HomeMy WebLinkAboutFire Sprinkler PlansALL MATERIAL APPLICABLE TO THIS PROJECT WILL is DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH 2O13 EDITION OF NFPA 13D. BE INDICATED WITH A (g/) • DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH ALL APPLICABLE LOCAL AND STATE CODES. • DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH 2O13 EDITION OF NFPA 13D, LOCAL • ALL PIPE AND FITTINGS USED ON THIS PROJECT TO BE IN ACCORDANCE WITH APPLICABLE CODES AND PLUMBING CODE AND ALL APPLICABLE LOCAL AND STATE CODES. WAFS STANDARDS. SEE PIPE AND FITTINGS GENERAL NOTES (WAFS DETAIL #00593N). ♦ALL PLASTIC PIPE / • ALL HANGERS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NFPA 13D AND THEIR LISTING. ALL PLASTIC PIPE 3/4" THROUGH 2%2" SHALL BE UL LISTE OR FM APPROVED CPVC MANUFACTURED IN 34" THROUGH 2Y2' SHALL BE UL LISTED OR FM APPROVED CPVC ACCORDANCE WITH ASTM F-442MANUFACTURED IN ACCORDANCE WITH F442. • ALL PENETRATIONS THROUGH RATED BUILDING ASSEMBLIES SHALL BE SEALED WITH FIRE CAULK IN • ALL PLASTIC FITTINGS SHALL BE UL LISTED OR FM APPROVED CPVC MANUFACTURED IN . ACCORDANCE WITH DETAILS PROVIDED. WAFS POLICY IS TO USE HILTI F S ONE OR STI LEI. ALL PLASTIC FITTINGS SHALL BE UL LISTED OR FM APPROVED (PVC MANUFACTURED IN ACCORDANCE ACCORDANCE WITH ASTM F438 ASTM F439 OR ASTM F1970. • UNDERGROUND MAINS AND LEAD-INS SHALL BE FLUSHED AND SIGNED TEST CERTIFICATES PROVIDED WITH ASTM F438, ASTM F439 OR ASTM F1970. BEFORE A CONNECTION IS MADE TO THE SPRINKLER SYSTEM. • ALL CPVC PIPE AND FITTINGS SHALL BE ASSEMBLED USING 'ONE STEP" 500 CEMENT. • ALL STEEL PIPE WILL BE SCHEDULE 40 HOT DIPPED GALVANIZED MANUFACTURED IN ACCORDANCE His WHEN SYSTEM IS FED USING PLUMBING SERVICE, PIPING SHALL STILL BE FLUSHED PRIOR TO (� ALL (PVC PIPE AND FITTINGS SHALL BE ASSEMBLE -US G ' E STEP' 500 CEMENT. WITH ASTM A795 OR ASTM A-53. CONNECTING THE SPRINKLER SYSTEM. • ALL PIPING SHALL BE INSPECTED AND APPROVED BY PROPER AUTHORITIES PRIOR TO COVERING WITH � CPVC PIPE SHALL BE ALLOWED TO BE USED IN ORDINARY HAZ. D ROOMS OF 400 SQUARE FEET OR • ALL THREADED FITTINGS SHALL BE GALVANIZED MALLEABLE IRON CLASS 150 OR CLASS 300 DRYWALL. COPIES OF SIGNED TEST CERTIFICATES ARE TO BE FORWARDED TO THE PROPER RECIPIENTS. LESS OF OTHERWISE LIGHT HAZARD OCCUPANCIES (NFPA 13 5E TION 6.3.6.2 OR NFPA 13R SECTION AND SHALL BE MANUFACTURED IN ACCORDANCE WITH ANSI 816.3 AND ASTM A 153. • ALL SYSTEMS SHALL BE TESTED AT 200 PSI FOR 2 HOURS PER WAFS STANDARDS. 5.2.2.3). • ALL GROOVED FITTINGS SHALL BE UL LISTED OR FM APPROVED AND MANUFACTURED IN • ALL SOFFITS REQUIRED TO CONCEAL SPRINKLER PIPING ARE BY OTHERS. ACCORDANCE WITH ASTM A-536 FOR DUCTILE IRON OR ASTM A-47 FOR MALLEABLE IRON. • ALL WIRING OF DEVICES IF PROVIDED (FLOW SWITCHES, TAMPER SWITCHES, ETC) IS BY OTHERS. ❑ ALL 1" TO 2" THREADED BLACK STEEL PIPE SHALL BE 4EIEDDYTHREAD' LISTED/FM APPROVED AND MANUFACTURED • BRASS PIPE AND FITTINGS WILL BE UTILIZED ONLY AS REQUIRED BY LOCAL WATER PURVEYOR. • CONTROL VALVES SHALL NOT BE REQUIRED TO BE MONITORED PER IN ACCORDANCE WITH ASTM A-135 OR A-795. ACCEPTLE PIPE BRANDS ARE WHEATLAND • WAFS TO PROVIDE CPVC COMPATIBLE 14 GAUGE TRACING WIRE ON ALL UNDERGROUND PIPING. o IN FLORIDA FBC 903.4 (1) 'MEGATHREAD', ALLIED 'DYNATHREAD', BULL MOOSE TUBAND WELDED TUBE-BERKELEY • UNDERGROUND MAINS AND LEAD-INS SHALL BE FLUSHED AT 100% AVAILABLE PRIOR TO D IN NORTH CAROLINA NCBC 901.6.1 (1) 'STEADY -THREAD'. ALL PIPE SHALL BE CPVC COMPATIBLE. CONNECTING TO OVERHEAD PIPING. • LOCAL WATERFLOW ALARMS SHALL BE PROVIDED ON ALL SPRINKLER SYSTEMS IN HOMES NOT • ALL PIPING SHALL BE BURIED A MINIMUM OF 30 INCHES BELOW GRADE TO THE TOP OF THE PIPE EQUIPPED WITH SMOKE ALARMS OR SMOKE DETECTORS IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE n ALL I" TO 2" THREADED GALVANIZED PIPE WILL BE SCHEDULE 40 HOT DIPPED GALVANIZED PER WAFS COMPANY STANDARDS. ALARM CODE. MANUFACTURED IN ACCORDANCE WITH ASTM A-795 OR ASTM A-53. • ALL PIPING UNDER ROADWAYS SHALL BE BURIED A MINIMUM OF 36 INCHES BELOW GRADE TO THE • CONNECTION OF SPRINKLER DEVICES TO THE BUILDING ALARM OR MONITORING SYSTEM, IF PROVIDED, IS ALL )" TO 2' THREADED BLACK STEEL PIPE SHALL BE SCHEDULE 40 UL LISTED/FM APPROVED AND TOP OF THE PIPE. BY OTHERS. • ALL PIPING SHALL BE INSPECTED AND APPROVED BY PROPER AUTHORITIES PRIG MANUFACTURED IN ACCORD ANCE WITH ASTM A-795. ACCEPT R TO COVERING. • ABLE PIPE MANUFACTURERS ARE ALL PAINTING OF PIPE AS RE QUIRED IS BY OTHERS. WHEATLAND ALLIED BULL MOOSE • ALL PIPING SHALL BE TESTED AT 200 PSI FOR 2 HOURS PER OAFS STANDARDS. 0 E TUBE AND WELDED TUBE-BERKELEY. • ALL PIPE SHALL BE (PVC ALL INSULATION REQUIRE D FOR FREEZE PROTECTION OF SPRINKLER PIPING IS BY OTHERS. ER . • HEATING OF ROOMS TO MAINTAIN TEMPERATURES OF 40 DEGREES OR GREATER I COMPATIBLE. • VALVES SHALL NOT BE REQUIRED TO BE MONITORED PER FLORIDA BUILDING CODE 903.4 (1). • SPRINKLERS SHALL NOT LI INSTALLED PRIOR TO THE FITTINGS BEING CEMENTED I • ALL PAINTING OF PIPE AS REQUIRED IS BY OTHERS. R BY OTHERS. N PLACE. ALL IV4 TO 4- GROOVED BLACK STEEL PIPE SHALL BE LISTED/FM APPROVED AND MANUFACTURED • WAFS TO PROVIDE ALL NECESSARY SIGNAGE INCLUDING BUT NOT LIMITED TO VALVES AND • ALL SPRINKLERS IN DWELLING UNITS SHALL BE UL LISTED OR FAPPROVED RESIDENTIAL SPRINKLERS. ❑ IN ACCORDANCE WITH ASTM A795. ACCEPTABLE BRANDS ARE BULL MOOSE 'EDDYFLOW', WHEATLAND HYDRAULIC PLACARDS. • SPARE SPRINKLERS WILL NOT BE PROVIDED AS THEY ARE NOT REQUIRED BY NFPA 13D. 'MEGA -FLOW'. ALLIED 'DYNA-FLOW' AND WELDED TUBE-B RKELEY 'STEADY -FLOW'. ALL PIPE SHALL BE • SEE CIVIL DRAWINGS FOR DETAILS OF PIPING PRIOR TO WAYNE AUTOMATIC'S POINT OF • SPRINKLERS SHALL BE INSTALLED IN ALL AREAS EXCEPT AS FOLLOWS: • REFER TO SPACING NOTES PLANS FOR MAXIMUM CALCULATED SPACING ALLOWANCES. CPVC COMPATIBLE. ECONNECTION. o BATHROOMS WHERE THE AREA DOES NOT EXCEED 55 SD FT. ALL 1!'s" TO 4" GROOVED BLACK STEEL PIPE SHALL BE SCHEDULE 10. UL LISTED/FM APPROVED AND • PER FLORIDA STATUTE 633.334, ALL UNDERGROUND FROM THE POINT OF SERVICE TO 1'-0" AFF OR CLOTHES CLOSETS, LINEN CLOSETS AND PANTRIES WITHIN THE DWELLING UNITS THAT 00 NOT SHALL BE INSTALLED BY ONE CLASS I, II OR V LICENSED CONTRACTOR. EXCEED 24 SQUARE FEET, THE LEAST DIMENSION DOES NOT EXCEED 3 FEET, AND THE WALLS AND MOOSE, WHEATLACTURED ND, ACCORDANCE WITH ASTM A -BEFI ACCEPTABLE MANUFACTURERS ARE BULL • ALL FERROUS PIPE AND FITTINGS SHALL BE EXTERNALLY WRAPPED AND COATED WITH A CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE OR LIMITED -COMBUSTIBLE MATERIALS AS DEFINED MOOSE. WHEATLAND, ALLIED AND WELDED TUBE-BERKELEY. ALL PIPE SHALL BE (PVC COMPATIBLE. BITUMINOUS COATING. BY NFPA 220, STANDARD ON TYPES OF BUILDING CONSTRUCTION. ALL GROOVED STEEL PIPE 6' AND LARGER SHALL BE UL LISTED/FM APPROVED SCHEDULE 10 AND OR CLEARANCES AROUND FIRE PROTECTION APPLIANCES SHALL BE PROVIDED AS REQUIRED BY LOCAL o ANY GARAGES, OPEN ATTACHED PORCHES, CARPORTS AND SIMILAR STRUCTURES. MANUFACTURED IN ACCORDANCE WITH ASTM A-135. AUTHORITY. o ATTICS. PENTHOUSE EQUIPMENT ROOMS, ELEVATOR MACHINE ROOMS, CONCEALED SPACES DEDICATED EXCLUSIVELY TO AND CONTAINING ONLY DWELLING UNIT VENTILAION EQUIPMENT, FLOOR/CEILING ❑ ALL GROOVED STEEL PIPE IY4" AND LARGER SHALL BE SCHEDULE TO HOT DIPPED GALVANIZED AND SPACES, ELEVATOR SHAFTS, CRAWL SPACES, AND OTHER CONCEALED SPACES THAT ARE NOT USED MANUFACTURED W ACCORDANCE WITH ASTM A-795. OR INTENDED FOR LIVING PURPOSES AND DO NOT CONTAIN FUEL -FIRED EQUIPMENT. o COVERED UNHEATED PROJECTIONS OF THE BUILDING AT ENTRANCES/EXITS AS LONG AS THERE IS ❑ ALL STEEL PIPE SHALL HAVE A CORROSION RESISTANCE RATIO'( (CRR) OF NOT LESS THAN 1.0 PER ANOTHER MEANS OF EGRESS FROM THE DWELLING UNIT. WAFS STANDARDS. o SPRINKLERS SHALL NOT BE REQUIRED FOR CEILING POCKETS THAT MEET THE FOLLOWING CONDITIONS: 1. THE TOTAL VOLUME OF UNPROTECTED CEILING POCKET DOES NOT EXCEED 100 CU, FT. ❑ ALL BLACK THREADED FITTINGS SHALL BE DUCTILE IRON: CLASS 150 OR CLASS 300 ANSI B16.3, CAST 2. THE ENTIRE FLOOR UNDER THE UNPROTECTED CEILING POCKET IS PROTECTED BY THE SPRINKLERS IRON CLASS 125 OR CLASS 250 ANSI B16.4 OR MALLEAB.IE IRON CLASS 150 OR CLASS 300 ANSI AT THE LOWER CEILING ELEVATION. B16.3. 3. THE INTERIOR FINISH OF THE UNPROTECTED CEILING POCKET IS NONCOMBUSTIBLE OR LIMITED -COMBUSTIBLE MATERIAL. ❑ ALL GALVANIZED THREADED FITTINGS SHALL BE MALLEABLE IRON CLASS 150 OR CLASS 300 ANSI 4. SKYLIGHTS NOT EXCEEDING 32 SQ. FT. SHALL BE PERMITTED TO HAVE A PLASTIC COVER. 816.3 WITH GALVANIZED COATING IN ACCORDANCE WITH ASTM A-153. • WAFS TO PROVIDE ALL REQUIRED SIGNAGE PER NFPA 130. • DEVICES THAT RESTRICT THE FLOW OR DECREASE THE PRESSURE OR AUTOMATICALLY SHUT OFF THE ❑ ALL WELDED OUTLETS SHALL BE UL LISTED OR FM APPROVED AND MANUFACTURED IN ACCORDANCE WATER TO THE SPRINKLER SYSTEM. SUCH AS WATER SOFTENERS, FILTRATION SYSTEMS, AND WITH ANSI 816.11. AUTOMATIC SHUTOFF VALVES. SHALL NOT BE ADDED TO THIS SYSTEM WITHOUT A REVIEW OF THEL ED FITTINGS SHALL BE UL LISTED OR FM APPROVE A MANUFACTURED IN ACCORDANCE WITH FIRE SPRINKLER SYSTEM BY A FIRE PROTECTION SPECIALIST. A-536 FOR DUCTILE IRON OR ASTM A-47 FOR MALLEABLE IRON. LVANIZED GROOVED FITTINGS SHALL BE UL LISTED OR FM APPROVED AND MANUFACTURED IN DANCE WITH ASTM A-536 FOR DUCTILE IRON OR ASTM A-47 FOR MALLEABLE IRON. NIZED COATING SHALL BE IN ACCORDANCE WITH ASTM A-153. OOVED STEEL PIPE SHALL BE ROLL GROOVED PER PIPE MANUFACTURER REQUIREMENTS. NFPA 13D 2013 GENERAL NOTES PIPE AND FITTINGS GENERAL NOTES NFPA 13D 2013 UNDERGROUND GENERAL NOTES A ALE NONE E SCALEI NONE SCALE: NONE ANGgwNsie FM Sprinklers, M. sp'liddma Irm AutBnHwt� Rkro , dm. 00576N 00593N 00325N System No. W-J-2072 F Rating 2 Hr T Rating 2 HIM L Rating at; Ambient - Less Than 1 CFMI ft L Rating at 400 F - 2 CFMI it SECTION A -A 1, WALL ASSEMBLY -MIN 5 IN, (127 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE, WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKSw, MAX DIAM OF OPENING IS 3 IN. (76 MM). SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. 2, THROUGH PENETRANTS -ONE NONMETALLIC PIPE TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM, THE ANNULAR SPACE BETWEEN PIPE AND THE PERIPHERY OF THE OPENING SHALL BE MIN 0 IN. (POINT CONTACT) TO A MAX 5/8 IN. (16 MM), THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES MAY BE USED, A. POLYVINYL CHLORIDE CPVC) PIPE -NOM 2 IN. (51 MM) DIAM (OR SMALLER)CELLULAR OR SOLID CORE SCHEDULE 40 (OR HEAVIER) PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS. B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE -NOM 2 IN. (51 MM) DIAM <OR SMALLER) SDR 13.5 CPVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS. C. CROSSLINKED POLYETHYLENE (PEX) TUBING -NOM 2 IN. (51 HIM) DIAM (OR SMALLER) SDR 9 PEX TUBING FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS, D. RIGID NONMETALLIC CONDUIT (RNC)+ -NOW 2 IN, DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT INSTALLED IN ACCORDANCE WITH ARTICLE 347 OF THE NATIONAL ELECTRICAL CODE, 3. FILL, VOID OR CAVITY MATERIAL* - SEALANT -MIN 5/8 IN, (16 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT POINT CONTACT LOCATION, A MIN 112 IN. (13 MM) DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED TO THE WALL/PENETRANT INTERFACE ON BOTHSURFACESOF THE WALL. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE SEALANT *BEARING THE UL CLASSIFICATION MARK + BEARING THE UL LISTING MARK Ss Reproduced by HILTI, Inc, Courtesy 'y" I F�F of Underwriters Laboratories, Inc. U UL _ June 20, 2000 HNti Firestop Systems FIRE CAULK - HILTI SYSTEM No. W-J-2072 UP TO 2' CPVC 6 CONCRETE OR BLOCK WALL - 2-HOUR SCALE: NOti= Autmneeo Ft® Sprik" . PICK 00201N PERMISSIBLE BENDING DEFLECTIONS SDR 13.5 (739F) NONE E D RESTRAINED) PIPE SIZE INCHES LENGTH OF RUN (L) IN FEET 2' 1 5' 7' 1 10' 12' 15' 17' 20' ' 1.3' 7,8' 15,4' 1 31,3' 45,1' 70,5' 90,6' 125.4' 1' LO' 6,3' 12. ' 1 25,0' 36.00 56,3' 72,3' 100.1' 1$' 018' 5,0' 93 1 19,8' 28,5' 4416' 57.3' 79,3' W 0.7' 43' 8.5 1 17.3' 24.9' 39,0' 50.1' 69,3' 2' 0,6' 3,5' 6.8 13.9, 20.0' 31.2' 40.0, 55AS 2V 0.5' 2,9' 5.6 11.4' 16,5' 25.8' 331' 45.8' 3' OAR 2,4' 4.6 9,4' 13.5' 1 21,2' 1 27,2' 37,6' L FEET D 2 d = 0,329 L - � d INCHES PERMISSIBLE BENDING (BOTH ENDS (DEFLECTIONS SDR 13.5 RESTRAINED) (734F) PIPE SIZE INCHES LENGTH OF RUN (L) IN FEET 2' 5' 7' 1 10' 12' 15' 17' 20' ' 0,3' 2,0' 3,8 7.8' 11.3' 17.6' 22.6' 31,3' 1' 0,3' 1.6' 31' 6,3' 9.0' 14.1' 1811, 25,0' 1!I' 0.2' 1,2' 2.4 5.0' 7.1' 11,2' 14,3' 19.8' 02' 1.1' 2,1' 4.3' 6,2' 9,7' 12,5' 17,3' 2' 0.1' 0.9' 1.7' 3,5' 1 5.0' 7,8' 1 10.0' 13.9' t 0.1' 0,7' 1,4' 2,9' 4.1' 6.4' 8,3' 11,4' 0.1' 0.6' 12' 2.4' 1 3,4' 1 5.3' 1 62' 9.4' d = 0.0823 2 D D L FEET D d INCHES / Fir. Sprinklars. Inc. CPVC BENDING DEFLECTION SCALE: 1' = 2' 00416N CURE TIMES WITH ONE STEP SOLVENT CEMENT 200 PSI (MAXIMUM) TEST PRESSURE (SEE NOTE D PIPE SIZE INCHES AMBIENT TEMPERATURE DURING CURE PERIOD 60OF TO 120°F 40-F TO 59°F ONE TO 396F Y4' 45 MIN. 1.5 HR. 24 HR. 1' 45 MIN. 1.5 HR, 24 HR, 1Y4' 1.5 HR. 16 HR. 120 HR, 1 ' 1.5 HR. 16 HR. 120 HR. 2' 6 HR. 36 HR. SEE NOTE 2 2w 8 HR. 72 HR. SEE NOTE 2 3' 8 HR. 72 HR. SEE NOTE 2 CURE TIMES WITH ONE STEP SOLVENT CEMENT 225 PSI (MAXIMUM) TEST PRESSURE (SEE NOTE 1) PIPE SIZE INCHES AMBIENT TEMPERATURE DURING CURE PERIOD 606F TO 1204E 40'F TO 594E 06F TO 39AF Y4' 1 HR, 4 HR. 48 HR, 1' 1.5 HR. 4 HR, 48 HR. 1Y4' 3 HR, 32 HR. 10 DAYS 1 ' 3 HR 32 HR. 10 DAYS 2' 8 HR. 48 HR. SEE NOTE 2 23Z' 24 HR, 96 HR. SEE NOTE 2 3' 24 HR, 96 HR. SEE NOTE 2 NOTE 1: THESE CURE TIMES ARE FOR NEW CONSTRUCTION. IF GLUING INTO EXISTING PIPING. SUCH AS IN THE CASE OF CUT -INS, CURE TIME SHOULD BE A MINIMUM OF 24 HOURS. NOTE 21 FOR THESE SIZES, THE SOLVENT CEMENT CAN BE APPLIED AT TEMPERATURES BELOW 324F, HOWEVER THE SPRINKLER SYSTEM TEMPERATURE MUST BE RAISED TO A TEMPERATURE OF 320F OR ABOVE AND ALLOWED TO CURE PER THE ABOVE RECOMMENDATIONS PRIOR TO PRESSURE TESTING, Fire Sprinklers, Inc. TYPICAL CPVC CURE TIMES SCAT E. 1' = 2 • 00415N 1' SPLIT RING HANGER- V x V (PVC BUSHING V CPVC BALL VALVE U Aw CL U 1f' CPVC 90 ELL 1f' SPLIT WALL PLATE CPVC 45 ELL GROUND FLOOR Fir. SpPtpkl.rs, lna BRANCH LINE - BRANCH LINE OTR 1' TO FIRE SPRINKLER IM SYSTEM I' CPVC CROSS CPVC U CU 0- 10 (PVC COUPLING W.A,F,S, POINT OF CONNECTION 1HIS 1'-0' A.F.F. - _�---GUAGE KIT (PVC FEMALE ADAPTER WILKINS #700XLFP DUAL -� CHECK VALVE. (LEAD FREE) -1' (PVC FEMALE ADAPTER 1' FIRE SPRINKLER UNDERGROUND BACK TO DOMESTIC WATER MAIN 1' 13D FIRE FIGURE A: TYPICAL ARMOVER WITH ELBOW (LER RISER SCALE: N,T,S, R00316L ARMOVER LENGTH DROP LENGTH FIGURE B: TYPICAL ARMOVER WITH TEE ARMOVER LENGTH CEILING ARMOVER TAII CEILING NOTE; SEE LAYOUT FOR PIPE SIZES & DIMENSIONS, IUNnoo � onesi .j SEE LAYOUT FOR HANGER SIZE, QUANTITY AND LOCATION, 3 MNV11dW00 30 FIELD FIGURECBNDITIONS WILL WILL E USED DONTANY IVENATE EARMOV RE A OR a0� 03IM31n "� TYPICAL ARMOVER CONFIGURATIONS A/A E SCALEI NONE Frs Sprinklars, Inc. 00667N THIS BRAVING IS BASED OR THE OWNER'S ACCEPTANCE GO THE CURRENTLY ADOPTED EDITION QIT ER STATE GR LOCAL) OF NFPA a AS HE APPLICABLE STANDARD FOR THE INSPECTION. TESTING AND NPI.TEDRACE OF WATER RASED FIRE PROTECTION SYSTEMS, PER SECTION AL THE RESPONMEI17Y FOR PROERLY MAINTAINING A WATER RANGES FIRE PROTECTION SYSTEM (SMALL BE THAT OPTOWNER, IF THE ALDING OWNER HAS NOT RECEIVED A COPY OF THIS PAMPHLET AND/OR IS NET FAMILIAR WITH THE OPERATION ADD MAINTENANCE GO THIS SYSTEM, PLEASE CONTACT THE NEAREST OFFICE OF WAYNE AUTOMATIC FINE SPRINKLERS INC CPVC COMPATIBILITY NOTICE CPVC FIRE SPRINKLER PIPING SYSTEMS HAVE BEEN USED SUCCESSFULLY FOR WHO THAN 20 YEARS IN NEW CONSTRUCTION,X-PIPE AND :PAIR CPVC PRODUCTS ARE IDEALLY SUITED FOR THESE APPLICATIONS WE TO THEIR OUTSTANDING CORROSICH RESISTANCE, OCCASIONALLY, HOWEVER, CPVC CAN BE DAMAGED BY CONTACT WITH CHEMICALS FOUND IN SOME CONSTRUCTION MATERIALS QO SOME WIRES, FWX 'RRpLEUN BASED PRDID S, ETC) AND ANCILLARY PRODUCTS SUCH AS THREAD SEALANTS LEAR DETECTORS FIRESTOP£ MOLD INHIBITORS RD CLEANERS, ETC ANY PRODUCT THAT CONES IN CONTACT WITH'. CPVC SPRINKLER PIPE MUST BE EVALUATED. FOR A LIST O COMPATIBLE PRODUCTS, PLEASE REVIEW NTTP//PARTS.SMFAVSM6CCN/CPLASP% C0P171RIGI-iT ALL DOCUMENTS, INCLUDING ORIGINAL ➢RAVINGS.. SPAYIFTCATI1NC. FF1 I, NFITrc. [cnwTFY AND nein..0 GRAPHICS EL EMENTS .NOTE 11, FIRE SPRINKLER CONSTRUCTION DRAWING S AN ➢ SHOP DRAWINGS MAY INCLUDE BACKGROUND DRAW INGS OGRAPHICS C$ SORROW ED FROM THE ARL T4 STRUCTURAL, CRY HER DRAWINESS, THESE REFERENCE BACKGROUND ELEMENTS ARE FOR GENERAL INFORMATION ON CONTEST ONLY AND THE FIRE SPRINKLER ENGINEER DOES RIIi ACCEPT ANY RESPONSIBILITY Fw THESE ELEMENTS. THE FIRE SPRINKLER ENGINEER IS ONLY RESPONSIBLE FOR iHpSF PORTIONS OF THE FIRE SPRINKLER DRAWINGSVRAWIM DEPICTING AG FIRE SPRINKLER SCITTRESEXPRESSIONS OF WORK. BACK REFEZIUND ID APPROVED AI MAY BE AL,UTILIZED STWIZED IN HERONCIVIL ➢RAWING2 FOR AUTHORITATIVE EXPRESSIONS OF BAWINGS OR INETAILS UN iFNT MAY HC UTILIYE➢ IN FIRE SPRINKLER DRAWINGS OR DETAILS WATER SUPPLY INFORMATION ACTUAL EXTRAPOLATE➢ FIRE PUMP SIZE. GPM GIPSI N/A STATIC PRESSURE 65 -- HYDRANT ELEV. 2'-6' 1 RESIDUAL PRESSURE 25 -- A E OF TE T 6/5/2019 FLOW IN GPM 780 TIME OF TEST I N/A PITDT READING 18 NI■ER OF PORTS FLOWED 1 TEST PROVIDED BY St Lucie County UtlUtles %lf CA OCEAN ESTATES DRIVE & AIA BLVD i SPRINKLERS SPACING i SYMBOL MAXIMUM I MINIMUM I COMMENTS MODEL TOTAL PER FLOOR TOTAL THIS SHEET T: SUBMITTALS BY 2017 WAFS. QA Review MC I /1\ I XX/XX/XX I -- I - I V"MMNIGIIIIII Automatic Fire Sprinklers, Inc. MAIN OFFICE - ORLANDO„ FLORIDA 222 CAPITOL COUNT OCOEE, FLORIDA 34781 PHONE (407) eye-3D30 FAX: < 658-soes JAQ(SONVLLE. FL TAMPA. R BLIDEBRIFELD BEACH, IBL USES D6TRWT.ON AVE WEST 32M CHEPAY PALM [FIVE SW 5, FpWE UNE RO_IINT A JACKSONVBNP FL 32266-2)46 TA A, R 336E1-9337 EEERFMO SEAM, R 39442 PHONE, (904) 2,W_ZR 30 PHRE OBIS) 530-0303 PHONE (95,I) 917-313SI0 FAX (90,1) 258-0 24 FAX (013) 830-D3¢ FAX US") 99-9424 FT. MYERS. FL CONCORD. INC STATE LICSISES: 4883 LAREDO AVE. 4370 MOTC USP01)T DRIVE NC SPr440$H DORM FT. MYE15 FL 33806-4924 CONCORD, NO 26027-@9T/ NC ALARM. 2922E SP LV mhsE (EGGS) 433-3030 PHODE (704) 782-3032 SC SP5NI081; IN FAX (239) 433-3263 FAX: (704) 796 G, 3C ALARLL 3395 Avalon Ocean Estates Drive Lot #25 North Hutchinson Island, Florida - ;` TRM Construction, Inc. 7230 Westpointe Blvd, Apt. 1212 Orlando, FL 32835 SHEET TITLE. Notes & Details REVIEWED FOR nRAwN BYI Michael Crawford TOTAL A/S. 26 DATE. 6/7/2019 ST. LUCIE COUN AHJ. St. Lucie County ncc CONTRACT # #9 5 6 2 1 €� CENTER OF TILE JOBT [:]YES NO I CENTER ON FIXTURES JOBP�YES ND SHEET # CONSTRUCTION TYPE, FP1 OF 3 OCCUPANCRB ANY DISTANCE (1/2 'S' MAX) i OR SPRINKLER TEE DROP SUPPORT SPACING WITH ONE RESTRAINT POINT — SEE TABLE 1 BELOW SPRINKLER 90k ELL DROP SUPPORT SPACING WITH ONE RESTRAINT POINT — SEE TABLE 1 BELOW TABLE I — SPRINKLER SUPPORT SPACING DISTANCE WITH ONE RESTRAINT POINT NOM, PIPE SIZE 'R' @ LESS THAN 100 PSI 'R' @ GREATER THAN 100 PSI INCH 0'-9' 0'-6' 1 INCH 11-0' 0'-9' 1V4 INCH 1'-4' 1'-0' U} INCH 2'-0' 1'-0' >L¢ INCH 2'-0' 1'-0' AX SPRINKLER DROP SUPPORT SPACING WITH TWO RESTRAINT POINTS — SEE TABLE 2 BELOW I— L MAX ----I MAXIMUM SUPPORT SPACING SEE TABLE 3 BELOW TYPICAL CEILING DIFFUSER IHANGER TYP Rl'—O' TYP. TYPSPRDKLI TEMPER'INiIATE' ® TURE CLASSIFICATmm TABLE 2 - SPRINKLER SUPPORT SPACING DISTANCE WITH TWO RESTRAINT POINTS NOM, PIPE SIZE 'S' @ LESS THAN 100 PSI 'S' @ GREATER THAN 100 PSI INCH 4'-0' 3'-0' 1 INCH 5'-0' 4'-0' 1Y4INCH 6'-0' 5'-0' 1,� INCH 7'-0' 7'-0' >lf INCH 7'-0' 7'-0' TABLE 3 - MAXIMUM SUPPORT SPACING NOM, PIPE Y4 INCH 1 INCH 114 INCH 1� INCH 2 INCH 23Z INCH 3 INCH SIZE SUPPORT SPACING 'L' 5'-G' 6'-0' 6'-6' 7'-0' 8'-0' 9'-0' 10'-0' 00356N L TYPICAL B PENDENT A SPRINKLER CEILING TYPICAL OBSTRUCTION DISTANCE FROM SPRINKLER TO SIDE OF OBSTRUCTION (A) MAXIMUM ALLOWABLE DISTANCE OF DEFLECTOR ABOVE BOTTOM OF OBSTRUCTION (IN,) (B) LESS THAN 1 FT, 6 IN, 0 1 FT. 6 IN TO LESS THAN 3 FT, 1 3 FT, TO LESS THAN 4 FT, 3 4 FT, TO LESS THAN 4 FT, 6 IN 5 4 FT, 6 IN. TO LESS THAN 6 FT, 7 6 FT, TO LESS THAN 6 FT, 6 IN, 9 6 FT, 6 IN. TO LESS THAN 7 FT, 11 7 FT, AND GREATER 14 NFPA 13R 8 13D RESIDENTIAL PENDENT — SPRINKLER CLEARANCE W/ OBSTRUCTION SCALE, NONE Fire Sprk,1clere. Inc. 00527N SPF Fire Sprinkbro, Inc. (ANY MODEL IS ACCEPTABLE PROVIDED PLAN VIEW OF BLADES IS 50% OPEN) CEILING SOFFIT I (OBSTRUCTION) B D A NFPA 13R 8 130 W/� C� FAN SCALE, NONE 00505N TYPICAL PENDENT SPRINKLER WALL A 2(D-8IN.)+B(A>(D-0.2M)+B) D 5 30 IN, (ORM) NFPA 13R 8 13D RESIDENTIAL PENDENT DDT SPRINKLER CLEARANCE W/ SOFFIT SCALE, NONE Are SprImMere, In. 00531N SIP TYPICAL LIGHT FIXTURE AIN ROOMS/COMPARTMENTS 400 CU. FT, OR LESS, SPRINKLERS MAY PLACED REGARDLESS OF LOCATION OF OBSTRUCTIONS, Fire Sp hklero, 5m. ALTERNATE USAGE OF FIG, 24 PIPE HANGER WOOD FRAMING MEMBER NFPA 13R 8 130 ( LIGHT �� SCALE, NONE 00504N VEW 'A'7FIG,24 ALTERNATE USAGE OFF FIG. 24 PIPE HANGER nF _ IA �J TCPVC PIPE HANGER SPRINKLER LINE (SP TO 2') #12 X IX' HARDENED HEX HEAD SELF -THREADING SCREW (X2) HANGER #04J 24 HANGER FOR a✓4 TO 2" CPVC PPE `A/�FIG. `Ev - E SCALE, NONE bw 00282N STRAP MAY BE USED IN THIS POSITION AS A RESTRAINER ONLY #12 X 1Y4' HARDENED HEX HEAD SELF —THREADING SCREW CPVC SPRINKLER LINE (Y' TO 2') TOLCO FIG, 22 PIPE STRAP (SIZED TO PIPE) WOOD FRAMING MEMBER HANGER #W _ FOR 3'i TO 2" CPVC PPE SCALE, NONE Fire sp°'d" fie' 00251N III�I �i �il��l�li' III I I I Ali' •► I • � . WALL SPRINKLER TEMP: DIbENSIDN 'A' INTERMEDIATE 1750-225e A a 12' TYPICAL S13EWALL SPRINKLER HOT AR DIFFUSER CLEARANCES viffm SCALE, NONE Are Sprkl&m. hm 00903N WALL LA . TEMP: I DIMENSION ORDINARY 135'170e I TYPICAL SIDEWALL SPRINKLER HOT AR DIFFUSER CLEARANCE Fire SpNnklere. Ym. —TYPICAL SIDEWALL SCALE, NONE 00903N RTANT OWNER INFORMATION BASE➢ pN THE OWNER'S ACCEPTANCE BE THE CURRENTLY A➢OPTE➢ EDITION tEITHER STATE BY LEGAL) IF NWA n AS ENPPLICA�Z TANDARD FOR THE INSPECTION TESTING AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS, PER SECTION 4d.BILITY FOR PROPERLY MAINTAINING A VATER BASE➢ FIRE PROTECTION SYSTEM SMALL BE TOUT OF THE OWNER, IF THE AS NOT RECEIVED A COPY OF THIS PAMPHLET ABOUTR IS NOT FAMILIAR WITH THE UPERATIW AND MANTENANCE OF THIS SYSTEMi PLEASE COBALT THE NEAREST OFFICE OF WAYNE AUTOMATIC EIRE SPRM(IERS INC. - VC COMPATIBILITY NOTICE CPVCPIPING SYSTEMS HAVE BEEN USED SUCCESSFULLY THE MORE THAN 20 YEARS IN NEW CONSTRETIU11 RE -PIPE MN REPAUCTS ARE IDEALLY SUITED FOR THESE APPLICATIONS BE TO THEIR OUTSTANDING CORRWICN RESISTANCE, OCCASIONALLY, 7HOWEVMCPVC C CAN BE DAMAGED BY CONTACT WITH CHEMICALS FOUND IN SOME CUNSTRUTION MATERIALS UE. SOME WIRESFLUX,PEiPRODUCTS, ETCJ AM ANCILLARY MEETS SUCH AS THREAD SEALANTS. LEAK pETECipRS. FIRESiDP$ NRD INWBITORS ANp . ANY PRODUCT THAT CRIES IN CONTACT WITH CPVC SPRINKLER PIPE MUSTBE EVALUATED FOR A LIST OF COMPATIBLE PRODUCTS PLEASE REVIEW HTTPJ/PMTS.SPEARSMFGOOM/CPLASPX COPYRIGHT ALL ➢OCUMENTS, INCLUDING GBIGINAL ➢RAVINGS SPECIFICATIONS FIELD NOTES ESTIMATES AND DATA INCLEM COMPUTER PROGRAMS PURSUANT TO THIS PROJECT ARE An WILL REMAIN THE PROPERTY OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC (WAFS) AS INSTRUMENTS OF SERVICE. THEY ARE NOT INTEN PR ➢ED. NOR REPRESENTED TO BE SUITABLE Phi RE -USE BY THE CLIENT, OR OTHERS. ON EXTENSION OF THIS PROJECT, OR FOR ANY OTHER PROJECT. ANY REUSE OR ADAPTATION OF THE INFORMATION CONTAINED HEREIN. WITHOUT SPECIFIC WRITTEN PERMISLON FROM WAFS WILL BE AT THE CLIENTS SOLE RISX, WITHOUT LIABILITY, OR LEGAL EXPOSURE TO WAFS AnWILL ENTITLE WAFS TO FURTHER COMPENSATION AT RATES TO BE AGREED GN BETWEEN WAEB AND THE CLIENT THE CLIENT SHALL ALSO INDEMNIFY AND HOLD WAFS HARMLESS FROM ANY AND ALL CLAIMS, ➢AMAGES. LOSSES AND EXPENSE$ INCLUDING ATTORNEYS FEES RESULTING FROM ANY SUCH PERMISSDTNS GRAPHICS ELEMENTS NOTE FIRE SPRINKLER CONSTRUCTION DRAWINGS AND SHOP DRAWINGS MAY INCLUDE BACKGROUND DRAWINGS OR GRAPHICS BORROWED FROM THE ARCHITECTURAL, CIVIL, STRUCTURAL, OR MEP DRAWINGS THESE REFERENCE BACKGROUND ELEMENTS ARE FOR GENERAL INFORMAIION OR CGNTEXT ONLY AND THE FIRE SPRINKLER ENGINEER DOES NOR ACCEPT ANY RESPONSIBILITY FEE THESE ELEMENTS, THE FIRE SPRINKLER ENGINEER IS ONLY RESPONSIBLE FOR THOSE PORTIONS OF THE FIRE SPRINKLER ➢RAVINGS DEPICTING FIRE SPRINKLER SCOPES OF WORM, REFER TO APPROVER ARCHITECTURAL STRUCTURAL HER OR CIVIL DRAWINGS FOR AUTHORITATIVE EXPRESSIONS OF BACKGROUND INFORMATION THAT MAY BE UTILIZED IN FIRE SPRINKLER ➢FAWINGA OR DETAILS WATER SUPPLY INFORMATION ACTUAL EXTRAPOLATED FIRE PUMP NIA SIZE, GPM @ PSI N/A STATIC PRESSURE 65 -- HYDRANT ELEV. 2'-6' RESIDUAL PRESSURE 25 -- 6/5/2019 FLOW IN GPM 780 -- TIME OF S WA PITOT READING 18 MD®ER Or PORTS FU9WEED I TEST PROVIDED BY St Lucie County Utilities C OCEAN ESTATES DRIVE & AlA BLVD ill SYMBOL I MAXIMUM I MINIMUM I COMMENTS ---, G— III STM11 1ST I - I - I - I SIN ISIZE I K ITEMPI MODEL I - - - TOTAL PER FLOOR - TOTAL THIS SHEET t 2/24/2D17 I W.A.F.S. 0A RevM# I MC I 11 /1\ I XXna/XX I -- I - I \m�� "V'SANNE Automatic Fire Sprinklers, Inc. MAIN OFFICE - ORLANDO. FLORIDA see CAPITOL COIFIT OCOEE, RMWA 347M PHOM (4073 868-3030 FAX ( ass —goes rACK300 ^" a TAMPA, FL dJOERFILD BEiACIL FL SERIES 001N&TIIXi AB E WEST BESIDE, CH211Y PALLt ONVE 1600 S. PpW@Y.9E R[ _U1T A JAMSONVLLE R. 3PPSS-ENE TAIRA R 335E1-83E7 pEi3Fgp FEgq� R SS11E PIAME W04) eBe-EMBED PIMPLE (90) S90-O309 p (9" 1117-3030 FAX SE04) 2011 ] FAX SISD 830-M FAX (SEWS 9p-91E4 FT. MYOM CMMM NC STATE UDBMIA: 4SS3 LARE)O AVE 43]O MOTOPSPpIT ONVE NC SPSNOHk 29745 FT. NYEPE. R 33BO6-,824 CONCO9O. NC 2SIGNE7, T` IL ALAIpk S.Bfi22 SP LV REGIME SEEK, 4 3!3913 RAIE AUWS R82-3092 SC SPKNOHk IRS FAX SEEK) 43}3283 FAX ()044 J 0413E SC ALApk SEEM Avalon Ocean Estates Drive Lot #25 North Hutchinson Island, Florida E TRM Construction, Inc. 7230 Westpointe Blvd. Apt. 1212 Orlando, FL 32835 -- ___ SHEET TITLE, Details DRAWN BY, Michael Crawford TOTAL A/SI 26 DATE, 6/7/2019 C, W AHJI St. Lucie County-,�_,, Lew CONTRACT # !CIE COUN #95621 CENTER OF TILE JOV YES &tNO I CENTER ON FIXTURES JOB?E]YES NI SHEET # CONSTRUCTION TYPE FP2 OF 3 OCCUPANCRB MASTER BEDROOM COMPARTMENT DESIGN PER NFPA 130, 2013 EDITION, SECTION 10.2.1 S4 16' X 16' SPACING 16.0 GPM @ 13.3 PSI S5 16' X 16' SPACING 13.0 GPM @ 7.0 PSI /ywaYN,E 00854N O MASTERSEDROOM O S4 EL0 4-BOD--'-' O 0 SCALE: 3/16" = 1'-on 2' 1' 0 4' 81 1 1 1 1 1 .4 IIIIIIIIIIIIIII1111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111 IIIIIII!!!!IIIIIIIIIII!!!!!!Ili I SCALE 3/16' = 1' -SPRINKLER RISER DESIGNED TO r- - - - - - - - NFPA 13D 2013 EDITION FIGURE A.B.I (A) ' I I I I 2-CAR GARAGE L - - -. - - - - ��J NO AIS - - - PER NFPA 13D 2013 EDITION 8 3 4 SPRINKLERS SHALL NOT @E REQUIRED IN GARAGES s I 11, �P�Q A y 10.0 ° L------- FOYER O 6$ a� O 2 100 101 i S2 0 la o' •KITCHEN Q �0�7 ei I • Lo • O L I w • DESIGN AREA #2 KITCHEN COMPARTMENT DESIGN PER NFPA 130, 2013 EDITION, SECTION 10ZI S2 18' X 18' SPACING 17.0 GPM @ 12,0 PSI S3 18' X 18' SPACING 17.0 GPM @ 12.0 PSI 00854N t. / GREAT ROOM \\ O u lr i \ ^$ ARE,4R PRINL RED O • O / 77- 0' BF 45 O O 0 i\ I. 110 fl v°+ - • 0 0 a Iw la- I 13 NOTES: 1. PER NFPA 13D, A FLOW SWITCH IS NOT REQUIRED TO BE INSTALLED ON THE SPRINKLER SYSTEM. 2. PER FBC 901.6.1 EXCEPTION #1, MONITORING OF THE FIRE SPRINKLER SYSTEM IS NOT REQUIRED. 3. PER NFPA 13D, A CONTROL VALVE IS OPTIONAL ON THE FIRE SPRINKLER SIDE OF THE RISER. A CONTROL VALVE IS NOT INCLUDED ON THE FIRE SPRINKLER RISER. SCOPE OF WORK: 1. W.A.F.S. TO INSTALL A NEW 13D FIRE SPRINKLER SYSTEM THROUGHOUT NEW RESIDENCE. 2. W.A.F.S. TO CONNECT AFTER DOMESTIC BACKFLOW AND INSTALL A NEW FIRE SPRINKLER RISER CONSISTING OF A LEAD FREE 1 M WILKINS 950XLT2 DUAL CHECK VALVE. 3. ALL FIRE SPRINKLER PIPING AND FITTINGS TO BE CPVC. \ L E I / \ 8 S F O OFFICE LIBRARY O - g ft BF2 BFl AWWAVALVE I `' FIRE HYDRANT FLOW TEST RESULTS TOTAL 1ST FLOOR AREA- 2 25d SQ,FT UG2 UGl (BY OTHERS) I STATIC: 65 PSI -2 _ RESIDUAL: 25 PSI TEE 15-0 FLOW: 780 GPM ENTIRE BUILDING IS RESIDENTIAL Tic LED13Y OTHERS) (BY OTHERS) ALLED BV OTHERS) (NIC) w FIRE SPRINKLER POINT OF SERVICE 2 REDUCED PRESSURE DETECTOR (INSTALLED BY OTHERS) 13 (NIC). z W.A.F.S. POINT OF CONNECTION tO I a 1ST FLOOR SPRINKLER PLAN SCALE: 3/16" = 1'-0" ?' 1' o i` e' DID w min SCALE 3/16' = Y HYDRAULIC -° SYSTEM THIS BUILDING IS PROTECTED BY A HYDRAULICALLY DESIGNED AUTOMATIC SPRINKLER SYSTEM. LOCATION I Be&oom 412 (Arse #A 1 NO. OF SPRINKLERS BASIS OF DESIGN L DENSITY [LDS r4+M/ad Ft. 2 OMIGNIECI AREA OF DISCHARGE N/A= 50 FT. SYSTEM DEMAND 1. GPM DISCHARGE #.