Project Information
Project Summary Job: wri htsofte ro� � Date: MARCH 2, 2021 9 Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM For: Notes: Pro'ect=lnformation PORTER MODEL- CUSTOM, RODNEY HALL 11771 APPALOOSA COURT, FORT PIERCE, I Weather: Fort Pierce, FL, US Winter Design Conditions Outside db 42 OF Inside db 70 OF Design TD 28 OF Heating Summary Structure 24867 Btuh Ducts 6819 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 31685 Btuh Infiltration Method Construction quality Fireplaces Simplified Average 0 Heating Cooling Area (ftZ) 2379 2379 Volume (ft3) 25310 25310 Air changes/hour 0.32 0.16 Equiv. AVF (cfm) 135 67 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual air flow Airflow factor Static pressure Space thermostat 100 EFF 7.7 kW 26289 Btuh 1317 cfm 0.042 cfm/Btuh 1.00 in H2O APR 19 , Permitting Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 21127 Btuh Ducts 9708 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturers data n Rate/swing multiplier 0.95 Equipment sensible load 29293 Btuh Latent Cooling Equipment Load Sizing Structure 2819 Btuh Ducts 2642 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 5461 Btuh Equipment Total Load (Sen+Lat) 34754 Btuh Req. total capacity at 0.70 SHR 3.5 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond 24ACC442AO0300 Coil FB4CNF042L AHRI ref 9509434 Efficiency 11.5 EER, 14 SEER Sensible cooling 27650 Btuh Latent cooling 11850 Btuh Total cooling 39500 Btuh Actual air flow 1317 cfm Air flow factor 0.043 cfm/Btuh Static pressure 1.00 in H2O Load sensible heat ratio 0.85 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. y -Fk- wrightsoTt® 2021-Mar-02 10:48:39 Right-yu'de� .tlfliw.ISal,2f111_�17 f1.4� R:$SkaS101 Rc��-••�M �'� ...HVAC\PORTER MODEL MOD (W ICY)- APPALOSSA CT.rup Cale = MJ8 Front Door faces: N wri htsoft° Ri ht-M Worksheet Job: 9 g Date: MARCH 2, 2021 Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name Egrosed wall Room height Room dimensions Room area Entire House 226A ft 10.6 ft d 2379.0 ft' BEDROOM 2 26.0 ft 9.3 ft heat/cool 14.0 x 12.0 ft 168.0 ft' Ty Construction number U-value (Btuh/ft2_ F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool 6 11 13F-7.5fcs 2 glazing, Or lower . 2 glazing, Or lgwn e 2 glazing, dr low-e 11130 13A-7.5fcs 2 olazina. clr low-e 13A7.5fcs 2 glazing, Or low-e 2 glazing, Or low-e 2 glazing; Or low-e 2 glazing, clr low-e 13A 7.5fcs " " 2 glazing, .cir low-e 2 glazmg driowLe_.._ . 11D0. 13A-7.5fcs 2 glazinq, clr low-e 16X19.Oad 1713-13al 0.083 0:656 0 650 0.650 0.390 0.083 0.650 0.083 0.650 0.083 0.650 0.650 0.650 0.083 0.650 0.650 0390 0.083 0.650 '0.408 0.105 0.989 n " n ' n n h ne ne a 6, s s s s w w.- :.w .-w nw nw - - - 232 18.20 18.20 18.20 10.92 232 18.20. 232 18.20' 232 18.20 18.20 18.20 . '232 ' 18:20 18.20 10.92 232 18.20 1.59 2.94. 27.69 ;_ 1.31 . 14.99 14.99 10.69 11.31 1.31 17.04 .1.31 33.77 1.31 14.99 14.99 14.99 1:31 33.77 33.77 11:31 1.31 17.04 .' 1.49 4.57 . 0.00 493 30 20 15 48 39 14 " 4 636 32 30 41 505 15 16 24 39 14 177.1 750 2.379 380 0 0 ` 0 48 25 0 489 . 0 533 32 30 41 .449 0 . ' .:. 0 24 25 0 1771 7.50 226 883 546 364 273 - 524 59 258 ..113.6 ' . 73 1240 582 546 743 1043 291 .291 262 59 258 2809 2204 ' . 6270 498 450 .300 160 - 543 33 . 241 641 . - 135 700 480 450 612 589 540 540 271 33 241 `2632 3424 0 0 0 0 0 0 0 0 112 0 130 16 0 0 • . 0 0 .-" D 0 0 0 168 0 168 0 0 0" 0 0 0 0 . . 112: ' : 0 114 16 0 0 0 0 .:. _. D 0 0 0 168 0 .. 