Loading...
HomeMy WebLinkAboutEvaluation Report; Metal RoofingEVALUATION REPORT OF METAL SALES MANUFACTURING 'CORPORATION 1-v RECEIVED ja 012021 s,L LL,, TLORIDABUM'DING CODE 7TH EDITION (2020) pz.,County Permitting FLORWAPRODUCT APPROVAL FL 146453rk4 ROOFING -REViEWED FOR METAL ROOFING CODE COMPLIANCE ST. LUCIE COUNTY BOCC ,Prepared For; Metal Sales Manufacturing Corporation 545&)uth YdStreet'l-Suite,260 Louisville., KY 40102 Telephone: (502) 955-4300 Nan (502).855-4200. Prepared By:. Bala 1:Rockafin am.,, Ph.M, P.E6 1 9 Florida Professional Engineer: #62240 12164 N Lansing .Ave. Suflie C. Tulsa, 'OK 14106 Telephone: -(918) 492-Z9.92. FAX: (860) 366-1543 This report consists of Evaluation Report (3 Pages including -cover) Installation Details (I Pagi-) Load'S an Table.(1 Pa p ge) Report No. C2397-3 Date: 10.1.2010. File Copy 0 K A L I No 62240 :wx STATE OF 0 B FL 14645.344 C2397-3 10.7.2020 Page 2 of 3 Manufacturer: Metal Sales Manufacturing Corporation Product Name: 5V-Crimp Panel Description: 24" wide coverage with (5) 1/2" high ribs Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653),°ors-! •7u' Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). Corrosion resistant as per FBC 2020 Section 1507.4.3. Deck Description: Min. -19/32" plywood or min. %" thick wood plank (min SG of 0.42) for new and existing constructions. Designed by others and installed as per FBC 2020. Deck Attachment: 8d x 2.5" long ring shank nails or #8 x 2" long wood screws at 6" o.c. (Minimum) in the field and at 4" o.c. at edges. Designed as per FBC 2020. New Underlayment: Minimum underlayment as per FBC 2020 Section 1507.4.5.1. Required for new construction and optional for reroofing construction. Existing Underlayment: One layer of asphalt shingles over one layer of #30 felt. For reroofing (Optional) ; �, , construction only. Slope: 1/2:12 or greater in accordance with FBC 2020 Section 1507.4.2. Requires applied lap sealant for roof slopes less than 3:12. Design Uplift Pressure: 41.6 psf at fastener spacing of 36" o.c. (Factor of Safety = 2) 74.8 psf at fastener spacing of 16" o.c. 196.75 psf at fastener spacing of 8" o.c. Fastener Pattern: Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener shall be of sufficient length to penetrate through the deck a minimum of 3/8". Fasteners are corrosion resistant as per FBC 2020 Section 1507.4.4. At panel ends 6" o.c. across panel width At intermediate 12" o.c. across panel width Test Standards: Roof assembly tested in accordance with TAS 125-03 `Standard Requirements for Metal Roofing Systems'. Code Compliance: The product described herein has demonstrated compliance with FBC 2020 Section 1507.4. Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2020 Section 1609 or ASCE 7-16 using allowable stress FL 14645.3-R4 C2397-3 10.7.2020 Page 3 of 3 design. The design pressure for reduced fastener spacing may be computed using rational analysis prepared by a Florida Professional Engineer or based on Metal Sales load span table. This evaluation report is not applicable in High Velocity Hurricane Zone. Fire classification is not within scope of this Evaluation Report. Refer to