HomeMy WebLinkAboutApproved PlansT-MOBILE PANEL RATING 200 AMPS PHASE 1 X MCB RATIN G 200 AMP
H-FRAME VOLTS 3 MAIN LUG ONLY AIC RATING: 10KA
CKT AMP AMP CKT
NO. A B POLE POLE A B NO.
1 0 - * * * 15/1 0.18 - 2
3-01/2" #12 #12 20/1 - 0.15 4
5 -6
7 -8
9 -10
11 -12
13 --14
15 - - 16
13 --18
19 - - 20
21 - - 22
23 - - 24
00 00
13.7 13.7 0.18 0.15
*
**
*** T-MOBILE SITE SUPPORT CABINET HAS POWER MONITORING AND LOAD SHEDDING CAPACITY TO MAINTAIN
OUTPUT LOAD BELOW 20kW DURING OPERATION OF 20kW EMERGENCY GENERATOR
SUB TOTAL KVA (CONT)
SUB TOTAL KVA (NON-CONT)
GFCI
SPACE
PANEL NAME:
LOCATION:
SUB TOTAL KVA (CONT)
SUB TOTAL KVA (NON-CONT)
SURGE SUPPRESSOR
SPACE
SPACE
120/240 WIRE
GND WIREGNDDESCRIPTION
SPACE
27.6 (***)TOTAL KVA
SPACE
NON-CONT + 125% CONT.
DESCRIPTION
*
KVA
60/2 * *
WIRE KVACOND COND
TOTAL AMPS114.9
PRE WIRED AT FACTORY
PROPOSED 200A FOUR POSITION CIRCUIT BREAKER, SQUARE D #QO2200.
SPACE
-
-13.7
200/2SITE SUPPORT CABINET (**)
13.7
#3/0 #6 2 1/2"
SPACE
SERVICE LIGHT
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE