Loading...
HomeMy WebLinkAboutAPPROVED CAUSLEY- MANUAL J (1)Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Project Summary Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information RAY AND AMI CAUSLEY, DON HINKLE CONSTRUCTIONFor: TREE TOP TRAIL, FORT PIERCE, FL 34951 Notes: Design Information Fort Pierce, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F42 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F28 Design TD °F15 Daily range M Relative humidity %50 Moisture difference gr/lb61 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh30156 Struc ture Btuh22878 Ducts Btuh8842 Ducts Btuh12646 Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh38998 Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load Btuh33747 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average 0Fireplaces Structure Btuh5000 Ducts Btuh3495 Central vent (0 cfm)Btuh0 CoolingHeating (none) 25452545Area (ft²)Equipment latent load Btuh8495 2692726927Volume (ft³) Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh42242 Equiv. AVF (cfm)72144 Req. total capacity at 0.70 SHR ton4.0 Heating Equipment Summary Cooling Equipment Summary Make Make Carrier Trade Trade CARRIER Model Cond 24ACB748A00310 AHRI ref Coil FV4CNB006L AHRI ref 10360207 Efficiency 100 EFF Efficiency 13.0 EER, 17 SEER Heating input kW10.0 Sensible cooling Btuh33600 Heating output Btuh34211 Latent cooling Btuh14400 Temperature rise °F19 Total cooling Btuh48000 Actual air flow cfm1600 Actual air flow cfm1600 Air flow factor cfm/Btuh0.041 Air flow factor cfm/Btuh0.045 Static pressure in H2O1.00 Static pressure in H2O1.00 Space thermostat Load sensible heat ratio 0.81 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name Entire House MASTER BEDROOM 2 Exposed wall 216.9 ft 35.0 ft 3 Room height 10.6 ft 10.3 heat/coolft 4 Room dimensions ft296.0x1.0 5 Room area 2545.0 ft²296.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 617 539 2159 1180 185 165 662 362 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 6 0 109 90 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 20 0 364 300 20 0 364 300 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 18 0 325 268 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 34 0 610 502 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 438 348 1392 761 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 12 1 218 385 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 45 3 819 1459 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 13 1 244 439 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 20 1 366 659 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 532 468 1874 1024 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 6 6 109 90 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 8 8 146 120 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 30 30 546 450 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 20 20 366 301 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 657 574 2297 1255 175 142 569 311 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 20 1 364 648 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 30 2 546 973 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 33 2 600 1079 33 2 600 1079 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 2545 2545 4035 3482 296 296 469 405 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2545 217 8248 0 296 35 1331 0 6 c) AED excursion 0 281 Envelope loss/gain 25737 15464 3995 2738 12 a) Infiltration 4419 1184 710 190 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 6230 250 Subtotal (lines 6 to 13)30156 22878 4705 3178 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 30156 22878 4705 3178 15 Duct loads 29%55%8842 12646 29%55%1380 1757 Total room load 38998 35524 6085 4935 Air required (cfm)Air required (cfm)1600 1600 250 222 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M BATH M WIC 2 Exposed wall 20.9 ft 0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft156.0x1.0 ft84.0x1.0 5 Room area 156.0 ft²84.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 84 84 335 183 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 112 100 399 218 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 12 1 218 385 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 156 156 247 213 84 84 133 115 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 156 21 795 0 84 0 0 0 6 c) AED excursion -52 -35 Envelope loss/gain 1995 948 133 80 12 a) Infiltration 385 103 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 600 Subtotal (lines 6 to 13)2380 1051 133 680 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 2380 1051 133 680 15 Duct loads 29%55%698 581 29%55%39 376 Total room load 3077 1632 172 1055 Air required (cfm)Air required (cfm)126 73 7 48 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name M TOILET FOYER/LIVING RM 2 Exposed wall 12.0 ft 20.0 ft 3 Room height 9.3 heat/coolft 14.0 heat/coolft 4 Room dimensions ft32.0x1.0 ft20.0x19.0 5 Room area 32.0 ft²380.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 65 59 237 129 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 6 0 109 90 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 47 47 186 102 280 202 807 441 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 45 3 819 1459 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 13 1 244 439 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 20 1 366 659 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 32 32 51 44 380 380 603 520 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 32 12 456 0 380 20 760 0 6 c) AED excursion -21 -177 Envelope loss/gain 1039 344 3598 3341 12 a) Infiltration 220 59 552 148 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 1000 Subtotal (lines 6 to 13)1259 403 4150 4488 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 14 11 14 Subtotal 1259 403 4164 4500 15 Duct loads 29%55%369 223 29%55%1221 2487 Total room load 1628 625 5385 6987 Air required (cfm)Air required (cfm)67 28 221 315 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name DINING RM KITCHEN 2 Exposed wall 12.0 ft 4.0 ft 3 Room height 14.0 heat/coolft 9.3 heat/coolft 4 Room dimensions ft12.0x15.0 ft20.0x15.0 5 Room area 180.0 ft²300.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 168 138 553 302 37 37 149 81 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 30 2 546 973 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 180 180 285 246 300 300 476 410 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 180 12 456 0 300 4 152 0 6 c) AED excursion 343 -104 Envelope loss/gain 1840 1863 777 388 12 a) Infiltration 331 89 73 20 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 200 1600 Subtotal (lines 6 to 13)2171 2152 850 2007 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 53 43 14 Subtotal 2171 2152 903 2051 15 Duct loads 29%55%637 1190 29%55%265 1134 Total room load 2808 3342 1168 3184 Air required (cfm)Air required (cfm)115 151 48 143 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name HALLWAY LAUNDRY RM 2 Exposed wall 0 ft 9.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft12.0x5.0 ft24.0x9.0 5 Room area 60.0 ft²216.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 84 64 255 139 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 20 20 366 301 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 60 60 95 82 216 216 342 296 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 60 0 0 0 216 9 342 0 6 c) AED excursion -4 -75 Envelope loss/gain 95 78 1305 661 12 a) Infiltration 0 0 165 44 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 0 750 Subtotal (lines 6 to 13)95 78 1470 1455 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -95 -78 34 28 14 Subtotal 0 0 1504 1482 15 Duct loads 29%55%0 0 29%55%441 819 Total room load 0 0 1944 2302 Air required (cfm)Air required (cfm)0 0 80 104 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 3 CLST 3 2 Exposed wall 13.0 ft 2.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft12.0x13.0 ft8.0x2.0 5 Room area 156.0 ft²16.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 121 106 424 232 19 19 74 41 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 15 15 273 225 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 156 156 247 213 16 16 25 22 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 156 13 494 0 16 2 76 0 6 c) AED excursion -72 -4 Envelope loss/gain 1439 598 176 59 12 a) Infiltration 238 64 37 10 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 730 0 Subtotal (lines 6 to 13)1677 1392 213 69 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 131 55 -213 -69 14 Subtotal 1808 1447 0 0 15 Duct loads 29%55%530 800 29%55%0 0 Total room load 2338 2246 0 0 Air required (cfm)Air required (cfm)96 101 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 CLST 2 2 Exposed wall 9.0 ft 2.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft8.0x9.0 ft8.0x2.0 5 Room area 72.0 ft²16.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 84 76 303 166 19 19 74 41 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 8 8 146 120 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 72 72 114 99 16 16 25 22 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 72 9 342 0 16 2 76 0 6 c) AED excursion -31 -4 Envelope loss/gain 905 353 176 59 12 a) Infiltration 165 44 37 10 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 200 0 Subtotal (lines 6 to 13)1070 597 213 69 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 237 89 -213 -69 14 Subtotal 1307 686 0 0 15 Duct loads 29%55%383 379 29%55%0 0 Total room load 1691 1066 0 0 Air required (cfm)Air required (cfm)69 48 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BEDROOM 2 HALL 2 Exposed wall 20.0 ft 0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft12.0x14.0 ft4.0x13.0 5 Room area 168.0 ft²52.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 130 115 461 252 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 15 15 273 225 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 56 56 223 122 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 168 168 266 230 52 52 82 71 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 168 20 760 0 52 0 0 0 6 c) AED excursion -75 -4 Envelope loss/gain 1985 754 82 68 12 a) Infiltration 366 98 0 0 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 600 0 Subtotal (lines 6 to 13)2351 1452 82 68 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 117 43 -82 -68 14 Subtotal 2468 1495 0 0 15 Duct loads 29%55%724 826 29%55%0 0 Total room load 3192 2322 0 0 Air required (cfm)Air required (cfm)131 105 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Apr-23 14:01:48 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 9 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Right-J® Worksheet Apr 23, 2021Date:Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name FAMILY RM CABANA BATH 2 Exposed wall 40.0 ft 18.0 ft 3 Room height 10.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft330.0x1.0 ft31.0x1.0 5 Room area 330.0 ft²31.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 227 193 773 422 56 38 152 83 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 .GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 18 0 325 268 11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 34 0 610 502 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 21 21 82 45 56 50 199 109 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 6 6 109 90 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0 WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 165 145 580 317 56 56 223 122 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 20 1 364 648 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0 CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 330 330 523 451 31 31 49 42 FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 330 40 1521 0 31 18 684 0 6 c) AED excursion 73 -40 Envelope loss/gain 4453 2459 1743 675 12 a) Infiltration 812 217 330 88 b) Room ventilation 0 0 0 0 13 Internal gains:Occupants @ 230230 0 0 0 0 Appliances/other 300 0 Subtotal (lines 6 to 13)5265 2976 2072 763 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 16 14 0 0 14 Subtotal 5281 2990 2072 763 15 Duct loads 29%55%1549 1653 29%55%608 422 Total room load 6830 4643 2680 1185 Air required (cfm)Air required (cfm)280 209 110 53 2021-Apr-23 14:01:54 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Job:Duct System Summary Apr 23, 2021Date: Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM Project Information RAY AND AMI CAUSLEY, DON HINKLE CONSTRUCTIONFor: TREE TOP TRAIL, FORT PIERCE, FL 34951 CoolingHeating External static pressure in H2O1.00in H2O1.00 Pressure losses in H2O0in H2O0 Available static pressure in H2O1.00in H2O1.00 Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500 Lowest friction rate in/100ft1.000in/100ft1.000 Actual air flow cfm1600cfm1600 Total effective length (TEL)ft183 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st3115.025.4VlFx0x06.01.00048691691hBATH 2 st3115.036.4VlFx0x07.01.0001051313192hBEDROOM 2 st3115.035.4VlFx0x07.01.000101962246cBEDROOM 3 st3115.045.4VlFx0x06.01.000531102680hCABANA BATH st1115.035.2VlFx0x08.01.0001511153342cDINING RM st1115.042.4VlFx0x07.01.0001051403415hFAMILY RM st1115.031.8VlFx0x07.01.0001051403415hFAMILY RM-A st2115.025.3VlFx0x08.01.0001571103494cFOYER/LIVING RM st2115.027.3VlFx0x08.01.0001571103494cFOYER/LIVING RM-A st1115.029.3VlFx0x08.01.000143483184cKITCHEN 95.03.6VlFx0x07.01.000104802302cLAUNDRY RM st4135.045.1VlFx0x06.01.000731263077hM BATH st4135.047.7VlFx0x05.01.00028671628hM TOILET st4135.040.2VlFx0x06.01.0004871055cM WIC st4135.046.9VlFx0x07.01.0001111253042hMASTER BEDROOM st4135.044.6VlFx0x07.01.0001111253042hMASTER BEDROOM-A Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 443 503 1.000 640 12.0 0x0 VinlFlx st4 Peak AVF 450 372 1.000 825 10.0 0x0 VinlFlx st2 st2 Peak AVF 671 686 1.000 642 14.0 0x0 VinlFlx st3 Peak AVF 406 307 1.000 745 10.0 0x0 VinlFlx 2021-Apr-23 14:01:54 Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2 E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb1 0x 16000 1600 0 0 0 0 x0 0 VlFx ��������������������������������������������������������������������������� ��������������������������������������������������������������������������������� �����������������������������������������������������