®GPBI� 2. RESIDUAL PRESSURE AT THE 4t BASE OF THE RISER Aubomat3c, Fire Sprinklers, Inc. CORPORATE OFFICE- JACKSONVILLE, Ft N%4) 268-3030 222 CAPITOL COURT FORT MYERS, FL (239) 433-3030 OCDEE FLORIDA 34761 POMPANO BEACH F.L (954) 917-3030 OFFICE- (407) 656-3030 TAMPA, FL (813) 630-0303 24 H U EMERGENCY, (407) 656-8946 CONCORD, NC (704) 782-3032 HYDRAULIC - SYSTEM THIS BUILDING IS PROTECTED BY A HYDRAULICALLY DESIGNED AUTOMATIC SPRINKLER SYSTEM. LOCATION dY•MB (Area #2) NO. OF SPRINKLERS 2 - BASIS OF DESIGN 1. DENSITY A5 OPM/SQ FT. 2. DESIGNED AREA OF DISCHARGE NVA sd FT. SYSTEM DEMAND L GPM DISCHARGE 34A 2. RESIDUAL PRESSURE AT THE oFA1 BASE OF THE RIM \'WJgE Automatic Fire Sprinklers, Inc. CORPORATE OFFICE- JACKSONVILLE, FL (904) 268-3030 222 CAPITOL COURT FORT MYERS. FL (239) 433-3030 muEE, FLORIDA 34761 POMPANO BEACH, FL (954) 917-3030 OFFICEI (407) 656-3030 TAMPA, FL (913) 6M-0303 24 HE EMERGENCY: (407) 656-8946 CONCORD, NC (704) 782-3032 HYDRAULIC - SYSTEM 'rmIS BUILDING IS PROTECTED BY A HYDRAULICALLY DESIGNED AUTOMATIC SPRINKLER SYSTEM. LOCATION I Mntar Belkwn (Has 03) NO. OF SPRINKLERS u BASIS OF DESIGN L DENSITY .05 (w+Lvao. H. 2. DESIGNED AREA OF DISCHARGE WA SYSTEM DEMAND I. GPM DISCHARGE 35A (PM 2 RESIDUAL PRESSURE AT THE BASE OF THE RISER 38S \"NOMAYNE Automatic Fire Sprinklers, Inc. CORPORATE OFFICE, JACKSONVILLE FL (904) 268-3030 222 CAPITOL COURT FORT MYERS, F4 (239) 433-3030 DCMZ FLORIDA 34761 POMPANO BEACH, Ft (954) 917-3030 OFFICE. (407) 656-3030 TAWA, FA. (813) 630-0303 24 HR. EMERGENCY- (407) 656-8946 CONCORD, MC (704) 7OL-3032 THIS llUVING IS BASED ON THE OWNER'S ACCEPTANCE OF THE CURRENTLY ADOPTED EDITION (EITHER STATE BR LOCAL) OF NFPA 25 AS THE APPLICAMLE STANDARD FOR THE INSPECRC1% TESTING AND MAINTENANCE 6 WATER BAKER FIRE PROTECTION SYSTEMS PER SWTIUN 44 THE RESPONSIBILITY Fm PF.OPERLY MAIMAINIM A WATER BASED FIRE PROTECTION SYSTEM SHALL BE THAT OF THE OWNER IF THE BUIL➢SS OWNER MOS MYT RECEIVED A COPY OF THIS PAMPHLET AND/M IS NOT FAMILIAR WITH THE OPERATION MI➢ MAINTENANCE OF THIS .SYSTEM PLEASE CONTACT THE NEAREST OFFICE OF WAYNE AUTOMATIC PITS SPRINKLERS, INS CPVC COMPATIBILITY NOTICE CPVC FIRE SPRINKIER PIPING SYSTEMS HAVE BEEN USED SUCCESSFULLY FOR MORE THAN 20 YEARS IN NEW C@ISTRUCTIBN, RE -PIPE AND PEPAIR, CPVC PRODUCTS ARE IDEAIY SUITED FUR THESE APPLICATIONS BUD TO THEIR UPSTANDING CORROSION RESISTANCE, OCCASIONALLY, MOWTVER, CPVC U.N BE. DAMAGED BY CONTACT WITH CHEMICALS FOUND IN SOME CONSTRUCTION MATERIALS (IEi SOME WORMFLUX PETROLEUM BASED PROGXXTS ETG) AND ANCILLARY PRODUCTS SUCH AS. THREAD SEALANTS, LEAK ➢EICITOR& FIRESTUM HOLD INVI917MS AND CLEANERS ETC. ANY PRODUCT THAT COMES IN CONTACT WITH CPVC SPRINKLER PIPE MUST BE EVALUATED. FOR A LIST OE WNPATIBLE PRODUCTS, PLEASE REVIEW NTTW//PARTS.. ARSWD.COM/CPLASPX COPYRIGHT ALL DOCUMENTS INCLUDING ORIGINAL DRAWINGS, SPECIFICATIONS FIELD NOTES ESTIMATES AND BAIN INCLUDING COMPUTER PROGRAMS PURSUANT TO THIS PROJECT WE AND WILL DOWN THE PROPERTY OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC, MAFS) AS INSTRUMENTS OF SERVICE. THEY ARE NOT INTENDED, NUR REPRESENTE➢ TO BE SUITABLE FOR RE -USE BY THE CLSEM OR OTHERS, ON EXTENSION a THIS PROJECT, 09 FOR ANY EITHER PROJECT. ANY ROME, ON ADAPTATION OF THE INFERNATIBN CONTAINED HEREIN, WITHOUT SPECIFIC WRITTEN PERMISSION FROM VATS WILL BE AT THE CLIENTS SOLE RISK, WITHOUT LIABILITY, OR LEGAL EXPOSURE TO WAFSAN➢ WILL ENTITLE WAFS TO FURTHER COMPENSATION AT RATES TO DE AGREED ON BETWEEN WKM AM THE Ca ENT. THE CLIENT SHALL ALSO IN➢EMOFY AND HOLD* VAFS HARMLESS FROM MY AMC ALL CLAIMS GRAPHICS ELEMENTS NOTE TIRE SPRINKLER CONSTRUCTION DRAWINGS AND SHOP DRAWINGS MAY INCLUDE BACKGROUND DRAWINGS OR GRAPHICS BORROWED FROM THE ARCHITECTURAL, CIVIL, STRUCTURAL, OR PER WNWINGS, THESE REFERENCE BACKGROUND ELEMENTS ARE FOR GENERAL INFORMATION OR CONTEXT ONLY AND THE FIRE SPRINKLER ENGINEER DOES NOT ACCEPT ANY RESPONSIBILITY FOR THESE ELEMENTS THE FIRE SPRINKLER ENGINEER IS ONLY RESPONSIBLE FOR THOSE .PORTIONS OF THE FIRE SPRINKLER DRAWINGS ➢EPICTING FIRE SPRINKLER SCOPES OF WORK, REFER TO APPROVED ARCHITECTURAL STRUCTURAL HOP GO CIVIL DRAWINGS FOR AUTHORITATIVE EXPRESSIONS OF BACKGRMND INFORMATION THAT MAY BE UTILIZED IN FIRE SPRINKLER DRAWINGS OR DETAILS - WATER SUPPLY INFORMATION ACTUAL EXTRAPOLATED (AV OrTHIJ SAY AM 11 FIRE PIMP SIZE- GPM @ PSI N/A STATIC PRESSURE 65 - HYDRANT ELEV. 2'-6' '- RESIDUAL PRESSURE 25 - A 6/5/2019 FLOW IN GPM 780 - TIME OF TEST N/A PITUT READING 18 NUMBER OF PORTS FLOWED 1 TEST PROVIDED BY St Lucie County Utilities A I N OCEAN ESTATES DRIVE & AIA BLVD DESIGN CRITERIA SYSTEM / DESIGN AREA # #1 #2 #3 HAZARD CLASS IPA 13D NFPA 13D NFPA 13D ) IF SPRINKLERS N DESIGN AREA 1 2 2 MINIMUM DENSITY .05 .05 .05 DESIGN AREA S.F. 1 HEAD DESIGN 2 HEAD DESIGN 2 HEAD DESIGN PSI REG'D @ BR 413 41.9 38,5 GPM RELIT @ BR 20.0 345 354 PSI RELIT @ TEST 54.7 593 56,0 GPM REOT @ TEST 20.0 345 35D ELEVATION @ HIGHEST SPRDLIER 20'-0' Ul-0' HOSE INSIDE/OUTSIDE I N/A N/A N/A DOMESTIC DEMAND I N/A N/A N/A SYMBOL MAXIMUM MINIMUM Q• 16' x 16' UNO 8'-01 (9 16' x 16' URRO 8'-V 16' x 16' UNO 84' .0 16' x 16' UNO 8'-0' SYMB, 1ST III - SIN SRE K TEMP MODEL 12 9 - R3516"43 RELIABLE MODEL F1 RESIDENTIAL WHITE PENDENT W/ SENT RECESSED WHITE ® 1 1 - R3516 ESCUTCHEON2 - - R3531 RELIABLE l�EL FI RESIDENTIAL WHITE NTAL SIDEWALL V/ SEMI 1 - - R3531 RECESSED ESCUTCHEON 16 1 10 1 TOTAL PER FLOOR 26 TOTAL THIS SHEET DATE SUBMITTALS BY 2/24/2017 W.A.F.S. 0A Review MC \"V4WmMWKff1FM i R Automatic Fire Sprinklers, Inc. MAIN OFFICE - ORLANDO. FLORIDA 282 CAPITOL COURT OCOEE, R-ORIDA 34761 PHONE: (407) 656-3030 FAX: (47) 656-0026 JAOWMVLlE Fi- TAWA. FL nf0NnFHD BEACH. FL IL328 OeTPbUTpN AVE. WEST Bass r.11HPT PALM DRVE 1500 S. POWERLINE SO MR A JACKSONVLIE, R. 32255-2745 TAAPA, FL 33619-6337 DEERPBD BEACH, FL 3344E PHONE.(904) 265-3030 PHONE (613) 630-0303 PHONE: (DISKS 8I7-3030 FAX; U04) 269-0724 FAX:(08) 630-03e FAX (954) 9V-9424 FT. myEw F - CONCOON0. NC STALE LICENSES: 4883 LAREDO AVE 4370 MOENBERGER DRIVE NO SPRINKLER 29745 FT BITERS, R. 33905-4924 CONCORD, NC 26HOU-6977 MIC ALARM 2922E SP LV PHONE (239) 433-3030 PHONE 004) 702-303E SO SPRBINLER Ile FAX. 239) 433-3263 FAX: M4) 795-6838 SC ALARM 3305 Avalon Ocean Estates Drive Lot #25 North Hutchinson Island, Florida TRM Construction, Inc. 7230 Westpointe Blvd. Apt.1212 Orlando, FL 32835 SHEET TITLE- I Fire Sprinkler Plans DRAWN BY- I Michael Crawford TOTAL A/SI 26 IEW EU I -UK DATE- 6/7/2019 AHJ, St. Lucie CAO CONTRACT # #95621 CENTER OF TILE J TER ON FIXTURES JDB7 ❑.YES NO SHEET # FP3 C%F 31 CONSTRUCTION TYPE, V-B OCCUPANCY, R3 Automatic Fire Sprinklers, Inc.. Hydraulic Calculations Wayne Automatic Fire Sprinklers, Inc. 1500 S. Powerline Rd Unit A Deerfield Beach, Florida 3344 954-917-3030 Job Name Avalon Lot #25 Sheet Number FP-3 Location Ocean Estates Drive —Lot #25 Design Area AREA #1 Contract #95621 Data File Area #1.WXF REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Wayne Automatic Avalon Lot #25 Page 1 Date 6/7/2019 HYDRAULIC CALCULATIONS for Project name: Avalon Location: Ocean Estates Drive —Lot #25 Drawing no: FP-3 Date: 6/7/2019 Design Remote area number: AREA #1 Remote area location: 2nd Floor Bedroom #2 Occupancy classification: R-3 Density: .05 - Gpm/SgFt Area of application: 1 Head Desig - SgFt Coverage per sprinkler: 400 - SgFt Type of sprinklers calculated: Reliable (R3516) Semi -Recessed White Pendent No. of sprinklers calculated: 1 In -rack demand: N/A - GPM Hose streams: - GPM Total water required (including hose streams): 20.0 - GPM @ 54.7 -Psi Type of system: Wet (NFPA 13D) Volume of dry or preaction system: N/A - Gal Water supply information Date: 6/5/2019 Location: Ocean Estates Drive & A1A Blvd Source: St. Lucie County Utlities Name of contractor: Wayne Automatic Fire Sprinklers, Inc. Address: 1500 S. Powerline Rd —Unit A Deerfield Beach, Florida 33442 Phone number: 954-917-3030 Name of designer: Michael Crawford Authority having jurisdiction: St. Lucie County Notes: (Include peaking information for gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve C Wayne Automatic Avalon Lot #25 Page 2 Date 6/7/2019 City Water Suppl : Demand: C1 - Static Pressure 65 D1 - Elevation 7.579 C2 - Residual Pressure: 25 D2 - System Flow : 20.024 C2 - Residual Flow 780 D2 - System Pressure 54.654 Hose ( Demand) D3 - System Demand : 20.024 Safety Margin 10.300 150 140 130 p 120 R 110 E 100 S 90 S 80 U 70 R 60 E 50 40 30 20 10 D1 100 200 300 400 500 600 700 800 900 FLOW (N A 1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Wayne Automatic Page 3 Avalon Lot #25 Date 6/7/2019 Fitting Legend Abbrev. Name '/2 < 1 1Y< 1'/z 2 2'/z 3 3Y2 4 5 6 8 10 12 14 16 18 20 24 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T 90' Flow Thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 u* CPVC 90' Elbow Tyco 0 4 5 6 7 9 12 13 0 0 0 0 0 0 0 0 0 0 0 0 V' CPVC Tee Branch Tyco 0 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Zig Wilkins 375DA Fitting generates a Fixed Loss Based on Flow Zik Wilkins 950XL Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Wayne Automatic Page 4 Avalon Lot #25 Date 6/7/2019 Node No. Elevation K-Fact Pt Actual Pn Flow Density Area Press Actual Reg. S1 20.0 4.9 16.7 na 20.02 0.05 400 16.7 1 21.0 17.32 na 200 21.0 19.28 na 201 21.0 20.26 na 102 12.0 26.88 na 103 12.0 27.66 na TR 12.0 28.59 na BR -2.5 41.35 na UG2 -2.5 42.56 na BF2 3.0 40.23 na BF1 -2.5 53.63 na UG1 -2.5 53.68 na TEE -2.5 56.82 na TEST 2.5 54.65 na The maximum velocity is 10.71 and it occurs in the pipe between nodes S1 and 1 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen -Williams Wayne Automatic Page 5 Avalon Lot #25 Date 6/7/2019 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. I.G. or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn S1 20.02 0.874 U 4.0 1.000 16.700 K Factor = 4.90 to 150.0 0.0 4.000 -0.433 1 20.02 0.2100 0.0 5.000 1.050 Vel = 10.71 0.0 20.02 17.317 K Factor = 4.81 1 20.02 0.874 V 3.0 6.333 17.317 to 150.0 0.0 3.000 0.0 200 20.02 0.2099 0.0 9.333 1.959 Vel = 10.71 200 0.0 0.874 V 3.0 1.667 19.276 to 150.0 0.0 3.000 0.0 201 20.02 0.2100 0.0 4.667 0.980 Vel = 10.71 201 0.0 0.874 V 3.0 10.000 20.256 to 150.0 0.0 3.000 ' 3.898 102 20.02 0.2099 0.0 13.000 2.729 Vel = 10.71 102 0.0 1.101 0.0 11.333 26.883 to 150.0 0.0 0.0 0.0 103 20.02 0.0682 0.0 11.333 0.773 Vel = 6.75 103 0.0 1.101 U 5.0 8.667 27.656 to 150.0 0.0 5.000 0.0 TR 20.02 0.0682 0.0 13.667 0.932 Vel = 6.75 TR 0.0 1.101 Zik 0.0 10.000 28.588 to 150.0 0.0 0.0 12.080 * * Fixed Loss = 5.8 BR 20.02 0.0681 0.0 10.000 0.681 Vel = 6.75 BR 0.0 1.598 31.11 21.0 80.000 41.349 to 150.0 V 8.0 29.000 0.0 UG2 20.02 0.0111 0.0 109.000 1.212 Vel = 3.20 UG2 0.0 2.067 E 5.0 6.000 42.561 to 120.0 0.0 5.000 -2.382 BF2 20.02 0.0047 0.0 11.000 0.052 Vel = 1.91 BF2 0.0 2.067 E 5.0 6.000 40.231 to 120.0 Zig 0.0 5.000 13.342 * * Fixed Loss = 10.96 BF1 20.02 0.0048 0.0 11.000 0.053 Vel = 1.91 BF1 0.0 2.067 E 5.0 6.000 53.626 to 120.0 0.0 5.000 0.0 UG1 20.02 0.0048 0.0 11.000 0.053 Vel = 1.91 UG1 0.0 1.827 G 0.828 15.000 53.679 to 150.0 T 8.284 9.112 3.000 * * Fixed Loss = 3 TEE 20.02 0.0058 0.0 24.112 0.139 Vel = 2.45 TEE 0.0 6.34 2E 46.217 25.000 56.818 to 140.0 0.0 46.217 -2.166 TEST 20.02 0.0 0.0 71.217 0.002 Vel = 0.20 0.0 20.02 54.654 K Factor = 2.71 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Automatic Fire Sprinklers, Inc. Hydraulic .Calculations. Wayne Automatic Fire Sprinklers, Inc. 1500 S. Powerline Rd Unit A Deerfield Beach, Florida 3344 954-917-3030 Job Name Avalon #25 Sheet Number FP-3 Location Ocean Estates Drive —Lot #25 Design Area AREA #2 Contract #95621 Data File Area #2.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Wayne Automatic Avalon #25 Page 1 Date 6/7/2019 HYDRAULIC CALCULATIONS for Project name: Avalon Location: Ocean Estates Drive —Lot #25 Drawing no: FP-3 Date: 6/7/2019 Design Remote area number: AREA #2 Remote area location: Kitchen Occupancy classification: R-3 Density. .05 - Gpm/SgFt Area of application: 2 Head Desig - SgFt Coverage per sprinkler: 324 - SgFt Type of sprinklers calculated: Reliable (R3516) Semi -Recessed White Pendent No. of sprinklers calculated: 2 In -rack demand: N/A - GPM Hose streams: - GPM Total water required (including hose streams): 34.5 - GPM @ 59.3 -Psi Type of system: Wet (NFPA 13D) Volume of dry or preaction system: N/A - Gal Water supply information Date: 6/5/2019 Location: Ocean Estates Drive & A1A Blvd Source: St. Lucie County Utlities Name of contractor: Wayne Automatic Fire Sprinklers, Inc. Address: 1500 S. Powerline Rd —Unit A Deerfield Beach, Florida 33442 Phone number. 954-917-3030 Name of designer: Michael Crawford Authority having jurisdiction: St. Lucie County Notes: (Include peaking information for gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve C Wayne Automatic Page 2 Avalon #25 Date 6/7/2019 City Water Supply: Demand: C1 - Static Pressure 65 D1 - Elevation 3.681 C2 - Residual Pressure: 25 D2 - System Flow : 34.506 C2 - Residual Flow 780 D2 - System Pressure 59.317 Hose ( Demand ) D3 - System Demand : 34.506 Safety Margin 5.558 150 140 130 p 120 R 110 E 100 S 90 S 80 U 70 R 60 E 50 40 30 20 10 100 200 300 400 500 600 700 800 900 FLOW (N^ 1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Wayne Automatic Page 3 Avalon #25 Date 6/7/2019 Fitting Legend Abbrev. Name '/z % 1 1 % 1'% 2 2'/2 3 3'/2 4 5 6 8 10 12 14 16 18 20 24 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T 90' Flow Thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 U. CPVC 90' Elbow Tyco 0 4 5 6' 7 9 12 13 0 0 0 0 0 0 0 0 0 0 0 0 V* CPVC Tee Branch Tyco 0 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Zig Wilkins 375DA Fitting generates a Fixed Loss Based on Flow Zik Wilkins 950XL Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Wayne Automatic Avalon #25 Page 4 Date 6/7/2019 Node No. Elevation K-Fact Pt Actual Pn Flow Density Actual Area Press Reg. S2 11.0 4.9 12.0 na 16.97 0.05 324 12.0 S3 10.0 4.9 12.8 na 17.53 0.05 324 12.0 3 12.0 12.76 na 2 12.0 12.34 na 100 12.0 14.02 na 101 12.0 21.58 na 102 12.0 22.17 na 103 12.0 24.29 na TR 12.0 26.84 na BR -2.5 41.92 na UG2 -2.5 45.23 na BF2 3.0 43.0 na BF1 -2.5 57.95 na UG1 -2.5 58.1 na TEE -2.5 61.48 na TEST 2.5 59.32 na The maximum velocity is 18.45 and it occurs in the pipe between nodes 100 and 101 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen -Williams Wayne Automatic Avalon #25 Page 5 Date 6/7/2019 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. I.G. or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn S2 16.97 0.874 U 4.0 1.000 12.000 K Factor = 4.90 to 150.0 0.0 4.000 -0.433 2 16.97 0.1546 0.0 5.000 0.773 Vel = 9.08 0.0 16.97 12.340 K Factor = 4.83 S3 17.53 0.874 V 3.0 2.000 12.802 K Factor = 4.90 to 150.0 0.0 3.000 -0.866 3 17.53 0.1642 0.0 5.000 0.821 Vel = 9.37 0.0 17.53 12.757 K Factor = 4.91 3 17.53 0.874 V 3.0 4.667 12.757 to 150.0 0.0 3.000 0.0 100 17.53 0.1641 0.0 7.667 1.258 Vel = 9.37 0.0 17.53 14.015 K Factor = 4.68 2 16.97 0.874 0.0 10.833 12.340 to 150.0 0.0 0.0 0.0 100 16.97 0.1546 0.0 10.833 1.675 Vel = 9.08 100 17.54 0.874 V 3.0 10.167 14.015 to 150.0 0.0 3.000 0.0 101 34.51 0.5745 0.0 13.167 7.565 Vel = 18.45 101 0.0 1.101 0.0 3.167 21.580 to 150.0 0.0 0.0 0.0 102 34.51 0.1866 0.0 3.167 0.591 Vel = 11.63 102 0.0 1.101 0.0 11.333 22.171 to 150.0 0.0 0.0 0.0 103 34.51 0.1866 0.0 11.333 2.115 Vel = 11.63 103 0.0 1.101 U 5.0 8.667 24.286 to 150.0 0.0 5.000 0.0 TR 34.51 0.1867 0.0 13.667 2.551 Vel = 11.63 TR 0.0 1.101 Zik 0.0 10.000 26.837 to 150.0 0.0 0.0 13.216 * * Fixed Loss = 6.936 BR 34.51 0.1866 0.0 10.000 1.866 Vel = 11.63 BR 0.0 1.598 31.1 21.0 80.000 41.919 to 150.0 V 8.0 29.000 0.0 UG2 34.51 0.0304 0.0 109.000 3.315 Vel = 5.52 UG2 0.0 2.067 E 5.0 6.000 45.234 to 120.0 0.0 5.000 -2.382 BF2 34.51 0.0132 0.0 11.000 0.145 Vel = 3.30 BF2 0.0 2.067 E 5.0 6.000 42.997 to 120.0 Zig 0.0 5.000 14.812 * * Fixed Loss = 12.43 BF1 34.51 0.0131 0.0 11.000 0.144 Vel = 3.30 BF1 0.0 2.067 E 5.0 6.000 57.953 to 120.0 0.0 5.000 0.0 UG1 34.51 0.0131 0.0 11.000 0.144 Vel = 3.30 UG1 0.0 1.827 G 0.828 15.000 58.097 to 150.0 T 8.284 9.112 3.000 * * Fixed Loss = 3 TEE 34.51 0.0158 0.0 24.112 0.382 Vel = 4.22 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen -Williams Wayne Automatic Page 6 Avalon #25 Date 6/7/2019 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ' "***** Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn TEE 0.0 6.34 2E 46.217 25.000 61.479 to 140.0 0.0 46.217 -2.166 TEST 34.51 0.0001 0.0 71.217 0.004 Vel = 0.35 0.0 34.51 59.317 K Factor = 4.48 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Automatic Fire Sprinklers, Inc. Hydraulic Calculations Wayne Automatic Fire Sprinklers, Inc. 1500 S. Powerline Rd Unit A Deerfield Beach, Florida 3344 954-917-3030 Job Name Avalon Lot #25 Sheet Number FP-3 Location Ocean Estates Drive —Lot #25 Design Area AREA #3 Contract #95621 Data File Area #3.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Wayne Automatic Avalon Lot #25 Page 1 Date 6/7/2019 HYDRAULIC CALCULATIONS for Project name: Avalon Location: Ocean Estates Drive —Lot #25 Drawing no: FP-3 Date: 6/72019 Design Remote area number. AREA #3 Remote area location: Master Bedroom Occupancy classification: R-3 Density: .05 - Gpm/SgFt Area of application: 2 Head Desig - SgFt Coverage per sprinkler. 256 - SgFt Type of sprinklers calculated: Reliable (R3516) Semi -Recessed White Pendent No. of sprinklers calculated. 2 In -rack demand. N/A - GPM ' Hose streams: - GPM Total water required (including hose streams): 35.0 - GPM @ 56.0 - Psi Type of system: Wet (NFPA 13D) Volume of dry or preaction system: N/A - Gal Water supply information Date: 6/5/2019 Location: Ocean Estates Drive & A1A Blvd Source: St. Lucie County Utlities Name of contractor. Wayne Automatic Fire Sprinklers, Inc. Address: 1500 S. Powerline Rd_Unit A Deerfield Beach, Florida 33442 Phone number. 954-917-3030 Name of designer. Michael Crawford Authority having jurisdiction: St. Lucie County Notes: (Include peaking information for gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve C Wayne Automatic Avalon Lot #25 Page 2 Date 6/7/2019 City Water Supply: Demand: C1 - Static Pressure 65 D1 - Elevation 3.537 C2 - Residual Pressure: 25 D2 - System Flow : 34.994 C2 - Residual Flow 780 D2 - System Pressure 56.035 Hose Demand ) D3 - System Demand : 34.994 Safety Margin 8.836 150 140 130 p 120 R 110 E 100 S 90 S 80 U 70 R 60 E 50 '40 30 20 10 100 200 300 400 500 600 700 800 900 FLOW( N"1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary Wayne Automatic Page 3 , Avalon Lot #25 Date 6/7/2019 Fitting Legend Abbrev. Name '/z % 1 1< 1'/2 2 2'/z 3 31/2 4 5 6 8 10 12 14 16 18 20 24 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T 90' Flow Thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 u* CPVC 90' Elbow Tyco 0 4 5 6 7 9 12 13 0 0 0 0 0 0 0 0 0 0 0 0 V' CPVC Tee Branch Tyco 0 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Zig Wilkins 375DA Fitting generates a Fixed Loss Based on Flow Zik Wilkins 950XL Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD Wayne Automatic Page 4 Avalon Lot #25 Date 6/7/2019 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Rea. S4 10.667 4.4 13.3 na 16.05 0.05 256 13.3 S5 10.0 4.9 14.95 na 18.95 0.05 256 7.0 4 12.0 14.62 na 5 12.0 15.03 na 103 12.0 20.78 na TR 12.0 23.4 na BR -2.5 38.53 na UG2 -2.5 41.93 na BF2 3.0 39.7 na BF1 -2.5 54.66 na UG1 -2.5 54.81 na TEE -2.5 58.2 na TEST 2.5 56.04 na The maximum velocity is 11.79 and it occurs in the pipe between nodes 5 and 103 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 • r Final Calculations - Hazen -Williams Wayne Automatic Avalon Lot #25 Page 5 Date 6/7/2019 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv., Ln. Total Pf Pn S4 16.05 0.874 21-1 8.0 2.583 13.300 K Factor = 4.40 to 150.0 V 3.0 11.000 -0.577 4 16.05 0.1394 0.0 13.583 1.893 Vel = 8.58 0.0 16.05 14.616 K Factor = 4.20 S5 18.95 0.874 V 3.0 2.000 14.952 K Factor = 4.90 to 150.0 0.0 3.000 -0.866 5 18.95 0.1896 0.0 5.000 0.948 Vel = 10.13 0.0 18.95 15.034 K Factor = 4.89 4 16.05 0.874 0.0 3.000 14.616 to 150.0 0.0 0.0 0.0 5 16.05 0.1393 0.0 3.000 0.418 Vel = 8.58 5 18.94 1.101 V 5.0 25.000 15.034 to 150.0 0.0 5.000 0.0 103 34.99 0.1915 0.0 30.000 5.746 Vel = 11.79 103 0.0 1.101 U 5.0 8.667 20.780 to 150.0 0.0 5.000 0.0 TR 34.99 0.1916 0.0 13.667 2.618 Vel = 11.79 TR 0.0 1.101 Zik 0.0 10.000 23.398 to 150.0 0.0 0.0 13.216 * * Fixed Loss = 6.936 BR 34.99 0.1915 0.0 10.000 1.915 Vel = 11.79 BR 0.0 1.598 3U 21.0 80.000 38.529 to 150.0 V 8.0 29.000 0.0 UG2 34.99 0.0312 0.0 109.000 3.402 Vel = 5.60 UG2 0.0 2.067 E 5.0 6.000 41.931 to 120.0 0.0 5.000 -2.382 BF2 34.99 0.0135 0.0 11.000 0.148 Vel = 3.35 BF2 0.0 2.067 E 5.0 6.000 39.697 to 120.0 Zig 0.0 5.000 14.812 * * Fixed Loss = 12.43 BF1 34.99 0.0135 0.0 11.000 0.149 Vel = 3.35 BF1 0.0 2.067 E 5.0 6.000 54.658 to 120.0 0.0 5.000 0.0 UG1 34.99 0.0135 0.0 11.000 0.148 Vel = 3.35 UG1 0.0 1.827 G 0.828 15.000 54.806 to 150.0 T 8.284 9.112 3.000 * * Fixed Loss = 3 TEE 34.99 0.0163 0.0 24.112 0.392 Vel = 4.28 TEE 0.0 6.34 2E 46.217 25.000 58.198 to 140.0 0.0 46.217 -2.166 TEST 34.99 0.0 0.0 71.217 0.003 Vel = 0.36 0.0 34.99 56.035 K Factor = 4.67 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 -WAYNE. Automatic Fire Sprinklers, Inc. PRODUCT DATA SUBMITTALS for Avalon Lot #25 St. Lucie County, FL WAFS JOB #95621 June 7, 2019 CONTENTS 1. Sprinklers 2. Pipe 3. Fittings 4. Hangers 5. Miscellaneous REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC WAYNE AUTOMATIC FIRE SPRINKLERS, INC. 1500 S. Powerline Road _Suite A - Deerfield Beach, FL 33442 TEL (954) 917-3030 or FAX (954) 917-9424 Bulletin 135 Rev. J W � p Model F1 m Residential Sprinklers for CO Design Density of .05 gpmfft2CO S11able Model F1 Res Sprinklers engineered for the lowest flows to meet the minimum design density of .05 gpm/ft2 Types: 1. F1 Res 30 Pendent 2. F1 Res 30 Recessed Pendent/F2 3. F1 Res 30 Recessed Pendent/FP 4. F1 Res 49 Pendent 5. F1 Res 49 Recessed Pendent/F1 6. F1 Res 49 Recessed Pendent/FP 7. F1 Res 58 Pendent 8. F1 Res 58 Recessed Pendent/F1 9. F1 Res 58 Recessed Pendent/FP 10. F1 Res 76 Pendent 11. F1 Res 76 Recessed Pendent/F1 12. F1 Res 76 Recessed Pendent/FP 13. F1 Res 30 CCP Pendent 14. F1 Res 49 CCP Pendent 15. F1 Res 58 CCP Pendent 16. F1 Res 76 CCP Pendent 17. F1 Res 44 HSW 18. F1 Res 44 Recessed HSW/F2 19. F1 Res 58 HSW 20. F1 Res 58 HSWX 21. KRes58 HSWX 22. F1 Res 58 HSW Recessed HSW/F2 23. F1 Res 44 SWC F1 Res 30, 49, 58 & 76 F1 Res 30, 49, 58 & 76 Recessed Pendent / F1 Recessed Pendent / FP F1 Res 30, 49, 58 & 76 CCP Pendent Listings & Approvals 1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) 2, NYC MEA 258-93-E Slope Ceiling Approvals: Refer to Bulletin 035 Sprinklers for .10 Density: Refer to Bulletin 176 UL Listing Category Residential Automatic Sprinkler UL Guide Number VKKW Patents F1 Res 44 & 58 F1 Res 44 SWC Recessed HSW/F2 ity glass -bulb and low profile decorative design. The F1 Res Horizontal Sidewall sprinklers (Figs. 5, 6 & 7) are equally attrac- tive when above ceiling piping cannot be used. The 3mm glass -bulb pendent sprinklers permit the efficient use of residential water supplies for sprinkler coverage in residential fire protection design. The low flow F1 Res sprinklers are specially engineered for fast thermal response to meet the sensitive fire protection applica- tion needs of the latest residential market standards (UL 1626 Standard). Upon fire conditions, rising heat causes a sprinkler's heat -sensitive element, glass bulb or link to actuate, releasing the waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire, Technical Data: • Thermal Sensor: Soldered Element (Link) or Nominal 3mm glass -bulb • Sprinkler Frame : Brass Casting US Patent No. 6,516,893 applies to the Model F1 Res 49 . Sprinklers' Pressure Rating : 175 psi & 58 Pendent Sprinklers Factory Hydrostatically Tested to 500 psi US Patent No. 7,353,882 applies to Model F1 Res 44 & 58 . Thread Size: '/2" NPT (R1/z) HSW Sprinklers . K-Factor: 3,0 (Actual) - F1 Res 30 Pendent Sprinkler US Patent No. 7,784,555 applies to Model F1 Res 44 SWC 4.9 (Actual) - F1 Res 49 Pendent Sprinkler Sprinklers Product Description 5.8 (Actual) - F1 Res 58 Pendent &HSW Sprinkler 7.6 (Actual) - F1 Res 76 Pendent Sprinkler Model F1 Res Pendent sprinklers (Figs, 1, 2, 3, & 4) are fast 4.4 (Actual) - F1 Res 44 HSW Sprinkler response sprinklers combining excellent durability, high sensitiv- . Density: Minimum 0.05 gpm/ft2 The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application Model F1 Res Sprinklers are used for Residential Fire Pro- tection according to UL 1626 Standard*. Be sure that ori- fice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of The National Fire Protection Association or the approving authority having jurisdiction. Installation Models F1 Res sprinklers are to be installed as shown. Model F1, F2 and FP Escutcheons, illustrated herewith, are the only recessed escutcheons to be used with Model F1 Res sprinklers. Use of any other recessed escutcheon will void all approvals and warranties. For installing Model F1 Res Pendent sprinklers use only the Model D sprinkler Wrench; for installing Models F1 Res Recessed Pendent, CCP & SWC sprinklers use only the Model GFR2 sprinkler • Model F1 Res 30, 49, 58 & 76 Pendent i 03SV I I 135FOOJ Fig. 1 wrench; for installing Model F1 Res Recessed HSW sprin- klers use only the Model GFR2 Sprinkler Wrench. Use of wrenches other than those specified may damage these sprinklers. Install F1 Res 44 with a ceiling to deflector dis- tance of 4" - 12". Flow arrow on deflector must point away from near wall and "Top" marking must face ceiling. Escutcheon*, F1 or F2, Data: Adjustment "A„ Face of fitting Type Inch (mm) Inch (mm) to ceiling Inch mm F1 3/4 (19.0) Min.=3/4" (19.1) 3/15 - 15/15 Max.=11/2" (38.1) (4.7 - 24.0) F2 1/2 (12.7) Min.=15/16" (23.8) 3/15 - 11/15 Max,=11/2" (38.1) 1 (4.7 - 17.4) * Note: Escutcheons F1 or F2 may be used with Model F1 Res 49, 58 & 76 Recessed Pendent Sprinkler • Model F1 Res 30 Recessed Pendent / F2 Mnrlal 1:1 Rac AQ RA R. 7R RaraQaarl Panrlanf / 1=1 F1 escutcheon, 3/4" (19mm) adjustment 2 1/" NIX£. (!1. 1 1 u/m• as F i 4 51, -13/1e P 6LVr06V/J 1fv/�/�/ .f/re-r1/1e !a csn+lvavll lionrslNenr I I IJSfCO].1 A ( 2 /N' M az�.*l Technical Data: F1 Res 30 Pendent and Recessed Pendent (SIN R3511) Fig. 2 Thread Nominal Orifice Max. Sprinkler Max. Actual Sprinkler Size Inch (mm) Pressure Temp. Ratin Ambient Temp. K Length OF °C °F °C psi bar Factor Inch mm 1/2" NPT R1/z 21/64" (8.2) 175 (12) 155 175 68 79 100 38 3.0 2.25 (57) Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector Minimum Max. Coverage area Max. Spacing 155°F/68°C 175°F/790C to Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (Umin) PSI bar GPM (Umin) PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 8(30,3) 7.0 (0,48) 8(30,3) 7.0 (0,48) 1 to 4 (25 to 100); '/2 recessed using 8(2.4) 14 x 14 (4,3 x 4,3) 14(4.3) 10 (37,8) 11 (0,76) 10 (37,8) 11 (0,76) F2 escutcheon For Ceilina tvoes refer to NFPA 13. 