FBC 2020 Section 1505 and current approved roofing materials directory or ASTM E108/UL790 report from an accredited laboratory for fire ratings of this product. Supporting Documents: TAS 125 Test Reports Farabaugh Engineering and Testing Inc Project No. T181-05, Reporting Date 7/21/05 (Tests #1 & 2) Project No. T240-09, Reporting Date 9/22/09 Architectural Testing, Inc. — West Palm Beach, FL (Formerly Hurricane Test Laboratory, LLC) Project No. 0103-0712-09, Reporting Date 9/l/09 EXISTING SHINGLES (OPTIONAL) NEW UNDERLAYMENT- (REQUIRED ONLY FOR NEW CONSTRUCTION) EXISTING SHINGLES (OPTIONAL) EXISTING UNDERLAYMENT (OPTIONAL) NEW UNDERLAYMENT- (REQUIRED ONLY FOR NEW CONSTRUCTION) EXISTING SHINGLES (OPTIONAL) EXISTING UNDERLAYMENT (OPTIONAL) SEE DETAIL 2 SEE DETAIL 1 NEW UNDERLAYMENT. (REQUIRED ONLY FOR -,,,,,,,--SEE � (PANEL OVERLAP) NEW CONSTRUCTION) EXISTING UNDERLAYMENT (OPTIONAL) MINIMUM ATTACHMENT: 8d x 2.5" LONG RING SHANK NAIL OR #8 x 2" LONG WOOD SCREWS SPACED ® 6" O.C. IN THE FIELD & FASTENER AT PANEL FLAT REQUIRED FOR PANEL ENDS ONLY. MIN. 2X- WOOD RAFTER/JOIST/J 4" O.C. AT PLYWOOD EDGES TRUSS AT MAX. 24" O.C. TYPICAL PANEL INSTALLATION X—SECTION #9-16 OR #10-14 WOODSCREWS WITH SELF SEALING WASHER AT MAXIMUM SPACING OF 36" O.C. 5V-CRIMP MIN 26 GA. PLYWOOD DETAIL 1 19/32" THICK (MIN.) #9-16 OR #10-14 WOODSCREWS WITH SELF SEALING WASHER AT MAXIMUM SPACING OF 36" O.C. 5V-CRIMP MIN 26 GA. PLYWOOD DETAIL 2 19/32" THICK (MIN.) PANEL FASTENER PER ALLOWABLE PRESSURE TABLE 5V-CRIMP GENERAL NOTES: 1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE (FBC). 2. ROOF PANELS SHALL BE MIN. 26 GA. (t = 0.0169"). EFFECTIVE COVERING WIDTH OF PANEL = 24". 3. THE ROOF PANELS SHALL BE INSTALLED OVER SHEATHING & STRUCTURE AS SPECIFIED ON THIS DRAWING. 4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LOADS ARE GREATER THAN THE ALLOWABLE WIND LOADS SPECIFIED ON THIS DRAWING. 5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING & THE FLORIDA BUILDING CODE. IF A DIFFERENCE OCCURS BETWEEN THE MINIMUM REQUIREMENTS OF THIS DRAWING & THE CODE, THE CODE SHALL CONTROL. 6. RAFTERS/JOISTS/TRUSSES MUST BE DESIGNED TO WITHSTAND WIND LOADS AS REQUIRED FOR EACH APPLICATION AND ARE THE RESPONSIBILITY OF OTHERS. 7. REQUIRES APPLIED LAP SEALANT FOR ROOF SLOPE < 3:12. d Ix 0 00 U N 0 u1N z to Fx 7N wo O - M U }} Lk Ewuo J0I =No Ln 00 Ln I OF 1 1 l 1 V METAL SALES: MANUFACTURING CORPORATION .S,V.Cnm -Uplift- �'p - (MiL 26 g%) DQspripOon Fastener; Spacing: puto4g Panel Length On), . Allowable Uplift Load. (yisf). ;coverage. width: 14" Panel Fasteners #9-16 or #10-- 14 hex. head wood screw&with sealed washer ;8 1968. 10 166.3 12, 135.8 14 16 74.9 18 71.5 20. 68.2 22 :64i,8 24 61.5 26 58.2 28 54.9; 56 5-L-6 52 48.2 34 �44.0 36 -41.6; Notes 1. The bold ft-umbers'indibatedesign loads calculated'ftom test data with safety factor of 2. 2. Panels must be,ingtalled.as per Evaluation.Report FL, 1,-4645.3 and Metal Sales current'installation,proped6 re. 3. Three or more spri;s condition. 1216 N Lansing Ave,-;. Suite C Tulsa, Ok 74106 918 492 5992 A dd .• v N N-0 .62240 STATE OF 0 0 .'-I 2C)2 C - Bala Sockalingam,Ph.D.j P.E. FL 62240