HomeMy WebLinkAboutBLOWER DOOR AND DUCT BLAST 7.22.21Envelope Leakage
(Blower Door Test)
R402.4.1.2 Compliance
Test Report
I Permit #
Job information
Builder: DR HORTON Communit :
Address: Y Ctee�
33i ��� C� Unit:
City: 2j'e - _ State FL
Air Leakage Test Results Passing results must be 7ACH(50) or less
1L�_x60=�- L= 3
CFM(SO) Building Volume ACH(SO)
�SS � FAIL
Lot:
Method for calculatin buildin volume:
0 Retrieved from architectural plans
O Code software calculated
0 Field measured and calculated
When ACH(50) is less than 3, Mechanical Ventilation installation must be verified by building department.
Certification of Test Results
n4uZA.12 resting. The building or dwelling uni7111111", I'll, t shall be tested and verified as having an air leakage rate of not exceeding 7 air changes
per hour in Climate Zones 1 and 2, 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a
pressure of 0.2 inches w.g. (50 Pascals). Testing shall be conducted by wither individuals as defined in Section 553.993(5) or (7), F.S. or
lts of the te
individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the resust
shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time all penetrations of the building thermal envelope. after creation of
Testing Company
Company Name: SUN SEAL LLC Phone:
321-412-0035
1 hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test:_71 :2 j 6-2 I
Signature of Tester:
Printed Name of Tester'
______RAULY BAGGETT
License/Certification # S06618S Issuing Authority gpl
UN
Duct Leakage Test Report
Prescriptive or Performance Method
Permit #
Job Information
Builder: DR HORTON Community: Cree s-�%
Address: Lot:
��.� � ���.�,`�� C �- Unit-
City &ej-cr State: FL
Zip:
Duct Leakage Test Results 0 Presciptive Method 0 Performance Method
System 1
cfm25 0 Prescriptive Method cfm25 (total)
System 2 To qualify as "substantially leak free" Qn must be less than or equal to 0.04
cfm25 if air handler unit is installed. If air handler unit is not installed, Qn Total
System 3 must be less than or equal to 0.03. This testing method meets the
cfm25 requirements in accordance with Section R403.2.2
Sum of any additional
systems cfm25
Total of all systems
Total of all systems Total Conditioned
Square Footage
EWPASS El FAIL
Testing Company
U Performance Method cfm25 (out or Total)
To qualify as "substantially leak free" Qn must not be greater than the
proposed duct leakage Qn specified on Form R405-2014
Leakage Type selected
on Form R405-2014
(Energy Calc)
Qn specified on Form
R405-2014 (Energy Calc)
Company Name: SUN SEAL LLC Phone: 321-412-0035
I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected
compliance path as stated above, either the Prescriptive Method or Performance Method.
Date of Test:—...
Signature of Tester:
Printed Name of Tester: RAULY BAGGETT
License/Certification # 5066185 Issuing Authority --,BPI