HomeMy WebLinkAboutAPPROVED CAUSLEY- MANUAL J (1)Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Project Summary Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
Project Information
RAY AND AMI CAUSLEY, DON HINKLE CONSTRUCTIONFor:
TREE TOP TRAIL, FORT PIERCE, FL 34951
Notes:
Design Information
Fort Pierce, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F42 Outside db °F90
Inside db °F70 Inside db °F75
Design TD °F28 Design TD °F15
Daily range M
Relative humidity %50
Moisture difference gr/lb61
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh30156 Struc ture Btuh22878
Ducts Btuh8842 Ducts Btuh12646
Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0
(none)(none)
Humidification Btuh0 Blower Btuh0
Piping Btuh0
Equipment load Btuh38998 Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load Btuh33747
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average
0Fireplaces Structure Btuh5000
Ducts Btuh3495
Central vent (0 cfm)Btuh0
CoolingHeating (none)
25452545Area (ft²)Equipment latent load Btuh8495
2692726927Volume (ft³)
Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh42242
Equiv. AVF (cfm)72144 Req. total capacity at 0.70 SHR ton4.0
Heating Equipment Summary Cooling Equipment Summary
Make Make Carrier
Trade Trade CARRIER
Model Cond 24ACB748A00310
AHRI ref Coil FV4CNB006L
AHRI ref 10360207
Efficiency 100 EFF Efficiency 13.0 EER, 17 SEER
Heating input kW10.0 Sensible cooling Btuh33600
Heating output Btuh34211 Latent cooling Btuh14400
Temperature rise °F19 Total cooling Btuh48000
Actual air flow cfm1600 Actual air flow cfm1600
Air flow factor cfm/Btuh0.041 Air flow factor cfm/Btuh0.045
Static pressure in H2O1.00 Static pressure in H2O1.00
Space thermostat Load sensible heat ratio 0.81
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name Entire House MASTER BEDROOM
2 Exposed wall 216.9 ft 35.0 ft
3 Room height 10.6 ft 10.3 heat/coolft
4 Room dimensions ft296.0x1.0
5 Room area 2545.0 ft²296.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 617 539 2159 1180 185 165 662 362
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 6 0 109 90 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 20 0 364 300 20 0 364 300
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 18 0 325 268 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 34 0 610 502 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 438 348 1392 761 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 12 1 218 385 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 45 3 819 1459 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 13 1 244 439 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 20 1 366 659 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 532 468 1874 1024 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 6 6 109 90 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 8 8 146 120 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 30 30 546 450 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 20 20 366 301 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 657 574 2297 1255 175 142 569 311
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 20 1 364 648 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 30 2 546 973 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 33 2 600 1079 33 2 600 1079
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 2545 2545 4035 3482 296 296 469 405
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 2545 217 8248 0 296 35 1331 0
6 c) AED excursion 0 281
Envelope loss/gain 25737 15464 3995 2738
12 a) Infiltration 4419 1184 710 190
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 6230 250
Subtotal (lines 6 to 13)30156 22878 4705 3178
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 30156 22878 4705 3178
15 Duct loads 29%55%8842 12646 29%55%1380 1757
Total room load 38998 35524 6085 4935
Air required (cfm)Air required (cfm)1600 1600 250 222
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name M BATH M WIC
2 Exposed wall 20.9 ft 0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft156.0x1.0 ft84.0x1.0
5 Room area 156.0 ft²84.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 84 84 335 183 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 112 100 399 218 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 12 1 218 385 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 156 156 247 213 84 84 133 115
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 156 21 795 0 84 0 0 0
6 c) AED excursion -52 -35
Envelope loss/gain 1995 948 133 80
12 a) Infiltration 385 103 0 0
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 600
Subtotal (lines 6 to 13)2380 1051 133 680
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 2380 1051 133 680
15 Duct loads 29%55%698 581 29%55%39 376
Total room load 3077 1632 172 1055
Air required (cfm)Air required (cfm)126 73 7 48
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 3
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name M TOILET FOYER/LIVING RM
2 Exposed wall 12.0 ft 20.0 ft
3 Room height 9.3 heat/coolft 14.0 heat/coolft
4 Room dimensions ft32.0x1.0 ft20.0x19.0