26 0 0 0 0 0 0 0 259 - 0 265 291 0 0 0 0 0 0 0 0 266" 0 720 0 0 0 0 0 0 0 " 146 0 150 240 0 0 0 . 0 - " :0 0' 0 0 250 0 0 t-G T-G49.3 Vh13A-7.5fcs V�/ Y-f C C IF22A-tpl 6 c)AED excursion 0 -90 Envelope loss/gain 20713 13514 1802 756 12 a) Infiltration b) Room ventilation 4154 0 1113 0 455 0 122 0 13 Internal gains: Occupants @ 230 Applianceslother 0 0 6500 0 0 750 Subtotal (lines 6 to 13) 24867 21127 2258 1628 14 15 Less a)demal load Less transfer Redistribution Subtotal Duct loads 27°/u 46% 0 0 0 24867 6819 131685 0 0 0 21127 9708 27 0 460/6 0 0 92 2350 644 0 0 40 1667 7fi6 Total room load Air required (cfm) T 1317 3835 0 1317 2994 124 2433 104 ACCA Of ...WAC%PORTER MODEL MOD (W ICY)- APPALOSSA CT.rup Cale = MJ8 Front Door faces: N wri htsoft° Ri ht-J® Worksheet Job: g 9 Date: MARCH 2, 2021 Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@,AOLCOM 1 Room name CLST 2 BATH 2 3 Exposed wall Room height 20 ft 9.3 ft heat/coal 6.0 ft 9.3 ft heat/cool 4 Room dimensions 10.0 x 2.0 ft 10.0 x 6.0 ft 5 Room area 20.0 ftZ 60.0 ft2 Ty Construction number LI-value (Btuh/ft2-°F) Or HTM (Btuhfft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat I Cool Grass I N/P/S Heat Cool 6 13A-7.5fcs 6.083 n -232 - 1.31 0. 0. 0 :.. 0' 0 0 0 0 0 0 0 0 2 glazirg,.dr low-e 0.650. n 18.20 14.99 .0. 0. 0: 0 0 0 2slazing, cir low=e 0.650 n 18:20' 14.99. 0 0 .. 0 0 0 0 2glazing;-drlbw-e 0.650 n'. 1820 10.68 0 0 -.0. 0 6 0 p 0 0 0 11 11D01 0.390 n 10.92 11.31 0 0- 0. 0" 0 0 yJ 13A-7.5fcs 0.0B3 ne 232 1.31 0 0 6 0 0 0 0 0 0 0 0 L--G 2 alazina.. clr Iow-e. 13A•7.5fcs w 0.650 0.083 ne a 18.20 232 _ 17.04 1.31.. 0 19 0 19. 0 43 p 24 0 56 52 120 6B V�J t G 2 glazing, cir low-e 6.650 a '18:20 3377 0 0 0 0 4 0 73 135 0 13A•7.5fcs 0.083 s 232 1.31 0 0 0 0 0 0 D 0 2glazing, clrlow-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 0 2 glazing, cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 0 2 glazing, cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 13A 7.5fcs . - 0.083 w 232 1.31 - 0 ` . 0 -0 0 , 0 0 0 0 . 0 0 2 glazing, cir lower 0.650 w 18.20 33.77 0 0 0 0 2 glazing, cl� lower . ` 0.650 ;w:. 18:20 _ 337E :, . 0. .... , . 0 0 . _ .: 0 0 .:... 0 0. _ 0 0 ... ..0. 0 11DO 0:390 w 10:92 1131 0 0 0 0 0 0 0 0 0 V)I 13A-7.5fcs 0.083 nw 232 1.31 0 0 0 0 0 0 0 0 t---G C 2 glazinq, cir low-e 16X19-0ad 0.650 0.408 nw ' - 18.20 1.59 17.04 1.49 0, 20 0 20 0 32 0 30 . 60 60 95 89 C 1713-6al 0.105 - 2.94 4.57 0 0 0 0 0 0 0 0 F 72AApl . 0.989 : - 27.69 I 0.00 20 2 55 ` . 0 60 6 166 0 6 c)AM excursion -1 -2 Enniope loss/gain 130 53 454 290 12 a) Infiltration 35 9 105 28 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 300 Appliances/other 0 Subtotal (lines 6 to 13) 165 62 560 618 Less extemal load 0 0 0 0 Less transfer 0 -165 0 -02 0 97 0 44 Redistribution 0 0 656 662 14 15 Subtotal Duct loads 27% 46% 0 0 270/6 46°/u 180 304 Total room load 0 0 0 0 836 35 966 41 Air required (cfm) all J 8th Ed 2021-Mar-02 10:48:39 ...HVACIPORTER MODEL MOD (NI ICY)- APPALOS-SA CT.rup Calc = Md8 Front Door faces: N wrightsoft° Ri g ht-J@ Worksheet Job: Date: MARCH 2, 2021 Entire House By. QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOLCOM 1 Room name BEDROOM 3 HALL 2 3 Exposed wall Room height 27.0 ft 9.3 ft heat/cod 0 ft 9.3 ft heaticoal 4 Room dimensions 1.0 x 179.0 ft 4.0 x 8.0 ft 5 Room area 179.0 ft2 32-0 W Ty Constriction U-value Or HTM Area (ft-) Load Area W) Load number (Btuh/ftZ °F) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Coal Gross N/PIS Heat Cool Grass N/P/S Heat I Cool 6 13A-7.5fcs 0.083 n 232 1.31 130 110 255 145 ' 0 0 '. 