13R or 13D 2. Technical Data: F1 Res 49 Pendent and Recessed Pendent (SIN R3516) Max Sprinkler Max. Actual Sprinkler Thread Nominal Orifice Pressure Tem . Ratin Ambient Temp. K Length Size Inch (mm) psi bar Factor Inch mm OF °C OF °C '/z" NPT 7/16" (11) 175 (12) 155 68 100 38 4.9 2.25 (57) R'/z 175 79 150 66 Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum Max Coverage area Max Spacing 155°F/68°C 175°F/790C Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (Umin) PSI (barL GPM Vmin PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48) 1 to 4 (25 to 100); '/z (13) recessed 14 x 14 (4,3 x 4,3) 14(4,3) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 16(4.9) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48) using F2 escutcheon, 3/4 (19) recessed 8(2,4) 18 x 18 (5,5 x 5,5) 18(5,5) 17 (64,3) 12 (0,83) 17 (64,3) 12 (0,83) using F1 escutcheon 20 x 20 (6,1 x 6,1) 20(6.1) 20 (75,7) 16.7 (1,14) 20 (75,7) 16,7 (1,14) For Ceiling types refer to NFPA 13, 13R or 13D Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum Max. Coverage area Max. Spacing 155°F/680C 1750F/79°C Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (Umin) PSI bar GPM UminI PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 15 (57) 9,4 (0,65) 15 (57) 9.4 (0,65) 4 to 8 (100 to 203); Y2 (13) recessed 14 x 14 (4,3 x 4,3) 14(4,3) 16 (60,5) 10.6 (0,73) 16 (60,5) 10.6 (0,73) 16 x 16 (4,9 x 4,9) 16(4,9) 17 (64,3) 12.0 (0,83) 17 (64,3) 12.0 (0,83) using F2 escutcheon, 3/4 (19) recessed 8(2,4) 18 x 18 (5,5 x 5,5) 18(5,5) 19 (72) 15.0 (1,0) 19 (72) 15.0 (1,0) using F1 escutcheon 20 x 20 (6,1 x 6,1) 20(6,1) 22 (83,2) 20.2 (1,4) 22 (83,2) 20.2 (1,4) 'Note: The F1 Res 49 pendent and recessed pendent residential sprinklers can be installed per NFPA 13, NFPA 13R and NFPA 13D in beamed ceilings meeting the following criteria: 1. Maximum beam depth = 7" (178mm) 2. Beam spacing at or greater than 7.5 ft, (2.3m) on center, Technical Data: F1 Res 58 Pendent and Recessed Pendent (SIN R3513) Thread Nominal Orifice Max Sprinkler Max. Actual Sprinkler Size Inch (mm) Pressure Tem . Ratin Ambient Temp. K Factor Length OF °C OF oC psi (bar) Inch (mm) 112" NPT /2" (13) 175 (12) 155 68 100 38 5.8 2.25 (57) (R1/2) 175 79 150 66 Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum Max Coverage area Max. Spacing 155°F/68°C 175°F/790C Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (Umin) PSI bar GPM Umin PSI bar 12 x 12 (3,6 x 3,6) 12(3.6) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53) 1 to 4 (25 to 100); Yz (13) recessed 14 x 14 (4,3 x 4,3) 14(4,3) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53) 16 x 16 (4,9 x 4,9) 16(4.9) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53) using F2 escutcheon, 3/4 (19) recessed 8(2,4) 18 x 18 (5,5 x 5,5) 18 (5,5) 19 (72) 10.8 (0,75) 19 (72) 10.8 (0,75) using F1 escutcheon 20 x 20 (6,1 x 6,1) 20(6.1) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4 (1,0) For Ceiling types refer to NFPA 13, 13R or 13D 3, Technical Data: F1 Res 76 Pendent and Recessed Pendent (SIN R7618) Thread Nominal Orifice Max. Sprinkler Max. K Sprinkler Size Inch (mm) Pressure Temp. Ratin Ambient Tem Factor Length OF °C OF cc psi (bar) Inch (mm) 3/4" NPT "/3z (13.5) 175 (12) 155 68 100 38 7.6 2.25 (57) (R'/2) 175 79 150 66 Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum Max Coverage area Max Spacing 155°F/680C 175°17/790C Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM Umin PSI bar GPM Umin PSI bar 12 x 12 (3,6 x 3,6) 12(3.6) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) 1 to 4 (25 to 100); '/2 (13) recessed 14 x 14 (4,3 x 4,3) 14(4.3) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) 16 x 16 (4,9 x 4,9) 16(4.9) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) using F2 escutcheon, 3/4 (19) recessed 8(2,4) 18 x 18 (5,5 x 5,5) 18(5.5) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) using F1 escutcheon 20 x 20 (6,1 x 6,1) 20(6,1) 23 (87,1) 9.2 (0,63) 23 (87,1) 9.2 (0,63) For Ceiling Woes refer to NFPA 13. 13R or 13D • Model F1 Res 30, 497,58 & 76 CCP Pendent 2 5/8- [66.7mm] DIA. 2 5/16" VIA. HOLE IN CEILING [58.7mm] CUP !'xl/2" REDUCER CUP j CEILING 31.5mm] MAX. FACE OF FITDNG TO FACE OF CEILING DIMENSION I A, COVER ADJUSTMENTI HEIGIG HT I 3 5/16" DIA. 135FG04D [84.1 mm] F1 RES 30, 49, 58 & 76 CCP PEND. Fig. 3 Note: The F1 Res 76 will use a 1" x 3/4" reducer. 4 • Model F1 Res 30, 49, 58 & 76 I 1 LIUJII-VII/U IIGCI I.I-VII GJIFU IIAIIGVII z aPo' ou. fear J rat a Qeac z e/re• ou fsrl� 1 nw r- r I I r• r r/P r2prne I ILL Quac J � FAQ' G" Ri➢.G L�\\ OxEN990x ry Aortrsarxr 1 uvmu F1 RES 49 PENDENTZ FP Fig. 4 Technical Data: F1 Res 30 CCP Pendent and Recessed Pendent/FP (SIN R3511) Thread Nominal Max. CCP Assembly Max. K Sprinkler Size Orifice Pressure Temp. Ratin Ambient Temp- Factor Length OF °C OF °C Inch mm psi bar Inch mm '/z" NPT 21/64" (8.2) 175 (12) 135 57 100 38 3.0 2.25 (57) R'/z Ordinary Temp. Rating Top of Deflector Minimum Max. Coverage area Max. Spacing 1550F/68°C to Ceiling Spacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM Umin PSI bar 12 x 12 (3,6 x 3,6) 12(3.6) 8(30,3) 7.0 (0,48) 1 to 4 (25 to 100); Yz (13mm) recessed 8(2.4) 14 x 14 (4,3 x 4,3) 14(4.3) 11 (37,8) 13.4 (0,92) using FP escutcheon For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516) Nominal Max. CCP Assembly Max. Sprinkler Thread Orifice Pressure Temp. Ambient K Length Size Inch psi (bar) Rating Temp. Factor Inch (mm) (mm) OF °C OF °C '/z" NPT (R/z) 7/16" (11) 175 (12) 135 57 100 38 4.9 2.25 (57) Max. Coverage Ordinary Temp. Rating Top of Deflector to Minimum area Max. Spacing 155°F/680C Ceiling Spacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (Umin) PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 13 (49) 7.0 (0,48) 1 to 4 (25 to 100); 14 x 14 (4,3 x 4,3) 14(4.3) 13 (49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 16(4,9) 14 (53) 8.2 (0,56) 1/z (13) recessed using FP escutcheon 8(2,4) 18 x 18 (5,5 x 5,5) 18 (5,5) 18 (68,1) 13.5 (0,93) 20 x 20 (6,1 x 6,1) 20(6,1) 20 (75,7) 16.7 (1,14) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513) CCP Options Data: "A„ "B„ Cover Adjustment CCP Height Inch mm Inch mm 1/2 (12.7) 15/1e (24) 6/1e (7.9) 3/4 (19) FP Data "A": «A„ FP Position Inch mm Max. Recessed 7/1e(11) Min. Recessed 15/1624 Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in the space above. Thread Nominal Max. CCP Assembly Max. K Sprinkler Size Orifice Pressure Temp. RatingFactor Ambient Temp. Length °F °C OF °C Inch (mm) psi bar Inch (mm) /z" NPT R'/z) 1/2" (13) 175 (12) 135 57 100 38 5.8 2.25 (57) Max. Coverage Ordinary Temp. Rating Top of Deflector to Minimum area Max. Spacing 155°F/68°C Ceiling Spacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM Umin PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 16 (61) 7.6 (0,53) 1 to 4 (25 to 100); 14 x 14 (4,3 x 4,3) 14(4.3) 16 (61) 7.6 (0,53) 16 x 16 (4,9 x 4,9) 16(4.9) 16 (61) 7.6 (0,53) /z (13) recessed using FP escutcheon 8(2,4) 18 x 18 (5,5 x 5,5) 18(5,5) 19 (72) 10.8 (0,75) 20 x 20 (6,1 x 6,1) 20(6.1) 22 (83,3) 14.4 (1,0) For Ceiling types refer to NFPA 13, 13R or 13D 5. Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618) Thread Nominal Max. CCP Assembly Max. Sprinkler Size Orifice Pressure Temp. RatingAmbient Temp.K Factor Length OF °C OF oC Inch (mm) psi (bar) Inch (mm) 3/(RN)T 3 17/32" (13.5) 175 (12) 135 57 100 66 7.6 2.25 (57) Max. Coverage Max. Spacing Ordinary Temp. Rating 155°F/68°C Top of Deflector to Minimum area Ft (m) Ceiling Spacing Flow Pressure Ft x Ft (m x m) GPM (Umin) PSI bar Inch (mm) Ft (m) 12 x 12 (3,6 x 3,6) 12(3,6) 21 (79,5) 7.6 (0,53) 1 to 4 (25 to 100); 14 x 14 (4,3 x 4,3) 14(4,3) 21 (79,5) 7.6 (0,53) 16 x 16 (4,9 x 4,9) 16(4,9) 21 (79,5) 7.6 (0,53) /2 (13) recessed using FP escutcheon 8(2,4) 18 x 18 (5,5 x 5,5) 18(5,5) 22 (83,3) 8.4 (0,58) 20 x 20 (6,1 x 6,1) 20(6,1) 25 (94,6) 10.8 (0,74) For Ceiling types refer to NFPA 13, 13R or 13D FACE OF FITTING TO WALL DIMENSION 1 114' MIN. 2 114" HOLE DIA. A" [57.2mm] 1�8 CEILING TO [3.2mm] DEFLECTOR 1- X 112" REDUCER DIMENSION n� i r-- �m 1 1511 OIA. J om I [49.2mmJ--- - - 2 27/32" DIA. [72.2mm] mu 1r L TURN COLLAR UNTIL �1 TIGHT AGAINST SPRINKLER WRENCH BOSS. 7I 112" [13mm] JSFC06—D ADJUSTMENT F1 RES 58 & 44 HSW/F2 Fig. 5 Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531) • Model F1 Res 44 & 58 HSW • Model F1 Res 44 & 58 Recessed HSW/F2 Thread Nominal Max. Sprinkler Max. Ambient K Sprinkler Size Orifice Pressure Temp. Rating Tem Factor Length Inch (mm) psi (bar) Inch (mm) 'F °C OF oC 1/2" NPT 3/8" (10) 175 (12) 155 68 100 38 4.4 2.45 (62) (R'/2) 175 79 150 66 0 F2 escutcheon, 1/2" (13mm) adjustment Escutcheon, F2, Data: Face of Fitting Type Adjustment Inch (mm) to wall Inch (mm) F2 1/2(13) 3/16 — 11/16 (4.7 - 17.4) Max Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (1550F/68°C Intermediate Temp. Rating 175°F/790C Top of Deflector to Ceiling Inch (mm) Minimum Spacing Ft (m) Flow GPM (Vmin) Pressure PSI bar Flow GPM Umin Pressure PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 12 (45,4) 7.5 (0,52) 12 (45,4) 7.5 (0,52) 4 to 6 (100 to 152); 112 (13) recessed using F2 escutcheon 8(2,4) 14 x 14 (4,3 x 4,3) 14(4.3) 14 (53,0) 10.2 (0,71) 14 (53,0) 10.2 (0,71) 16 x 16 (4,9 x 4,9) 16(4,9) 16 (60,6) 13.3 (0,92) 16 (60,6) 13.3 (0,92) 16 x 18 (4,9 x 5,5) 16(4,9) 18 (68,1) 16.8 (0,53) 18 (68,1) 16.8 (0,53) 18 x 18 (5,5 x 5,5) 18(5.5) 19 (72,0) 18.7 (1,29) 19 (72,0) 18.7 (1,29) 16 x 20 (4,9 x 6,1) 16(4.9) 23 (87,1) 27.4 (1,89) 23 (87,1) 27.4 (1,89) 12 x 12 (3,6 x 3,6) 12(3.6) 14 (53,0) 10.2 (0,71) 14 (53,0) 10.2 (0,71) 6 to 12 (152 to 305); '/2 (13) recessed using F2 escutcheon 14 x 14 (4,3 x 4,3) 14(4.3) 16 (60,6) 13.3 (0,92) 16 (60,6) 13.3 (0,92) 16 x 16 (4,9 x 4,9) 16(4.9) 17 (64,4) 15,0 (1,04) 17 (64,4) 15.0 (1,04) 16 x 18 (4,9 x 5,5) 16(4,9) 20 (75,7) 20.7 (1,43) 20 (75,7) 20,7 (1,43) 16 x 20 (4,9 x 6,1) 16(4,9) 23 (87,1) 27.4 (1,89) 23 (87,1) 27.4 (1,89) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 58 HSW & HSW/F2 SIN R3533) Escutcheon, F2, Data: Nominal Max. Face of Fitting Thread Orifice Ambient K 1 Pressure Temp. Rating Length TYI� Inch mm to wall Size Inch Tem . Factor ( ) Inch mm ( ) (mm) psi (bar) 'F ,C °F °C Inch (mm) 1/2" NPT 155 68 100 38 F2 '/2 (13) 3/7 - 17. '/2" (13) 175 (12) 5.8 2.45 (62) (4.- 7.4) (RY2) 175 79 150 66 Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum Max. Coverage area Max. Spacing 155°F/68°C 175°F/79°C Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (Umin) PSI bar GPM Umin PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 16 (60,6) 7.6 (0,53) 16 (60,6) 7.6 (0,53) 4 to 6 (100 to 152); 14 x 14 (4,3 x 4,3) 14(4,3) 18 (68,2) 9.7 (0,69) 18 (68,2) 9,7 (0,69) 16 x 16 (4,9 x 4,9) 16(4.9) 21 (79,5) 13.2 (0,91) 21 (79,5) 13,2 (0,91) /2 (13) recessed using F2 escutcheon 16 x 18 (4,9 x 5,5) 16(4.9) 25 (94,7) 18.6 (1,28) 25 (94,7) 18.6 (1,28) 8(2.4) 16 x 20 (4,9 x 6,1) 16(4,9) 29 (109,8) 25.0 (1,73) 29 (109,8) 25,0 (1,73) 12 x 12 (3,6 x 3,6) 12(3,6) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4 (1,0) 6 to 12 (152 to 305); 112 (13) recessed 14 x 14 (4,3 x 4,3) 14(4,3) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4 (1,0) 16 x 16 (4,9 x 4,9) 16 (4,9) 26 (98,4) 20.1 (1,39) 26 (98,4) 20.1 (1,39) using F2 escutcheon 16 x 18 (4,9 x 5,5) 16(4.9) 31 (117,4) 28.6 (1,97) 31 (117,4) 28.6 (1,97) or Ceiling types refer to NFPA 13, 13R or 13D • Model F1 Res 44 SWC ,• to 12' 1101.60mm To 1 1. 1/4' [J7.75-1 Af-rmum J04.80mm] Fvice OL rilt:ig ro Dim bn PUSH ON COVER. THEN TURH TO AOJUSr UNRL RGHr AGNNSr WALL 1 • X 7/2' Reducer 1 Rerommended"r ` Wall Hole 2 .74m. [66.68mmJ Oio. J 5/I6' [64. 14 Dio. TURN cOLLAR UNOL ' 1 RGHr Ac4/NSr SPRINKLER WRENCH BOSS. 7 21/J2' [4T.07mm] 2• [l2.70m.] Adjusbnent F1 RES 44 SWC Fig. 6 Technical Data: F1 Res 44 SWC (SIN R3531) Nominal Max. Cover Max. Sprinkler Thread Orifice Pressure Temp. Ambient K Length Size Inch (mm) psi (bar) Rating Temp. Factor Inch (mm) ,F °C ,F 0C 1/2" NPT R'/2) 3/8" (10) 175 (12) 135 57 100 38 4.4 2.45 (62) Ordinary Temp. Rating Top of Deflector to Minimum Max. Coverage area Max. Spacing 155°F/68°C) Ceiling Spacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (Umin PSI bar 12 x 12 (3,6 x 3,6) 12(3,6) 13 (49,2) 8.7 (0,60) 4 to 6 (100 to 152); 14 x 14 (4,3 x 4,3) 14(4,3) 14 (53,0) 10.2 (0,71) 16 x 16 (4,9 x 4,9) 16(4.9) 17 (64,3) 15.0 (1,1) /2 (13) recessed using F2 escutcheon 16 x 18 (4,9 x 5,5) 16(4,9) 19 (71,8) 18.7 (1,13) 8(2.4) 16 x 20 (4,9 x 6,1) 16(4,9) 23 (87,1) 27.4 (1,89) 12 x 12 (3,6 x 3,6) 12(3,6) 14 (52,9) 10.2 (0,71) 6 to 12 (152 to 305); 1/2 (13) recessed 14 x 14 (4,3 x 4,3) 14(4,3) 15 (56,7) 11.7 (0,81) 16 x 16 (4,9 x 4,9) 16(4,9) 18 (68,1) 16.8 (1,16) using F2 escutcheon 16 x 18 (4,9 x 5,5) 16(4,9) 20 (75,6) 20.7 (1,43) For Ceiling types refer to NFPA 13, 13R or 13D a Technical Data: Fi Res 58 HSWX (SIN RA3533) Thread Nominal Max. Sprinkler Max. Ambient PCSize Sprinkler Sprinkler Orifice Pressure Temp. Rating Tem Factor Length Identification Inch (mm) psi (bar) Inch (mm) Number (SIN) OF °C OF °C Bulb /z NPT (R/2) 1/2" (13) 175 (12) 155 175 68 79 100 150 38 66 5.8 2.45 (62) RA3533 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating 155°F/68°C Intermediate Temp. Rating 175°F/790C Top of Deflector to Ceiling (mm) Minimum SpacingInch Ft (m) Flow GPM (Umin) Pressure PSI bar Flow GPM Umin Pressure PSI bar 18 x 20 (5,5 x 6,1) 18(5,5) 30 (114) 26,8 (1,85) 30 (114) 26.8 (1,85) 4 to 6 (100 to 152); 1/2 (13) recessed using F2 escutcheon 8(2,4) 20 x 20 (6,1 x 6,1) 20(6.1) 30 (114) 26,8 (1,85) 30 (114) 26.8 (1,85) 16 x 22 (4,9 x 7,3) 16(4.9) 33 (125) 32.4 (2,23) 33 (125) 32.4 (2,23) 16 x 24 (4,9 x 7,3) 16(4,9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96) 14 x 26 (4,3 x 7,9) 14(4.3) 42 (160) 52.4 (3,75) 42 (160) 52.4 (3,75) 18 x 20 (5,5 x 6,1) 18(5.5) 35 (133) 36.4 (2,5) 35 (133) 36.4 (2,5) 6 to 12 (152 to 305); 1/2 (13) recessed using F2 escutcheon 16 x 22 (4,9 x 6,7) 16(4.9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96) 16 x 24 (4,9 x 7,3) 16(4.9) 42 (160) 52.4 (3,6) 42 (160) 52.4 (3,6) 14 x 26 (4,3 x 7,9) 14(4,3) 46 (174) 62.9 (4,34) 46 (174) 62.9 (4,34) For Ceiling types refer to NFPA 13, 13R or 13D FACE OF FITTING TO WALL DIMENSION 1 I V16" MIN. 2 114" HOLE DIA. [31.8mm] A" [57.2mm] 1�8" CEILING TO [J.2mmJ DEFLECTOR 1" X 112" REDUCER DIMENSION 1 15116" DIA. f nni [49.2mm] "i --� I I 2 27132" OK ®i [72.2mm] TURN COLLAR UNTIL \1 TIGHT AGAINST SPRINKLER \\ WRENCH BOSS. IJ5FC08 I 112" [13mm] ADJUSTMENT F1 RES 58 HSWX Fig. 7 a • Model F1 Res 58 HSWX (Bulb) Technical Data: KRes58 HSWX (RA3593) Thread Nominal Max. Max. Ambient K Sprinkler Sprinkler Size Orifice Pressure Temp. Factor Length Identification Inch (mm) psi (bar) Inch (mm) Number (SIN) 'F ,C Link 1/2" NPT (R'/2) 1/2" (13) 175 (12) 100 38 5.8 2.45 (62) RA3593 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating 165°Fl74°c Top of Deflector to Inch Ceiling ling(mm Minimum Spacin g Ft Spacing Flow GPM Umin Pressure PSI bar 18 x 20 (5,5 x 6,1) 18(5,5) 29 (109) 25 (1,72) 4 to 6 (100 to 152); 112 (13) recessed using F2 escutcheon 8(2,4) 20 x 20 (6,1 x 6, 1) 20(6,1) 30(114) 26.8(1,85) 16 x 22 (4,9 x 7,3) 16(4,9) 33 (125) 32.4 (2,23) 16 x 24 (4,9 x 7,3) 16(4,9) 38 (144) 42.9 (2,96) 14 x 26 (4,3 x 7,9) 14(4,3) 42 (160) 52.4 (3,75) 18 x 20 (5,5 x 6,1) 18(5,5) 35 (133) 36.4 (2,5) 6 to 12 (152 to 305); /2 (13) Recessed using F2 escutcheon 16 x 22 (4,9 x 6,7) 16 (4,9)' 38 (144) 42.9 (2,96) 16 x 24 (4,9 x 7,3) 16(4,9) 42 (160) 52.4 (3,6) 14 x 26 (4,3 x 7,9) 14(4,3) 46 (174) 62.9 (4,34) For Ceiling types refer to NFPA 13, 13R or 13D Maintenance Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res 44 Sprinklers should be inspected quarterly, and the sprinkler system maintained in accordance with NFPA 25, 13, 13D, and 13R. Do not clean sprinkler with soap and water, Ammonia or any other cleaning fluids, Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has been painted (other than factory applied) or damaged in any way, A stock of spare sprin- klers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should remain in the original cartons and pack- aging until used. This will minimize the potential for dam- age to sprinklers that could cause improper operation or non -operation. Model F1 Res 30, 49 & 58 Pendent Sprinkler Specifications Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential pendent sprin- klers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer's installation guide- lines and the applicable installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers 1W shall be listed for such use. Deflector -to -ceiling distance listing shall be 1" to 8" maximum. Sprinkler frame and deflector shall be of bronze frame construction having a'/2" NPT thread. Water seal assembly shall consist of a Teflon -coated Belleville spring washer with top -loaded extruded or cold head cup with 3 mm glass bulb con- taining no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K-factor of 3,0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome -plated] [White Polyester] [Special fin- ish- specify]. Residential pendent sprinklers shall be Re- liable Model F1 Res 30, 49 & 58, SIN R3511, R3516 & R3513 (Bulletin 135). Model Fi Res 49 & 58 Recessed Pendent/F1, Model F1 Res 30, 49 & 58 Recessed Pendent/ F2, Model 171 Res 30, 49 & 58 Recessed Pendent/ FP Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential recessed pen- dent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer's instal- lation guidelines and the applicable installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use, Deflector -to -ceil- ing distance listing shall be 1" to 8" maximum. Sprinkler frame and deflector shall be of bronze frame construction having a'/2" NPT thread. Water seal assembly shall con- sist of a Teflon -coated Belleville spring washer with top - loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K-factor of 3.0, 4.9 & 5.8. Standard fin- ish: [Bronze] [Chrome -plated] [White Polyester] [Special finish— specify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with 1/2" adjustment (Model F2)] [with 3/a" adjustment (Model F1)] [of push -on and thread off design with 1/2" adjustment (Model FP)]. Standard finish shall be [brass][bright chrome] [white painted]. Residential recessed pendent sprinklers shall be Reliable [Model F1 Res 30, 49 & 58 Recessed Pen- dent/F1] [Model F1 Res 30, 49 & 58 Recessed Pendent/ F2] [Model F1 Res 30, 49 & 58 Recessed Pendent/FP] SIN R3511, R3516 & R3513 (Bulletin 135). Model F1 Res 30,49 & 58 CCP Pendent (Con- cealed) Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential concealed sprinklers engineered to provide a minimum design den- sity of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprinklers shall be in- stalled in conformance with the manufacturer's installa- tion guidelines and the applicable installation standard. Where pendent residential sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Sprinkler frame and deflector shall be of bronze frame construction having a 1/2" NPT thread. Water seal assembly shall consist of a Teflon -coated Belleville spring washer with top -loaded extruded or cold head cup with 3 mm glass bulb contain- ing no plastic parts, and having a temperature rating of 155°F (68°C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange. Meth- od of attaching the cover plate to the sprinkler cup shall be a push -on and thread -off design allowing a'/2" cover plate adjustment. Cover plate temperature rating shall be 135°F (57C). A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color— specify]. ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 30, 49 & 58 CCP, SIN R3511, R3516 & R3513 (Bul- letin 135). Model F1 Res 44, F1 Res 58 Horizontal Side - wall, F1 Res 58 HSWX & KRes58 HSWX Resi- dential Sprinkler Specifications Sprinklers shall be [cULus Listed] low flow residential horizontal sidewall sprinklers engineered to provide a minimum design density of 0,05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manu- facturer's technical data sheets are to be used. Residen- tial sprinklers shall be installed in conformance with the manufacturer's installation guidelines and the applicable installation standard. Where horizontal sidewall residen- tial sprinklers are installed under sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers shall be listed for such use. Sprinkler frame and deflector shall be of bronze frame construction having a 1/2" NPT thread. Water seal assembly shall consist of a Teflon -coated Belleville spring washer with top -loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. The solder element (Link) version, the water seal consist of a cap with a bellville spring washer and a temperature rat- ing of 165°F (74°C). The recessed assembly forthe HSWX (Bulb & Link) should be a steel two pieces escutcheon with 1/2" adjustment (Model F2) standard finish should be Bright Chrome and white painted, The F1 Res 58 HSW is also available with low lead frame. F1 Res 58 HSW and HSWX sprinklers shall have a nominal K Factor of 5.8 and F1 Res 44 a nominal K factor of 4.4. Standard fin- ish: [Bronze] [Chrome -plated] [White Polyester] [Special finish— specify]. Residential horizontal sidewall sprinklers shall be Reliable Model F1 Res 44, F1 Res 58, F1 Res 58 HSWX & Model KRes58 HSWX, SIN R3531, RA3533 & RA3593 (Bulletin 135). Model F1 Res 44 Recessed Horizontal Sidewall Sprinkler Use description for the Model F1 Res 44 horizontal side - wall sprinkler with the following modifications: Replace "horizontal sidewall sprinkler" with "recessed horizontal sprinkler." Add: Recessed escutcheon assembly shall be a steel, two-piece escutcheon with 1/2" adjustment (Model F2). Standard finish shall be [brass][bright chrome] [white painted] [Special finish— specify]. Residential recessed horizontal sidewall sprinklers shall be Reliable Model F1 Res 44/F2, SIN R3531 (Bulletin 135). 11. Model F1 Res 76 Pendent Sprinklers shall be [cULus Listed] low flow residential pendent sprinklers engineered to provide a minimum de- sign density of 0,05 gpm/ftz over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer's in- stallation guidelines and the applicable installation stan- dard. Sprinkler frame and deflector shall be of bronze frame construction having a 3/4" NPT thread. Water seal assembly shall consist of a Teflon -coated Belleville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a tempera- ture rating of [1550F (680C)] [1750F (79°C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome -plated] [White Polyester] [Special fin- ish— specify]. Residential pendent sprinklers shall be Reli- able Model F1 Res 76, SIN R7618 (Bulletin 135). Model F1 Res 76 Recessed Pendent/F1, Model F1 Res 76 Recessed Pendent/F2, Model F1 Res 76 Recessed Pendent/FP Sprinklers shall be [cULus Listed] low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0,05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manu- facturer's technical data sheets are to be used. Residen- tial sprinklers shall be installed in conformance with the manufacturer's installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a 3/4" NPT thread. Water seal assembly shall consist of a Teflon -coated Bel- leville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and hav- ing a temperature rating of [1550F (680C)] [175OF (790C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome -plated] [White Polyester] [Spe- cial finish— specify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with 1/2" adjust- ment (Model F2)] [with 3/4" adjustment (Model F1)] [of push -on and thread off design with'/2" adjustment (Mod- el FP)]. Standard finish shall be [brass][bright chrome] [white painted]. Residential recessed pendent sprinklers shall be Reliable [Model F1 Res 76 Recessed Pendent/ F1] [Model F1 Res 76 Recessed Pendent%172] [Model F1 Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135). Model F1 Res 76 CCP Pendent (Concealed) Sprinklers shall be [cULus Listed] low flow residential concealed sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer's technical data sheets are to be used. Residential sprin- klers shall be installed in conformance with the manufac- turer's installation guidelines and the applicable instal- lation standard. Sprinkler frame and deflector shall be of bronze frame construction having a 3/4" NPT thread. Water seal assembly shall consist of a Teflon -coated Bel- leville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of 155°F (68°C). Cover plate assem- bly shall consist of a brass cover plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push -on and thread -off design allowing a'/2" cover plate adjustment. Cover plate tem- perature rating shall be 1350F (570C). A plastic protec- tive cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color— specify], ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135). Finishes (1) Standard Finishes F1, F2, FP Sprinkler Escutcheons Cover Plates Bronze Brass White Painted Chrome Plated Bright Chrome Plated Chrome White and Black Polyester White Painted Coated Special Application Finishes Sprinkler F1' F2' Cover Plates Escutcheons Bright Brass Bright Brass Bright Brass Black Plated Black Plated Black Plated Black Paint Black Paint Black Paint Off White Off White Off White Satin Chrome Satin Chrome Satin Chrome Other finishes and colors are available on special order. Consult factory for details. Note: Paint or any other coating applied over the factory finish will void all approvals and warranties. Ordering Information Specify: 1. Sprinkler Model 2. Sprinkler Type 3. Temperature Rating 4. Sprinkler Finish 5. Escutcheon Finish 6. Cover Plate Finish The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. ®Recycled Relle" (800) 431-1588 Sales Offices Paper iabi (800) 848-6051 Sales Fax Revision lines indicate updated or new data. (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 05/13 PM 9999970235 Sprinkler Emergency Cabinets • Model A4 Designed to carry an emergency supply of sprinklers and a sprinkler wrench. Made of light weight steel with holes for mounting. These compact cabinets are fin- ished in attractive red enamel and are furnished with knockouts to accommodate either 1/2' or 3/4" sprinkler threads. The Model A4 Cabinets are available in the fol- lowing sizes: • 3 Capacity - For residential sprinklers in NFPA 13D and 13R systems 5" high x 73,6" long x 2X" deep. Locate wrench separately. • 6 Capacity Standard - For }2" and X" NPT standard and large orifice sprinklers. 5" high x 14" long x 2X" deep. • 6 Capacity Large - For ESFR, XLO and VELO Sprinklers. 6}4" high x 14" long x 3}e" deep. • 12 Capacity Standard - For y" and X" NPT standard and large orifice sprinklers. 