E-1
1 OF 2GENERATORADDITION RISERDIAGRAMNEW GENERATOR FOR:SAM COMER8590 GERMANY CANAL RD.FORT PIERCE, FL. 34987NTS
1 GENERATOR ADDITION RISER DIAGRAM DATEREVISIONMARKDATE:
SHEET DATEDESIGNEDDRAWNCOMPLETE ELECTRIC, INC.637 SEBASTIAN RD.SEBASTIAN, FL. 32958(772) 388-0533EC 0001911SCOPE OF WORK:
·RELOCATE ABANDONED AT&T BOX.
·EXISTING METER CAN GROUNDING ELECTRODE MAY REQUIRE TO BE SHIFTED TO
MAKE ROOM FOR NEW ATS AND PANEL FEEDER FROM ATS. FIELD VERIFY IF
REQUIRED.
·INSTALL 200AMP SE RATED ATS TO THE RIGHT OF EXISTING UTILITY METER CAN ON
EXTERIOR WALL.
·RE-FEED INTERIOR PANEL FROM NEW ATS. SEPARATE NEUTRALS AND GROUNDS IN
PANEL IF REQUIRED.
·INSTALL COLD WATER BOND FROM ATS TO NEAREST CU WATER PIPING.
·FORM AND POUR CONCRETE PAD FOR GENERATOR. UTILIZE 2"x10" FORM BOARDS.
·PROVIDE AND INSTALL (1) 24kW GENERAC GENERATOR.
·PROVIDE AND INSTALL CONDUIT AND CONDUCTORS FROM ATS TO GENERATOR.
WILL HAVE TO HAND TRENCH NEW CONDUIT FROM ATS TO GENERATOR.
·PROVIDE (2) LOAD SHED DEVICES PER SIZING DATA THIS SHEET.
·NEW LP TANK TO BE PROVIDED AND INSTALLED BY FERRELLGAS UNDER A
SEPARATE PERMIT.
·NO NEW BRANCH CIRCUIT LOADS SHALL BE ADDED TO HOUSE PANEL UNDER THIS
SCOPE OF WORK.
EXISTING
200 AMP
METER CAN
120/240 1Ø
NEW
200 AMP
GENERAC
SE RATED
ATS
100AMP
BREAKER
EXISTING (2) 5/8" X 8'
CU GROUND RODS
EXISTING
200 AMP
PANEL
NEW GENERATOR:
AIR COOLED
GENERAC 24KW
GRADE
GENERAL NOTES:
1.
2.
LIGHT LINE WORK REPRESENTS EXISTING TO REMAIN.
DARK AND RED LINE WORK REPRESENT NEW
EQUIPMENT, CONDUIT, AND WIRE.
ATTIC ATTIC
GRADE
ELECTRICAL LEGEND:
SURFACE MOUNT 120/240V, 1Ø, 3-WIRE PANELBOARD
FLUSH MOUNT 120/240V, 1Ø, 3-WIRE PANELBOARD
SURFACE MOUNT 277/480V, 3Ø, 4-WIRE PANELBOARD
FLUSH MOUNT 277/480V, 3Ø, 4-WIRE PANELBOARD
UTILITY METER CAN OR METER/MAIN COMBO UNIT
GENERATOR AND GENERATOR PAD
GAS STORAGE TANK
SURFACE MOUNT AUTOMATIC TRANSFER SWITCH
NON-FUSED DISCONNECT
FUSED DISCONNECT
30AR
NF 3R
FRAME SIZE
NEMA RATING
NON FUSED
30AR
30AF 3R
FRAME SIZE
NEMA RATING
FUSE SIZE
CONDUIT AND WIRE SCHEDULE
SYMBOL DESCRIPTION
EXISTING 2"PVC UNDERGROUND SERVICE FEEDER
EXISTING OVERHEAD SERVICE RISER, WEATHERHEAD, AND UTILITY FEEDERS
EXISTING 1/2"PVC W/ (1) #4 BARE CU
2"PVC W/ (3) #4/0 THWN AL
2"PVC W/ (3) #4/0 THWN AL, (1) #6 THHN CU GROUND
1-1/4"PVC SLEEVE W/ GENERAC CABLE W/ (3) #3 THHN CU, (1) #8 THHN CU GROUND,
(5) #14THHN CU
1-1/4"PVC W/ (3) #3 THHN CU, (1) #8 THHN CU GROUND