0 0 0 2 glazing, dr low,e 0.650 ..n 18.20 14M - 0 0 0 . 0 0 - 0 0 0 2 glazing, clr low-e 0.650 n _ 18.20 .14.99 20 0 364 300 0 0 0 2glazing,:drlow�. 0:650 - n. 18:20 .: . 10.68 0 0. 0 0. 0 0 0. 0 11 11D0. 0.390. n 10.92 11:31 0 0 - 0 0 0 0 0 0 V�J t-G. 13Ar7.5fcs 0.083 ne 2.32 1.31 0 0 0 0 0 0 0 0 0 2 clazina, clr low-e 0.650 . ne. 16.20 17.04 0 0 0 0 0 ' 0 -0 0 0 0 �N 13A-7.5fcs 0.083 e - 2-32 1.31 121 12t . 281 .: 159 0 T---G .2 glazing, dr lower - 0.650 � e 18.20 3377 _ 0 0 0 0 0 0 0 0 0 13A-7.5fcs 0.083 s 2.32 1.31 0 0 0 0 0 0 0 --G 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing, dr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 0 �I--CG 2 glazing, clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 13A-1.5fcs 0,089 W 232 1.31 0 0 0 0 0 0 0 6 0 2 glazing clr low- 0:650 w 18.20 . 33.77 0 0 0 0 0 0 0 2glazmg ,drloW�...._. O.BSD :w.:. . 1&20 , 33.77- '. 0 0 ._ . 0 0 0 3... . 0'. 0 0. 0 91D0 0.390 w- 10.92 11.31 0 0 0 0. 0 0 0 0 W 13Ar7.5fcs 0.083 nw 2-32 1.31 0 0 0 0 0 0 0 2 glazinq, clr lower 0.650 nw 18.20 17.04 0 0 0 0 0 0 0 51 0 48 C 16X1 O408 - 1.59 1.49 .179 179 284 266 32 32 - C 17&M 0.105 . - 2-94 4.57 0 0 0 0 0 0 0 0 F 22A-tpl. 0.989 - 27-69 :' 0.00 179 . 27 748 0 32 0 0' 0 6 c)AED excursion -29 -1 Envelope loss/gain 1933 840 51 47 12 a) Infiltration 473 127 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 600 0 Subtotal (lines 6 to 13) 2405 1567 51 47 Less external load 0 0 0 0 Less transfer 0 13 0 14 0 -51 0 -47 14 Redistribution Subtotal 2419 1580 0 0 15 Duct loads 27% 46%1 663 726 27% 46% 0 0 Total mom load 3082 2307 0 01 0 0 Air required (cfm) 1281 98 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ F}t- wrigF�tsoft ^ 2021-Mar-02 10:48:39 -Fage -' '��..HUACIPORTER MODEL MOD (W lCY)- APPALOSSA CT.rup Calc = Md8 Front Door faces: N -�- wrightsoft° Right-JO Worksheet Date: Entire House Date: MARCH 2, 2027 By: QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOLCOM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area WIC 3 O ft 10.5 ft heaticool 6.0 x 5.0 ft 30.0 ftz AN O ft 11.6 ft heat/cool 3.0 x 5.0 ft 15.0 ft' Ty Construction number U-value (Btuh/Wz-°F) Or HTM (Btuhtftz) Area (ft-) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross WP/S Heat Cool 6 11 13Pr7.5fcs 2 glazing, cir low-e . 2 glazing, clr low-e 2 glazing, cir lower 11DO 13A-7.5fcs 2 alazina. clr low-e 13A 7.5fcs . • . - Zdaziri' .clrlow-e 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, cir low-e 13Pr7.5fcs 2 glazing, clr low-e 2.91azirg, :.cir lower :' .. ' 11DO 13A-7.5fcs 2 giazinq, cir low-e 16X19-Oad 17B-6al 22A3p1 0.083 0.650 0.650 0.650 0.390 O.OB3 0.650 M083 0.656 0.083 0.650 0.650 0.650 0.083 0.650 . ... 0.650 0.390. 0.083 0.650 0.408 0.105 "0.989 .n . n n . n n ne ne •e a s s s s w. W. _w'.: w nw nw = - - 232 18.20 18;20 18.20 10.92 232 1 B.20 232 18.20 232 18.20 18.20 18.20 232 18.20 18 20 .10.92 232 18.20 1.59 294 I 27:69 1.31 .14.99 14.99 10.66 11.31 1.31 17.04 1.31 33.77 1.31 14.99 14.99 14.99 .1.31 33.77 33r77 11.31 1.31 17.04 1.49 4.57 O.OD 0 ` 0 ` 0 0 0 0 0 0 0 0 0 0 0 0 .. 0 [) 0 0 0 15 19 30 0 0 0 0. 0 0 0 ' 0 0 0 0 0 0 0 0 .:. D 0- 0 0 15 19 " 0 0 0 0' 0 0 0 0. 0 0 0 0 0 0 0 0 _.. ; 0 0 0 0 24 55 -0 0.' 0 0 0` 0 0 0 0 0 0 0 0 0 0: 0 0 O 0 0 22 86 0'- 0 0. 0 0 0 0 0 0 0' 0 0 0 0 0 0 .... _ .., .0 0 0 0 c. 0 19 15 a 0 0 0 0 0 0 0 .0 0' 0 0 0 0 0- -.0 :. 0 0 0 0 0 19 0 0 " .0: 0 0 0 0 0 0 0 0 0 0 0 0 0 . 