5" high x 14" long x 4" deep. • Model A3 Model A3 Cabinets are designed to carry an emergency supply of decorative type sprinklers and an installation wrench. They are able to accommodate 12 Reliable Models G Recessed, G1, G4, G4FR, ZX or Model B Flush Sprinklers, and up to 6 sprinklers with a 1" adjust- able inlet. Installation Data: Size of Cabinet: 16%6" long x 14}4" high x 3%16" deep. Size of Mounting Holes: X diameter. Spacing of Mounting Holes: 13y length -11" height. Ordering Information When ordering, specify Model (A4 or A3) and cabinet capacity size and type (Standard or Large). Sprinklers and sprinkler wrenches are to be ordered separately. Sprinkler Escutcheons These escutcheons enhance the appearance of instal- lations by covering exposed fittings of automatic sprin- kler systems that are visible beyond finished ceilings and walls. Furnished to accommodate NPT male pipe threads, escutcheons are held firmly in place by the sprinklers. The finishes provided are decorative and in- tended for indoor use. Bulletin 204 Rev. V •Sprinkler Emergency Cabinets *Sprinkler Escutcheons Model A4 3 Capacity Residential ivioaei H4 6 Capacity Standard Model A4 6 Capacity Large 12 Capacity The Reliable Automatic Sprinkler Co., Inc.,103 Fairview Park Drive, Elmsford, New York 10523 co c_ m N O m a Approvals There are no UL Listings or FM Approvals associated with the Models A, B, and C one piece escutcheons or the Model HB two piece escutcheon. They may be used with any Reliable Sprinkler with the exception of re- cessed sprinklers which are listed together with their re- spective escutcheons. Refer to the appropriate technical bulletins for this information. • Model B - One Piece Available in steel with satin chrome, bright chrome and brass plated and white painted finishes. Inner fingers grip tightly to the sprinkler. Also available for 10mm sprinklers. r . Diameter: 27/s"; Depth: p Ys ; }z" NPT. • Model C - One Piece Available in steel with satin chrome, bright chrome and brass plated and white painted finishes. Inner fingers grip tightly to the sprinkler. Also MEN available for 10mm sprinklers Diameter: 27/$ Depth: Ys"; '/2" NPT. Model HB - Two Piece Telescoping design permits up to 1" adjustment to compensate for variations in the distance that pipe couplings extend below ceilings. Made of steel and available in brass, chrome, satin nickel and off-white finishes. Diameter: 3y"; Depth: 2" Min, 3" Max;'/2" and 3/4" NPT. The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. Reliable" (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address ® Recycled Paper Revision lines indicate updated or new data. PG. Printed in U.S.A. 12107 P/N 9999970035 This building contains a CPVC fire sprinkler system. This CPVC fire sprinkler system is a Life Safety Assembly and must be treated carefully. Please read the following before any activity which could contact this system: CPVC piping components may be damaged by certain substances and construction practices. • DO NOT stack, support, hang equipment, or hang flexible wire/cable, especially communications cable, or other material on the fire sprinkler system. • ONLY system compatible materials including, but not limited to solvent cements, caulks, sealants, cutting oils and thread pastes as noted by the CPVC fire sprinkler piping system manufacturer's installation instructions should be used in contact with this system. • DO NOT expose CPVC products to incompatible substances, such as cutting oils, non -water based paints, packing oils, traditional pipe thread paste and dope, fungicides, termiticides, insecticides, detergents, building caulks, adhesive tape, solder flux, flexible wire/ cable (with special consideration for communications cabling), and non -approved spray foam insulation materials. • DO NOT expose CPVC products to edible oils, solvents, or glycol -based anti -freeze fluids. • DO NOT expose CPVC products to open flame, solder, and soldering flux. • DO NOT handle CPVC products with gloves contaminated with oils (hydrocarbons) or other incompatible materials. Failure to follow this notice may cause cracks or fractures to develop in CPVC products resulting in property damage due to leaks or flooding. The presence of any visible cracks may require partial or full system replacement. For additional information contact the general contractor or the fire sprinkler system installer. c FOR ADDITIONAL INFORMATION CONTACT SPEARS® MANUFACTURING COMPANY AT 1-800-862-1499 Rev. 3.0 Jan 2008 FGN-7-0108 Important Information with Regards to Your CPVC Fire Sprinkler System CONGRATULATIONS! This building contains a state-of-the-art FlameGuard° life safety system. Your CPVC fire sprinkler system will enhance the safety and security of your building when properly cared for. CPVC Fire Sprinkler Products resist attack from a wide range of chemicals that are corrosive to metallic piping. As with any piping material, there are certain chemicals that can be detrimental to CPVC. Occasionally, some of these chemicals may be found in some construction products, site preparations and building maintenance. There are certain things that you need to be mindful of in caring for or working around your CPVC fire sprinkler system. Keep your system clear from contact with the following products and chemicals unless product labels state materials are compatible with CPVC: NOTICE Ordinary Considerations, Cleaning Products/Detergents Oils/Lubricants/Greases Rubbery Materials For Hired Contractors & Dodt-Yourselfers Corrosion Inhibitors Glycol -based antifreezes Solder Flux Thread Sealants Flexible Cable/Wiring (especially communications cabling) Caulks/Mastics Adhesive Vinyl/Electrical Tape Non -Water Based Paint Paint Thinners Wood Finishes/Varnishes You should also avoid the following: nance Services Fungicides Mold Remediation Chemicals/Termiticides/Insecticides • Sitting, standing, hanging, leaning, or resting anything on the pipe, fittings, and sprinkler heads • Grounding electrical wiring to the pipe or fittings • Ambient temperatures below 40°F/4°C where your fire sprinkler system is located. (Unless an approved compatible antifreeze or insulation method is installed.) • Hot work around the pipe, i.e. blow torches, soldering, etc. Be certain this document is reviewed and understood by anyone working on or around your CPVC life safety system. If you have any questions or need assistance on chemical compatibility with your CPVC fire sprinkler system, contact the manufacturer listed on the pipe. Proper care will help your CPVC fire sprinkler system provide protection for years to come. FOR ADDITIONAL � INFORMATION CONTACT `'� SPEARS® MANUFACTURING CIPVC FIRE OPHINNUR PII'IMMS COMPANY AT 1-800-862-1499 CPVC Fire Sprinkler 11irnover Document 06-20-16 FGT-7-0616 SPEARS FlameGvard' CPVC FIRE SPRINKLER PIPING PRODUCTS T' .4 4 Novemb SUPERSEDES ALL Pf CERr/ L UKA S MA19GEMEW n n 5 Visit our uriah site: Assessed tojgo,gool:-giom .1115 FG4 nV' Certificaie, 6mber 29 j r 3 , IONS Ej FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS The information contained in this section is based on current information and Product design at the time of publication and is subject to change without notification. Our ongoing commitment to product improvement may result in some variation. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability for particular applications or results to be obtained therefrom. For verification of technical data or additional information not contained herein, please contact Spears"Technical Services Department [West Coast: (818) 364-1611—East Coast: (678) 985-1263]. General Information RECOMMENDATIONS FOR INSTALLERS AND USERS: Plastic piping systems should be ENGINEERED, INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS AND PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the installer and/or user prior to installation of a plastic piping system. All Installation and maintenance personnel should be trained in the proper handling and installation requirements and precautions of plastic piping systems. PRIOR TO ASSEMBLY, all piping system components should be inspected for damage or irregularities. Mating components should be checked to assure that tolerances and engagements are compatible. Do not use any components that appear irregular or do not fit properly. Contact the appropriate manufacturer of the component product in question to determine usability. Consult all applicable codes and regulations for compliance prior to installation. Installation must be made in accordance with Spears° Manufacturing Company FlameGuard@ CPVC Fire Sprinkler Piping Products Installation Instructions - FG-3 NOTE — Individual or group instruction in correct solvent welding procedures is available by contacting your local distributor or your servicing Spears° Regional Distribution Center. SOLVENT CEMENT CONNECTIONS — Spears" Manufacturing Company recommends the use of Spears° FS-5 One Step solvent cement for joining Spears° products. Use of solvent cementing products not approved for CPVC fire sprinkler systems, or failure to follow installation instructions will automatically void the warranty. THREADED CONNECTION — Spears" Manufacturing Company recommends the use of Spears° BLUE 75TM Thread Sealant. This product has been tested by Spears" and the sealant manufacturer for compatibility with the Spears° CPVC fire sprinkler products. Consult the sprinkler head manufacturer before using this product. WARNING: OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN THE CPVC OR OTHER FITTING COMPONENTS. Care must be taken to avoid over torquing - generally 1 to 2 turns beyond finger tight is all that is required to make up a threaded connection. Factory testing has indicated 10-25 ft. lbs. of torque is adequate to obtain a leak free seal. GASKET SEALED THREAD CONNECTIONS —This type of connection can only be made with Spears@ TorqueSafeTM, SofTorqueTM or QuickTorqueTM style Gasket Sealed Female Sprinkler Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER. Tape or paste may impair proper sealing and function. Testing has shown that hand tight until snug for the TorqueSafeTM adapter and finger tight plus 14um is all that is needed to seal this special connection. Sprinkler heads in these specialty fittings can then be additionally tightened clockwise to bring sprinkler frames into desired alignment without stressing the fitting. See specific adapter instructions in package for details. GripLocTM CONNECTIONS —This type of connection can only be made with Spears@ GripLocTM Couplings or Repair Couplings. DO NOT USE ANY TYPE OF SOLVENT CEMENT OR SEALANT WHEN INSTALLING THIS TYPE OF CONNECTION. Uses an internal stainless steel gripper ring with an internal elastomer gasket seal. Connection allows immediate system use. See specific instructions in package for details. Installation Training Available - Contact Spears° Technical Services for Details FlameGuard@ Products must be installed in accordance with Spears" FlameGuard° CPVC Fire Sprinkler Piping Products Installation Instructions, National Fire Protection Association Standards 13,13R,13D, and in accordance with local codes. Code requirements and field conditions may differ. It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements. Dimension Reference G = (LAYING LENGTH) Intersection of center lines to bottom of socket/thread; 90° elbows, tees, crosses; ± 1/32 inch. M = Outside diameter of socket/thread hub; ± 1/16 inch. H = Intersection of center lines to face of fitting; 90° elbows tees, crosses; ± 1/32 inch. N = Socket bottom to socket bottom; couplings; ± 1/16 inch. J = Intersection of center lines to bottom of socket/thread; 45' elbows; ± 1/32 inch Q = Width of flats; ±1/16 inch. L = Overall length of fittings; ± 1/16 inch. W = Height of cap; ± 1/16 inch. CPVC FIRE SPRINKLER PIPE SDR 13.5 (ASTM F 442) Part Number Nominal Size Average O.D. Average I.D. Approx. Weight Lbs.IFt. Inches (mm) Inches (mm) Inches (mm) CP-007 3/4 (19.1) 1.050 (26.7) .874 (22.5) 0.168 CP-010 1 (25.4) 1.315 (33.4) 1.101 (28.2) 0.262 CP-012 1-1/4 (31.8) 1.660 (42.2) 1,394 (35.6) 0.418 CP-015 1-1/2 (38.1) 1.900 (48.3) 1.598 (40.7) 0.548 CP-020 2 (50.8) 2.375 (60.3) 2.003 (50.9) 0.859 CP-025 2-1/2 (63.5) 2.875 (73.0) 2.423 (61.5) 1.257 CP-030 3 (76.2) 3.500 (88.9) 2.950 (75.0) 1.867 "Lead Free" low lead certification — unless other wise specified, all Spears° FlameGuard° fittings specified here -in are certified by NSF International to ANSIINSFO Standard 61, Annex G and is in compliance with California's Health & Safety Code Section 116825 (commonly known as AB1953) and VermontAct 193. Weighted average lead content-0.25%. Spears° PVC and CPVC Pipe, Fittings and Valves have always been lead-free and Certified by NSF International for use in potable water systems. Spears" offers a wide range of lead-free specialty fittings and transition adapters for plumbing applications. However, certain brass threaded adapter fittings for applications that are not intended to convey water for human consumption through drinking or cooking are still produced and available. SPEARS@ MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El SOCKET DIMENSIONS SCH 40 - ASTM F438 C SCH 80 -ASTM F439 B A Socket Socket SCH 40 Minimum SCH 80 Minimum Size Entrance A Bottom B Tolerance Socket Length C Socket Length C 3/4 1.058 1.046 ± .004 .719 1.000 1 1.325 1.130 ± .005 .875 1.125 1-1/4 1.670 1.655 ±.005 .938 1.250 1-1/2 1.912 1.894 ±.006 1.094 1.375 2 2.387 2.369 ± .005 1.156 1.500 2-1/2 2.889 2.868 ± .007 1.750 1.750 3 3.516 3.492 ±.008 1.875 1.875 TEE Socket Socket Socket I I - - j- t j�G Part Number Size G H L M Approx. Wt. (Lbs.) 4201-007 3/4 9/16 1-1/2 2-31/32 1-5/16 .11 4201-010 1 7/8 1-13/16 3-5/8 1-5/8 .20 4201-012 1-1/4 15/32 2-3/32 4-7/32 2 .29 4201-015 1-1/2 1-5/32 2-9/16 5-3/32 2-11/32 .54 4201-020 2 1-13/32 2-15/16 5-7/8 2-7/8 .86 4201-025 2-112 1-23132 3-1/2 7 3-15/32 1.62 4201-030 3 2-1/16 3-31/32 7-15/16 4-5/32 2.53 REDUCING TEEM1 -� Socket x Socket x Socket M � M H1 1 1 G1 G2 H H2 L Part Size G G1 G2 H H1 H2 L M M1 M2 Number Wpprox(Lbs.) 4201-102 3143141 3/4 3/4 3/4 1-11/16 1-25/32 1-11/16 3-13/32 1-5/16 1-21/32 1-5/16 .13 4201-125 10/43/4 23132 7/8 23/32 1-25/32 1-13/16 1-21/32 3-7/16 1-19/32 1-11/32 1-5116 .16 4201-126 1xNA 23/32 23/32 3/4 1-27/32 1-27/32 1-3/4 3-19/32 1-5/8 1-5/8 1-5/16 .17 4201-131 W0/4 11/16 13/16 11116 1-13/16 1-13/16 1-13/16 3-5/8 1-5/8 1-5/16 1-5/8 .17 4201-157 1-11410/4 11/16 1-1/32 11/16 1-15/16 2-1132 1-13/16 3-25/32 2-3/32 1-13/32 1-23/32 .32 MADE IN THE U.S.A. 7 wo FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS REDUCING TEE (continued) r--►tM1 Socket x Socket x Socket -T H1 Mg!tM2 G1 G2 H2 LHL Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4201-158 1-1/4xlxl 27/32 29/32 25/32 2-1/16 2-1/32 1-29/32 3-15/16 1-31/32 1-5/8 1-5/8 .24 4201-159 1-1/41x1-1/4 31132 31/32 31/32 2-7/32 2-7/32 2-3/32 4-11/32 2-1/8 2-1/8 1-23132 .36 4201-167 1-114x1-1/404 21/32 1 21/32 1-29/32 2 1-29/32 3-13/16 2 1-5/16 2 .22 4201-168 1-1/41-1/4x1 13/16 1 1 13/16 2-1116 1 2-1/8 2-1/16 1 4-1/8 1-31/32 1 1-21/32 1-31/32 1 .24 4201-169 1-1/4xl-1/4xl-1/2 1-1/8 15/16 1-1/8 2-3/8 2-11/32 2-3/8 4-3A 2-3/32 2-11/32 2-3/32 .51 4201-201 1-101-1/4x3/4 11/16 1 1/4 2-1/16 2 1-15/16 4 2-5/16 1-3/8 2-1/16 .41 4201-202 1-1/2xl-114xl 27/32 1-1132 1 2-7/32 2-5/32 2-1/4 4-15/32 2-5/16 1-11/16 2-1/16 .42 4201-210 1-1/2xl-1/20/4 11/16 1-1/32 11/16 2-1/16 2-1/32 2-1/16 4-5/32 2-11/32 1-13/32 2-11132 .39 4201-211 1-112xl-1/2xl 13/16 1-3/32 13/16 2-3/16 2-1/4 2-3/16 4-3/8 2-11/32 1-3/4 2-11/32 .41 4201-212 1-1/2x1-112x1-1/4 1-1/32 1 1-3/32 1-1/32 1 2-13/32 2-11132 1 2-13/32 4-13116 1 2-11/32 2-1/8 1 2-11/32 .49 4201-213 1-1/2xl-102 1-9/32 1-5/32 1-9/32 2-21/32 2-21132 2-21132 5-11/32 2-11/32 2-29/32 2-11/32 .64 4201-248 2x2x3/4 11/16 1-13/32 11/16 2-7/32 2-7/16 2-7/32 4-7/16 2-27/32 1-3/8 2-27/32 .52 4201-249 2x2xl 27/32 1-13/32 27/32 2-11/32 2-9/16 2-11/32 4-23/32 2-7/8 1-3/4 2-7/8 .58 4201-250 WA-1/4 1-1/32 1-11/32 1-1/32 2-17/32 2-19/32 2-17/32 5-3/32 2-7/8 2-3/32 2-7/8 .65 4201-251 WA-1/2 1-5/32 1-7/16 1 1-5/32 2-11/16 2-13/32 2-11/16 1 5-3/8 2-7/8 1 2-13132 2-7/8 1 .79 4201-289 2-112x2-1/2xl 27/32 1-23132 27/32 2-5/8 2-27/32 2-5/8 5-1/4 3-17/32 1-23132 3-17/32 1.01 4201-290 2-102-112xl-1/4 1-3/32 1-23/32 1-1/32 2-13/16 2-31132 2-13/16 5-21/32 3-9/16 2-3/32 3-9/16 1.13 4201-291 2-112x2-101-1/2 1-3/16 1/2 1-3/16 2-15/16 1-7/8 2-15/16 5-7/8 3-15/32 2-11/32 3-15/32 1.26 4201-292 2-1/2x2-102 1-13/32 1-5/8 1-13/32 3-3/16 3-1/8 3-3/16 6-3/8 3-1/2 2-7/8 3-1/2 1.37 4201-335 3x3xl 7/8 1-15/16 7/8 2-3/4 3-1/16 2-3/4 5-15/32 4-3/16 1-23/32 4-3/16 1.26 4201-336' MA-1/4 1-3/8 1 1-3/4 1 1-3/8 1 3-5/16 1 3-1/2 3-5/16 6-518 4-1/8 1 2-7/8 1 4-1/8 1 1.94 4201-337 MA-1/2 1-5/32 1 2-1/16 1 1-5/32 3-1/32 3-7/16 3-1/32 6-3/32 4-3/16 1 2-3/8 1 4-3/16 1 1.46 4201-338 3x3x2 1-7/16 1 1-13/16 1 1-7/16 3-5/16 1 3-5/16 3-5/16 6-19132 4-3/16 2-7/8 4-3/16 1 1.69 4201-339 &W-1/2 1-3/4 1 1-31/32 1 1-3/4 35/8 1 3-23132 3-5/8 7-1/4 4-3/16 1 3-17/32 1 4-3/16 1 2.11 ' Branch Outlet Sized with Bushing TorqueSafe"I SPRINKLER HEAD TEE Gasket Sealed Brass -01 Thread Insert StyleG� Socket x Socket x Gasket Fipt H1 With Elastomer Seal - Use NO Thread Sealant - 4GG M222 L Part Number Size G G1 G2 H 1-11 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101 G 3/4314112 7116 1-3/16 7116 1-7/16 1-7/16 1-17/32 2-29/32 1-3/8 1-3/8 1-3/8 .22 4202-124 G 1x3/41/2 7/16 1-11/32 9/16 1-9/16 1-11/16 1-9/16 3-1/8 1-11/16 1-318 1-3/8 .26 4202-130 G 1x1x1/2 7/16 1-11/32 7116 1-9/16 1-11/16 1-9/16 3-1/8 1-23/32 1-3/8 1-23/32 .28 4202-131 G 1xlx3/4 17/32 15/16 17/32 1-11/16 1-5/8 1-11/16 3-11/32 1-23/32 1-9/16 1-23132 .31 4202-166 G 1-1/41-1/41/2 7/16 1-5/8 7/16 1-11/16 1-15/16 1-11/16 3-3l8 2-1116 1-3/8 2-1/16 .34 4202-209 G 1-112x1-1/2x112 112 1-13/16 1/2 1-7/8 2-3/32 1-7/8 3-3/4 2-11/32 1-3/8 2-11/32 .41 4202-247 G WA/2 1/2 2-1/16 1/2 2 2-11132 2 4-1/32 2-27/32 1-318 2-27/32 1 .54 Not intended to convey or dispense water for human consumption through drinking or cooking SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El SPRINKLER HEAD TEE M1 Brass Thread Insert Style G, Socket x Socket x Fipt M -- -1- H1 - MII2 G G2 EG ii H— L H2 Part Number Size G I G1 G2 H I H1 I H2 I L M M1 M2 Approx. Wt. (Lbs.) 4202-010 1x1x1 1 21/31 1 1-1/8 1 21/31 1 1-25/32 1 1-29/32 1 1-25/32 1 3-19/32 1 1-23/32 1 1-23/32 1 1-23/32 1 .37 Not intended to convey or dispense water for human consumption through drinking or cooking SofTorqueTM SR REDUCING TEE Gasket Sealed Special Reinforced Plastic Thread Style Socket x Socket x SR Fipt M1 With Elastomer Seal - Use NO Thread Sealant e+ I , 1 i M M2 G2 H H2 L Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101GSR 3143/4112 7116 1-1/2 7/16 1-3/8 1-7/8 1-3/8 2-3/4 1-5/16 1-3/8 1-5/16 .16 4202-130GSR 1x1x1/2 7/16 1-5/8 1 7/16 1-1/2 2 1-1/2 3 1-5/8 1-3/8 1-5/8 .20 SPRINKLER REDUCING HEAD TEE Brass Thread Insert Style Socket x Socket x Fipt M, fi— H1 M - - M2 G1 GH H2 2 L Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101 3/43141/2 7/16 1-1/16 7/16 1-15/32 1-518 1-15/32 2-29/32 1-13/32 1-3116 1-13/32 .20 4202-124 1x3/4112 7116 1-11/32 9/16 1-9/16 1-11/16 1-9/16 3-1/8 1-11/16 1-3/8 1-3/8 .26 4202-130 1x1x112 7116 1-7/32 7/16 1-9/16 1-25/32 1-9/16 3-1/8 1-3/4 1-3/16 1-3/4 .26 4202-156 1-1/41x1/2 7/16 1-7/16 9116 1-11/16 2-1/32 1-11/16 3-3/8 2-3/32 1-3/16 1-23/32 .30 4202-166 1-114xl-1141/2 7/16 1-15/32 1 7/16 1-11/16 1 2-1/32 1-11/16 1 3-3/8 2-3/32 1 1-3/16 2-3/32 .31 4202-199 1-1/2xl-1/4112 1/2 1-5/8 9/16 1-7/8 2-3/16 1-13/16 3-11/16 2-11/32 1-3/16 2-1/16 .37 4202-209 1-1/2xl-1/2x112 112 1-5/8 1/2 1-7/8 2-3/16 1-7/8 3-3/4 2-11/32 1-3/16 2-11/32 .38 4202-237 2xl-1/2x112 1/2 1-27/32 17/32 2 2-7/16 1-29/32 3-15/16 2-7/8 1-3/16 2-11/32 .47 4202-247 2x2x112 1/2 1-7/8 1/2 2 2-7/16 2 4-1132 2-27/32 1-3/16 1 2-27/32 1 .50 Not intended to convey or dispense water for human consumption through drinking or cooking MADE IN THE U.S.A. [ES FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS SPRINKLER HEAD TEE Special Reinforced �M1t Plastic Thread Style G1 Socket x Socket x SR Fipt F 7 1 M M2 G G2 Ijr-H- L H2 Part Number Size G G1 G2 I H I H1 I H2 I L I M M1 M2 Approx. Wt. (Lbs.) 4202-010SR 1x1x1 1 21/32 1 3/4 1 21/32 1-25/32 1 1-5/8 1-25/32 3-19/32 1-23/32 1-11/16 1-23/32 .26 SPRINKLER REDUCING HEAD TEE Special Reinforced Plastic Thread Style Socket x Socket x SR Fipt I.-M1-►I "' M - 1 M2 G1 G G2 H H2 L Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101SR 3/4x3/4xl/2 19/32 25/32 19/32 1-19/32 1-7/16 1-19/32 3-7/32 1-13/32 1-3/16 1-13/32 .15 4202-124SR 1x3/4xl/2 7/16 29/32 9/16 1-19/32 1-5/8 1-9/16 3-5/32 1-23/32 1-3/16 1-17/32 .19 4202-130SR 1x1x1/2 7/16 29/32 7/16 1-9/16 1-5/8 1-9/16 3-1/8 1-23/32 1-3/16 1-23/32 .20 4202-156SR 1-1/4102 15/32 1-5/32 19/32 1-23/32 1-7/8 1-23/32 3-13/32 2-3/32 1-3/16 1-23/32 .26 4202-166SR 1-1/4x1-1/4x1/2 7/16 1-1/8 7/16 1-11/16 1 1-27/32 1-11116 1 3-3/8 2-3/32 1 1-3/16 2-3/32 1 .26 4202-168SR 1-1/4xl-1/4xl 27/32 1-1/32 27/32 2-3/32 1-29/32 2-3/32 4-7/32 2-3/32 1-11/16 2-3/32 .34 4202-199SR 1-1/2xl-1/4xl/2 9/16 1-9/32 17132 1-15/16 2 1-25/32 3-23/32 2-11/32 1-3/16 2-3/32 .33 4202-209SR 1-1/2xl-1/2xl/2 1/2 1-1/4 1/2 1-7/8 1-31/32 1-7/8 3-3/4 2-11/32 1-3/16 2-11/32 .35 4202-211SR 1-1/2xl-1/2x1 1 27/32 1-7/32 27/32 2-7/32 2-1/8 2-7/32 4-15/32 2-11/32 1-23/32 2-11/32 .44 4202-237SR 2x1-1/2x1/2 1 23/32 1 1-9/16 1 3/8 2-7/32 2-9/32 1-3/4 1 3-31/32 1 2-7/8 1 1-3/16 1 2-11/32 .45 4202-247SR 2x2x1/2 1 1/2 1 31/32 1 1/2 2 1 1-11/16 19/32 1 4 1 2-7/8 1 1-3/16 1 2-7/8 48 4202-287SR 2-1/2x2-1/2xl/2 1 17/32 1 1-3/4 1 17/32 2-9/32 1 2-1/2 2-9/32 1 4-19/32 1 3-1/2 1 1-7/32 1 3-1/2 .78 SOFTO RQU ETM SR SPRINKLER HEAD TEE i Gasket Sealed Special I H, Reinforced Plastic Thread Style ' M __ _ _ ' M G Socket x SR Fipt x Socket I i Stainless Steel Collar With Elastomer Seal Use , r H2G2 NO Thread Sealant H H2 Part Number Size G I G1 I G2 H I H1 H2 I L M M1 M2 Approx. Wt. (Lbs.) 4203-122GSR 1xl/2x1 1 13/16 1 13/16 1 1-1/2 1 1-27/32 1 1-27/32 1 1-31/32 3-13/16 1 1-5/8 1 1-5/8 1 1-3/8 1 .22 5 SPEARS® MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS El TorqueSafeTM SPRINKLER HEAD TEE M1 Gasket Sealed Brass Thread Insert Style__ Socket x Gasket Apt x Socket G1 H1 4—§ M2 With Elastomer Seal - Use NO Thread Sealant G G2 H L H2 Part Number I Size I G I G1 I G2 H I H1 H2 I L M M1 M2 Approx. Wt. (Lbs.) 4203-122 G I txl/2x1 1 19/32 1 13/16 1 1-13/32 1 1-19/32 1 1-27/32 1 1-3/4 1 3-11/32 1 1-5/8 1 1-5/8 1 1-3/8 .25 Not intended to convey or dispense water for human consumption through drinking or cooking SPRINKLER HEAD TEE M1 Brass Thread Insert Style Socket x Fipt x Socket G1 H1 M -- -4-- L ' M2 H G2 H2 L Part Number I Size I G I G1 G2 I H H1 H2 L I M M1 M2 Approx. Wt. (Lbs.) 4203-122 1 lx112x1 1 23132 1 3/4 1 1-1/4 1 1-5/8 1 1-5/8 1-15/16 3-1/2 1 1-23/32 1 1-23/32 1 1-3/16 1 .25 Not intended to convey or dispense water for human consumption through drinking or cooking SPRINKLER HEAD TEE Special Reinforced M1—►1 Plastic Thread Style Socket x SR Fipt x Socket H1 M r -�- V JG L Part Number Size G G1 G2 H H1 H2 I L M M1 M2 Approx. Wt. (Lbs.) 4203-122SR 1xl/2xl 27/32 23132 1-3/32 1-23/32 1-5/8 1-25/32 1 3-13/32 1-3/4 1-3/4 1-3/16 .21 MADE IN THE U.S.A. 6 El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS STREET TEE Spigot x Socket x Socket M1—► OR M2 H1 ' G1 G G2 H ��— H2 L Part Number Size G G1 G2 H H1 H2 L M1 M2 Approx. Wt. (Lbs.) 4244-007 3/4 13/16 27/32 27/32 1-13/16 1-7/8 1-7/8 3-5/8 1-13/32 1-13/32 .16 4244-010 1 1-5/32 1-1/32 1-1/32 2-1/8 1-29/32 1-29/32 4-3/16 1-3/4 1-3/4 .27 4244-012 1-1/4 1-1/4 1 1 2-7/16 2-9/32 2-9/32 4-27/32 2-3/32 2-3/32 .42 4244-015 1-1/2 1-13/16 1-1/8 1-1/8 2-7/8 2-9/16 2-9/16 5-11/32 2-11'132 2-11/32 .56 4244-020 2 1-23/32 1-7/16 1-13/32 3-1/4 1 2-15/16 2-15/16 1 6-5/32 2-7/8 1 2-7/8 .84 900 ELBOW Socket x Socket G H Part Number Size G H M Approx. Wt. (Lbs.) 4206-007 314 9/16 1-1/2 1-5/16 .07 4206-010 1 3/4 1-5/8 1-5/8 .11 4206-012 1-1/4 15/16 2-3116 2 .22 4206-015 1-1/2 1-5132 2-17/32 2-3/8 .41 4206-020 2 1-13/32 2-29132 2-7/8 .62 4206-025 2-1/2 1-15/32 3-3/8 3-1/2 1.15 4206-030 3 1-5/32 3-3/32 4-3/16 1.83 SPEARS® MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS SPEAKS , SIDE OUTLET ELBOW Socket x Socket x Socket I- -- M Gt, H Part Number Size G H M Approx. Wt. (Lbs.) 4213-007 3/4 27/32 1-19/32 1-5/16 .09 4213-010 1 13/16 1-7/8 1-5/8 .18 REDUCING 900 ELBOW H1 Socket x Socket G1- G i-- - M1 H M Part Number Size G G1 H H1 M M1 Approx. Wt. Lbs. 4206-131 1x314 21132 13116 1-25/32 1-13/16 1-19/32 1-5/16 .11 TorqueSafeTM 900 SPRINKLER HEAD ELBOW Gasket Sealed Brass Thread Insert Style Socket x Gasket Fipt With Elastomer Seal - Use NO Thread Sealant H1 G1- G _ M1 H M Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101 G 3/41/2 9/16 1-7/32 1-13/32 1-17/32 1-13/32 1-3/8 .19 4207-130G 1x1/2 7/16 1-3/16 1-9/16 1-11/16 1-23/32 1-3/8 .23 4207-166 G 1-1/41/2 15132 1-19/32 1-15/16 1-11/16 2-3/32 1-318 .25 Not intended to convey or dispense water for human consumption through drinking or cooking MADE IN THE U.S.A. El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS SPRINKLER HEAD 900 ELBOW Brass Thread Insert Style H1 Socket x Fipt G1 G I- — - M1 H �II II M - ►1 Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101 3/41/2 1/2 1-3/32 1-1/2 1-5/8 1-13/32 1-3/16 .17 4207-130 1x1/2 7/16 1-7/32 1-19/32 1-25/32 1-23/32 1-3/16 .21 4207-131 1 x3/4 17/32 1-11 /32 1-21 /32 1-31132 1-23/32 1-3/8 .25 4207-166 1-1/41/2 15/32 1-17/32 1-11/16 1-15/16 2-3132 1-17/32 .33 Not intended to convey or dispense water for human consumption through drinking or cooking SofTorqueTM SR 900 ELBOW SPRINKLER HEAD ADAPTER Gasket Sealed Special Reinforced Plastic Thread Style Socket x SR Fipt 1 With Elastotomer Seal -Use NO Thread Sealant G G <. .e T H i h-- M Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101GSR 3/41/2 7/16 1-17/32 1-3/8 1-27/32 1-11/32 1-3/8 .17 4207-130GSR 1x1/2 7/16 1-11/16 1-1/2 2 1-21/32 1-3/8 .19 4207-166GSR 1-1/4xl/2 7/16 1-7/8 1-11/16 2-7/32 2 1-3/8 .22 SPRINKLER HEAD 900 ELBOW Special Reinforced Plastic Thread Style H1—'j Socket x SR Fipt GI- G - M1 H i I~ M --►� Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101SR 3/4112 11132 13/16 1-15132 1-1/2 1-13/32 1-3/16 .14 4207-130SR 1x1/2 7/16 7/8 1-9116 1-5/8 1-23/32 1-3/8 .20 4207-131SR 1x3/4 1/2 7/8 1-5/8 1-9/16 1-23/32 1-3/8 .16 4207-166SR 1-1/41/2 1 13/32 1 1-1/32 1 1-21/32 1 1-23132 1 2-3/32 1 1-7/32 1 .19 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El 900 STREET ELBOW Spigot x Socket H1� G1 G M1 qH L --►�- PIPE O.D. Part Number Size G G1 H H1 M1 Approx. Wt. (Lbs.) 4209-007 3/4 29/32 19132 1-15/16 1-11/16 1-13/32 .12 4209-010 1 1-9/32 23/32 2-13/32 1-27/32 1-3/4 .21 4209-012 1-1/4 1-9/16 27/32 2-13/16 2-3/32 2-3/32 .32 4209-015 1-1/2 1-15/32 1-3/16 2-27/32 2-9/16 2-11132 .42 4209-020 2 1-23/32 1-3/8 3-7/32 2-15/16 2-27/32 .65 22-1120 ELBOW Socket x Socket P�i�l M-►� Part Number Size H J M Approx. Wt. (Lbs.) 4216-007 3/4 1-3116 7/32 1-13/32 .09 4216-010 1 1-3/8 9/32 1-25/32 .14 4216-012 1-1/4 1-1/2 5/16 2-3132 .20 4216-015 1-1/2 1-7/16 13/32 1-3/8 .19 4216-020 2 1-7/8 3/8 2-27/32 .43 4216-030 3 2-3/8 1/2 4-5/32 1.00 22-1120 STREET ELBOW Spigot x Socket M1 H1 f H PIPE O.D. Part Number Size H H1 J J1 M1 Approx. Wt. (Lbs.) 4242-007 3/4 1-1/4 1-112 1/4 112 1-3/8 .08 4242-010 1 1-7/16 1-11/32 5/16 7/32 1-23/32 .14 4242-012 1-1/4 1-9116 1-25/32 17132 11/16 2-1/16 .21 4242-015 1-1/2 1-13/32 1-23/32 1/2 11/32 2-11/32 .28 4242-020 2 1-29/32 2-1/8 7132 5/8 2-7/8 .42 4242-025 2-1/2 2-1/8 2-1/4 13/32 1/2 3-1/2 .68 4242-030 3 2-13/32 2-13/32 9/16 17/32 4-5/32 .99 MADE IN THE U.S.A. 10 El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 450 ELBOW Socket x Socket I H I � M —►I Part Number Size H J M Approx. Wt. (Lbs.) 4217-007 3/4 1-5/16 5116 1-5116 .07 4217-010 1 1-13/32 3/8 1-5/8 .11 4217-012 1-1/4 1-5/8 3/8 2-5/32 .21 4217-015 1-1/2 1-27/32 15/32 2-11/32 .32 4217-020 2 2-1/8 21/32 2-718 .48 4217-025 2-1/2 2-17/32 3/4 3-1/2 .88 4217-030 3 2-29/32 29/32 4-5/32 1.17 CROSS Socket x Socket x Socket x Socket G1 M- -- �- - L1 L H1 LJ H L Part Number Size G G1 H H1 L L1 M Approx. Wt. (Lbs.) 4220-007 3/4 5/8 5/8 1-21/32 1-21/32 3-5116 3-5116 1-13/32 .22 4220-010 1 3/4 3/4 1-5/8 1-5/8 3-1/4 3-1/4 1-23/32 .20 4220-012 1-1/4 1-1/8 1-1/8 2-3/8 2-3/8 4-3/4 4-3/4 2-3/32 .63 4220-015 1-1/2 1-7/32 1-7/32 2-5/8 1 2-5/8 5-7/32 5-7/32 2-3/8 .80 4220-020 2 1-1/2 1-1/2 3 3 6 6 3 1.43 4220-025 2-1/2 1-11/16 1-11/16 3-7116 3-7116 6-718 6-7/8 3-17/32 2.16 4220-030 3 2-3/32 2-3132 3-31/32 3-31/32 7-15/16 7-15/16 4-7/16 3.37 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El 450 STREET ELBOW Spigot x Socket H1J1 M1 H� r ►I -PIPE O.D. Part um er Size H Hl i ill Ml Approx. Wt. s. 4227-010 1 1-1/2 1-5/16 1 /2 114 1-5/8 .10 4227-012 1-1/4 1-25/32 1-9/16 9/16 11/32 1-31/32 .15 4227-015 1-1/2 2-1/32 2-1/8 19/32 25/32 2-11/32 .29 4227-020 1 2 1 2-5/16 1 1-15/16 1 25132 1 13/32 1 2-7/8 1.44 REDUCING CROSS Socket x Socket x Socket x Socket r--►j M1 ML1 L LTG Part Number Size G G1 H H1 L L1 M M1 Approx. Wt. (Lbs.) 4220-131 104 23/32 5/8 1-5/8 1-5/8 3-1/4 3-1/4 1-7/8 1-1/2 .31 4220-167 1-1/43/4 1-1/16 23/32 2-1/16 1-31/32 4-3/32 3-31/32 2-1/16 1-13/32 .35 4220-210 1-112x3/4 11116 1-5/32 2-3/32 2-3/16 4-3/16 4-11/32 2-3/8 1-13/32 .42 4220-248 24/4 11/16 1-7/16 2-7/32 2-7/16 4-13/32 4-7/8 2-29/32 1 1-13132 1 .56 4220-289 2-112xl 29132 1-3/4 2-11/16 2-7/8 5-11/32 5-3/4 3-1/2 1 1-3/4 1 .98 COUPLING Socket x Socket - - - - N -- M Part Number Size L M N Approx. Wt. (Lbs.) 4229-007 3/4 2-1/8 1-5/16 3116 .05 4229-010 1 2-3116 1-5/8 3/32 .08 4229-012 1-1/4 2-19/32 2 3/32 .13 4229-015 1-1/2 2-7/8 2-11/32 3/32 .22 4229-020 2 3-1/8 2-7/8 1/8 .33 4229-025 2-1/2 3-11/16 3-15/32 3116 .48 4229-030 3 4 4-3/16 1/4 .89 MADE IN THE U.S.A. 12 FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS REDUCER COUPLING Socket x Socket M ---- --- M1 I� L Part Number Size L M M1 N Approx. Wt. (Lbs.) 4229-131 10/4 2-3/8 1-23/32 1-13/32 7/32 .10 4229-167 1-1/43/4 2-19/32 2-3/32 1-5/8 11/32 .17 4229-168 1-1/41 2-11/16 2-3/32 1-23/32 5/16 .18 4229-210 1-1/2414 2-13/16 2-11/32 1-13/32 15/32 .19 4229-211 1-1/2xl 2-7/8 2-11/32 1-15116 3/8 .24 4229-212 1-112x1-114 2-13116 2-13/32 2-1/8 5/32 .23 4229-248 20/4 3-3116 2-7/8 1-7/16 23/32 .32 4229-249 2x1 3-1/8 2-7/8 1-23/32 1/2 .31 4229-250 2x1-1/4 3-3/16 2-7/8 2-1/8 17/32 .33 4229-251 2x1-1/2 3-3/16 2-27/32 2-11/32 - 9/32 .31 4229-291 2-1/2xl-1/2 3-23/32 3-15/32 2-11/32 21/32 .51 4229-292 2-1/2x2 3-21/32 3-1/2 2-7/8 13/32 .52 4229-337 3x1-1/2 3-1/2 4-3/16 2-3/8 7/32 .71 4229-339 3x2-1/2 3-27/32 4-3/16 3-1/2 3/16 .80 GripLoCTM COUPLING - LEAD FREE w/EPDM 0-Ring Seals L 175 psi Maximum Infernal Pressure @ 150°F — — — — ----- ---jM L1� WARNING: DO NOT INSERT FINGERS. Part Number Size L M1 N Approx. Wt. (Lbs.) GL4229-007 