5 Room area 32.0 ft²380.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 65 59 237 129 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 6 0 109 90 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 47 47 186 102 280 202 807 441
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 45 3 819 1459
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 13 1 244 439
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 20 1 366 659
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 32 32 51 44 380 380 603 520
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 32 12 456 0 380 20 760 0
6 c) AED excursion -21 -177
Envelope loss/gain 1039 344 3598 3341
12 a) Infiltration 220 59 552 148
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 1000
Subtotal (lines 6 to 13)1259 403 4150 4488
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 14 11
14 Subtotal 1259 403 4164 4500
15 Duct loads 29%55%369 223 29%55%1221 2487
Total room load 1628 625 5385 6987
Air required (cfm)Air required (cfm)67 28 221 315
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 4
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name DINING RM KITCHEN
2 Exposed wall 12.0 ft 4.0 ft
3 Room height 14.0 heat/coolft 9.3 heat/coolft
4 Room dimensions ft12.0x15.0 ft20.0x15.0
5 Room area 180.0 ft²300.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 168 138 553 302 37 37 149 81
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 30 2 546 973 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 180 180 285 246 300 300 476 410
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 180 12 456 0 300 4 152 0
6 c) AED excursion 343 -104
Envelope loss/gain 1840 1863 777 388
12 a) Infiltration 331 89 73 20
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 200 1600
Subtotal (lines 6 to 13)2171 2152 850 2007
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 53 43
14 Subtotal 2171 2152 903 2051
15 Duct loads 29%55%637 1190 29%55%265 1134
Total room load 2808 3342 1168 3184
Air required (cfm)Air required (cfm)115 151 48 143
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 5
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name HALLWAY LAUNDRY RM
2 Exposed wall 0 ft 9.0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft12.0x5.0 ft24.0x9.0
5 Room area 60.0 ft²216.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 0 0 0 0 84 64 255 139
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 20 20 366 301
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 60 60 95 82 216 216 342 296
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 60 0 0 0 216 9 342 0
6 c) AED excursion -4 -75
Envelope loss/gain 95 78 1305 661
12 a) Infiltration 0 0 165 44
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 750
Subtotal (lines 6 to 13)95 78 1470 1455
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -95 -78 34 28
14 Subtotal 0 0 1504 1482
15 Duct loads 29%55%0 0 29%55%441 819
Total room load 0 0 1944 2302
Air required (cfm)Air required (cfm)0 0 80 104
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 6
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name BEDROOM 3 CLST 3
2 Exposed wall 13.0 ft 2.0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft12.0x13.0 ft8.0x2.0
5 Room area 156.0 ft²16.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 121 106 424 232 19 19 74 41
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 15 15 273 225 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 156 156 247 213 16 16 25 22
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 156 13 494 0 16 2 76 0
6 c) AED excursion -72 -4
Envelope loss/gain 1439 598 176 59
12 a) Infiltration 238 64 37 10
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 730 0
Subtotal (lines 6 to 13)1677 1392 213 69
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 131 55 -213 -69
14 Subtotal 1808 1447 0 0
15 Duct loads 29%55%530 800 29%55%0 0
Total room load 2338 2246 0 0
Air required (cfm)Air required (cfm)96 101 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 7
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name BATH 2 CLST 2
2 Exposed wall 9.0 ft 2.0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft8.0x9.0 ft8.0x2.0
5 Room area 72.0 ft²16.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 84 76 303 166 19 19 74 41
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 8 8 146 120 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 72 72 114 99 16 16 25 22
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 72 9 342 0 16 2 76 0
6 c) AED excursion -31 -4
Envelope loss/gain 905 353 176 59
12 a) Infiltration 165 44 37 10
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 200 0
Subtotal (lines 6 to 13)1070 597 213 69
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 237 89 -213 -69
14 Subtotal 1307 686 0 0
15 Duct loads 29%55%383 379 29%55%0 0
Total room load 1691 1066 0 0
Air required (cfm)Air required (cfm)69 48 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 8
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name BEDROOM 2 HALL
2 Exposed wall 20.0 ft 0 ft
3 Room height 9.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft12.0x14.0 ft4.0x13.0