0 0 0 0 0 54 0 0 0 0 0 0 0 0 0 0' 0 0 0 0 0 0 0. 0 0 0 0 85 0 vrJ I--G W Lam_• C C F 6 c)AED excursion -2 -2 Envelope loss/gain 79 1061 54 83 12 a) Infiltration b) Room ventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6to 13) 79 106 541 83 14 15 Less wdemal load Less transfer Redistritxrtion Subtotal Duct loads 27% 46% 0 0 36 115 31 0 0 50 156 71 270/6 46% 0 0 -54 0 0 0 0 -113 0 0 Total room load Air required (crm) 146 6 22-71 10 0 0 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. +#F- wrightsoft� 2021-Mar-0210:48:39 _.-ds. =m_ ...�... --.1:..._ ��-___--.tee. -r-vc^rc^-v-.m-.s.-a+ss-m-s.- :c. roux_ -.-.•.-...- --------_'_'_'----'.:a AG �A rtlyui= W�emi uiuvnaai cuz, c,:u:'vc'n w.,,u, Page-4 ...HUAC\PORTER MODEL MOD (W ICY)- APPALOSSA CT.rup Calc = Md8 Front Door faces: N FF wri htsoft® Ri ht-J® Worksheet Job: 9 g Date: MARCH 2, 2021 Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name E)q)osed wall Room height Room dimensions Room area CLST 4 0 ft 10.1 ft heaUcool 1.0 x 17.0 ft 17.0 ft' BEDROOM 4 21.0 ft 9.3 ft heaticod 1.0 x 149.5 ft 149.5 ft' Ty Construction number U-value (Btuh/ftz-°F) Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ft') or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 . 13A 7.5fcs 2 glazing, _ cir low-e 2glazirig, clr.louv a 2 glazi ng,.dr lower 11D0. 13A•7.5fcs 2 alazina, clr low-e 13A 7:5fcs . ; 2 glazing, cir iow-e 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing; clr lowb 2 glazing clr lower ...: 11D0 13A 7.Sfcs 2 glazirq, clr lower 16X19-0ad 17B-6al API- 0.083 0.650 0.650 0.650 0.390 0.083 0.650 0.083 0.660 0,083 0.650 0.650 0.650 0:083 0:650 0.650 0.39D 0.083 0.650 0.408 0.105 0-989 ::n .. ' n n . n'` n ne ne a ie s s l s s .. w .w'. .w.. w nw nw -. - - 232 18.20. 1.8,20 18.20. 10.92 232 18.20 232 18.20 232 18.20 18.20 18.20 232 18.20. 18.20 ` 10.92 232 18.20 1:59: 2.94 27:69 1.31 14.99 . '14.99 10.68 11.31 1.31 17.04 1.31 33.77 1.31 14.99 14.99 14.99 1.31 33.77 33.77 11.31 1.31 17.04 ' 1.49 4.57 . ' - 0.00 0 0 0 , : 0 0 0 0 0 Q 0 0 0 0 0 .0 0 0 0 0 11 7 - 17 , 0 0 0 0 0 0 0 0 0 0 0 0 0 _ 0 0 0 0 0 0 11 71 ' . OI . 6 0 0 0 '' 0 0 0 0 0 0 0 0 0 : . 0 0 0 0 0 0 '. , 18 21 : ... ':0 0 0. 0 _. 0 0 0 0 -0: 0 0 0 0 0 0 0 0 0 0 0 17 33 0 112 30 0 0 0 0 0 :41 :.. 0 0 0 0 0 .. .: 37 0 ., 0 0 0 0 ' . 148 2 150 62 - ` 0 0 ' 0 0 0 p_ 47 - 0 0 0 0 0 37 0. .. 0 `: p 0 0 148 2 :. ` 21 190 546 0.. 0' 0. 0 0 . 108 0 0 0 0 0 86 0 .. 0 0 0 0 234' 6 582 107 450 0 0 0 0 0 61. 0 0 0 0 0 49 0 _: -0. 0. 0 0 220 - _ 10 p yJ I--G , 1G Vh13A-7.5fcs'-. VjJ t---G C C F - 6 c)AED excursion -1 -29 Envelope loss/gain 39 49 1752 867 12 a) infiltration b) Room ventilation 0 0 0 0 368 0 99 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 1 600 Subtotal (lines 6 to 13) 39 49 2120 1566 14 15 Less eMemal load Less transfer Redistribution Subtotal Duct loads 27% 46°/, 0 0 39 0 0 0 0 49 0 0 27% 461/6 0 0 22 2142 587 0 0 27 1593 732 Total room load Air required (cfm) 0 0 0 0 2729 113 2325 99 CA to Of 2021-Mar-02 10:48:39 ...WAMPORTER MODEL MOD Mf ICYY APPALOSSA CT.rup Calc = Md8 From Door faces: N +1:1- wrightsoft, Right-.)® Worksheet Job: Date: MARCH 2, zozl Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM 1 2 3 4 5 Room name E)posed wall Room height Room dimensions Room area FOYER 12-0 ft 9.8 ft heaVcool 1.0 x 145.5 ft 145.5 ft2 KITCHEN 0 ft 13.6 ft heaticool 1.0 x 159.0 ft 159.0 ftz Ty Construction number U-value (Btuh/ftZ-°F) Or HTM (Btuh/ft2) Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 13A,7.5fcs : 2 glazing, dr lower 2•glazmg; dr lovv a .2gg1 ing,;drloww-e 1100 13A7.5fcs 2 alazino.. clr low-e 13A7.5fis;" .; 2glazing, -clr low-e 13A7.5fcs - 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, cir low-e 13A7.5fcs 2 glazing, clr lower. 