3/4 4 1-15/16 1-29/32 .25 GL4229-010 1 4-5/32 2 2-1/4 .34 13 SPEARS° MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS GROOVED COUPLING ADAPTER Groove x Socket PIPE OM1 .D. �L N L Part Number Size L M1 N Approx. Wt. (Lbs.) 4233-012 1-1/4 3-5/8 2-3/32 2-11/32 .72 4233-015 1-1/2 3-3/4 2-11132 2-11/32 .83 4233-020 1 2 3-27/32 1 2-27132 1 2-11132 1 1.27 4233-025 2-1/2 4-3/16 3-15132 2-7/16 2.02 4233-030 3 4-5/16 4-1/8 2-7/16 2.76 Not intended to convey or dispense water for human consumption through drinking or cooking FEMALE ADAPTER Brass Thread Insert Style Socket x Fipt M — N- -L L M1 Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-007 3/4 2 1-13132 1-3/8 5/16 .23 4235-010 1 2-3/16 1-3/4 1-11/16 11/32 .25 4235-012 1-1/4 2-3/8 2-3/32 2-1/16 3/8 .36 4235-015 1-1/2 2-17/32 2-3/8 2-7/16 3/8 .47 4235-020 2 2-25/32 2-27/32 3-3/16 7/16 1.05 Not intended to convey or dispense water for human consumption through drinking or cooking FEMALE ADAPTER Special Reinforced Plastic Thread Style Socket x SR Fipt M M1 INI L Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-007SR 314 1-7/8 1-13/32 1-3/8 3/32 .08 4235-010SR 1 2-5/32 1-23/32 1-7/8 3/32 .22 4235-012SR 1-1/4 2-5/16 2-1/8 2-1/16 3/16 .20 MADE IN THE U.S.A. 14 7 FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style Socket x SR Fipt M ----- — M1 Imo- L—►I Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101SR 3/4112 1-29/32 1-13/32 1-3116 1/8 .08 4235-130SR 1x112 1-31132 1-23/32 1-3/8 3/32 .16 4235-131SR 1x3/4 2-3/32 1-3/4 1-3/8 1/4 .13 FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style with Socket Wrench Flats Socket x SR Fipt M--------PL M1 M = Flat -to -Flat Dimension N Part Number Size L M M1 N Approx. Wt. (Lbs.) W4235-101SR 3141/2 2-9/32 1-13/32 1-3/16 17/32 .09 W4235-130SR 1x1/2 2-9/32 1-3/4 1-3/16 13/32 .12 15 SPEARS® MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS Ej SPIGOT FEMALE ADAPTER Brass Thread Insert Style Spigot x Fipt PIPE _____ M1 O.D. .L N-L Part Number Size L M1 N Approx. Wt. (Lbs.) 4278-007 3/4 2-5/32 1-3/8 17132 .15 4278-010 1 2-9132 1-11/16 7116 .22 Not intended to convey or dispense water for human consumption through drinking or cooking SPIGOT FEMALE ADAPTER Special Reinforced Plastic Thread Style Spigot x SR Fipt PIPE ----- M1 O.D. .L. L� Part Number Size L M1 N Approx. Wt. (Lbs.) 4278-007SR 3/4 1-15/16 1-3/8 11/32 .08 4278-010SR 1 2-1/4 1-23/32 13/32 .13 TorqueSafeTm FEMALE SPRINKLER HEAD ADAPTER Gasket Sealed Brass Thread Insert Style Socket x Gasket Fipt With Elastomer Seal - Use NO Thread Sealant M ----- M1 N L Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101 G 3/41/2 1-7/8 1-13132 1-3/8 9/16 .15 4235-130GS 1x112 2-1132 1-11/16 1-3/8 17/32 .17 4235-131 G 104 2 1-11116 1-9/16 9/16 .18 Not intended to convey or dispense water for human consumption through drinking or cooking MADE IN THE U.S.A. 16 El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS FEMALE SPRINKLER HEAD ADAPTER Brass Thread Insert Style Socket x Fipt M — — M1 N L Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101 3/4112 1-7/8 1-13/32 1-17/32 15/32 .19 4235-130 1x1/2 2-11/32 1-11/16 1-3116 5/8 .16 4235-131 1x314 2-5/16 1-11/16 1-3/8 17/32 .18 Not intended to convey or dispense water for human consumption through drinking or cooking Sofl'orqueT"' SR FEMALE SPRINKLER HEAD ADAPTER Gasket Sealed Special Reinforced Plastic Thread Style Socket x SR Fipt With Elastomer Seal -Use NO Thread Sealant � MQN Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101GSR 3/4112 25/16 1-5/16 1-3/8 31/32 .11 4235-130GSR 1x1/2 2-13/32 1-19/32 1-3/8 31/32 .13 4235-131GSR 1x3/4 2-13/32 1-5/8 1-23/32 1 .16 QuickTorqueTM SR FEMALE SPRINKLER HEAD ADAPTER Gasket Sealed Special Reinforced Plastic Thread Style Socket x SR Metal Fipt With Elastomer Seal - Use NO Thread Sealant L ` M ----- M1 —N-- Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101GMR 3/4112 1-15/16 1-5/16 1-9/16 13/16 .17 4235-13OGMR 1x1/2 2-3/16 1-19/32 1-9/16 15116 .19 17 SPEARS® MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS El FEMALE SPRINKLER HEAD ADAPTER Brass Thread Insert Style M ----- M1 with Long Body Socket x Fipt N L Part Number Size L M M1 N Approx. Wt. (Lbs.) L4235-130 1x112 1 2-3/16 1 1-23/32 1-7132 112 .19 Not intended to convey or dispense water for human consumption through drinking or cooking FEMALE SPRINKLER HEAD ADAPTER Brass Thread Insert Style with Positioning Ring M — — M1 Socket x Fipt L Part Number Size L M M1 N Approx. Wt. (Lbs.) R4235-101 3/41/2 2-1/32 1-7/16 1-3/16 15/32 .15 Not intended to convey or dispense water for human consumption through drinking or cooking FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style with Positioning Ring Socket x SR Fipt I Part Number I Size I L I M I M1 I N I Approx. Wt. (Lbs.) R4235-101SR 3/41/2 1-15/16 1-7/16 1-7/32 7/32 .09 TorqueSafeTm FEMALE SPIGOT SPRINKLER HEAD ADAPTER Gasket Sealed Brass Thread Insert Style Spigot x Gasket Fipt With Elastomer Seal - Use NO Thread Sealant PIPE O.D. ----- M7 N L Part Number Size L M N Approx. Wt. (Lbs.) 4238-101 G 3/41/2 1-15/16 1-3/8 21/32 .14 4238-130 G 1x112 2-1/16 1-3/8 19132 .15 Not intended to convey or dispense water for human consumption through drinking or cooking MADE IN THE U.S.A. 18 0 FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS SPIGOT FEMALE SPRINKLER HEAD ADAPTER Brass Thread Insert Style Spigot x Fipt PIPE M1 O.D. �I L Part Number Size L M1 N Approx. Wt. (Lbs.) 4238-101 3/41/2 1-15/16 1-17/32 17/32 .18 4238-130 1x1/2 1 2-1/4 1 1-3/16 11/32 .19 Not intended to convey or dispense water for human consumption through drinking or cooking TorqueSafeTM BUSHING - GASKET SEALED Brass Thread Insert Style Spigot x Gasket FIPT With Elastomer Seal - Use NO Thread Sealant O.D. L Part Number Size L Approx. Wt. (Lbs.) 4238-130BR G 1x1/2 1-7/32 .10 Not intended to convey or dispense water for human consumption through drinking or cooking BUSHING with BRASS THREAD INSERT Spigot x Fipt O.D. Imo- L-�i Part Number E Size L Approx. Wt. (Lbs.) 4238-130BR I 1x1/2 1 .13 Not intended to convey or dispense water for human consumption through drinking or cooking SPIGOT FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style Spigot x SR Fipt PT-- IPE — —� 01 I.L� Part Number Size L M1 N Approx. Wt. (Lbs.) 4238-101SR 3/4112 1-29/32 1-7/32 1/8 .07 4238-130SR 1x1/2 2-1132 1-7/32 7/32 .09 19 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El MALE ADAPTER With CPVC Lined Thread Brass Insert Mipt x Socket ------ — - — - N L M1 Part Number Size L M1 N Approx. Wt. (Lbs.) 4236-007 3/4 2-17/32 1-13/32 13/16 .26 4236-010 1 2-15/16 1-23/32 29132 .43 4236-012 1-1/4 3-1/8 2-3/32 31/32 .66 4236-015 1-1/2 3-9/32 2-11/32 31132 .80 4236-020 2 3-7/16 2-27/32 31132 1.00 ADJUSTABLE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style Socket x SR Fipt Q N1 Body L Width Part Number Size L N Q Body Width Approx. Wt. (Lbs.) Min Max Min Max 42001SR 3141/2 6-9/32 8 4-7/16 6-114 1-7/16 2-3/16 .66 42011SR 1x1/2 6-13/32 8 4-1/2 6-1/8 1-7/16 2-1/8 .68 ADJUSTABLE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style Spigot x SR Fipt PIPE Q =4N �' �N Body L Width L N Part Number Size Q Body Width Approx. Wt. (Lbs.) Min Max Min Max 42004SR 3/41/2 5-1/32 6-5116 3-3/16 4-15132 1-5/16 2-1/8 .36 F7�1 1x112 T6-7/16 8-1/8 4-7/16 6-1/4 1-7/16 2-3116 .67 MADE IN THE U.S.A. 20 FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS REDUCER BUSHING Flush Style Spigot x Socket PIPE _ O.D. L N L Part Number Size L N Approx. Wt. (Lbs.) 4237-131 1x3/4 1-1/4 1/4 .04 4237-167 1-1/4x3/4 1-7/16 7/16 .10 4237-168 1-1/4xl 1-13/32 9/32 .06 4237-210 1-1/2014 1-5/8 5/8 .19 4237-211 1-1/2x1 1-17/32 13/32 .13 4237-212 1-1/2xl-1/4 1-9116 5116 .07 4237-248 20/4 1-29/32 29/32 .28 4237-249 2x1 1-23/32 9/16 A 4237-250 2x1-1/4 1-11/16 7/16 .21 4237-251 2x1-1/2 1-11/16 5116 .15 4237-290 2-1/2xl-114 2-5/32 7/8 .41 4237-291 2-1/2xl-112 2-5/32 3/4 .39 4237-292 2-102 2-9/32 314 .28 4237-338 3x2 2-7/32 11/16 .63 4237-339 3x2-1/2 2-5/16 1/4 1 .42 TRANSITION BUSHING IPS Spigot x CTS Socket PIPE - - -_-_ O.D. . N L I Part Number Size L N Approx. Wt. (Lbs.) 4240-101 3141/2 1-1/8 5/8 .03 4240-130 1x112 1-1/4 23132 .05 CAP Socket M -- - W Part Number Size M W Approx. Wt. (Lbs.) 4247-007 3/4 1-5/16 1-5/16 .04 4247-010 1 1-5/8 1-9/16 .06 4247-012 1-1/4 2-3/32 1-27/32 .13 4247-015 1-1/2 1 2-11132 1 2 1 .17 4247-020 2 2-27/32 2-9/32 .39 4247-025 2-1/2 3-17132 2-5/8 .50 4247-030 3 4-3/8 3 .92 21 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS SPEARS a TEST PLUG - 0-ring Sealed Mipt - For Pressure Testing Only, Not For use with Z4235 Series Adapters L M1 —L- 1/2-14NPT--�M Part Number Size L M M1 Approx. Wt. (Lbs.) FTP-005 1/2 1-27/32 1-15/16 1-7/32 .03 TEST PLUG (PVC White) Not UL Listed; For Pressure Testing Only, Mipt L �I Part Number Size L Approx. Wt. (Lbs.) 4250-005 1/2 27/32 .02 MADE IN THE U.S.A. 22 7 �j FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS FLANGE - ONE PIECE 4 Bolt Holes, 175 psi Socket M L R ED N I Imo- BOLT CIRCLE DIA.: �- MAX O.D. �J No. of Bolt Min. Part Number Size L M N R Bolt Circle Bolt Bolt Max. Approx. Wt. Size O.D. (Lbs.) Holes Dia. Len th 4251-007 3/4 1-5/32 1-1/2 1/8 17/32 4 2-3/4 1/2 2 3-29/32 .31 4251-010 1 1-5/16 1-13/16 1/8 11/16 4 3-1/8 1/2 2-1/4 4-9132 .35 4251-012 1-1/4 1-13/32 2-7132 5/32 11/16 4 3-1/2 112 2-1/4 4-5/8 .44 4251-015 1-1/2 1-19/32 2-1/2 3/16 23/32 4 3-27/32 1/2 2-1/2 5-1/16 .61 4251-020 2 1-27/32 3 5/16 27/32 4 4-3/4 5/8 3 5-31132 .95 4251-025 2-1/2 2-7/32 3-1/2 7/16 1-1/32 4 5-1/2 5/8 3-1/4 7 1.50 BLIND FLANGE 4 Bolt Holes, 175 psi �R I� BOLTCIRCCLE DIA. MAX O.D. Part Number Size R Bolt Circle Dia. No. oBolt Holes Bolt Size Min. Bolt Length Max. O.D. Approx. Wt. (Lbs.) 4253-007 314 17/32 2-3/4 4 1/2 2 3-27/32 .30 4253-010 1 23132 3-1/8 4 1/2 2-1/4 4-1/4 .35 4253-012 1-1/4 21/32 3-1/2 4 112 2-1/4 4-5/8 .40 4253-015 1-1/2 23/32 3-27/32 4 1/2 2-1/2 5-1/16 .52 4253-020 2 27/32 4-3/4 4 5/8 3 5-31/32 .86 4253-025 2-1/2 1-1/32 51/2 4 5/8 3-1/4 6-15/16 1.70 4253-030 3 1-5/16 6 4 5/8 3-1/4 7-5/8 1.72 FLANGE - TWO PIECE Van Stone Style, 4 Bolt Holes, 175 psi Socket M L R N-BOLT CIRCLE DIA.-►I MAX O.D. Bolt Circle No. of Bolt Min. Bolt Part Number Size L M N R Dia. Holes Bolt Size Length Max. O.D. Approx. Wt. (Lbs.) 4254-030 1 3 1 2-1/8 4-1/4 9/32 1 1-1/32 6 4 1 5/8 1 3-1/4 1 7-15/32 1 1.75 23 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El FLANGE - TWO PIECE Van Stone Style, 4 Bolt Holes, 175 psi PIPE O.D. 01 Spigot L 4N "IRC R .. Bolt No. of Bolt Min. Bolt Approx. Wt. Part Number Size L N R Bolt Size Max. O.D. Circle Dia. Holes Length (Lbs.) 4256-007 3/4 1-15/16 13/16 17/32 2-3/4 4 112 2 3-27/32 .30 4256-010 1 2-7/32 1-1132 11/16 3-1/8 4 1/2 2-1/4 4-1/4 .41 4256-012 1 1-1/4 2-3/8 1 1 11/16 3-1/2 4 1 112 2-1/4 4-5/8 .50 4256-015 1-1/2 2-7/16 1-3/32 23132 3-7/8 4 112 2-1/2 4-31/32 .65 4256-020 2 2-3/4 1-5/32 25/32 4-3/4 4 5/8 3 5-15/16 1.00 4256-025 2-1/2 3-1/16 1-9132 1-1/32 5-1/2 4 518 3-1/4 6-15/16 1.62 4256-030 3 3-3/8 1-13132 1-1/32 6 4 5/8 3.1/4 7-9/16 1.76 TRANSITION UNION Brass Thread Insert Style Socket x Fipt 175 psi NUT O.D. M -- N L Part Number Size L M N Nut O.D. Approx. Wt. (Lbs.) 4259-010BR 1 2-13/16 1-7/8 1-1/32 2-7/8 .52 4259-012BR 1-1/4 3 2-3/16 1-1/8 3-9/32 .98 4259-015BR 1-112 3-3/4 2-1/2 1-9/16 3-17/32 .93 4259-020BR 1 2 1 3-5/8 1 2-7/8 1 1-1/4 1 4-5/16 1 1.64 Not intended to convey or dispense water for human consumption through drinking or cooking UNION Socket Socket 175 psi NUT M O.D. N L -►I Part Number Size L M N Nut O.D. Approx. Wt. (Lbs.) 4257-007 3/4 2-3/8 1-17/32 3/8 2-1/2 .38 4257-010 1 2-9/16 1-27132 3/8 2-7/8 .41 4257-012 1-1/4 2-27/32 2-7/32 11/32 3-5/16 .52 4257-015 1-1/2 3-1/8 2-1/2 3/8 3-17/32 .63 4257-020 2 1 3-5/8 1 3-1/32 1 9/16 4-3/16 1.09 MADE IN THE U.S.A. 24 FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS SofTorqueTM SR FEMALE SPIGOT SPRINKLER HEAD ADAPTER Gasket Sealed Special Reinforced Plastic Thread Style Spigot x SR Fipt With Elastomer Seal - Use NO Thread Sealant PIPE M1 O.D. - -- - N L Part Number Size L M1 N Approx. Wt. (Lbs.) 4278-101GSR 3/4112 2-1/4 1-3/8 1 .11 SHORT REPAIR COUPLING Spigot x Socket 175 psi L2 L1 L3 I S Part Number Size L1 L2 L3 M S Approx. Wt. (Lbs.) SH118-07CO 3/4 4-13116 5-17/32 3/4 1-3/4 2-3116 .31 SH118-1000 1 4-3/4 5-6/8 31/32 2-1/16 2-5/32 .40 GripLocTM REPAIR COUPLING — LEAD FREE w/EPDM 0-Ring Seals 175 psi Maximum Pressure @ 150°F WARNING: DO NOT INSERT FINGERS. Part Number Size L L1 L2 M S Approx. Wt. Lbs. SG118-1000 1 1-17/32 7-17/32 4-1/4 2-1/4 2-27/32 .73 25 SPEARS® MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS FlameGuard° CPVC Drain & Swing Check Valves for NFPA 13D Applications Only El Application: FlameGuard® CPVC Orange Swing Check Valves and PVC/CPVC True Union Drain Valves are for use in configuring CPVC Fire Sprinkler System connection to water supply (riser/drain assembly) in NFPA 13D installations only. These valves are not UL Listed and NOT for use in any other locations within the fire sprinkler system. TRUE UNION INDUSTRIAL DRAIN VALVES CPVC Gray Valve with CPVC Orange End Connector Socket Socket E i D i A B C Part Number Size A B C D E 1822-007CFG 314 2-1/4 2-3/4 4-3/4 2-7/8 3-3/8 1822-010CFG 1 2-1/2 2-7/8 5-1/8 3-1/8 3-7116 1822-012CFG 1-1/4 3-1/16 3-1/4 5-3/4 3-5/8 3-7/8 1822-015CFG 1-1/2 3-1/2 3-1/2 6-1/4 4 4-3/16 1822-020CFG 2 4-1/4 4-3/4 7-3/4 4-1/2 5-1/8 Not UL Listed TRUE UNION DRAIN VALVES PVC Valve with CPVC End Connector Socket x Socket E D I A B C Part Number Size A B C D E 3622-007FG 3/4 2-1/4 2-3/4 4-3/4 2 3 3622-010FG 1 2-1/2 2-7/8 5-1/8 2-5/16 3-7/16 Not UL Listed MADE IN THE U.S.A. 26 El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS COMPACT 2000 DRAIN VALVE Socket x Socket E A jrqB D --- C Part Number Size A B C D E 6622-007C0 3/4 1-13/16 1-1/2 3-9/16 2 3 6622-01000 1 2-1/16 1-3/4 4 2-5/16 3-7/16 Not UL Listed CPVC SWING CHECK VALVES Socket x Socket *IT is -- -- D lA--- _ L � I B C Part Number Size A B C D Approx. Wt. (Lbs) S1520-1000 1 1-11/16 2-5/16 4-9/16 2-5/8 .33 S1520-12C0 1-1/4 2-1/16 2-15/16 5-1/2 3-3/8 .42 S1520-15C0 1-112 2-7/16 3 5-5/8, 3-3/8 .89 Not UL Listed CPVC SPECIAL REINFORCED THREAD INLET SWING CHECK VALVES SR Fipt x Socket A_ —• —•— D B C Part Number Size A B C D Approx. Wt. (Lbs) S1520-10FSRSCO 1 1-11/16 2-15116 4-9/16 2-5/8 .33 S1520-12FSRSCO 1-1/4 2-1/16 3-5/8 5-1/2 3-3/8 .42 S1520-15FSRSC0 1-112 2-7/16 3-11/16 5-5/8 3-3/8 .89 Not UL Listed 27 SPEARS® MANUFACTURING COMPANY NOTES NOTES PRODUCT LIMITED LIFETIME WARRANTY Except as otherwise specified for certain products, mandated by law or herein provided, Spears° Manufacturing Company ("Company") warrants Standard Catalog Products ("Products") which have been directly manufactured by them to be free from defects in material and workmanship for as long as the original intended end user of the Products ("End User") retains ownership and possession of the Products and complies with this Warranty ("Warranty Period"). Each other person or entity acquiring or employing the Products, including buyers, contractors and installers ("Buyer") and End Users ("Buyer/End User") agrees that this Warranty shall be effective only during the Warranty Period so long as the Products are used solely for the normal purposes for which they are intended and in conformance with industry established standards, engineering, installation, operating, and maintenance specifications, recommendations and instructions including explicit instructions by the Company; the Products are properly installed, operated and used, and have not been modified; and all the other terms of this Warranty are complied with. Any violation thereof shall void this Warranty and relieve Company from all obligations arising from this Warranty and the Products. Upon receipt or discovery of any Products that appear questionable or defective each Buyer/End User shall promptly inspect and return any such Prod- uct to the Company at 15853 Olden Street, Sylmar, California 91342, accompanied by a letter stating the nature of any problems. If the Prod- ucts are determined by Company to be defective in materials or workmanship directly provided by Company, Company, at its sole option, may ei- ther repair or replace the defective Products, or reimburse applicable Buyer/End User for the cost of such Products. The applicable Buyer/End User shall bear all applicable shipping costs. THIS SHALL BE BUYERS/END USERS' SOLE REMEDY. EACH BUYER/END USER AGREES THAT COMPANY WILL NOT BE RESPONSIBLE FOR ANY OTHER OBLIGATIONS RELATING TO THE PRODUCTS, INCLUDING ANY OTH- ER MATERIALS OR LABOR COSTS, LOSS OF USE OR ANY OTHER ITEM OR FOR ANY DELAYS IN COMPLYING WITH THIS WARRANTY BEYOND COMPANY'S REASONABLE CONTROL. COMPANY SHALL NOT BE LIABLE FOR, DOES NOT ASSUME, AND EXPRESSLY DISCLAIMS, ANY LIABILITY, RESPONSIBILITY AND DAMAGES: DUE TO ANY BUYER/END USER'S FAILURE TO COMPLY WITH THIS WARRANTY, INCLUDING IMPROPER INSTALLATION, USE OR OPERATION; USE WITH PRODUCTS FROM OTHER MANUFACTURERS THAT DO NOT MEET ASTM OR OTHER APPLICABLE PRODUCT STANDARDS; IMPROPER CONTROL OF SYSTEM HYDRAULICS, IMPROPER WINTERIZATION PROCEDURES, IMPROPER VOLTAGE SUPPLY, CON- TACT WITH INCOMPATIBLE MATERIALS OR CHEMICALS, EXCAVATION/DIGGING, EXCESSIVE WEIGHT, AND VANDALISM; DUE TO REASONABLE WEARANDTEARAND DUE TOANYACTS OF NATURE, INCLUDING LIGHTNING, EARTHQUAKES, GROUND MOVEMENT, FROST HEAVE, OR FLOODS. COMPANY EXTENDS ONLYTHIS WARRANTYAND EXPLICITLY DISCLAIMSALL OTHER WARRANTIES, WHETHER IMPLIED OR OTHERWISE EXPRESSED, WHETHER ORAL, STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTIES ORAFFIRMATIONS FOR SUITABILITY, MERCHANTABILITY OR FITNESS FORA PARTICULAR PURPOSE. NOAFFIRMATION BY COMPANY ORANY OF ITS REPRESENTATIVES, BY WORDS, CONDUCT OR OTHERWISE, SHALL CONSTITUTE A WARRANTY. THIS WARRANTY MAY NOT BE TRANSFERRED, EXTENDED, ALTERED OR OTHERWISE MODIFIED IN ANY MANNER, EXCEPT BY WRITTEN AGREEMENT SIGNED BY COMPANY. BY ITS ACCEPTANCE OF THE PRODUCTS, EACH BUYER/END USER EXPRESSLY WAIVES ALL OTHER LIABILITY OR OBLIGATION OF ANY KIND OR CHARACTER OF COMPANY, INCLUDING LIABILITY PREDICATED UPON CONTRACT, TORT, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE GROUNDS, AND ALL, IF ANY, DAMAGES AND LOSSES AS A RESULT THEREOF, INCLUDING ALL, IF ANY, COMPENSATORY, GENERAL, SPECIAL, CONSEQUENTIAL, INCIDENTAL, OR PUNITIVE DAMAGES. WITH RESPECT TO SUCH WAIVERS, EACH BUYER/END USER EXPLICITLY WAIVES CALIFORNIA CIVIL CODE §1542 WHICH STATES "A GENERAL RELEASE DOES NOT EXTEND TO CLAIMS WHICH THE CREDITOR DOES NOT KNOW OR SUSPECT TO EXIST IN HIS FAVOR AT THE TIME OF EXECUTING THIS RELEASE, WHICH IF KNOWN BY HIM MUST HAVE MATERIALLY ADVERSELY AFFECTED HIS SETTLEMENT WITH DEBTOR" AND ALL OTHER SIMILAR STATU- TORY, COMMON AND CASE LAW RIGHTS, DEFENSES AND LIMITATIONS. Having previously independently inspected the Products, or a sample, as fully as desired, or having the opportunity to and having not done so, upon acceptance of delivery of the Products, and except as otherwise herein explicitly provided, each Buyer/End User by acceptance or use of the Products accepts them in their "AS IS" and "WITH ALL FAULTS" condition without any other warranty, expressed, implied or otherwise, and accepts and assumes the entire risk and cost of all servicing, remediation and consequences thereof. This Warranty shall be governed by California law and any unenforceable provisions severed without affecting the remaining provisions. As used herein, "including" includes "without limitation." Spears° Quality Policy It is the policy and objective of Spears® Manufacturing Company to produce a superior quality product suitable for its intended use, with regard to functionality, structural integrity and conformance to established industry standards and practices. It is the commitment of this Company to do so in a manner which provides consistency of product quality, optimum availability, and superior customer service, while maintaining efficiency of operations and profitability necessary to perpetuate product improvement and customer satisfaction. Furthermore, it is recognized that the attainment of these objectives is the responsibility of all Company operations and personnel according to their respective functions. The information contained in this publication is based on current information and product design at the time of publication and is subject to change without notification. Our ongoing commitment to product improvement may result in some variations. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability for particular application or results to be obtained therefrom. For information not contained herein, please contact Spears° Technical Services Department (West Coast: (818) 364-1611— East Coast: (678) 985-1263j. Reproduction of this publication in whole or in part is prohibited without the authorized consent of Spears° Manufacturing Company, Sylmar, California. © Copyright 2014 Spears" Manufacturing Company. All Rights Reserved. Printed in the United States of America. SPEARS® MANUFACTURING COMPANY THEE � ® Corporate Office SPEARS 15853 Olden Street - Sylmar, CA 91342' PO Box 9203 - Sylmar, CA 91392 (818) 364-1611 • http://www.spearsmfg.com ��r rR19w © Copyright 2015 Spears® Manufacturing Company. All Rights Reserved. Printed in the United States of America 11115. FGA-1115 FlameGuar& CPVC Fire Sprinkler Products INSTALLATION INSTRUCTIONS To Make Reliable Threaded Connections ... Gasket Sealed Head Adapter No Thread Sealant to be Used Hand Tight + 10 to 25 ft-Ibs Torque to Rotate for Sprinkler Head Alignment For Other Thread Connections: 1. Use a compatible paste sealant. Spears®EDTy recommends BLUE 751m, tested for i compatibility with CPVC products. 2. Apply sealant to male threads. 3. Install Sprinkler Heads or make metal ! 11iREAD SEA NT pipe transitions, tighten as follows: 07� ,10` Adapter for SR Plastic Metal Metal Pipe Thread Thread Transition I Hand tight Min. 5 ft-Ibs Min.15 ft-Ibs +1.5 to 2 Max.10 ft-Ibs Max. 20 ft-Ibs Turns Torque Torque October4, 2010 Pdnled01/13 FG-3-1010 Flame(luard® LIMITED LIFETIME WARRANTY Except as otherwise specified for certain products, mandated by law or herein provided, Spears' Manufacturing Company ("Company? warrants Standard Catalog Products ("Products") which have been directly manufactured by them to be free from defects in material and workmanship for as long as the original intended end user of the Products ("End User") retains ownership and possession of the Products and complies with this Warranty ("Warranty Period"). Each other person or entity acquiring or employing the Products, including buyers, contractors and installers ("Buyer") and End Users ("Buyer/End User) agrees that this Warranty shall be effective only during the Warranty Period so long as the Products are used solely for the normal purposes for which they are intended and in conformance with industry established standards, engineering, installation, operating, and maintenance specifications, recommendations and instructions including explicit instructions by the Company; the Products are property installed, operated and used, and have not been modified; and all the other terms of this Warranty are complied with. Any violation thereof shall void this Warranty and relieve Company from all obligations arising from this Warranty and the Products. Upon receipt or discovery of any Products that appear questionable or defective each Buyer/ End User shall promptly inspect and return any such Product to the Company at 15853 Olden Street, Sylmar, California 91342, accompanied by a letter stating the nature of any problems. If the Products are determined by Company to be defective in materials or workmanship directly provided by Company, Company, at its sole option, may either repair or replace the defective Products, or reimburse applicable Buyer/End User for the cost of such Products. The applicable Buyer/End User shall bear all applicable shipping costs. THIS SHALL BE BUYERS/END USERS' SOLE REMEDY. EACH BUYER/END USER AGREES THAT COMPANY WILL NOT BE RESPONSIBLE FOR ANY OTHER OBLIGATIONS RELATING TO THE PRODUCTS, INCLUDING ANY OTHER MATERIALS OR LABOR COSTS, LOSS OF USE OR ANY OTHER ITEM OR FOR ANY DELAYS IN COMPLYING WITH THIS WARRANTY BEYOND COMPANY'S REASONABLE CONTROL. COMPANY SHALL NOT BE LIABLE FOR, DOES NOT ASSUME, AND EXPRESSLY DISCLAIMS, ANY LIABILITY, RESPONSIBILITY AND DAMAGES: DUE TO ANY BUYER/END USER'S FAILURE TO COMPLY WITH THIS WARRANTY, INCLUDING IMPROPER INSTALLATION, USE OR OPERATION; USE WITH PRODUCTS FROM OTHER MANUFACTURERS THAT DO NOT MEET ASTM OR OTHER APPLICABLE PRODUCT STANDARDS; IMPROPER CONTROL OF SYSTEM HYDRAULICS, IMPROPER WINTERIZATION PROCEDURES, IMPROPER VOLTAGE SUPPLY, CONTACT WITH INCOMPATIBLE MATERIALS OR CHEMICALS, EXCAVATION/DIGGING, EXCESSIVE WEIGHT, AND VANDALISM; DUE TO REASONABLE WEARAND TEARAND DUE TOANY ACTS OF NATURE, INCLUDING LIGHTNING, EARTHQUAKES, GROUND MOVEMENT, FROST HEAVE, OR FLOODS. COMPANY EXTENDS ONLY THIS WARRANTY AND EXPLICITLY DISCLAIMS ALL OTHER WARRANTIES, WHETHER IMPLIED OR OTHERWISE EXPRESSED, WHETHER ORAL, STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTIES OR AFFIRMATIONS FOR SUITABILITY, MERCHANTABILITY OR FITNESS FORAPARTICULAR PURPOSE. NO AFFIRMATION BY COMPANY OR ANY OF ITS REPRESENTATIVES, BY WORDS, CONDUCT OR OTHERWISE, SHALL CONSTITUTE A WARRANTY. THIS WARRANTY MAY NOT BE TRANSFERRED, EXTENDED, ALTERED OR OTHERWISE MODIFIED IN ANY MANNER, EXCEPT BY WRITTEN AGREEMENT SIGNED BY COMPANY. BY ITS ACCEPTANCE OF THE PRODUCTS, EACH BUYERIEND USER EXPRESSLY WAIVES ALL. OTHER LIABILITY OR OBLIGATION OF ANY KIND OR CHARACTER OF COMPANY, INCLUDING LIABILITY PREDICATED UPON CONTRACT, TORT, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE GROUNDS, AND ALL, IF ANY, DAMAGES AND LOSSES AS A RESULT THEREOF, INCLUDING ALL, IF ANY, COMPENSATORY, GENERAL, SPECIAL, CONSEQUENTIAL, INCIDENTAL, OR PUNITIVE DAMAGES. WITH RESPECT TO SUCH WAIVERS, EACH BUYER/END USER EXPLICITLY WAIVES CALIFORNIA CIVIL CODE §1542 WHICH STATES "A GENERAL RELEASE DOES NOT EXTEND TO CLAIMS WHICH THE CREDITOR DOES NOT KNOW OR SUSPECT TO EXIST IN HIS FAVORAT THE TIME OF EXECUTING THIS RELEASE, WHICH IF KNOWN BY HIM MUST HAVE MATERIALLY ADVERSELY AFFECTED HIS SETTLEMENT WITH DEBTOR" AND ALL OTHER SIMILAR STATUTORY, COMMON AND CASE LAW RIGHTS, DEFENSES AND LIMITATIONS. Having previously independently inspected the Products, or a sample, as fully as desired, or having the opportunity to and having notdone so, upon acceptance ofdelivery of the Products, and except as otherwise herein explicitly provided, each Buyer/End User by acceptance or use of the Products accepts them in their "AS IS" and "WITH ALL FAULTS" condition without any other warranty, expressed, implied or otherwise, and accepts and assumes the entire risk and cost of all servicing, remediation and consequences thereof. This Warranty shall be governed by California law and any unenforceable provisions severed without affecting the remaining provisions. As used herein, "including" includes 'Without limitation." TABLE OF CONTENTS Warranty..........................................................................................................Inside Cover IMPORTANT INFORMATION..............................................................................................4 Use of this Manual • Hazards & Information Definitions...............................................4 System Engineering, Installation & Maintenance..........................................................4 InstallerTraining............................................................................................................5 General Installation Safety Instructions...........................................................................5 Introduction.........................................................................................................................5 Handling& Storage............................................................................................................6 Pipe& Fittings...............................................................................................................6 One -Step Solvent Cement............................................................................................6 