3/4"PVC W/ (7) #14 THHN CU
1/2"PVC W/ (1) #4 BARE CU
A
B
C
D
E
F
G
H
I
D
POINT OF NEW CONNECTION
EXISTING
WATER LINE
F
(EXISTING)B
AC ALTERNATING CURRENT
A/C AIR CONDITIONING
AFG ABOVE FINISHED GRADE
AL ALUMINUM (CONDUCTOR)
AHU AIR HANDLING UNIT
ATS AUTOMATIC TRANSFER SWITCH
AMP AMPERE
AFCI ARC FAULT CIRCUIT INTERRUPTER
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
C CONDUIT
CU COPPER (CONDUCTOR)
COVB CITY OF VERO BEACH
DC DIRECT CURRENT
DISC DISCONNECT
EXIST EXISTING
FPL FLORIDA POWER & LIGHT
G GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
IRC INDIAN RIVER COUNTY
KVA KILOVOLT AMPERE
KW KILOWATT
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANELBOARD
MTS MANUAL TRANSFER SWITCH
MSB MAIN SWITCHBOARD
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NON-SE NON SERVICE ENTRANCE RATED
PLCS PLACES (QUANTITY)
PNL PANEL
PVC POLYVINYL CHLORIDE CONDUIT
RMC RIGID METAL CONDUIT
RTU ROOF TOP UNIT
SE SERVICE ENTRANCE RATED
TYP TYPICAL
TEMP TEMPORARY
TRANS, TX TRANSFORMER
UG UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
V VOLT
VA VOLT AMPERE
W WATT
XFMR TRANSFORMER
ABBREVIATIONS:
NATURAL GAS METER
NOTE:
NOT ALL CONDUIT AND WIRE SHOWN ON THIS SCHEDULE MAY PERTAIN TO THIS PROJECT.
(SOME SYMBOLS SHOWN MAY NOT PERTAIN TO THIS PROJECT)
INTERIOREXTERIOR
INTERIOREXTERIOR
EXTERIORINTERIOR
EXTERIORINTERIOR
FINISHED FLOOR
C I
GROUND ROD
LOAD MANAGEMENT
"LCM" LOAD SHED
LOAD MANAGEMENT TECHNOLOGY ALLOWS THE LOAD CONTROL MODULE TO MONITOR GENERATOR PERFORMANCE AND
ONLY SHED LOADS WHEN ABSOLUTELY NECESSARY BY MONITORING GENERATOR CURRENT AND FREQUENCY. BY ONLY
SHEDDING THE NONESSENTIAL CIRCUITS, THE ESSENTIAL CIRCUITS ARE ALWAYS POWERED. LOADS ARE SHED THROUGH
INTERRUPTION OF INDIVIDUAL CONTROL CIRCUITS (AHU/AC) AND POWER CIRCUITS (RANGE AND WATER HEATER).
GENERAL NOTES:
·THE ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE ALL ELECTRICAL SERVICE ROUGH IN AND INSTALLATION
DETAIL WITH THE LOCAL UTILITY POWER COMPANY.
·THIS ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 7TH EDITION (2020), LOCAL
ORDINANCE, AND THE NATIONAL ELECTRIC CODE NFPA 70 (2017).
·ALL ELECTRICAL WORK FOR THE ENTIRE PROJECT SHALL BE PERFORMED IN A NEAT AND CRAFTSMAN LIKE MANNER BY
PERSONS SKILLED IN THE ELECTRICAL TRADE, AND SHALL BE DONE UNDER THE SUPERVISION OF A MASTER ELECTRICIAN
LICENSED IN THE STATE OF FLORIDA.