2 glazing,' cir low-e 11D0 13A7.5f. s 2 glazirq, clr low-e 16X19-0ad 17B3a1 22A4p1 0.083 0:650 0.650 0.650 0.390 0.083 0.650 0.083 0.650 0.083 0.650 0.650 0.650 0.'083 0.650 -0.650 0.396 0.083 0.650 a4D8 0.105 0.989 w. n ` ' n n n ',n ne ne -- a a s s s s w w W : w nw nw '- .'_ 232 18.20 ' 18.20 18.20 10.92 232 18.20 232 18.2.0 232 18.20 18.20 18.20 232 18 20 18,20 10.92 232 18.20 - A.59 2.94 27.69 1.31 . 14.99 . 14.99 10:68 11.31 1.31 17.04. -: 1.31. 33.77 1.31 14.99 14.99 14.99 1.31 33.77 33.77 11.31 1.31 17.04 1.49 4.57 0.00 . 112 0 0 : 6 48 0 0 0- _ .0 0 0 0 0 ...0 0 : ' 0 0 0 0 111 42 146 64 0 p 0 ' 48 0 0 0 0 0 0 0 0 0 0 0 0 0 0 111 42 .' 12 ' 148 0 0 0 524 0 0 0 0 0 0 0 0 0 0 ".. - 0 0 0 0 176 124 332 83 0 0 0 ` 543 0 0 .' 0' 0 0 0 0 0 0 0 ._ 0 0: 0 0 165 193 0 D 0 0 0 0 0 0 0 0 0 0 0 0 0 r 0 0 0 0 0 51 133 159 0 0 0 ,' 0 0 0 0 0 0 0 0 0 0 0 .0 :..:.: 0 0 0 0 51 133 0 ' 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ...0 0 0 0 81 391 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ..:0 0 0 0 76 807 0 - VN I---G �j -G WWWW V�/ L_..G C C F 6 c)AED excursion -19 31 Envelope loss/gain 1305 965 472 653 12 a) Infiitration b) Room ventilation 210 0 56 0 0 01 0 0 13 Intemai gains: Occupants @ 230 Appliances/other 0 0 0 0 0 1000 Subtotal (lines 6 to 13) 1515 1022 472 1653 14 15 Less a)demal load Less transfer Redistribution Subtotal Duct loads 27% 469/6 0 I 0 21 1536 421 0 0 32 1054 484 270 46% 0 0 0 472 129 0 0 0 1653 759 Total room load Air required (cfm) 1957 81 1538 66 601 25 2412 103 Calculations awroved bvACCA to meet all requirements of Manual J 8th Ed. fj.F- wricar,tsos�- 2021-Mar-02 10:48:39 n.u-uz"rcsuu8105 age 6 - �� ...WAC%PORTER MODEL MOD (W ICY) APPALOSSA CT.rup Calc = Md8 Front Door faces: N -►� wrightsoft° Right-M) Worksheet Job: Entire House Date: MARCH 2, zoz, By: QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS AOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area M. BEDROOM 34.0 ft 10.4 ft heaticool 17.0 x 17.0 ft 289.0 ftz M. WIC 0 ft 9.7 ft heat/cool 6.0 x 6.0 ft 36.0 ftZ Ty Constriction number U-value (Btuh/ftz °F) Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 13A-7.5fcs , .. 2 glazing, cir lower 2-glazing,, clr laws 2.glazing, cIr IcW-e . '11130 13A-7.5fcs 2 alazino. clr low-e 13X7.5fcs_ 2 glazing, clrlow-6. 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 5tcs. 2 glazing; :clr lower 2 glazmg;.clr lower ': 11D0 13A-7.5fcs 2 glazinq, clr low-e 16X19-0ad 17B-6al 22A 01' 0.083 0.650 0.650 0:650 U90 0.083 0.650 . 0.083 0.650 0.083 0.650 0.650 0.650 0.083 0.650 DZ50 0.390 0.083 0.650 0.408 0.105 0.989 ' n n n n. . n ne ne ': . e s s s s w . w -:Vv : w nw nw ' ` - - .. - 2-K 18.20' 1820 18.20 10.92 232 18.20 . 232. 1a.20 232 18.20 18.20 18.20 232 18.20. 18.2D 10.92 232 18.20 1.59 2.94 27.69 1.31 .14.99 14.99 10.68 " 11.31 1.31 17.04 1.31 33.77 1.31 14.99 14.99 14.99 1.31 33.77 3377 11.31 1.31 17.04 1.49 4.57 0.06 D D 0 ' .0 . 0 0 0 ".. 0 0- 170 16 0 0 170 16 _ D 0 0 0 23B 63 ` 289 0 0 . 0' : 0 0 0 0 ;.., 0.. 0 154 16 0 0 154 • 0 0 0 0 0 238 63 34 0 0 0 .0 0 0 0. 0 0 358 291 0 0 358 291 _ _ 0 0 0 0 377 185 942 0 0 .; 0 0 0 0 0 0 ' 0 202 240 0 0 202 540 - _. , . D 0 0 0 354 287 0 0 0 0' 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 30 7 .36 0 0 0 . 