Listing, Approvals, Application & Use..............................................................................7 LightHazard Occupancies............................................................................................7 Residential Occupancies...............................................................................................7 Low Pressure Dry Pipe and Pre -action Systems..........................................................8 Concealed Installations.................................................................................................9 Combustible Concealed Installation with Specific Use Sprinklers.................................9 Combustible Attic Spaces with Specific Use Sprinklers..............................................10 Exposed Installations..................................................................................................10 Expanded Use with Light Hazard Extended Coverage and Residential Sprinklers ....10 Unfinished Basement with Exposed Solid Wood Joist Installation..............................11 Extended Coverage Quick Response Sprinklers........................................................14 Return Air Plenum Installation • Garage Installations..................................................15 Ambient Temperature Limitations • High Temperature Areas......................................15 Cold Temperature Areas.............................................................................................15 Fire Sprinkler System Risers.......................................................................................16 Underground. Fire Service • C-UL Listing Requirements.............................................18 Factory Mutual Approvals............................................................................................20 Loss Prevention Certification Board LPCB..................................................................20 NSFInternational........................................................................................................21 Penetrating Fire -related Walls & Partitions.................................................................21 Heat Sources & Open Ceiling Areas...........................................................................21 Use With Other Manufacturers' Pipes, Fittings & Solvent Cement .............................22 Installation& Joining.......................................................................................................22 Solvent Cement Welded Joints...................................................................................22 Solvent Cement Requirements...................................................................................27 Threaded Connections................................................................................................27 TorqueSafe"Gasket Sealed Thread Connections.......................................................29 Painting Pipe & Fittings • Cleaning..............................................................................30 Transition to Other Materials • Flanged Connections..................................................30 Flange Data & Bolt Torque • Grooved Coupling Adapters...........................................31 Adjustable Sprinkler Head Adapter Installation...........................................................33 FlushingSystem.........................................................................................................34 System Acceptance Testing (Hydrostatic Pressure Test)..........................................34 Recommended Cut -in Procedures for Systems Modification or Repair......................35 EngineeringData..............................................................................................................37 Pipe & Fitting Specifications • Hydraulic Design.........................................................37 Allowance for Fdcfion Loss in Fittings.........................................................................38 Hanger& Supports......................................................................................................38 RiserSupport..............................................................................................................41 Exposed Installations • Earthquake Bracing • Trenching............................................42 SnakinglDefiection of Pipe..........................................................................................43 Backfilling....................................................................................................................45 MaterialProperties......................................................................................................46 Expansion & Contraction.............................................................................................47 Expansion Loop & Offset Configurations....................................................................49 Review- Do's & Don'ts.....................................................................................................52 Material Safety Data Sheet...............................................................................................53 FG-3-1010 © 2013 Spears® Manufacturing Company Page 3 IMPORTANT INFORMATION Please Read The Following Section Before Proceeding Use of this Manual Spears" FlameGuard° CPVC Fire Sprinkler Products are approved for use in combination with other listed manufacturers' products (see, "Use With Other Manufacturers' Pipes, Fittings, and Solvent Cements" section). However, specific application approvals may not be the same amongst manufacturers. It is the installer's responsibility to verify suitability of products used in combination according to each manufacturer's installation instructions. Engineering data related to the installation and use of CPVC Fire Sprinkler Pipe provided in this manual is based on product manufactured by Spears" Manufacturing Co. (Spears" FlameGuard°), the Victaulic Company (Victaulic FireLock") or Harvel Plastics, Inc. (Harvel BlazeMaster°), as designated herein. If products other than Spears(, Victaulic or Harvel are used, follow the appropriate manufacturer's installation instructions. Contact Spears® if questions on any application are not addressed in this manual. This manual is intended for use by specifiers, installers, and users in the selection, design, installation, and inspection of Spears° FlameGuard° CPVC Fire Sprinkler Products for fire protection service. Due to the critical safety and loss prevention uses of such. systems, all information contained herein is considered vital to obtain proper system performance and must be read and understood carefully before starting the installation. The information contained within this manual is accurate at the time of publication to the best of our knowledge. It is not meant as a replacement for formal installer training. We do not make any guarantees nor assume any liabilities arising out of its use. If you need additional copies, or if you have any questions about the safe installation and use of these products, contactSpearso Manufacturing Company, P.O. Box 9203, Sylmar, CA 91392 or call (800) 862-1499. Additional copies of this manual may be downloaded from our web site: www.spearsmfg.com. Hazards & Information Definitions Definitions for identifying the various hazard levels are as follows: • WARNING - The use of the word "WARNING" identifies the presence of hazards or unsafe practices that could result in severe personal injury if instructions, including recommended precautions, are not followed. • CAUTION - The use of the word "CAUTION" identifies possible hazards or unsafe practices that could result in personal injury, product damage, and/ or property damage if instructions, including precautions, are not followed. • NOTICE - The use of the word "NOTICE" identifies special instructions that are highly important but not related to hazards. • Text information in bold print —Text in bold print identifies additional important information that may or may not be related to a hazard, according to the topic and context. System Engineering, Installation & Maintenance CPVC Fire Sprinkler Systems must be engineered, installed and maintained in accordance with local codes, standards and Spears° FlameGuard° CPVC Fire Sprinkler Products Installation Instructions. Code requirements and field conditions may differ. It is the responsibility of the installing contractorto insure that the product is suitable for the intended use and that all requirements have been satisfied. Page 4 © 2013 Spears® Manufacturing Company FG-3-1010 Installer Training Spears" Manufacturing Company recommends that installers receive proper installation training and that training be renewed every two (2) years. Training will be provided at no charge by contacting an authorized Spears') FlameGuard" CPVC Fire Sprinkler Products distributor or your nearest Spears" Regional Distribution Center. General Installation Safety Instructions • Use only recommended accessories. Use of improper accessories or unapproved system components in conjunction with Spears" FlameGuard° CPVC Fire Sprinkler Products will void the warranty and may result in improper operation of the system. • CAUTION: Avoid dangerous environments. If utilizing electrically powered tools for installation, be sure that the area is free of moisture or wetness that could create an unsafe condition. Keep work area clean and well illuminated. Allow sufficient space for measuring and system dry -fit to accommodate proper installation. • Prevent back injury. Always practice safe lifting and installation techniques. • Use only tools specifically designed for plastic pipe and fittings. • Inspect the products. Be sure that all parts are included and that you have all necessary tools available to properly install the system. CAUTION: Follow all workplace safety requirements. Wear safety glasses, hardhat, and safety footwear. Always practice safety first. When solvent cementing, always work in a well -ventilated area. Avoid sources of heat or open flames. DO NOT smoke. Wear protective gloves. PVA-coated protective gloves are recommended for use while solvent cementing. If hands come in contact with solvent cement, use a waterless, abrasive soap. • Wear ear protection. Protect your hearing if you are exposed to long periods of very noisy job -site operations. INTRODUCTION Spears" FlameGuard" CPVC Fire Sprinkler Products are manufactured from high quality, Post -Chlorinated Poly Vinyl Chloride (CPVC), a specialty thermoplastic material tested and approved by certifying agencies for use in CPVC fire sprinkler systems. Spears" FlameGuard" CPVC Fire Sprinkler Products provide unique advantages over traditional metal fire sprinkler systems through superior hydraulics, ease of installation and handling and quick assembly using readily available, inexpensive tools. FG-3-1010 © 2013 Spears" Manufacturing Company Page 5 Handling & Storage Pipe & Fittings Spears" FlameGuard° CPVC Fire Sprinkler Products resist attack from a large group of chemicals that are corrosive to metallic piping. However, care must be taken to avoid contact with chemicals that are harmful to CPVC including those found in some common construction products. Specific chemicals or chemical vapors that contact CPVC can weaken or severely damage the system. Consult with the chemical manufacturer or Spears" before use. WARNING: DO NOT expose Spears® FlameGuard® CPVC Fire Sprinkler Products to edible oils, esters, ketones, or petroleum -based products, such as cutting oils, packing oils, traditional pipe thread paste or dopes, and some lubricants. Do not store or install CPVC products in direct contact with plasticizer containing materials such as electrical tape or certain wire and cable insulations. Consult with the chemical manufacturer for compatibility with CPVC or Spears® before use. Contact with incompatible chemicals could cause serious personal injury, property damage, and product damage. Spears° FlameGuard° CPVC Fire Sprinkler Pipe should be stored indoors with a maximum storage temperature of 110° F (43° C). If storing outdoors, the products must be covered with a non -transparent material to prevent extended exposure to sunlight. Brief exposure to direct sunlight on the job site may result in color fade, but it will not affect the physical properties. Spears° FlameGuard° CPVC Fire Sprinkler Fittings should be stored indoors in their original containers to keep them free from dirt and to help reduce the possibility of damage. WARNING: Spears® FlameGuard® CPVC Fire Sprinkler Products must not be subjected to prolonged sunlight exposure. The use of pipe and fittings that have been damaged due to improper storage could cause serious personal injury, property damage, and product damage. Reasonable care must be exercised in handling Spears° FlameGuard° CPVC Fire Sprinkler Products. DO NOT drop the products or drop anything on them. If improper handling results in scratches, splits, or gouges, the damaged fitting or section of pipe must be discarded. WARNING: DO NOT install Spears® FlameGuard® CPVC Fire Sprinkler Products that have been scratched, split, or gouged. The use of pipe and fittings that have been damaged due to improper handling could cause serious personal injury, property damage, and product damage. One -Step Solvent Cement Spears° FS-5 One -Step Low VOC Solvent Cement must be stored out of direct sunlight in an ambient temperature between 40° F (4° C) and 90' F (32° C). The solvent cement may be used for a period of two years from the date stamped on the container. Expired solvent cement must be discarded in an environmentally friendly fashion, in accordance with local regulations. To prolong the life of the cement, the containers must be kept tightly closed when not in use and covered as much as possible when in use. WARNING: • Spears® FS-5 One -Step Low VOC Solvent Cement is highly flammable. Eliminate all ignition sources. • Avoid breathing vapors. Use only with adequate ventilation. Explosion -proof, general mechanical ventilation or local exhaust is recommended to maintain vapor concentrations below recommended exposure limits. In confined or partially enclosed areas, a NIOSH approved organic vapor cartridge respirator with a full face -piece is recommended. Avoid frequent contact with skin. It is recommended that you wear PVA coated gloves and an impervious apron. Page 6 © 2013 Spears® Manufacturing Company FG-3-1010 • Avoid contact with eyes. Splash -proof chemical goggles are recommended. • Review the Material Safety Data Sheet (MSDS) and the important product information provided on the label for Spears® FS-5 One -Step Low VOC Solvent Cement. Failure to follow the above recommendations could result in death or serious personal injury. Listings, Approvals, Application & Use Spears° FlameGuard° CPVC Fire Sprinkler Products are fully tested and approved for use in wet pipe fire sprinkler systems by Underwriters Laboratories Inc., FM Global, and the Loss Prevention Certification Board. Spears" FlameGuard° CPVC Fire Sprinkler Products are approved for use in low pressure dry pipe or pre -action systems by Underwriters Laboratories Inc. Spears° FlameGuard° CPVC Fire Sprinkler Products are listed by NSF International for use in potable water systems. For specific listing information not covered in this manual concerning Factory Mutual, The Loss Prevention Certification Board or NSF International, please contact your nearest Spears° Regional Distribution Center. NOTICE: National Fire Protection Association (NFPA) Standards 13, 13R, and 13D must be referenced for design and installation requirements in conjunction with this manual and all local codes. CAUTION: Spears° FlameGuard° CPVC Fire Sprinkler Products are NOT listed for outdoor applications. Outdoor installation could result in product failure and property damage and will not be covered under the Spears° FlameGuarda CPVC Fire Sprinkler Products warranty. CAUTION: Spears° FlameGuard° CPVC Fire Sprinkler Products are to be used in wet pipe systems only, except as provided for dry pipe or pre -action systems in this manual. A wet pipe system is one that contains water and is connected to a water supply system so that the water will discharge immediately when the sprinkler is opened. A low pressure dry pipe or pre - action system is a piping system containing air or nitrogen under pressure that is release with the opening of a sprinkler which activates a special dry pipe valve allowing water to flow into the piping system and to the open sprinkler. WARNING: Spears" FlameGuard° CPVC Fire Sprinkler Products must never be used for distribution of compressed air or other gases except as provided for under Low Pressure Dry Pipe and Pre -action Systems specified in this manual. Failure to follow this warning could result in product failure, property damage and severe personal injury or death. Light Hazard Occupancies Spears° FlameGuard° CPVC Fire Sprinkler Products are UL Listed for use in Light Hazard Occupancies, as defined in the NFPA 13. In accordance with NFPA 13, 2002 Edition paragraph 6.3.6.2, "Pipe ortube listed for light hazard occupancies shall be permitted to be installed in ordinary hazard rooms of otherwise light hazard occupancies where the room does not exceed 400 square feet". NOTICE: Local jurisdictions must approve of this exception. Residential Occupancies Spears° FlameGuard° CPVC Fire Sprinkler Products are UL Listed for use in: Residential occupancies up to and including four stories in height, as defined in NFPA 13R. Residential occupancies, as defined in the Standard for the Installation of Sprinkler Systems in One and Two Family Dwellings and Manufactured Homes, NFPA 131). FG-3-1010 © 2013 Spears® Manufacturing Company Page 7 Low Pressure Dry Pipe and Pre -action Systems In accordance with the UL° Listing, Spears° FlameGuard° CPVC Fire Sprinkler Products may be used in Low Pressure Dry Pipe and Pre -action System applications in Light Hazard and Residential occupancies in accordance with NFPA 13,13D and 13R when subject to the following additional limitations- A CPVC Low Pressure Dry Pipe or Pre -action System is a piping system intended for use where piping could be subjected to freezing temperatures and water filled pipe cannot be utilized. The minimum rated temperature is -20* F (-29° C). Low Pressure Dry Pipe systems contain compressed air or nitrogen (gas) having an internal gage pressure of not more than 15 psig (105 kPa). These specially designed systems require separate control valve mechanisms for this application (supplied by others) that activate to release water into the dry piping section and to the sprinkler heads. The water -filled portion of the system control device must be in an area protected from freezing. It is the installer's responsibility to be sure the system is installed in accordance with the limitations of this manual and specifications of a Dry Pipe or Pre -action Fire Sprinkler System design Engineer for proper control devices, pipe sizing, and other important design and maintenance criteria applicable to each project. CPVC dry systems must be designed with the following maximum water delivery time delay. Occupancy Hazard* Remote Sprinklers Open Water Delivery Delay, sec. Residential 1 15 Light 1 60 *As described in NFPA 13, Standard for the Installation of Sprinkler Systems. Spears° FlameGuard° CPVC Fire Sprinkler Products are UL° Listed for use in Dry Pipe or Pre -action type systems when installed with UL° Listed Spears" FlameGuard°, or BlazeMaster° brands of CPVC Fire Sprinkler Products that are also Listed for this application. CPVC installation in a Dry Pipe or Pre -action sprinkler system must be concealed (protected) by either: (1) A 3/8 in. thick or thicker gypsum wallboard; (2) A suspended membrane ceiling with lay -in panels or tiles having a weight of not less than 0.35 Ib/ft2 when installed with metallic support grids; or (3)1/2 in. plywood soffits. CPVC pipe and fittings used in a Dry Pipe or Pre -action System are not for use in combustible concealed spaces where sprinklers are required by NFPA 13, 13D and 13R. Pipe and fittings are for indoor use only, down to a minimum temperature of -20- F (-29- C). CPVC pipe in Dry Pipe or Pre -action Systems must be installed with proper pitch to allow system drainage for removal of water. NFPA 13 requires a minimum pitch of 1/2 inch per 10 feet (4 mm/m) for main lines and branch lines in areas subject to freezing. The following types of sprinklers and arrangements shall be permitted for dry pipe systems, current NFPA 13: (1) Upright sprinklers; (2) *Listed dry sprinklers; (3) Pendent sprinklers and sidewall sprinklers installed on return bends, where the sprinklers, return bend, and branch line piping are in an area maintained at or above 40* F (4° C); (4) Horizontal sidewall sprinklers installed so that water is not trapped; Page 8 © 2013 Spears® Manufacturing Company FG-3-1010 (5) Pendent sprinklers and sidewall sprinklers, where the sprinklers and branch line piping are in an area maintained at or above 40° F (4° C), the water supply is potable, and the piping for the dry pipe system is copper or CPVC specifically listed for dry pipe applications. Residential sprinklers used in CPVC Dry Pipe Systems shall be specifically listed for such use. Low Pressure Dry Systems have a maximum installed air pressure of 15 psi (1 BAR). Air (or Nitrogen) supply for charging the system must be filtered, clean, oil -free, and must be pressure regulated to assure that the 15 psi (1 BAR) pressurization is not exceeded. WARNING Oil in the air (or Nitrogen) supply can cause environmental stress cracking in CPVC materials. WARNING — Over pressurization can result in system damage or serious injury. The system must be hydrostatically tested in accordance with System Acceptance Testing (Hydrostatic Pressure Test) as specified in this manual. Concealed Installations In concealed installations, the minimum protection shall be one layer of 3/8- inch gypsum wallboard, 1/2-inch plywood soffits, or a suspended membrane ceiling with lay -in panels or tiles having a minimum weight of not less than 0.35 Ibs/ftz when installed with metal support grids. The minimum protection for residential occupancies, defined in NFPA 13D and 13R, may consist of one layer of 1/2-inch plywood. Spears" FlameGuard° CPVC Fire Sprinkler Products must be used in sprinkler systems employing sprinkler heads rated at 225' F (107° C) or lower. NOTICE • Spears° FlameGuard° CPVC Fire Sprinkler Products CANNOT be installed in spaces designated by NFPA 13 as combustible, concealed spaces that require sprinklers, unless the space is protected by sprinkers that are specifically Listed for the application. • NFPA 13D and NFPA 13R permit the omission of sprinklers in combustible, concealed spaces. Spears" FlameGuard° CPVC Fire Sprinkler Products can be installed in these areas when sprinkling residential occupancies in accordance with these standards. Combustible Concealed Installations with Specific Use Sprinklers In accordancewith UL Listing, Spearsa FlameGuard°CPVC Fire Sprinkler Products can be used in specific light -hazard, combustible concealed and noncombustible concealed spaces that require sprinkler protection when installed with UL Listed Victaulic Model V2502, Tyco Fire Products Model CC1— 2.8 K-Factor or Model CC2 — 5.6 K-Factor Combustible Concealed Space Sprinklers, Specific Application Upright, or UL Listed Viking Microfas? COIN'm Quick Response Combustible Interstitial Space Upright Sprinklers for Specific Application. The system must be installed in accordance with the applicable sprinkler manufacturer's information contained in Victaulic Model V2502, Submittal 40.09, Tyco Fire Products Model CC1 — 2.8 K-Factor Combustible Concealed Space Sprinkler Technical Data Sheet (dated July 2004), Tyco Fire Products Model CC2 — 5.6 K-Factor Combustible Concealed Space Sprinkler Technical Data Sheet (dated July 2007) or,Viking Microfas? COIN IM Quick Response Upright Sprinkler SIN VK900 (Specific Application) Technical Data Sheet (dated February 2, 2007). NOTICE: When installing Spears" FlameGuard° CPVC Fire Sprinkler Products in combustible concealed areas where sprinklers are required, the specific application sprinkler must be used in accordance with the UL Listing. Contact the local authority having jurisdiction with questions concerning code requirements. FG-3-1010 © 2013 Spears® Manufacturing Company Page 9 Combustible Attic Spaces with Specific Use Sprinklers Product Description In accordance with the LIL Listing, Spears" FlameGuard° CPVC Fire Sprinkler Products may be installed within the attic space provided the attic space is protected with UL Listed Tyco Fire Products Specific Application Attic Sprinklers. Specific Application Attic Sprinklers are sprinklers designed to provide protection of specific light hazard combustible, as well as non- combustible, attic spaces requiring sprinkler protection. Installation Requirements When using the Specific Application Attic Sprinklers, Spears° FlameGuard° CPVC Fire Sprinkler Products may be installed to feed the wet system sprinklers below the ceiling and exposed to feed wet system specific application attic sprinklers provided the system is installed in accordance with the Tyco Fire Products' Technical Data Sheet TFP610 (dated May 2008) for Specific Application Attic Sprinklers. Exposed Installations Spears° FlameGuard° CPVC Fire Sprinkler Products are UL Listed for use in installations without protection (exposed), with the following restrictions: Exposed CPVC Fire Sprinkler piping is installed below a smooth, flat, horizontal ceiling construction utilizing UL Listed support devices. • Listed, Quick -Response, ordinary temperature -rated pendent sprinklers having deflectors installed within 8 inches from the ceiling. Listed, Residential, ordinary temperature -rated, pendent sprinklers located in accordance with their Listing. The maximum distance between sprinklers must not exceed 15 feet. The piping must be mounted directly to the ceiling. • Listed, Quick -Response, ordinary temperature -rated horizontal sidewall sprinklers having deflectors installed within 6 inches from the ceiling and within 4 inches from the sidewall. Listed, Residential, ordinary temperature rated horizontal sidewall sprinklers located in accordance with their Listing. The maximum distance between sprinklers must not exceed 14 feet. The piping must be mounted directly to the sidewall. • Listed, Quick -Response, upright sprinklers having a maximum temperature rating of 155° F (68' C) must be installed so that the deflectors are a maximum of 4" from the ceiling. The maximum distance from the ceiling to the centerline of the main run of pipe must be 7-1/2". The distance from the centerline of a sprinkler head to a hanger must be 3". Rigid pipe hangers secured to the ceiling must be used. Expanded Use with Light Hazard Extended Coverage and Residential Sprinklers In accordance with the UL Listing, Spears" CPVC Fire Sprinkler products may be installed without protection (exposed) when subject to the following additional limitations. The following installations shall be below a smooth, flat, horizontal ceiling construction and require the use of FS-5 one step solvent cement. The piping shall be mounted directly to the sidewall. Listed quick response, 200° F (93° C) maximum temperature rated, horizontal sidewall sprinklers having deflectors installed within 12 inches (304 mm) from the ceiling and within 6 inches (152 mm) from the sidewall or Listed residential, 200' F (93° C) maximum temperature rated, horizontal sidewall sprinklers located in accordance with their Listing and a maximum distance between sprinklers not to exceed 14 feet (4.27 m). The following installations shall be below a smooth, flat, horizontal ceiling construction, are limited to unobstructed construction, require the use of Schedule 80 fittings for sizes 1-1/2 in. and greater, and require the use of FS-5 one step solvent cement. The piping shall be mounted directly to the sidewall. Page 10 © 2013 Spears® Manufacturing Company FG-3-1010 • Listed light hazard, extended coverage, quick response, 175° F (79° C) maximum temperature rated, horizontal sidewall sprinklers having deflectors installed within 12 inches (304 mm) from the ceiling and within 6 inches (152 mm) from the sidewall, a maximum distance between sprinklers not to exceed 16 feet (4.87 m), and an application density not less than 0.10 gpm/ftz (4.08 mm/min). • Listed residential, 165' F (74' C) maximum temperature rated, horizontal sidewall sprinklers having deflectors installed within 12 inches (304 mm) from the ceiling and within 6 inches (152 mm) from the sidewall, a maximum distance between sprinklers not to exceed 18 feet (5.48 m), and an application density not less than 0.10 gpm/ft2 (4.08 mm/min). • Listed light hazard, extended coverage, quick response 165' F (74° C) maximum temperature rated, horizontal sidewall sprinklers having deflectors installed within 12 inches (304 mm) from the ceiling and within 6 inches (152 mm) from the sidewall, a maximum distance between sprinklers not to exceed 18 feet (5.48 m), and an application density not less than 0.10 gpm/ftz (4.08 mm/min). • Listed light hazard, extended coverage, quick response,155' F (68' C) maximum temperature rated, horizontal sidewall sprinklers (manufactured by Reliable Automatic Sprinkler Co. Inc. SIN RA0362) having deflectors installed within 12 inches (304 mm) from the ceiling and within 6 inches (152 mm) from the sidewall, a maximum distance between sprinklers notto exceed 24 feet (7.31 m), and a flow not less than 40 gpm (152 Umin) per sprinkler. Spears° FG-3 installation instructions must be referenced for complete information regarding installation. Additional requirements may be listed in NFPA 13,13D and 13R. Unfinished Basements with Exposed Solid Wood Joist Installations NOTICE: Use of Spears° FlameGuard° CPVC Fire Sprinkler Products is limited to basements where the quantity and combustibility of contents is low and fires with relatively low rates of heat release are expected. Refer to NFPA 13D, "Standard for Installation of Sprinkler Systems in One and Two Family Dwellings and Manufactured Homes", for more information regarding installation in unfinished basements with exposed, solid wood joists. Spears° FlameGuard° CPVC Fire Sprinkler Products can be installed in unfinished basements with exposed, solid wood joists with the following limitations: 1. The ceiling shall be horizontal and constructed utilizing nominal 2 in. x 10 in. solid wood joists on 16 in. centers. OR The ceiling must be horizontal and constructed utilizing nominal 2 in. x 12 in. solid wood joists on 16 in. centers. When installing Spears" FlameGuard° CPVC Fire Sprinkler Products in conjunction with 2 in. x 12 in. solid wood joists, the maximum system working pressure under flowing conditions must not exceed 100 psi and the maximum system working pressure under non - flowing conditions must not exceed 175 psi. 2. Schedule 80 fittings are required for installations involving 1-1/2" through 3" piping. 