5 Room area 168.0 ft²52.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 130 115 461 252 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 15 15 273 225 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 56 56 223 122 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 168 168 266 230 52 52 82 71
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 168 20 760 0 52 0 0 0
6 c) AED excursion -75 -4
Envelope loss/gain 1985 754 82 68
12 a) Infiltration 366 98 0 0
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 600 0
Subtotal (lines 6 to 13)2351 1452 82 68
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 117 43 -82 -68
14 Subtotal 2468 1495 0 0
15 Duct loads 29%55%724 826 29%55%0 0
Total room load 3192 2322 0 0
Air required (cfm)Air required (cfm)131 105 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Apr-23 14:01:48
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 9
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Right-J® Worksheet
Apr 23, 2021Date:Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
1 Room name FAMILY RM CABANA BATH
2 Exposed wall 40.0 ft 18.0 ft
3 Room height 10.3 heat/coolft 9.3 heat/coolft
4 Room dimensions ft330.0x1.0 ft31.0x1.0
5 Room area 330.0 ft²31.0 ft²
Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load
number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 13A-4ocs13A-4ocs 0.1430.143 nn 4.004.00 2.192.19 227 193 773 422 56 38 152 83
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
.GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 0 0 0 0 18 0 325 268
11 GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 nn 18.2018.20 14.9914.99 34 0 610 502 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ee 4.004.00 2.192.19 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.0832.08 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ee 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ss 4.004.00 2.192.19 21 21 82 45 56 50 199 109
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 6 6 109 90
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ss 18.2018.20 14.9914.99 0 0 0 0 0 0 0 0
WW 13A-4ocs13A-4ocs 0.1430.143 ww 4.004.00 2.192.19 165 145 580 317 56 56 223 122
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 20 1 364 648 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.4232.42 0 0 0 0 0 0 0 0
GG 2 glazing, clr low-e 0.6502 glazing, clr low-e 0.650 ww 18.2018.20 32.7632.76 0 0 0 0 0 0 0 0
CC 16X19-0md16X19-0md 0.4080.408 --1.591.59 1.371.37 330 330 523 451 31 31 49 42
FF 22A-tph22A-tph 1.3581.358 --38.0238.02 0.000.00 330 40 1521 0 31 18 684 0
6 c) AED excursion 73 -40
Envelope loss/gain 4453 2459 1743 675
12 a) Infiltration 812 217 330 88
b) Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 300 0
Subtotal (lines 6 to 13)5265 2976 2072 763
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 16 14 0 0
14 Subtotal 5281 2990 2072 763
15 Duct loads 29%55%1549 1653 29%55%608 422
Total room load 6830 4643 2680 1185
Air required (cfm)Air required (cfm)280 209 110 53
2021-Apr-23 14:01:54
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 1
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Job:Duct System Summary Apr 23, 2021Date:
Entire House By:
QUICK CALCS, INC.
317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax: 772-466-6796 Email: QUICKCALCS@AOL.COM
Project Information
RAY AND AMI CAUSLEY, DON HINKLE CONSTRUCTIONFor:
TREE TOP TRAIL, FORT PIERCE, FL 34951
CoolingHeating
External static pressure in H2O1.00in H2O1.00
Pressure losses in H2O0in H2O0
Available static pressure in H2O1.00in H2O1.00
Supply / return available pressure 0.500 / 0.500 in H2O in H2O0.500 / 0.500
Lowest friction rate in/100ft1.000in/100ft1.000
Actual air flow cfm1600cfm1600
Total effective length (TEL)ft183
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st3115.025.4VlFx0x06.01.00048691691hBATH 2
st3115.036.4VlFx0x07.01.0001051313192hBEDROOM 2
st3115.035.4VlFx0x07.01.000101962246cBEDROOM 3
st3115.045.4VlFx0x06.01.000531102680hCABANA BATH
st1115.035.2VlFx0x08.01.0001511153342cDINING RM
st1115.042.4VlFx0x07.01.0001051403415hFAMILY RM
st1115.031.8VlFx0x07.01.0001051403415hFAMILY RM-A
st2115.025.3VlFx0x08.01.0001571103494cFOYER/LIVING RM
st2115.027.3VlFx0x08.01.0001571103494cFOYER/LIVING RM-A
st1115.029.3VlFx0x08.01.000143483184cKITCHEN
95.03.6VlFx0x07.01.000104802302cLAUNDRY RM
st4135.045.1VlFx0x06.01.000731263077hM BATH
st4135.047.7VlFx0x05.01.00028671628hM TOILET
st4135.040.2VlFx0x06.01.0004871055cM WIC
st4135.046.9VlFx0x07.01.0001111253042hMASTER BEDROOM
st4135.044.6VlFx0x07.01.0001111253042hMASTER BEDROOM-A
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st1 Peak AVF 443 503 1.000 640 12.0 0x0 VinlFlx
st4 Peak AVF 450 372 1.000 825 10.0 0x0 VinlFlx st2
st2 Peak AVF 671 686 1.000 642 14.0 0x0 VinlFlx
st3 Peak AVF 406 307 1.000 745 10.0 0x0 VinlFlx
2021-Apr-23 14:01:54
Right-Suite® Universal 2021 21.0.02 RSU08101 Page 2
E:\Documnets\Wrightsoft HVAC\CAUSLEY R ESIDENCE.rup Calc = MJ8 Front Door faces: E
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb1 0x 16000 1600 0 0 0 0 x0 0 VlFx
���������������������������������������������������������������������������
���������������������������������������������������������������������������������
�����������������������������������������������������