Loading...
HomeMy WebLinkAboutApproved PlansT-MOBILE PANEL RATING 200 AMPS PHASE 1 X MCB RATIN G 200 AMP H-FRAME VOLTS 3 MAIN LUG ONLY AIC RATING: 10KA CKT AMP AMP CKT NO. A B POLE POLE A B NO. 1 0 - * * * 15/1 0.18 - 2 3-01/2" #12 #12 20/1 - 0.15 4 5 -6 7 -8 9 -10 11 -12 13 --14 15 - - 16 13 --18 19 - - 20 21 - - 22 23 - - 24 00 00 13.7 13.7 0.18 0.15 * ** *** T-MOBILE SITE SUPPORT CABINET HAS POWER MONITORING AND LOAD SHEDDING CAPACITY TO MAINTAIN OUTPUT LOAD BELOW 20kW DURING OPERATION OF 20kW EMERGENCY GENERATOR SUB TOTAL KVA (CONT) SUB TOTAL KVA (NON-CONT) GFCI SPACE PANEL NAME: LOCATION: SUB TOTAL KVA (CONT) SUB TOTAL KVA (NON-CONT) SURGE SUPPRESSOR SPACE SPACE 120/240 WIRE GND WIREGNDDESCRIPTION SPACE 27.6 (***)TOTAL KVA SPACE NON-CONT + 125% CONT. DESCRIPTION * KVA 60/2 * * WIRE KVACOND COND TOTAL AMPS114.9 PRE WIRED AT FACTORY PROPOSED 200A FOUR POSITION CIRCUIT BREAKER, SQUARE D #QO2200. SPACE - -13.7 200/2SITE SUPPORT CABINET (**) 13.7 #3/0 #6 2 1/2" SPACE SERVICE LIGHT SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE