APPROVED AC Manual J (1)
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57 Right-Suite® Universal 2021 21.0.06 RSU29066 Page 1 ...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Load Short Form 4/28/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Hernandez Residence, Air Conditioning UnlimitedFor: 5802 Birch Dr, Ft. Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Goodman Mfg. Trade Trade GOODMAN Model Cond GSX16S361A AHRI ref Coil ASPT47D14A AHRI ref 201785534 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.3 Sensible cooling Btuh24500 Heating output Btuh24937 Latent cooling Btuh10500 Temperature rise °F19 Total cooling Btuh35000 Actual air flow cfm1167 Actual air flow cfm1167 Air flow factor cfm/Btuh0.049 Air flow factor cfm/Btuh0.054 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.76 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) WIC 42 1073 378 53 20 Laundry 24 459 864 23 46 Hall 36 0 0 0 0 Master Bed 242 2507 3027 124 163 Master Bath 133 3389 1600 168 86 Foyer 72 1305 676 65 36 Bed 3 161 2580 2314 128 124 Bed 2 167 3529 2106 175 113 Bath 59 1013 746 50 40 Lin 5 0 0 0 0 Hall 2 28 0 0 0 0 Living Room 293 2994 4707 148 253 Pantry 8 0 0 0 0 Kitchen 268 4728 5310 234 285 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57 Right-Suite® Universal 2021 21.0.06 RSU29066 Page 2 ...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N House 1536 23577 21728 1167 1167 Other equip loads 2425 1288 Equip. @ 0.95 RSM 21957 Latent cooling 7416 TOTALS 1536 26001 29373 1167 1167 2021-Apr-28 14:17:57 Right-Suite® Universal 2021 21.0.06 RSU29066 Page 1 ...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Building Analysis 4/28/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Hernandez Residence, Air Conditioning UnlimitedFor: 5802 Birch Dr, Ft. Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 18.347663.1Walls 11.5300317.6Glazing 0.3743.7Doors 5.915231.0Ceilings 22.357943.83.8Floors 10.627461.8Infiltration 21.85672Ducts 00Piping 00Humidification 9.32425Ventilation0Adjustments 100.026001Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 13.130161.9Walls 16.2373821.9Glazing 0.3753.7Doors 12.027721.8Ceilings 000Floors 3.37680.5Infiltration 27.56340Ducts 5.61288Ventilation 21.85020Internal gains 00Blower 0Adjustments 100.023016Total Latent Cooling Load = 7416 Btuh Overall U-value = 0.109 Btuh/ft²-°F Data entries checked. 2021-Apr-28 14:17:57 Right-Suite® Universal 2021 21.0.06 RSU29066 Page 1 ...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Component Constructions 4/28/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Hernandez Residence, Air Conditioning UnlimitedFor: 5802 Birch Dr, Ft. Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 6113.155.10.109194ne 3912.02 8802.0213753.155.10.109436se 6532.0210213.155.10.109324sw 7702.0212053.155.10.109382nw 26942.0242123.155.10.1091337all Knee wall, R-30 Kw Ins, 1/2" Gyp Bd Int Fnsh 31sw 551.78371.2130.00.042 Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 2511.465052.9411.00.101172 Knee wall, R-30 Kw Ins, 1/2" Gyp Bd Int Fnsh 9 161.78111.2130.00.042 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.16); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (1.25 ft window ht, 1 ft sep.); 6.8 ft head ht 19317.216014.200.49011ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 103722.184118.000.62047ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (4.17 ft window ht, 1 ft sep.); 6.8 ft head ht 19421.515216.800.5809se Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (3.17 ft window ht, 1 ft sep.); 6.8 ft head ht 40121.132016.800.58019sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 6.5 ft overhang (6.67 ft window ht, 1 ft sep.); 6.8 ft head ht 74814.0100518.800.65053sw 2021-Apr-28 14:17:57 Right-Suite® Universal 2021 21.0.06 RSU29066 Page 2 ...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 70622.652516.800.58031nw Doors Fbrgls Door 753.73743.697.00.12720ne Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341536 27721.8015230.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00579428.700.989202 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57 Right-Suite® Universal 2021 21.0.06 RSU29066 Page 1 ...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Project Summary 4/28/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Hernandez Residence, Air Conditioning UnlimitedFor:5802 Birch Dr, Ft. Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh17905 Structure Btuh15388 Ducts Btuh5672 Ducts Btuh6340Central vent (76 cfm) 2425 Btuh Central vent (76 cfm) Btuh1288 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh26001 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh21957 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh2553 Ducts Btuh1924Central vent (76 cfm) Btuh2940 CoolingHeating Outside air15361536Area (ft²) Equipment latent load Btuh7416 1360613606Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh29373 Equiv. AVF (cfm) 4586 Req. total capacity at 0.70 SHR ton2.6 Heating Equipment Summary Cooling Equipment Summary Make Make Goodman Mfg.Trade Trade GOODMAN Model Cond GSX16S361AAHRI ref Coil ASPT47D14A AHRI ref 201785534Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.3 Sensible cooling Btuh24500Heating output Btuh24937 Latent cooling Btuh10500 Temperature rise Total coolingActual air flow Actual air flow Air flow factor Air flow factorStatic pressure Static pressure Space thermostat Load sensible heat ratio Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57Right-Suite® Universal 2021 21.0.06 RSU29066 Page 1...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Right-J® Worksheet 4/28/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House WIC 2 Exposed wall 202.0 ft 13.0 ft 3 Room height 8.9 ft 8.0 heat/coolft 4 Room dimensions ft6.0x7.0 5 Room area 1536.0 ft²42.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 272 194 611 391 0 0 0 0 .GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 nene 14.2114.21 17.1917.19 11 0 160 193 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 47 0 841 1037 0 0 0 0 .DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 20 20 74 75 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 446 436 1375 880 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.5421.54 9 1 152 194 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 397 324 1021 653 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 19 4 320 401 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 53 53 1005 748 0 0 0 0 WW Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 swsw 1.211.21 1.781.78 31 31 37 55 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 414 382 1205 770 48 48 151 97 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 172 172 505 251 56 56 165 82 PP Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 --1.211.21 1.781.78 9 9 11 16 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 1536 1536 1523 2772 42 42 42 76 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1536 202 5794 0 42 13 373 0 6 c) AED excursion 459 -10 Envelope loss/gain 15159 9601 730 244 12 a) Infiltration 2746 768 85 24 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4100 0 Subtotal (lines 6 to 13)17905 15388 815 268 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 17905 15388 815 268 15 Duct loads 32%41%5672 6340 32%41%258 110 Total room load 23577 21728 1073 378 Air required (cfm)Air required (cfm)1167 1167 53 20 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57Right-Suite® Universal 2021 21.0.06 RSU29066 Page 2...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Right-J® Worksheet 4/28/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Laundry Hall 2 Exposed wall 4.0 ft 6.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x4.0 ft6.0x6.0 5 Room area 24.0 ft²36.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 nene 14.2114.21 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 swsw 1.211.21 1.781.78 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 32 32 94 47 48 48 141 70 PP Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 --1.211.21 1.781.78 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 24 24 24 43 36 36 36 65 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 24 4 115 0 36 6 172 0 6 c) AED excursion -21 -5 Envelope loss/gain 233 68 349 130 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)233 568 349 130 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 116 43 -349 -130 14 Subtotal 349 612 0 0 15 Duct loads 32%41%110 252 32%41%0 0 Total room load 459 864 0 0 Air required (cfm)Air required (cfm)23 46 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57Right-Suite® Universal 2021 21.0.06 RSU29066 Page 3...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Right-J® Worksheet 4/28/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bed Master Bath 2 Exposed wall 16.5 ft 34.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft241.8x1.0 ft133.3x1.0 5 Room area 241.8 ft²133.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 nene 14.2114.21 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 72 72 227 145 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 20 20 63 40 116 107 336 215 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 10 2 160 200 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 swsw 1.211.21 1.781.78 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 112 81 255 163 84 84 265 169 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 PP Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 --1.211.21 1.781.78 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 242 242 240 436 133 133 132 240 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 242 17 473 0 133 34 975 0 6 c) AED excursion 189 30 Envelope loss/gain 1555 1535 2094 1000 12 a) Infiltration 233 65 479 134 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 0 Subtotal (lines 6 to 13)1788 2100 2573 1133 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 116 43 0 0 14 Subtotal 1904 2144 2573 1133 15 Duct loads 32%41%603 883 32%41%815 467 Total room load 2507 3027 3389 1600 Air required (cfm)Air required (cfm)124 163 168 86 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57Right-Suite® Universal 2021 21.0.06 RSU29066 Page 4...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Right-J® Worksheet 4/28/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Foyer Bed 3 2 Exposed wall 11.0 ft 16.0 ft 3 Room height 10.0 heat/coolft 10.0 heat/coolft 4 Room dimensions ft71.5x1.0 ft14.0x11.5 5 Room area 71.5 ft²161.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 65 41 130 83 115 76 240 154 .GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 nene 14.2114.21 17.1917.19 4 0 53 64 8 0 107 129 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 31 0 561 691 .DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 20 20 74 75 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 swsw 1.211.21 1.781.78 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 45 45 142 91 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 36 36 106 53 0 0 0 0 PP Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 --1.211.21 1.781.78 9 9 11 16 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 72 72 71 129 161 161 160 291 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 72 11 315 0 161 16 459 0 6 c) AED excursion -16 -61 Envelope loss/gain 760 403 1668 1294 12 a) Infiltration 115 32 282 79 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 250 Subtotal (lines 6 to 13)875 435 1950 1622 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 116 43 9 16 14 Subtotal 991 479 1959 1639 15 Duct loads 32%41%314 197 32%41%621 675 Total room load 1305 676 2580 2314 Air required (cfm)Air required (cfm)65 36 128 124 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57Right-Suite® Universal 2021 21.0.06 RSU29066 Page 5...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Right-J® Worksheet 4/28/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Bath 2 Exposed wall 33.5 ft 8.5 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft167.0x1.0 ft58.8x1.0 5 Room area 167.0 ft²58.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 92 76 241 154 0 0 0 0 .GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 nene 14.2114.21 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 16 0 280 346 0 0 0 0 .DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 112 112 353 226 68 59 186 119 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.5421.54 0 0 0 0 9 1 152 194 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 swsw 1.211.21 1.781.78 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 64 64 202 129 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 PP Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 --1.211.21 1.781.78 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 167 167 166 301 59 59 58 106 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 167 34 961 0 59 9 244 0 6 c) AED excursion -56 58 Envelope loss/gain 2202 1100 640 478 12 a) Infiltration 472 132 120 33 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)2674 1482 760 511 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 6 10 10 17 14 Subtotal 2680 1492 769 528 15 Duct loads 32%41%849 614 32%41%244 218 Total room load 3529 2106 1013 746 Air required (cfm)Air required (cfm)175 113 50 40 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57Right-Suite® Universal 2021 21.0.06 RSU29066 Page 6...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Right-J® Worksheet 4/28/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Lin Hall 2 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft2.5x2.0 ft7.0x4.0 5 Room area 5.0 ft²28.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 nene 14.2114.21 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 swsw 1.211.21 1.781.78 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 PP Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 --1.211.21 1.781.78 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 5 5 5 9 28 28 28 51 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 5 0 0 0 28 0 0 0 6 c) AED excursion 0 -2 Envelope loss/gain 5 9 28 49 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)5 9 28 49 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -5 -9 -28 -49 14 Subtotal 0 0 0 0 15 Duct loads 32%41%0 0 32%41%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57Right-Suite® Universal 2021 21.0.06 RSU29066 Page 7...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Right-J® Worksheet 4/28/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Living Room Pantry 2 Exposed wall 15.5 ft 5.5 ft 3 Room height 10.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft15.0x19.5 ft2.5x3.0 5 Room area 292.5 ft²7.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.490Impact, Clear Low-e 0.490 nene 14.2114.21 17.1917.19 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .DD Fbrgls DoorFbrgls Door 0.1270.127 nene 3.693.69 3.733.73 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 sese 16.8216.82 21.5421.54 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 124 71 223 142 24 24 76 48 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.0821.08 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 53 53 1005 748 0 0 0 0 WW Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 swsw 1.211.21 1.781.78 31 31 37 55 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 20 20 63 40 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 PP Knee wall, R-30 Kw I 0.042Knee wall, R-30 Kw I 0.042 --1.211.21 1.781.78 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.801.80 293 293 290 528 8 8 7 14 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 293 16 445 0 8 6 158 0 6 c) AED excursion 423 -5 Envelope loss/gain 2000 1896 304 98 12 a) Infiltration 273 76 78 22 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)2273 3332 381 119 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 1 1 -381 -119 14 Subtotal 2274 3334 0 0 15 Duct loads 32%41%720 1373 32%41%0 0 Total room load 2994 4707 0 0 Air required (cfm)Air required (cfm)148 253 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-28 14:17:57Right-Suite® Universal 2021 21.0.06 RSU29066 Page 8...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Right-J® Worksheet 4/28/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Kitchen 2 Exposed wall 38.5 ft 3 Room height 9.0 heat/coolft 4 Room dimensions ft267.8x1.0 5 Room area 267.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Blk Wall, Stucco Ext 0.109 ne 3.15 2.02 0 0 0 0 .G Impact, Clear Low-e 0.490 ne 14.21 17.19 0 0 0 0 .G Impact, Clear Low-e 0.620 ne 17.98 22.15 0 0 0 0 .D Fbrgls Door 0.127 ne 3.69 3.73 0 0 0 0 11 W Blk Wall, Stucco Ext 0.109 se 3.15 2.02 194 194 610 390 G Impact, Clear Low-e 0.580 se 16.82 21.54 0 0 0 0 W Blk Wall, Stucco Ext 0.109 sw 3.15 2.02 113 103 325 208 G Impact, Clear Low-e 0.580 sw 16.82 21.08 10 2 160 200 G Impact, Clear Low-e 0.650 sw 18.85 14.02 0 0 0 0 W Knee wall, R-30 Kw I 0.042 sw 1.21 1.78 0 0 0 0 W Blk Wall, Stucco Ext 0.109 nw 3.15 2.02 41 41 128 82 G Impact, Clear Low-e 0.580 nw 16.82 22.64 0 0 0 0 P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 0 0 0 0 P Knee wall, R-30 Kw I 0.042 -1.21 1.78 0 0 0 0 C Attic, Shngl Roof, R 0.034 -0.99 1.80 268 268 265 483 F On Grade Depth, Tile 0.989 -28.68 0.00 268 39 1104 0 6 c) AED excursion -65 Envelope loss/gain 2591 1298 12 a) Infiltration 611 171 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 2 460 Appliances/other 1700 Subtotal (lines 6 to 13)3202 3629 Less external load 0 0 Less transfer 0 0 Redistribution 389 132 14 Subtotal 3590 3761 15 Duct loads 32%41%1137 1549 Total room load 4728 5310 Air required (cfm)234 285 2021-Apr-28 14:17:58 Right-Suite® Universal 2021 21.0.06 RSU29066 Page 1 ...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Duct System Summary 4/28/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Hernandez Residence, Air Conditioning UnlimitedFor: 5802 Birch Dr, Ft. Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.526 / 0.174 in H2O in H2O0.526 / 0.174 Lowest friction rate in/100ft0.300in/100ft0.300 Actual air flow cfm1167cfm1167 Total effective length (TEL) ft234 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3120.044.0VlFx0x05.00.32148601013hBath st3125.050.5VlFx0x08.00.3001362103529hBed 2 st1100.025.2VlFx0x06.00.4201491532580hBed 3 st1100.031.8VlFx0x05.00.39944771305hFoyer st3120.037.3VlFx0x07.00.3341711402655cKitchen-A st3120.047.2VlFx0x07.00.3141711402655cKitchen-B st2100.021.4VlFx0x04.00.4335627864cLaundry st1100.027.8VlFx0x06.00.411152892354cLiving Room st1100.028.2VlFx0x06.00.410152892354cLiving Room-A st2105.030.1VlFx0x07.00.3891032013389hMaster Bath st2100.019.9VlFx0x05.00.43998741513cMaster Bed st2100.018.4VlFx0x05.00.44498741513cMaster Bed-A st2100.020.2VlFx0x05.00.43724641073hWIC Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 551 526 0.300 701 12.0 0x0 VinlFlx st1 st1 Peak AVF 959 1022 0.300 732 16.0 0x0 VinlFlx st2 Peak AVF 441 378 0.389 809 10.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Apr-28 14:17:58 Right-Suite® Universal 2021 21.0.06 RSU29066 Page 2 ...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb8 0x 8250 896 58.2 0.300 642 16.0 x0 0 VlFx rb4 0x 2130 219 0 0 0 0 x0 0 VlFx rb3 0x 2100 136 0 0 0 0 x0 0 VlFx rb2 0x 1530 149 0 0 0 0 x0 0 VlFx 2021-Apr-28 14:17:58 Right-Suite® Universal 2021 21.0.06 RSU29066 Page 1 ...ents\Wrightsoft HVAC\5802 Birch Dr PSL Prop.rup Calc = MJ8 Front Door faces: N 1480Job:Manual S Compliance Report 4/28/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Hernandez Residence, Air Conditioning UnlimitedFor: 5802 Birch Dr, Ft. Pierce, FL 34982 Cooling Equipment Design Conditions °F77.0Entering coil DB:Btuh23016Sensible gain:°F90.4Outdoor design DB: °F64.2Entering coil WB:Btuh7416Latent gain:°F77.4Outdoor design WB: Btuh30432Total gain:°F75.0Indoor design DB: cfm1167Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: GSX16S361A+ASPT47D14AModel:Goodman Mfg.Manufacturer: cfm1167Actual airflow: % of load118Btuh27063Sensible capacity: % of load101Btuh7499Latent capacity: %78SHR:% of load114Btuh34562Total capacity: Heating Equipment Design Conditions °F67.6Entering coil DB:Btuh26001Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1167Actual airflow: °F50Temp. rise:% of load96kW7.3Output capacity: Meets all requirements of ACCA Manual S.