0 0' 0 0 0 0 0 0 0 0 0 .0. .: . ': . A 0 0 0 30 7 0 0 0 0 0 0 0 0 .. 0 0 0 0 0 0 0 0 0 0 0 0 48 22 .. 0 0 0 0 w .0 ' 0 0 0 ' .., 0 0 0 0 0 0 0 0 .._D 0 0 0 45 34 0 VN I- G T-Ge vh13A-7.5fcs Vh13A-7 Val L- G C C F ' 6 c)AED excursion 116 -1 Envelope loss/gain 2802 1942 69 77 12 a) Infiltration b) Room ventilation 640 0 172 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 400 0 0 0 Subtotal (lines 6 to 13) 3442 2513 69 77 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 27% 46% 0 I 0 0 3442 944 0 0 0 2513 1155 27% 46 0 0 0 0 69 19 0 0 0 77 35 Total room load Air required (cfm) 4386 182 3668 157 1 88 4 112 5 Calculations rements ...HVACIPORTER MODEL MOD (W (CY)- APPALOSSA CT.rup Cato = MJ8 Front Door faces: N - - wrightsoft' Right-M Worksheet Job: Entire House Date: MARCH 2, 2021 By: QUICK CALCS, INC. 317 ST. LUCIE LN.. FORT PIERCE. FL 34946 Phone: 7724666799 Fax: 7724666796 Email: QUICKCALCS c(AOL.COM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area LAUNDRYROOM O ft 9.3 ft heat/cool 1.0 x 68.0 ft 68.0 ft' M.TOILIFT O ft 9.3 ft heat/cool 3.0 x 5.0 ft 15.0 ft' Ty Construction number U-value (Btuh/ftz°F) Or HTM (Btuh/ft') Area (ft') or perimeter (ft) Load (Btuh) Area (" or perimeter (ft) Load (Btuh) Heat Cool Gross WKS Heat Cool Gross N/PIS Heat I Cool 6 11 V1 13A•7i5fcs 2,glazing,:clrlowe 1 2: l Ong, 'cir low-e 9 2glazing,:ciflow-e' 11 D0 13A 7 5fcs 2 olazma clr low-e . 13P 7 5frs.. 2'glazing; cirlow4 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr law-e 2 glazing, clr lower 13X7.5Fcs 2 glazing .clr low-e 2 glazing _cJrJow a-. i1p0 13A-7.5fcs 2 glazing,. clr low-e 16X1906d a 176-6al MPAT. - 0.083 A650 0.650 0.650 0.390 0.083 0.650 0:083 0:650 0.083 0.650 0.650 0.650 0.083 0.65D 0.650 039D 0.083 0.65D 0.408 0.105 0.989 . n . n n, n n ne ne e- - e ' s s s s _, w w .w.. -w nw nw - - - ' . -: 232 '18.20 18.20 18.20 10.92 232 18.20 232` 18.20 232 18.20 l 18.20 18.20 232 18.20 1820 10.92 2.32 18.20 1.59 294 27-69 1.31 14.99 14.99 10.68 11.31 1.31 17.04 1.31 33.77 1.31 14.99 14.99 14.99 1:31 33.77 33.77 11.31 1.31 17.04 1.49 4.57 '` 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 A 0 0 0 68 0 .: 68 0 0 0 OI 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 68. 0 6 0 0 0 0 0 0 0 A - 0 0 0 0 0 0 ..... 0 0 0 0 '108 0 . :0 0 0 U- 0 0 0 0 0. 0 0 0 0 0 0 0 0 0 0 ' `101 0 .. 0 0. 0' 0 9 0, 0 0 0. 0 0 0 0 0 0 0 0.. 0 0 ., 15 0 _ .. 15 0 .. D. 0 0'. 0 0 0. _:.. 0 . 0, 0 0 0 0 0 0: 0 0 0 ". 15 0 . . -. 0 0 0 0 0 0 0 0 0 : 0 0 0 0 0 0. 0 0 0 0 24 0 6. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 22 0 .0 - ���--DDD yJ I Ga �1 �---G llJ G, C ., C F 6 c)AED excursion -14 -6 Envelope loss/gain 108 87 24 16 12 a) Infiltration b) Room ventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 650 0 0 300 Subtotal (lines 6to 13) 108 737 24 316 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 27% 46% 0 0 0 108 30 0 0 0 737 339 27% 461/6 0 0 0 24 7 0 0 0 316 145 Total room load Air required (cfm) I I 137 6 1076 46 30 1 462 20 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wr�ghtsoYCO 2021-Mar-02 10:48:39 '�- �•��RI nt JLII�'u�IVLISSr Luf c�:v: V IG7iJUo H!� AC-i✓A 9 gag--e 8���. ...WACIPORTER MODEL MOD (W ICY} APPALOSSA CT.rup Calc = MJB Front Door faces: N f-1- wrightsoft° Right,J® Worksheet Job: Entire House Date: MARCH 2, 2021 By: QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOLCOM 1 Room name M. BATH GREAT ROOM 2 F)posed wall 12.0 ft 28.0 ft 3 Room height 9.3 ft heaticod 14.0 ft heat/cod 4 Room dimensions 1.0 x 117.0 ft 1.0 x 428.0 ft 5 Room area 117.0 ft2 428.0 ft2 Ty Construction number Ll-value (Btuh/ft2--°F) Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat I Cool 6 �-G 13A-7.5frs . 2 glazing,'cir lower 2 glazing, clrlowme. 0.083 0.650 0.650 h . :n n 2.32 18:20 18.20 1.31 _ 14.99 14:99 0 0 0 0 0 0 0 0 0' 0- 0 0 0 0 0 0 0 0. 0 0 0 0 0 0 11 2 glazing, ctr lower . 11 D0 ' 13A-7.5fcs 2 olazino. cir low-e 13X7'5fcs; 2 glazing; clr low -el ' ' 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, clr low-e 13A•7 5fcs 2laze g ng,:clrlow-e -0650 0.390 0.083 0.650 0.083 0:650 0.083 0.650 0.650 0.650 0.083 0.650 . n` . n ne ne . e a s s s s - w. w 1820 1 10:92 232 18.20 232. 18.20 232 18.20 18.20 18.20 232 .18.20 16:68 11.31 1.31 17.04 1.31. 33.77 1.31 14.99 14.99 14.99. 1.31 33:77 0 0 0 0 0 0'. 0 0 0 0 - 112 0 0 0 0 0 0 ' 0 0 0 0 0 96, 0 , ' . 0 0 0 0... 0 ' 0 0 0 0 0 222 0 0 0 0 0 :. 0.- . 0 0 0 0 0 125 0 . ' 0 0 U 0 0 0 336 0 30 41 0' 0 0' 0 0 0 0 ... 0.. 265 0 30 41 0 0 0 0 0 0 0 0 616 0 546 743 _ 0 0 0 0 0 0 0 -0 348 0 450 612 0 .:0_ ViJ I-G �j �--G vh13A-7.5fcs W 2 glazing, r]r-low-e 11D0 0:650 0:390, w.. w :1820 10.92 33.77 11.31 - 16 `0 0- 0 < ..291 0 540 0 ... 0 0 ..:.. ....• 0 0- . _..0 0 0 0 1N L� 13A-7.5fcs 2 glazirtq, cir low-e 16X19-0sd 0.083 0.650 0.408 nw nw - 232 18.20 1.59 1.31 17.04 1 A9 0 0 117 _ 0 0 117 0 0 186 0 0 174 0 0 57 0 0 57 0 0 90 0 0 85 C . G 17B-6ai 0.105 - 2.94 4.57 0 0 0 0 458 45B 1346 2091 F 22A,tpl 0.989. - 27..69 0.00 117 . - 12 332, 0 428 28 775 0 6 c)AED excursion 195 -88 Envelope loss/gain 1031 1034 4116 3496 12 a) Infiltration 210 56 633 169 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 1100 subtotal (lines 6 to 13) 1241 1091 4749 4766 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 29 34 14 subtotal 1241 1091 4778 4800 15 Duct loads 1 279/6 46% 340 501 27% 46%1 1310 2206 Total room load 1 1582 1592 6088 7006 Air required (cfm) 1 66 68 253 299 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. r wrigF�tsoft 2021-Mar-02 10:48:39 slcc% -� --- � rtiym-au i� virvcia i cvc i'c .v:vc nowo �o i -"`--Page 9 ...WACIPORTER MODEL MOD (W ICY} APPALOSSA CT.rup Calc = M.16 Front Door faces: N - wrightsoft® Right-J@ Worksheet Job: Entire House Date: MARCH 2, zoz, By., QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOLCOM 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BONUS ROOM 58.4 ft 9.3 ft heat/ccol 1.0 x 427.0 ft 427.0 ft2 PANTRY 0 ft 9.3 ft heattcool 4.0 x 6.0 ft 24.0 ft? Ty Construction number U-value (Btuh/ft? °F) Or HTM (Btuh/ft� Area ' (ft-) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 Vi/ 13A-7.5fcs .. 2 glazing, clr lower 2 glazing,'.clr lcw-e 2 glazin clr law-e "' 11D0 13A-7.5fcs 2 olazina. clr Iow-e 13Ar7:5fcs 2 glazing, clr low-e 13A-7.5fcs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 13Pr7:5fcs , :. 2 glazing,.clr lower 2 glazing, clr low-e. .. 11D0..- 13A•7.5fcs 2 glazinq, clr low-e 16X19;6 d 17B-6al 22AAIA 0.093 0.650- 0.650 0.650 0.390 0.083 0.650 0:083 0.650 0.083 0.650 0.650 0.650 0.083 0.650 6.656 0.390 0.083 0.650 0A08 0.105 0:989 . n n , n• n , n' ne ne `: a a s s s s . w w , :w W. nw nw . - - - 232 18.20 18.20" 18.20 10.92 232 18.20 232 18:20 232 18.20 18.20 18.20 232 18.20 1820. 10.92 232 18.20 1.59 2.94 27.69 ' 1.31 14.99 14.99 16.6E 11:31 1.31 17.04 1:31 33.77 1.31 14.99 14.99 14.99 1:31 33 77 33.77 11:31 1.31 17.04. : 1.49 4.57 0.00 140 0 0- '. 15. 0 39 14 - ' . 