3. The distance from the floor to the bottom of the solid wood joists must be between 7 ft and 8 ft. 4. All system mains shall be run perpendicular to the joists. All branch lines shall be run parallel to the joists. 5. When the total protected area exceeds 1,000 square feet, blocking shall be utilized to divide the area into individual compartments not exceeding 1,000 square feet. FG-3-1010 © 2013 Spears® Manufacturing Company Page 11 6. The maximum length along the joist must not exceed 32 feet. When the length exceeds 32 feet, blocking must be utilized. The blocking must be constructed of minimum 1/2 in. plywood and shall be the full depth of the wood joists. Refer to drawing below. Solid Wood Joists (Typical) Center Wall Riser with Center Room Main Center Wall Riser with Main at Wall Riser in Corner 7. Listed residential pendent sprinklers with a maximum temperature rating of 155° F and a minimum K-factor of 3.0 must be used for this type of installation. NOTE: The maximum sprinklerspacing shall notexceed 12 feet. 8. The system must be designed to UL Listed flows for the sprinklers being used. However, the flow must not be less than 11 gpm per sprinkler. Sprinklers must be installed with the deflectors below the solid wood joists for future installation of a finished ceiling. However, deflector placement must not exceed 1-3/4 inches below the solid wood joist (refer to following Figures "A" and "B"). For more information, refer to NFPA 13D, "Standard for Installation of Sprinkler Systems in One and Two Family Dwellings and Manufactured Homes". Bra nches Supported with BIocN 0 'f- Joist Depth Max. 1'14 Max. FIGURE "A" ing E FG-3-1010 © 2013 Spears® Manufacturing Company Page 13 9. When installing Spears" FlameGuard° CPVC Fire Sprinkler Products perpendicular (system mains) to the solid wood joists, UL Listed support devices for thermoplastic sprinkler piping or other UL Listed support devices shall be used which mount the piping,directly to the bottom of the solid wood joists. In addition, it is acceptable to cut holes in the solid wood joists at or below the center of the depth of the solid wood joist for support. Holes must be oversized to allow for movement and must be located in an area that will not compromise joist integrity. Consult the authority having jurisdiction for more information regarding structural integrity. 10. When installing Spears° FlameGuard° CPVC Fire Sprinkler Products parallel (branch lines) to the solid wood joists, the pipe and fittings must be installed in the cavity below the bottom of the ceiling and above the bottom of the joist. Branch lines must be located at or below the center of the depth of the solid wood joist. UL Listed support devices must be used to mount piping directly to nominal 2 in. wood blocking. In addition, UL Listed support devices can be used that offset the pipe a nominal distance of 1-1/2 in. from the solid wood joists. Extended Coverage Quick Response Sprinklers In accordance with the UL Listing, Spears° FlameGuard° CPVC Fire Sprinkler Products may be installed without protection (exposed) when subject to the following additional limitations: 1. Exposed piping is to be installed below a smooth, flat, horizontal ceiling construction. 2. Listed pendent, light hazard, quick response, extended coverage sprinklers,1551 F maximum temperature rating having deflectors installed within 8 in. from the ceiling and a maximum distance between sprinklers not to exceed 20 ft. with an application density of at least 0.10 gpm/sqft. 3. Listed pendent residential sprinklers, 1550 F maximum temperature rating having deflectors installed within 8 in. from the ceiling and a maximum distance between sprinklers not to exceed 20 ft. with an application density of at least 0.10 gpm/sqft. 4. Listed horizontal sidewall, light hazard, quick response, extended coverage sprinklers, 1651 F maximum temperature rating having deflectors installed within 6 in. from the ceiling and within 4 in. from the sidewall and a maximum distance between sprinklers not to exceed 18 ft. with an application density of at least 0.10 gpm/sqft. 5. Listed horizontal sidewall residential sprinklers, 1651 F maximum temperature rating having deflectors installed within 6 in. from the ceiling and within 4 in. from the sidewall and a maximum distance between sprinklers and not to exceed 18 ft. with an application density of at least 0.10 gpm/sgft. 6. When using fittings in the 1-1/2 in, and greater size only Schedule 80 fittings may be used. 7. The end use application is limited to unobstructed construction. 8. All solvent cementjoints shall be made with Spears" FS-5 One Step Solvent Cement, or any other cements referenced on page 23 of this manual. Page 14 © 2013 Spears® Manufacturing Company FG-3-1010 Return Air Plenum Installation Spears° FlameGuard° CPVC Fire Sprinkler Products meet the combustibility requirements for thermoplastic sprinkler pipe, as described in the Standard for Installation of Air Conditioning and Ventilating Systems, NFPA 90A. Spears" FlameGuard° CPVC Fire Sprinkler Products may be installed in the plenum space adjacent to, but not over, an opening in the ceiling, such as a ventilation grill. Garage Installations Spears° FlameGuard° CPVC Fire Sprinkler Products are suitable for use in garages requiring sprinklers, as defined in NFPA 13R, with the following requirements: Minimum protection consisting of either one layer of 3/8-inch thick gypsum or 1/2-inch thick plywood must be provided. Listed pendent or sidewall sprinklers with a maximum temperature rating of 225° F (107° C) must be used. All sprinklers must be installed per the manufacturer's published installation instructions. The system must be installed per the requirements of NFPA 13R and these installation instructions. Ambient Temperature Limitations Spears' FlameGuard° CPVC Fire Sprinkler Products are suitable for use in areas where ambient temperatures are within the range of 35° F (2° C) to 150' F (65° C). The Loss Prevention Certification Board (LPCB) listing states the maximum ambient temperature shall not exceed 120° F (50° C). High Temperature Areas Spears" FlameGuard° CPVC Fire Sprinkler Products can be installed in areas, such as an attic, where the ambient temperature exceeds 150' F (65° C) if ventilation is provided or if insulation is used around the product to maintain a cooler environment. WARNING: DO NOT install Spears® FlameGuard® CPVC Fire Sprinkler Products in areas where the ambient temperature exceeds 150° F (65° C) without adequate ventilation or insulation around the productto maintain a cooler environment. Cold Temperature Areas Spears° FlameGuard° CPVC Fire Sprinkler Products can be used in areas where the ambient temperature remains above 35° F (2° C). These products can also be used in an area subject to freezing temperatures if the sprinkler system installation is protected from freezing. Many standard cold weather piping design and installation practices can be used to protect the system from freezing, including, but not limited to the use of low pressure dry pipe and pre -action systems (see titled section in this manual), the use of glycerin, insulation installation techniques, and pipe insulation. Contact the manufacturers for compatibility of their products with Spears° FlameGuard" CPVC Fire Sprinkler Products. FG-3-1010 © 2013 Spears® Manufacturing Company Page 15 NOTE:'Attention must be given to local insulating techniques and codes that require a particular method. Since very cold weather will make Spears° FlameGuarde CPVC Fire Sprinkler Products more susceptible to damage, extra care should betaken to avoid rough handling or impact to these products. WARNING: DO NOT allow a sprinkler system to freeze. A frozen system will deactivate and the pressures built up can cause the sprinkler heads to open or damage the pipe and fittings. Antifreeze solutions of water and LISP or CP grade GLYCERIN are acceptable for use with Spears" FlameGuard° CPVC Fire Sprinkler Products. Refer to NFPA 13, NFPA 13R, NFPA 13D and consult the local authority having jurisdiction before using glycerin solutions in fire sprinkler applications. WARNING: DO NOT use glycol -based antifreeze solutions. Glycol solutions are not chemically compatible with the CPVC material and can cause damage to the CPVC Fire Sprinkler System. The following information can be used to determine the quantity of a glycerin based antifreeze solution needed to protect the piping system. Nominal Pipe Size -inch Actual mm Size US Gallons of Water Per Foot 3/4 (DN20) 26,9 .0311 1 (DN25) 33,7 .0494 1-1/4 (DN32) 42,4 .0792 1-1/2 (DN40) 48,3 .1042 2 (DN50) 60,3 .1636 2-1/2 (DN65) 73,0 .2395 3 (DN80) 88,9 .3555 NOTE: The gallons per foot column can be used for calculations when adding GLYCERIN to the piping system for freeze protection. All fire protection systems winterized with glycerin solutions must conform to local, state, and NFPA requirements. Glycerin based solutions are the only antifreeze solutions recommended for use. Glycol solutions are not chemically compatible with the CPVC material, and their use may result in damage to the CPVC Fire Sprinkler System. Fire Sprinkler System Risers In accordance with the UL Listing, Spears" FlameGuard° CPVC Fire Sprinkler Products may be used as system risers in accordance with NFPA 13D and 13R when subject to the following additional limitations: 1. When installed protected (concealed), the minimum protection shall consist of either one layer of 3/8 in. (9.5 mm) thick gypsum wallboard or 1/2 in. (12.7 mm) thick plywood. Page 16 © 2013 Spears® Manufacturing Company FG-3-1010 2. When installed without protection (exposed), the following limitations shall apply: a) The riser shall be installed below a smooth, flat, horizontal ceiling construction. A Listed residential pendent sprinkler is to be installed with its deflector at the distance from the ceiling specified in the sprinkler Listing. OR The riser shall be installed below a horizontal unfinished basement ceiling (in accordance with NFPA 13D) constructed utilizing nominal 2 in. x 10 in. or nominal 2 in, x 12 in. exposed solid wood joists on 16 in. centers. A Listed residential pendent sprinkler is to be installed with its deflector a maximum of 1-3/4 in. below the bottom of the solid wood joist in anticipation of future installation of a finished ceiling. • When installing Spears" FlameGuard° CPVC Fire Sprinkler Products in conjunction with 2 in. x 12 in. solid wood joists, the maximum system working pressure under flowing conditions shall not exceed 100 psi and the maximum system working pressure under static (nonflowing) conditions shall not exceed 175 psi. b) The Listed residential pendent sprinkler is to have a maximum temperature rating of 155° F and a minimum K-factor of 3.0 and is to be installed at a maximum horizontal distance of 12 inches from the centerline of the riser. The system is to be designed based upon the Listed flows for the sprinkler being used. However, the flow must not be less than 11 gpm per sprinkler. c) The riser shall be supported vertically within 2 feet of the ceiling or bottom of the joist. d) The minimum riser diameter shall be 1 in. and the maximum riser diameter shall be 2 in. e) The maximum distance between the wall(s) and the outside surface of the riser pipe shall be 1-1/2 in. f) All solvent cement joints shall be made with Spears° FS-5, or any of the solvent cements referenced on page 23 of this manual. g) These installations require the use of Schedule 80 fittings for riser sizes 1-1/2 in, and larger. 3. The system shall be installed per the requirements of NFPA 13, Support of Risers. Sections 9.2.5 (2002 Edition). 4. Spears° FlameGuard° CPVC Fire Sprinkler Products shall be installed per the manufacturer's installation and design manual and this addendum. 5. Risers shall be supported by pipe clamps or by hangers located on the horizontal connection close to the riser. Only Listed hangers and clamps shall be used. 6. Vertical lines must be supported at intervals, described in 7 & 8 below, to avoid placing excessive load on a fitting at the lower end. Do this by using riser clamps or double bolt pipe clamps Listed for this service. The clamps must not exert compressive stresses on the pipe. If possible, the clamps should be located just below a fitting so that the shoulder of the fitting rests against the clamp. If necessary, a coupling can be modified and adhered to the pipe as a bearing support such that the shoulder of the fitting rests on the clamp. Follow the manufacturer's recommended cure time. FG-3-1010 © 2013 Spears® Manufacturing Company Page 17 7. Recommended method for securing CPVC fire sprinkler pipe vertically. Place clamp below shoulder of fitting. WARNING: Modified riser collar shall only be used to provide support to the riser and shall not be used to join two pieces of pipe. Moddied FlameGuard- Coupling Adhered to Pipe Cut _ -Above a.........Seat Top View Cut Perpendicular to Seat Snug but mt Tight 8. Do not use riser clamps that squeeze the pipe and depend on compression of the pipe to support the weight. 9. Hangers and straps shall not compress, distort, cut or abrade the piping and shall allow forfree movement of the pipe to allowforthermal expansion and contraction. 10. Maintain vertical piping in straight alignment with supports at each floor level, or at 10 feet (3.05 m) intervals, whichever is less. 11. CPVC risers in vertical shafts or in buildings with ceilings over 25 feet (7.62 m), shall be aligned straight and supported at each floor level, or at 10 feet (3.05 m) intervals, whichever is less. Underground Fire Service Spears° FlameGuarda CPVC Sprinkler Products are UL Listed for use in underground water service when installation is in accordance with: • ASTM D 2774, "Standard Recommended Practice for Underground Installation of Thermoplastic Pressure Piping" • ASTM F 645, "Standard Guide for Selection, Design and Installation of Thermoplastic Water Pressure Piping Systems" • NFPA 24, "Standard for the Installation of Private Fire Service Mains and Their Appurtenances" The installation procedures detailed in this manual apply to CPVC Fire Sprinkler Products with solvent cemented joints in sizes 3/4 inch through 3 inches. C-UL Listing Requirements Spears° FlameGuard° CPVC Fire Sprinkler Products are C-UL Listed in accordance with Canadian requirements for use in: Light Hazard occupancies defined in the Standard for Installation of Sprinkler Systems, NFPA 13. Page 18 © 2013 Spears® Manufacturing Company FG-3-1010 Residential occupancies as defined in the Standard for Installation of Sprinkler Systems in Residential Occupancies up to Four Stones in Height, NFPA 13R. Residential occupancies as defined in the Standard for Installation of Sprinkler Systems in One and Two Family Dwelling and Manufactured Homes, NFPA 13D. Protected Installations When used with standard response sprinklers, protection shall be provided for Spears° CPVC piping products by ceilings, walls or soffits consisting of the following minimum protection: lath and plaster, 9.5 mm thick gypsum wallboard, 13 mm thick plywood or a suspended membrane ceiling with lay - in panels or tiles, classified with respect to surface burning characteristics having mass of not less than 1.7 kg/sq m and installed in steel suspension grids. The effectiveness of this protection can be impaired if penetrated by openings such as ventilation grills, exhaust fans connected to metal ducts serving washrooms excepted. Where such penetration is present, individual openings exceeding 0.03 sq in but not exceeding 0.71 sq m in an area must be located so that the distance from the edge of the opening to the nearest sprinkler does not exceed 300 mm. This piping shall not be used where such openings exceed 0.71 sq in in area. The effect of the presence of non -rated recessed lighting fixtures, public address speakers and other interruptions of the protective membrane has not been investigated. Exposed Installations As an alternative to the protection requirements, Spears° FlameGuard° CPVC Fire Sprinkler Products may be installed without protection (exposed) when subject to the following additional limitations: • Exposed piping is to be installed below a smooth, flat, horizontal, fixed ceiling construction. • Listed Quick -Response pendent sprinklers having deflectors installed within 8 inches from ceiling or Listed Residential pendent located in accordance with their Listing and a maximum distance between sprinklers not to exceed 15 feet. • Listed Quick -Response horizontal sidewall sprinklers having deflectors installed within 6 inches from the ceiling and within 4 inches of the sidewall or Listed Residential horizontal sidewall sprinklers located in accordance with their Listing and a maximum distance between sprinklers not to exceed 14 feet. During remodeling or repair, appropriate precautions shall be implemented to properly shield the piping from the protected occupancy. Spears" FlameGuard° CPVC Fire Sprinkler Piping Products are to be installed in accordance with the requirements specified in NFPA 13, NFPA 13R or NFPA 13D and the National Building Code of Canada. Spears° FlameGuard° CPVC Fire Sprinkler Piping Products must be installed in accordance with the other special installation and design criteria relative to handling, assembly, pipe hanger spacing, piping and sprinkler restraint, sprinkler temperature rating, piping location, testing procedures, friction loss characteristics and other applicable requirements specified in the manual. The use of Spears° FlameGuard" CPVC Fire Sprinkler Products in ceiling spaces above non- sprinklered areas has not been investigated. FG-3-1010 © 2013 Spears® Manufacturing Company Page 19 Spears° FlameGuard° CPVC Fire Sprinkler Piping Products are Listed for use in wet pipe systems only, and are not Listed for outdoor use. Spears" FlameGuard° CPVC Fire Sprinkler Products are C-UL Listed in accordance with Canadian requirements for use in combination with CPVC sprinkler products Listed in accordance with Canadian requirements and manufactured by Victaulic (pipe and fittings), Harvel (pipe), Ipex (pipe and fittings), TYCO Fire Products (pipe and fittings), Viking (pipe), or Nibco (fittings). NOTICE: While Spears" FlameGuard° CPVC Fire Sprinkler Products are Listed for use in combination with other listed manufacturers' products, specific application approvals may not be the same amongst manufacturers. It is the installer's responsibility to verify suitability of products used in combination according to each manufacturer's installation instructions. Contact Spears° if you have questions on any application not addressed. Spears° recommends the use of FS-5 One Step Low VOC Solvent Cement. However, Victaulic 899; Ipex BM-5; Central Sprinkler CSC-500; Nibco FP-1000 and TYCO Fire Products TFP-500 CPVC Solvent Cements can also be used in place of the FS-5 One Step Low VOC Solvent Cement, provided that the assembly and curing information referenced within this manual is used. Factory Mutual Approvals F M' APPROVED Spears" FlameGuard° CPVC Fire Sprinkler Products have been approved by Factory Mutual for use in exposed environments in Light Hazard Occupancies as defined in: NFPA 13, the Standard for "Installation of Sprinkler Systems." Residential occupancies, as defined in NFPA13R, the Standard for"Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height" Residential occupancies, as defined in NFPA 13D, the Standard for"Installation of Sprinkler Systems in One and Two Family Dwellings and Manufactured Homes." Spears° FlameGuard° CPVC Fire Sprinkler Products are FM Approved for use with Fire Resistant Barriers for CPVC Pipe and Fittings in Light Hazard Occupancies under FM Approval of the Soffi-SteelTm System manufactured by Grice Engineering, Inc. Installation is to be made in accordance with the FM Approval requirements for the Soffl-SteelTm System. Loss Prevention Certification Board LPCB LOSS PREVENTION CERTIFICATION BOARD Spears° FlameGuard° CPVC Fire Sprinkler Products are approved for use as agreed between plastics suppliers, purchaser/installer, authority having jurisdiction and/or insurer in accordance with documented supplier Installation Instructions but subject to the following criteria taking precedence: Page 20 0 2013 Spears® Manufacturing Company FG-3-1010 • Use of plastic pipe and fittings is subject to water authority agreement for the territory concerned. • LPCB Approved quick response sprinklers shall be used with exposed (i.e., fire exposure) plastic pipe and fittings. • Plastic pipe and fittings are suitable for use only with wet pipe systems. • Care should be exercised to ensure that joints are adequately cured, in accordance with the manufacturer's installation instructions prior to pressurization. • Plastic pipe and fittings shall not be installed outdoors. • Where plastic pipe and fittings are exposed (i.e., fire exposure), the system shall be installed close to a flat ceiling construction. • Sprinkler systems which employ plastic pipe and fittings shall be designed where possible to ensure no "no flow" sections of pipework in the event of sprinkler operation. In addition, the maximum normal ambient temperature shall not exceed 120° F (50° C). The product shall only be installed in the UK by LPCB Certificated or Registered installing companies or by firms outside the UK who can provide evidence of personnel training in the installation of the product. NSF International NSF Spears' FlameGuard° CPVC Fire Sprinkler Products have been approved by NSF@ for potable water applications. These products meet all applicable performance standards for a pressure rated application, as required in ANSI/ NSF@ Standard 14, and they comply with ANSI/NSF@ Standard 61 for health effects. Spears@ FlameGuard@ CPVC Fire Sprinkler Products are tested against ASTM Standards F 438 and F 439. Penetrating Fire -rated Walls & Partitions Before beginning, consultthe building codes and authorities having jurisdiction in your area. Several UL Classified, through -penetration firestop systems are approved for use with CPVC pipe. Consult the UL Building Materials Directory, the UL Fire Resistance Directory, and the system manufacturer for proper selection and application. Two manufacturers of Listed systems for use with CPVC pipe are Nelson Fire Stop Products (800-331-7325) and Tremco (800- 321-7906). Consult Spears' Manufacturing Company for further information. Heat Sources & Open Ceiling Areas Piping systems using Spears" FlameGuard@ CPVC Fire Sprinkler Products must be laid out so that the piping is not closely exposed to heat producing sources, such as light fixtures, ballasts, and steam lines. Pipe must not be positioned directly over open ventilation grills. During remodeling or ceiling repair, appropriate precautions must be implemented to properly protect the piping. FG-3-1010 © 2013 Spears® Manufacturing Company Page 21 Use With Other Manufacturers' Pipes, Fittings, & Solvent Cements Spears" FlameGuarda CPVC Fire Sprinkler Products may be used only in connection with UL, FM and NSF@ certified CPVC products of other manufacturers. Use of Spears@ FlameGuard@ CPVC Fire Sprinkler Products in connection with CPVC products of other manufacturers which are not UL, FM and NSF@ certified may result in inappropriate product application and inconsistent determinations in the event of warranty claims. Spears@ FlameGuard@ CPVC Fire Sprinkler Products are UL Listed for use in combination with UL Listed CPVC sprinkler products manufactured by Victaulic (pipe and fittings), Harvel (pipe), Ipex (pipe and fittings), TYCO Fire Products (pipe and fittings), Viking (pipe), or Nibco (fittings). NOTICE: While Spears@ FlameGuard@ CPVC Fire Sprinkler Products are UL Listed for use in combination with other listed manufacturers' products, specific application approvals may not be the same amongst manufacturers. It is the installer's responsibility to verify suitability of products used in combination according to each manufacturer's installation instructions. Contact Spears" if you have questions on any application not addressed in this manual. Spears" recommends the use of FS-5 One Step Low VOC Solvent Cement. However, Victaulic 899; Ipex BM-5; Central Sprinkler CSC-500; Nibco FP-1000 and TYCO Fire Products TFP-500 CPVC Solvent Cements can also be used in place of the FS-5 One Step Low VOC Solvent Cement, provided that the assembly and curing information referenced within this manual is used. Installation & Joining Make sure you follow all assembly and curing information referenced within this manual when installing Spears' FlameGuard@ CPVC Fire Sprinkler Products. Failure to follow this instruction could cause improper curing, resulting in serious personal injury, significant property damage, joint leakage, or joint failure. Before assembling any Spears@ FlameGuard@ CPVC Fire Sprinkler Products, you must inspect all components for cuts, scratches, gouges, split ends, or any other irregularities that have occurred during