·THIS ELECTRICAL INSTALLATION SHALL BE PROTECTED FROM PHYSICAL DAMAGE AND SECURELY SUPPORTED AND
FASTENED, WITH WORKING SPACE PER NATIONAL ELECTRICAL CODE NFPA 70, ARTICLE 110.26 SPACES ABOUT ELECTRICAL
EQUIPMENT.
·PVC SCHEDULE 40 CONDUIT SHALL BE USED UNDERGROUND, IN OR BELOW CONCRETE AND WHERE EXPOSED NOT
SUBJECT TO DAMAGE. PVC SCHEDULE 80 CONDUIT SHALL BE USED WHERE EXPOSED, SUBJECT TO DAMAGE.
·ALL MATERIAL SHALL BE NEW, FREE FROM DEFECT AND SHALL BE LISTED AND BEAR THE LABEL OF A RECOGNIZED
TESTING LABORATORY.
·GROUNDING PER NATIONAL ELECTRICAL CODE NFPA 70, ARTICLE 250 GROUNDING AND BONDING.
·STANDBY SYSTEM INSTALLATION PER NATIONAL ELECTRICAL CODE NFPA 70, ARTICLE 702 OPTIONAL STANDBY SYSTEMS,
AND MANUFACTURER INSTALLATION INSTRUCTIONS.
FROM NEW ATS
E
E
ETO EXISTING
PANEL
F:\GENERATOR DRAWINGS\05-20-2021 Sam Comer\05-20-2021 Sam Comer.dwg, 5/27/2021 9:06:25 AM
COVERED
PATIO
COVERED
PATIO
COVERED
PATIO
CONC.
SLAB
DRIVEWAY
NEW 500 GAL.
LP TANK
(BY OTHERS)
15'-0"NEW UNDERGROUND
GENERATOR FEEDER
AND CONTROL CABLES
NEW UNDERGROUND
GENERATOR GAS LINE
EXISTING UNDERGROUND
GENERATOR GAS LINE
EXISTING UTILITY
METER
NEW ATS
EXISTING PANEL
SINGLE FAMILY
RESIDENCE
8590 GERMANY CANAL RD.
FORT PIERCE, FL. 34987
OAK TREE
60'-0"
05/27/2021
2 OF 2GENERATORSITE PLAN &PAD DETAILDATEDESIGNEDDRAWNCOMPLETE ELECTRIC, INC.637 SEBASTIAN RD.SEBASTIAN, FL. 32958(772) 388-0533EC 0001911DATEREVISIONMARKDATE:
SHEET
E-2
1/2" = 1'-0"
2 GENERATOR PAD DETAIL
TOP VIEW
LEFT ELEVATION FRONT ELEVATION
DRILL
DRILL
1/4"
DEEPER
THAN
ANCHOR
EMBEDMENT
CLEAN DRIVE TIGHTEN
3-5 X
DRILL BIT SIZE: 1/2"TIGHTENING
TORQUE: 45ft.lbs.
MIN. ANCHOR
EMBEDMENT: 2-1/2"
1/4" MIN.54"
32"
10" MIN.
32"54"
NOTE:
UTILIZE 2"x10" FORM BOARDS. TOP OF
GENERATOR PAD TO BE A MINIMUM OF 10"AFG
0'3"6"1'2'
SCALE: 1/2" = 1'-0"
NOTE:
1.THE USE OF A CARBIDE DRILL BIT
CONFORMING TO ANSI STANDARD B212.15 IS
RECOMMENDED.
2.ANCHOR BOLTS TO BE 3/8"DIA.x3-3/4"LONG
UNLESS OTHERWISE NOTED.NEW GENERATOR FOR:SAM COMER8590 GERMANY CANAL RD.FORT PIERCE, FL. 349871" = 10'-0"
1 GENERATOR SITE PLAN
N
W
S
E
0'2.5'5'10'20'
SCALE: 1" = 10'-0"F:\GENERATOR DRAWINGS\05-20-2021 Sam Comer\05-20-2021 Sam Comer.dwg, 5/27/2021 9:03:29 AM