140 0 0 0 0 0 ' . 186 0 . 0 :24. 39 14 427 0 . 42T . 125 .. 0-. 0 0 0 25 0 140 • 0 0 0 0 0 162 0. . _.. 0 24 25 0 427 0 58 . 289 0 D . 273 0 59 258.. : 324 . 0 0 0 0 0 376 0 D .262 59 258 ` . .677 0 1618 :.. 163. 0 0 16D 0 33 241, : 183 ': 0 0 0 0 0 ` ,. .- 212 '0 D 271 33 241 635 0 0' 0 0 0 0. 0. 0 0 0 0 0 0 0 0 .. . 0 . . 0 A 0 0 0 '. 24. 0 24 0- 0 .0 0 0 0 0 0 . ' ' 0 0 0 0 0 0- 0 '..: ,. .. 0--- 0 0 0 24.1 0 0 0 ." 0 0 . 0 0 0 0 - 0' 0 0 0 0 0 0 0 0, .0 0 0 38 0 0 .: 0 0 0 0 0 0 0 0 0 0 0 0 0 : - 0 0 .. .. _.0: 0 0 0 36. 0 .. 0 yJ I--J; YLS 1/� L-G C C F 6 c)AED excursion -56 1 -1 Envelope lossfgain 4453 2118 38 35 12 a) Infiltration b) Room ventilation 1024 0 274 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 800 0 0 0 Subtotal (lines 6 to 13) 5477 3193 38 35 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 279/6 46% 0 0 0 5477 1502 0 0 0 3193 1467 279/6 46% 0 0 0 38 10 0 0 0 35 16 Total room load Air required (cfm) 6979 290 4660 199 1 48 121 51 2 AC J 8th ...WAC\PORTER MODEL MOD (W ICY} APPALOSSA CT.rup Calc = MJ8 Front Door faces: N +�- wrightsofte Duct System Summary Entire House QUICK CALCS, INC. 317 ST. LUCIE LN.. FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOL.COM • • • For: PORTER MODEL- CUSTOM, RODNEY HALL CONSTRUCTION 11771 APPALOOSA COURT, FORT PIERCE, FL 34987 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1317 cfm Job: Date: MARCH 2, 2021 By: Cooling 1.00 in H2O 0 in H2O 1.00 in H2O 0.500 / 0.500 in H2O 1.000 in/100ft 1317 cfm 170 ft Supply Braric,h Detail Table Name Design (Btuh) f Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH c 966 35 41 1.000 6.0 Ox0 VIFx 16.2 115.0 stl BEDROOM 2 h 2994 124 104 1.000 7.0 Ox 0 VIFx 18.6 115.0 stl BEDROOM 3 h 3082 128 98 1.000 7.0 Ox0 VIFx 20.8 115.0 st1 BEDROOM h 2729 113 99 1.000 7.0 OxO VIFx 5.0 95.0 BONUS ROOM h 3490 145 99 1.000 7.0 Ox0 VIFx 23.3 115.0 st2 BONUS ROOM -A h 3490 145 99 1.000 7.0 Ox 0 VIFx 33.0 115.0 st2 FOYER h 1957 81 66 1.000 6.0 Ox0 VIFx 23.2 115.0 st2 GREAT ROOM c 3503 126 150 1.000 8.0 Ox0 VIFx 21.3 115.0 stl GREAT ROOM -A c 3503 126 150 1.000 8.0 Ox 0 VIFx 13.8 115.0 stl KITCHEN c 2412 25 103 1.000 7.0 Ox0 VIFx 34.9 135.0 st3 LAUNDRY ROOM c 1076 6 46 1.000 6.0 Ox0 VIFx 20.4 115.0 st2 M. BATH c 1592 66 68 1.000 6.0 Ox0 VIFx 35.4 135.0 st3 M. BEDROOM h 4386 182 157 1.000 8.0 Ox0 VIFx 35.4 135.0 st3 M. Wic c 112 4 5 1.000 6.0 Ox0 VIFx 31.8 135.0 st3 M.TOILET c 462 1 20 1.000 4.0 Ox0 VIFx 33.2 135.0 st3 PANTRY c 51 2 2 1.000 4.0 Ox0 VIFx 16.5 115.0 st2 WIC 3 c 227 6 10 1.000 6.0 Ox 0 VIFx 6.0 95.0 Supply Trunk Detail Table .- Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st3 Peak AVF 278 352 1.000 646 10.0 0 x 0 VinlFlx st2 st1 Peak AVF 540 543 1.000 691 12.0 0 x 0 VinlFlx st2 Peak AVF 657 665 1.000 622 14.0 0 x 0 VinlFlx 444- wri htsoft- 2021-Mar-02 10:48:46 •M..tN.og.e RightSuite@ Universal 2021 21.0.02 RSU08101 Pagel ... WACIPORTERMODEL MOD (WICY)-APPALOSSACT.rup Calc=MJ8 FrontDoorfaces: N .Return' ,B ranch ,D.etai l Table - . : Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 1317 1317 0 0 0 0 Ox 0 VIFx wrightsoft, ^� �,�.• �N. r�m,a RightSuite® Universal 2021 21.0.02 RSU08101 2021-Mar-02 10:48:46 Page 2 AC K ...WACIPORTER MODEL MOD (W ICY)- APPALOSSA CT.rup Calc = MJ8 Front Door faces: N :i�5 This document was created with Win2PDF available at http://www.win2pdf.com. The unregistered version of Win2PDF is for evaluation or non-commercial use only. This page will not be added after purchasing Win2PDF.