shipping and handling. Solvent Cement Welded Joints Cut Pipe Square. CPVC pipe can be easily cutwith a ratchet cutter, a wheel -type plastic tubing cutter, a power saw or a fine toothed saw. Tools used to cut CPVC , must be designed for plastic use and must be in good condition in accordance with the tool manufacturer's recommendations. It is important to cut the pipe square. A square cut provides the surface of the pipe with maximum bonding area. If any indication of damage or cracking is evident at the pipe end, cut off at least 2 inches (50 mm) beyond any visible crack. Notice: Avoid splitting the pipe when using ratchet cutters. Failure to do so may result in pipe failure or leakage. • Only use ratchet cutters that contain a sharp blade (blades dull quickly). • Only use ratchet cutters at temperatures of 50° F (10* C) or warmer. • Only use well -maintained, good quality ratchet cutters capable of consistently cutting the pipe squarely. Page 22 © 2013 Spears® Manufacturing Company FG-3-1010 Deburr & Bevel Pipe. Burrs and filings can prevent proper contact between pipe and fitting during assembly, and must be removed from the outside and the inside of the pipe. A chamfering/reaming tool or a file is suitable for this purpose. A slight bevel (approximately 10° to 15°) shall be placed at the end of the pipe to ease entry of the pipe into the socket. This will minimize the chance that the edges of the pipe will wipe solvent cement from the fitting socket during the the insertion of the pipe. Ryli M Fitting Preparation The pipe should enter the fitting socket easily one-third to two-thirds of the way (full interference fit). Contact between the pipe and fitting is essential in making a good joint. If the pipe bottoms Full Fit with little interference (net fit), use extra solvent cement in making the joint.I (+ This contact allows the solvent cement (which is applied in the next step) to effectively join the pipe and fitting. NptFit Using a clean, dry rag, wipe loose dirt and moisture from the fitting socket and pipe end. Moisture can slow the cure time and at this stage of assembly, excessive water can reduce joint strength. Solvent Cement Application CAUTION: Prior to using Spears° FS-5 One -Step CPVC solvent cement, or other approved CPVC fire sprinkler cement, review and follow all precautions found on the container labels, material safety data sheet, and Standard Practice for Safe Handling ASTM F 402. Failure to follow precautions may result in injury. Special care shall be exercised when assembling CPVC fire sprinkler systems in temperatures below 40' F (4° C). In colder temperatures extra time must be allowed for the solvent cement to set and cure. Extra care should be taken to prevent damaging the pipe during handling. When solvent welding pipe and fittings in colder temperatures, make certain that the cement has not become lumpy or has "gelled". Gelled cement must be discarded. At temperatures above 80' F (27' C) make sure both surfaces to be joined are still wet with cement during assembly. Higher temperatures and/or wind accelerate the evaporation of the volatile solvents in the cement. Pipe stored in direct sunlight may have surface temperatures 20° F to 30' F above the air temperature. If possible store the pipe and fittings, or, at least, the ends to be solvent welded, out of the direct sunlight prior to cementing. The solvents will penetrate hot surfaces more deeply, In conditions like this it is very important to avoid puddling the solvent cement inside the fitting socket. Use a dauber that is properly sized for the pipe, no less than 1/2 the diameter of the pipe being assembled. Only use solvent cements that have been specifically formulated and listed/ approved for use with CPVC fire sprinkler systems and approved by the pipe and fitting manufacturers. FG-3-1010 © 2013 Spears® Manufacturing Company Page 23 Vigorously apply a heavy, even coat of cement to the outside pipe end. Apply a medium coat to the fitting socket. Pipe sizes 1-1/4 inch (DN32, 32mm) and above shall always receive a second cement application on the pipe end. FIRST APPLY CEMENT ON THE PIPE END, THEN IN THE FITTING SOCKET, AND; FINALLY, ON THE PIPE END AGAIN. Notice: Too much solvent cement can cause clogged waterways or weaken the wall of the pipe or fitting and result in pipe failure or leakage. • Do not allow excess cement to puddle in the pipe and fitting assembly. To prevent this puddling, apply a lighter coating of solvent cement to the inside of the fitting socket than the outside of the pipe. • Wipe off excess cement on the outside of the joint. The solvents will evaporate, but the solvent cement inside the fitting will stay there. • Take care to prevent cement from running into the threads of Sprinkler Head Adapters and Adjustable Sprinkler Head Adapters. Where possible, it is recommended to pre -install head adapters on to pre-cut Drops (section of pipe) and allow to achieve initial set in the inverted position. The head adapter and drop combination can then be installed into the system fitting. Assembly After applying cement, immediately insert the pipe into the fitting socket, while rotating the pipe one -quarter turn until the pipe bottoms out at the fitting stop. Rotate the pipe as it is inserted into the fitting not after it has bottomed out in the fitting. Properly align the fitting for the installation at this time. Pipe must bottom to the stop. Hold the assembly for 30 seconds to ensure initial bonding. A bead of solvent cement should be evident around the pipe and fitting juncture. If this bead is not continuous around the socket shoulder, it may indicate that insufficient cement was applied. If insufficient cement is applied, the fitting must be cut out and discarded. Cement in excess of the bead should be wiped off with a rag. Continuous Bead } + ♦ ' i Bead Notice: Failure to allow sprinkler head adapter fitting joints to cure before installing sprinklers may result in cement in the sprinkler waterway. • Install sprinkler heads only after all the CPVC pipe and fittings, including the sprinkler head adapters, are solvent welded and allowed to cure for a minimum of 30 minutes. • Do not install sprinklers in the fittings prior to the fittings being cemented in place. Page 24 © 2013 Spears® Manufacturing Company FG-3-1010 • Prior to installing any sprinklers, the entire system including drops must be thoroughly flushed to remove all pipe shavings, dirt and debris left from installation. Fill lines slowly and bleed air from the farthest and highest point, then flush with full flow. Exercise care when installing sprinklers. Allow sprinkler head fittings and previously joined fittings to cure fora minimum of 30 minutes prior to installing the sprinkler. When installing sprinklers, be sure to anchor or hold the pipe drop securely to avoid rotating the pipe in previously cemented connections. Notice: Too much solvent cement can cause clogged waterways. • Visuallyinspect sprinkler fittings to ensure that the waterway and threads are clear of any excess cement. Once the installation is complete and cured per Table I, II or III, then test the system as described in the System Acceptance Testing (Hydrostatic Pressure Test) section of this manual. Set and Cure Times Notice: Inadequate curing of solvent cement joints may cause pipe failure or leakage. Solvent cement set and cure times are a function of pipe size, temperature, relative humidity, and tightness of fit. Cure times should be increased when moisture is present such as during cut - ins to live sprinkler lines. (NOTE: refer to Recommended Cut -In Procedures for System Modification or Repair section in this manual.) The assembly must be allowed to set, without any stress on the joint, for 5 minutes, depending on pipe size and temperature. Following the initial set period, the assembly can be handled carefully, avoiding significant stresses to the joint. Refer to Tables I, II, and III for MINIMUM cure times prior to pressure testing. Table 1: Minimum Cure Time Table for Pressure Test up to 225 psi (15.5 bar) Ambient Temperature During Cure Nominal 60° F to 120" F 40° F to 59° F 0° F to 39° F Pipe Sizes (16- C to 49° C) (4" C to 15° C) (-18° C to 3° C) 3/4" (DN20) 1 hour 4 hours 48 hours 1" (DN25) 1-1/2 hours 4 hours 48 hours 1-1/4" & 1-1/2" (DN32 & DN40) 3 hours 32 hours 10 days 2" (DN50) 8 hours 48 hours Note 1 2-1/2" & 3" (DN65 & DN80) 24 hours 96 hours Note 1 FG-3-1010 © 2013 Spears® Manufacturing Company Page 25 Table 2: Minimum Cure Time Table for Pressure Test up to 200 psi (13.8 bar) Ambient Temperature During Cure Nominal 60° F to 120° F 40' F to 59° F 0° F to 39' F Pipe Sizes (16° C to 49° C) (4° C to 15° C) (-18° C to 3° C) 3/4" (DN20) 45 minutes 1-1/2 hours 24 hr. 1" (DN25) 45 minutes 1-1/2 hours 24 hr. 1-1/4" & 1-1/2" (DN32 & DN40) 1-1/2 hours 16 hours 120 hours 2" (DN50) 6 hours 36 hours Note 1 2-1/2" & 3" (DN65 & DN80) 8 hours 72 hours Note 1 Note 1: For these sizes, the solvent cement can be applied at temperatures below 40" F (4° C). However, the sprinkler system temperature must be raised to a temperature of 40* F (4" C) or above and allowed to cure per the above recommendations prior to pressure testing. Table 3: Minimum Cure Time Table for Pressure Test up to 100 psi (6.9 bar) Ambient Temperature During Cure Nominal Pipe Sizes 60' F to 120" F (16° C to 49° C) 40' F to 59° F (4" C to 15° C) 0° F to 39° F (-18° C to 3° C) 3/4" (DN20) 15 minutes 15 minutes 30 minutes 1" (DN25) 15 minutes 30 minutes 30 minutes 1-1/4" (DN32) 15 minutes 30 minutes 2 hours NOTICE: 1-1/2-Inch and larger must be tested ONLY In accordance with Table 1 and Table 2. WARNING: Make sureyou allow the cement to cure according to the times listed in the charts for the pipe size and ambient temperature. These cure times have been tested and approved for Spears® FlameGuar0 CPVC Fire Sprinkler products. DO NOT install any sprinkler heads until the piping system has cured for a minimum of 30 minutes. Page 26 © 2013 Spears® Manufacturing Company FG-3-1010 The following guidelines provide an estimate of the quantities of Spears° FS-5 Low VOC Solvent Cement that you will need to complete the assembly. Solvent Cement Requirements Solvent Cement Nominal Fitting Sizes Number of Joints Per Quart (estimated) 3/4" (DN20) 270 1 (DN25) 180 1-1/4" (DN32) 130 1-1/2" (DN40) 100 2" (DN50) 70 2-1/2" 50 (DN65) 3" (DN80) 40 Threaded Connections WARNING: Use only thread sealant recommended by Spears®. Other joint compounds or pastes may contain substances that could cause stress cracks in the CPVC. Cutting oils used in metal pipe threading cause stress cracking in CPVC materials. All cutting oils must be removed and the metal pipe thoroughly flushed and degreased prior to assembly with CPVC systems. APPLY SEALANT ONLY TO MALE THREAD DO NOT use a combination of tape and paste sealants. DO NOT clog waterway with excessive sealant. RECOMMENDED SEALANT: BLUE 1" 51 . Spears° Manufacturing Company recommends the use of Spears° BLUE 75Tm thread sealant, which has been tested for compatibility with Spears" products. Please follow the sealant Manufacturer's Application/Installation instructions. Choice of another appropriate thread sealant is at the discretion of the installer. ASSEMBLE JOINT BY HAND Thread Sprinkler Head in "finger tight" for initial assembly. FG-3-1010 © 2013 Spears® Manufacturing Company Page 27 WRENCH MAKE-UP Use an adjustable wrench on the flats of the Head Adapter and Wrench recommended by Sprinkler Manufacturer for Head. Generally,' wrench make-up of 1 to 2 turns a beyond finger tight is sufficient. Avoid . "backing up" the wrenched assembly. For Sprinkler Head Adapter connections: Metal Thread & Special Reinforced Zinc SR Plastic Thread SR) Plastic Thread Min. Torque: 15 ft: lbs. 5 ft: Ibs. Max. Torque: 20 ft: Ibs. 10 ft: Ibs. For Female Adapter transitions to metal pipe, tighten hand -tight plus 1-1/2 turns. DO NOT over -tighten. IF A TAPE SEALANT MUST BE USED: 1. Use TFE tape no less than 2.5 mil thick. 2. Initial wrap must fully cover the thread end. 3. Wrap clockwise with standard pipe threads. 4. For Head Adapters, use ONLY 2 - 3 wraps of tape and tighten to specified torque. 5. For Female Adapter transition to metal pipe, use ONLY 5 - 54/2 wraps of tape and tighten hand -tight plus 14/2 turns. WARNING: Always use commercially available strap wrenches. Do not use conventional pipe wrenches that can damage fitting. WARNING: DO NOT over -torque any threaded connections. Generally, one to two turns beyond finger -tight are required to make a threaded connection. Factory testing has indicated that 15 - 20 ft-Ibs of torque on Metal Thread Head Adapters and 5 -10 ft-Ibs on Special Reinforced (SR) Plastic Thread Head Adapters is adequate to obtain a leak free seal for Sprinkler Head Installations. Transitions to metal pipe using Female Adapters should be hand tight plus 1-1/2 turns. NOTICE: Sprinkler heads must be installed only after all fire sprinkler pipe fittings, including the sprinkler head adapters, are cemented to the piping and have been allowed to cure for a minimum of 30 minutes. Plastic, threaded plugs are available for use in pressure testing. Before installing the sprinkler head, the sprinkler head fittings must be visually inspected or probed with a wooden dowel to ensure that the waterway and threaded areas are free of any excess cement that may restrict the flow of water. Page 28 © 2013 Spears® Manufacturing Company FG-3-1010 TorqueSafe'" Gasket Sealed Thread Connections This type of connection can only be made when using the FlameGuard° TorqueSafeTm Gasket Female Sprinkler Head Adapter. This special adapter has a special thread with gasket for sealing the sprinkler head. The adapter provides a special thread insert that can be rotated for proper frame alignment during installation. Warning: DO NOT USE ANY TYPE OF THREAD SEALANT when installing this adapter. Use of tape or paste sealant may impair proper sealing and function of the adapter. INSTALL SPRINKLER HEAD BY HAND Check that elastomer gasket and threads are clean, dry and gasket is seated at the base of the adapter thread. Install sprinkler head hand r ;. tight into adapter. DO NOT use any thread sealant! No a NO Paste P J: Handinstall undlsnug. RRUAWRENCH ALIGNMENT With wrench on sprinkler head, rotate sprinkler head clockwise until frame is properly aligned (Brass insert and 6.015 �!. -� , �..� Align Sprinkler head will rotate together. g This will require approximately 10 to 25 ft-lbs torque at final orientation). Align Sprinkler Caution: DO NOT use back-up Head Frame wrench on brass insert flats. with Pipe Centerline NEVER Reverse or Back up \ Threaded Assembly. If over - adjusted, continue to rotate clockwise until properly aligned. NOTE: Back-up wrench may be applied to brass insert flats ONLY for removal of sprinkler head if required. Align Sidewall Sprinkler Head & Frame Horizontally NOTICE: Sprinkler heads must be installed only after all fire sprinkler f , pipe fittings, including the sprinkler r head adapters, are cemented to the piping and have been allowed to cure for a minimum of 30 minutes. Plastic, { threaded plugs are available for use li in pressure testing. Before installing the sprinkler head, the sprinkler head fittings must be visually inspected or probed with a wooden dowel to ensure that the waterway and threaded areas are free of any excess cement that may restrict the flow of water. FG-3-1010 © 2013 Spears® Manufacturing Company Page 29 Painting Pipe & Fittings CAUTION: The UL Listing DOES NOT cover painted CPVC fire sprinkler piping products. Use of certain paints, such as oil -based, can damage CPVC fire sprinkler piping products. Before painting any CPVC fire sprinkler piping products, you must consult with your local authority having jurisdiction for restrictions. Cleaning Spears" FlameGuard° CPVC Fire Sprinkler Products can be cleaned using a mild soap and water solution. DO NOT use ammonia or other harsh chemical cleaners. Transitions to Other Materials Specifically designed female threaded adapters, grooved coupling adapters, and flanges are Listed for connecting systems incorporating Spears" FlameGuard° CPVC Fire Sprinkler Products to other materials, valves, and accessories. A special, reinforced female threaded adapter is available for connection to the sprinkler head. Flanged Connections Piping runs joined to the flanges must be installed in a straight line in relation to the flange to avoid stress at the flange due to misalignment. In addition, piping must be secured and supported to prevent lateral movement, which can create stress and damage the flange. Use only full-faced, Grade E, EPDM,1/8" thick flange gaskets. W111A Attach Flange to Pipe. The flange must be attached to UL Listed CPVC pipe following procedures for Solvent Cement Welded Joints in this manual. NOTICE: When using "One -Piece" type flanges (fixed flange ring), care must be taken to align bolt holes with mating flange during solvent welding installation to pipe, or assure that pipe in system can be adequately rotated for correct hole alignment. Position Gasket & Align Flanges. With gasket between flanges, align gasket and mating flange bolt holes by rotating flange ring (see notice above). RUlJk■ Install Bolts, Nuts, & Washers. Bolts should be lubricated with an acceptable anti -seize lubricant (such as IMS Copper Flake). Insert required bolts through flange bolt holes being sure to use two (2) flat washers per bolt, one at head and one below nut. Make sure that mating flanges are flush against gasket and properly aligned. Tighten nuts by hand until snug. WARNING: Certain lubricants can cause stress cracking in CPVC materials. E Tighten Flange Bolts. Establish uniform pressure over the flange face by tightening bolts in 5-ft. lbs. increments using the sequence shown in Figure 1 and specified torque values. Page 30 © 2013 Spears® Manufacturing Company FG-3-1010 CAUTION: DO NOT use bolts to draw together improperly mated flanges. Care must be taken to avoid "bending" the flange ring when attached to a raised -face flange or wafer style valves. Flange Data & Bolt Torque The following recommendations are based on the use of two standard flat washers, standard nuts, and 1/8-inch thick EPDM full -face gasket. Actual field conditions may require a variation in these recommendations. FIG.1 3 1 2 4 Flange Size Recommended Nominal In. Torque ft-lbs (N-m) 3/4 to 1-1/2 12 (DN20 - DN40) (16,3) 2to3 25 (DN50 - DN80) (33,9) Flange Size Nominal in. Bolt Holes Bolt Diameter inches (mm) Minimum Bolt Length inches (mm) 3/4 (DN20) 4 1/2 2 (50,8) (12,7) 1 (DN25) 4 1/2 2-1/4 (57,2) (12,7) 1-1/4 (DN32) 4 1/2 2-1/4 (57,2) (12,7) 1-1/2 (DN40) 4 1/2 2-1/2 (63,5) (12,7) 2 (DN50) 4 5/8 3 (76,2) (15,9) 2-1/2 & 3 (DN65 & DN80) 4 5/8 3-1/4 (85,6) (15,9) Grooved Coupling Adapters Spears° FlameGuard° CPVC Grooved Coupling Adapters are designed for use with Victaulic Style 75 and Style 77 Flexible Couplings. Other UL Listed couplings of similar flexible design may be used. CAUTION: The use of rigid style couplings will damage the Grooved Coupling Adapter, Consult coupling manufacturer for proper selection. Inspect Pipe & Adapter. Check to ensure that both pipe and Grooved Coupling Adapter are free of indentations, projections, or roll marks on the gasket seating areas. Pipe end must be cut square and any loose scale, paint or dirt removed. FG-3-1010 © 2013 Spears® Manufacturing Company Page 31 NOTICE: Use a standard grade "E" (EPDM) compound gasket with a green stripe or a grade "E," type "A" gasket with a purple stripe that is suitable for wet fire sprinkler service. Inspect & Lubricate Gasket. Be sure the gasket is clean and free of any cracks, cuts, or other defects that could cause leaks. DON OT allow solvent cement to contact the sealing surface of the gasket. Lubricate the gasket with a vegetable soap -base lubricant to prevent pinching and to assist in the seating and alignment process. Apply a thin layer of lubricant to the gasket lips and exterior surface. Pre -lubricated gaskets may be used. It is the installer's responsibility to determine both the gasket suitability and chemical compatibility of any lubricants. Consult gasket and lubricant manufacturers. WARNING: Certain lubricants may contain petroleum based or other chemical that can damage the gasket or adapter. Verify the suitability of the lubricant with the manufacturer before use. Align Components & Install Gasket. Place the gasket over the pipe end making sure the gasket lip does not overhang the end of the pipe. Align the grooved coupling adapter with the end of the pipe and slide the gasket over the seating surface of the adapter, centering the gasket between the two grooves. Make sure the gasket is not pinched between the pipe and the adapter fitting. No portion of the gasket should extend into the grooves. Install Coupling. Place the coupling housings over the gasket, making sure the housing keys engage into the grooves of the pipe and the adapter fitting. Insert the bolts and apply the nuts finger -tight. Using a socket wrench or other appropriate tool, tighten the nuts alternately and equally until you achieve metal -to -metal contact at the housings' bolt pads. WARNING: You must tighten the bolts alternately and evenly to achieve metal -to -metal contact at the housings' bolt pads. Inspect thejoints before and after pressure testing. Look for gaps between the bolt pads and for housing keys that are not inside the grooves. Ensure that the pipe alignment does not place undue stress on the grooved coupling adapters. The maximum recommended pipe hanger distance from the grooved coupling adapter fitting is shown in the following table. Page 32 © 2013 Spears® Manufacturing Company FG-3-1010 Nominal Pipe Sizes Maximum Recommended Hanger Spacing feet (meters) 1-1/4 6-1/2 (DN32) (2,0) 1-1/2 7 (DN40) (2,1) 2 8 (DN50) (2,4) 2-1/2 9 (DN65) (2,7) 3 10 (DN80) (3,0) As an added precaution to enhance the structural design of the system, it is suggested that a hanger or support be located at or near the grooved coupling adapter joint. This hanger or support can be on either side of the coupling. However, this is not a requirement, since the hanger spacing shown in the above table meets the minimum requirements established by UL. Adjustable Sprinkler Head Adapter Installation Spears° FlameGuard° CPVC Adjustable Fire Sprinkler Head Adapter comes pre -assembled. There is no need for lubrication. It is recommended that the adjustable sprinkler head adapter be adjusted completely "in" by hand before beginning the installation process. Install Adapter on Drop. The Adjustable Sprinkler Head Adapter must be installed in accordance with the approved procedures for Solvent Cement Welded Joints, as outlined in this manual. It is recommended that the drop/riser pipe be solvent cemented into the adjustable sprinkler head adapter first, and then into the drop/riser tee or elbow. CAUTION: Care must be taken to prevent solvent cement from coming in contact with the internal 0-ring seal or sealing surface. All pipe shavings, dirt and debris must be flushed from the drop prior to adjustment. DO NOT over extend the adjustment barrel. Extend only to the point that free movement stops or damage to internal sealing components may result. Install Sprinkler Head. Sprinkler head installation must be in accordance with the approved procedures for Threaded Connections, as outlined in this manual. TheAdjustable Sprinkler Head Adapter has multiple wrench flats provided to hold the adjustment barrel while installing the sprinkler head. These same wrench flats must be used to adjust the sprinkler head adapter to its required position. CAUTION: Never use wrenches, pliers, or any other tool on the threaded portion of the adjustment barrel. DO NOT over extend the adjustment barrel. FG-3-1010 © 2013 Spears® Manufacturing Company Page 33 Adjust Finished Height. The maximum range of travel is 1-5/8". Always use multiple wrench flats for making adjustments. Make adjustments slowly if system is pressurized in order to avoid inadvertently over extending adjustment barrel. CAUTION: Care must be taken not to extend or retract the adjustment barrel excessively, since this may result in damage to the adapter. Adjust only to the point that free movement stops. For the purpose of hydraulic calculations, the adjustable sprinkler head equivalent length of pipe in feet are as follows: 3/4"x1/2" = 6-ft.,1 "x1/2" = 94 Flushing System Prior to installing any sprinklers and testing, the entire system including drops must be thoroughly flushed to remove all pipe shavings, dirt and debris left from installation. Fill lines slowly and bleed air from the farthest and highest point, then flush with full flow. System Acceptance Testing (Hydrostatic Pressure Test) Once an installation is completed and joints are properly cured per the above recommendations, the system should be hydrostatically pressure tested with water at 200 psi (13.8 bar) for 2 hours. See Table II for curing conditions at 200 psi (13.8 bar). The system should be pressure tested with water at 50 psi (3.4 bar) in excess of maximum pressure when the maximum system pressure is to be maintained in excess of 150 psi (10.3 bar). See Table I for curing conditions at 225 psi (15.5 bar). This requirement is in accordance with the requirements established by NFPA Standard 13, Section 24.2.1(2007 Edition). Sprinkler systems in one- and two-family dwellings and mobile homes may be pressure tested with water at line pressure, after following Table III curing conditions, in accordance with the requirements established by NFPA 13D, Section 4.3 (2007 Edition). Prior to testing, be sure that the entire system including drops has been thoroughly flushed to remove all pipe shavings, dirt and debris left from installation as specified in the preceding section. When pressure testing, the sprinkler system shall be slowly filled with water and the air bled from the highest and farthest sprinkler heads before pressure testing is applied. Air must be removed from piping systems (plastic or metal) to prevent it from being locked in the system when pressure is applied. Entrapped air can generate excessive surge pressures thatcan result in bodily injury and/or property damage, regardless of the piping materials used. If a leak is found, the fitting must be cut out and discarded. A new section can be installed using couplings or a union. Unions should be used in accessible areas only. Page 34 © 2013 Spears® Manufacturing Company FG-3-1010 Recommended Cut -in Procedures for system Modification or Repair Existing system modifications or repairs can be made using Spears" FlameGuard° CPVC Fire Sprinkler Products. In order to maintain full system integrity, the following procedure must be followed when making a system tie-in or repair by cutting into an existing system line. A careful review of all Joining Procedures must be made prior to making a cut -in on an existing system and the Minimum Cut -in Cure Times schedule listed below must be followed. A variety of fitting combinations can be used to tie into an existing system or replace a section between fixed cut -in points. These include using a socket Tee for add-ons or a socket Coupling for repairs in combination with a mechanical joint such as a union grooved coupling adapter, or flange. Regardless of the components selected, the following must be adhered to: System modification cut -ins should be made on the smallest diameter pipe section, in close proximity to the area of modification, capable of properly supplying the system change. Carefully plan and measure prior to cutting into existing system. Be sure to provide adequate space and insure that full insertion into fitting sockets can be made during assembly. Note: Allowance must be made for making a 1/4-turn twist when inserting the pipe into the fitting during assembly of the tee (or other component), especially on 1-1/2" and larger pipe sizes. This may require assembly of components in combination with the cut -in tee to create a shortspool piece for final connection using socket unions, flanges, or grooved coupling adapters. