Dated: November 28,2018 Job Order# R18941
ACR1.Com Commercial Roofing RECEIVED
1924 N. Elm Street
Muncie,IN 47303
Attn: Elaine Newnum DEC - 3 2018
RE: Field Withdrawal Resistance Test
Permitting Department
Grose's Interstate Moving St. Lucie Count FL
1270 Grose Road y�
Ft. Pierce,FL 34982
Dear: Sirs:
Pursuant to your request, Federal Engineering & Testing, Inc. (FE&T) has performed a field withdrawal resistance
test in compliance with Testing Application Standard TAS-105 and the Florida Building Code High Velocity
Hurricane Zone at the above referenced site. The purpose of our test was to determine the uplift capacity of the
mechanical fasteners at the above referenced project. FE&T is a Miami Dade Certified Testing Laboratory
(Certification#16-0203.07).
On 11/28/2018 our field representative visited the referenced site and conducted ten (10) field withdrawal resistance
tests on the HDP #14 screw fasteners into the metal roof deck. All tests were found in compliance with the Florida
Building Code and TAS-105. See attached copies of TAS-105 forms with test results.
The test results presented reflect the condition of the roof system at the time of the test. These results are time and
sample dependent since roof conditions are continuously changing due to exposure to the elements. All tests were
conducted according to the Florida Building Code Test Protocol TAS-105 using a calibrated Comten Industries
Fastener Tester Model No.DFG 2W2000 (see attached calibration).
FE&T is an independent third party providing un-biased testing information and results. FE&T is not affiliated
ated with
our client nor do we have any financial interest in the project or determination of the test results.
Federal Engineering& Testing, Inc., appreciates the opportunity to be of service to you at this phase of your project.
If you have any questions or comments, please give us a call. It has been a pleasure working with you and look
forward to doing so in the near future.
Sincerely,
Keith LeBlanc, P.E. �� Z d/i�` Attachments include the following:
0 1Testing,F_dera �n ir,,;erin and Inc. Field Withdrawal Resistance Test Results
g S
Florida Reg.Number 59394 Field Sketch
Certificate of Authorization#5471 Comten Calibration
Miami-Lade County Certification# 16-0203.07
ederaI
. ngineering
Florida Building Code Test Protocol TAS-105 ®Oesting, Inc.
Building Code Compliance Office
Testing Application Standard TAS 105-11
Field Withdrawal Resistance Test Results
General Information:
Job Name: Grose's Interstate Moving
Job Address: 1270 Grose Road
Ft.Pierce,FL 34982
Contact Individual
at jobsite(if any) Elaine Newnum
Testing Agency/Equipment Information:
Note: The undersigned acknowledges that all testing has been conducted and results have
been reported in compliance with Florida Building Code Test Protocol TAS-105
Testing Agency Name: Federal Engineering&Testing Inc.
Company Address: 250 SW 13th Ave Pompano Beach,FL 33069
Company Telephone: (954)784-2941
Company Fax: (954) 784-7875
Representative Name: Mr.Keith LeBlanc P.E.
Representative Title: Professional Engineer
Signature: �J
Testing Apparatus: Comten Industries Fastener Tester Modef DFG2 W2000
i
• Q ederal
Q ngineering
Building/Roof System Information: Area Number: 1 & Q esting, Inc.
Roof Area Height 21 ft.
Roof Area Length 59 ft.
Second Largest Dimension 50 ft.
Total Roof Area 2950 ft2
30 sq.
Perimeter Area 945 ft2
(See RAS 117)
Building/Roof System Information: Area Number:
Roof Area Height ft.
Roof Area Length ft.
Second Largest Dimension ft.
Total Roof Area ft2
sq.
Perimeter Area ft2
(See RAS 117)
Building/Roof System Information: Area Number:
Roof Area Height ft.
Roof Area Length ft.
Second Largest Dimension ft.
Total Roof Area ft2
sq.
Perimeter Area ft2
(See RAS 117)
• • oQ ederal
OQ ngineering
®OQ esting, Inc.
Field Withdrawal Resistance Recording Sheet
Component to be secured: Area Number 1
❑ Insulation (Refer to deck dimensions on Page No.2)
❑ Membrane Fastener Type: #14
❑ Anchor or Basesheet Fastener Manufacturer: HDP
❑ Woodblocking Predrilled: Yes ❑ No 21
❑ Metal Profiles If Yes,Drill Bit Size: N/A "diameter
0 Resistance Verification Only Hole Depth: N/A
See Section 8 to determine number of tests(if drill is high tolerance include range in 1/1000"tolerance)
Sample& Plan Initial Failure Sample& Plan Initial Failure
Identifier Load (Ibf) Roof Area Identifier Load (lbf) Roof Area
1 310 C 26
2 263 C 27
3 305 C 28
4 283 C 29
5 311 P 30
6 297 P 31
7 283 P 32
8 296 P 33
9 228 F 34
10 295 F 35
11 36
12 37
13 38
14 39
15 40
16 41
17 42
18 43
19 44
20 45
21 46
22 47
23 48
24 49
25 50
Fastener Installation Information:
Is the fastener a self driller? Yes ❑ No
If yes, list the type of tool used for fastener installation: Cordless Drill
Speed of tool: Variable rpm's
Number of tests conducted: n= 10
* See Section 8 of Test Protocol TAS 105
* Note the locations of all tests on'Building Information"Detail#1,attached)
• • Oederal
Q ngineering
& OQ esting, Inc.
Mean Failure Load F= 287.10 lbf
Sample Standard Deviation Sf= 25.30 lbf
Minimum Characteristic Resistance Force F'= 275.73 lbf
Notes:
1)Use of the results herein to determine the required number of fasteners for insulation attachment or an acceptable anchor or base sheet
fastener spacing,as outlined in RAS 117,shall utilize the minimum characteristic resistance force(F'),determined in compliance with
Section 9 of TAS 105.No margin of safety shall be applied to field withdrawal resistance test results determined in compliance with
TAS 105.
2) A safety factor of 2 to 1 shall be applied to all results of laboratory testing.
3) The following pages shall be completed for each roof area and included with all Field Withdrawal Resistance Test Recording Sheets.
Roof Area 1
(If no parapet wall exists insert"N/A")
N/A
21 Feet
Ground Level
Building Information- Detail# 1