARE NOT USED OR INTENDED FOR LIVING PURPOSES.
5.) HANGERS TO BE LISTED AND APPROVED TWO HOLE STRAPS FOR CPVC PIPING
SPRINKLER PIPING PLAN 2nd. FI.
GAUGE 0 " -"W*- 1`WATERFLDWALARM SWITCH
DRPoN VALVE WWI
1 INCH FIGURE 519 RISER MAMtFOL❑
SCALE: 3/16" = V-011
"" "A FIRE
(92A m 1 I SPRINKLER
DRT, 1' NPT
�1a'
(S2.6ImmJ
VlI0
OMESTIC 8-9116'
PORT. I f2aB.o mml
1' NPT
{-15116'
(125.i mm1
WATER
SUPPLY I
PORT. VNPT ,6N mmy
MODEL REV.1 1' 7YC0 RESIDENTIAL DOMESTIC SHUTOFF VALVE
SPRINKLER PIPING PLAN 3rd. FI.
SCALE: 3/16" = 11-0"
CONCRETE DECK
HILTI PIN --' � `
CPVC PIPING
\\\PIPE STRAP
PER PIPE MANUFACTURES SPEC
TWO HOLE PIPE STRAP
r� 43
6" ELEC. BELL
3
SUPPLY TC SPRINKLERS
1' RISER MANIFOLD
fSEE DETAIL THIS SHT
SUPPLY TO DOMESTIC
1" DOMESTIC SHUTOFF /
(SEE DETAIL THIS SHT )
MAIN OL
t METER
GV ��
Hydraulic Information
OCCUPANCY CLASSIFICATION
Residential
DENSITY
0.050gpm/ft2 for 1500.00ft2 (Actual 392.37ft2)
TOTAL HEADS FLOWING
2
K-FACTOR
4.9
TOTAL WATER REQUIRED
26.44
TOTAL PRESSURE REQUIRED
42.877
SAFETY MARGIN (psi)
+22.123 (34.0%)
PIPING TO EXISTING SYSTEC
NEW CEILING
VIKING CONCEALED SPRINKLER OR
48 _ TYCO 1/2", CONCEALED PENDENT SPRINKLER
SERIIES LFII WHITE PENDENT, K=4.2, 155 DEGREE
REV. #
DATE
DESCRIPTION
DATE: 4-23-19
SIME Residence
(At WaterSong�it
4940 Wate rson way,
g �'
Fort Pierce FL 34949
��
,-,--;,�,�, ��adlf
r'L I /IjV
�- ',
; •
''��'` `• �; �� f �f/r'f v/� �(i%��l��v� ��`��: lyloC�'iyr►r � rlja'��r.�'aril
l f
SPRIHKL R ERVICES
FIRE SPRINKLER
4-23-19
FIRE SPRINKLER PIPING PLAN AND DETAILS
JOB NUMBER: S120C19
DRAWN BY: Shelly Schuyler
SHT. 1 OF 1
SCALE: 3/1611= 11-011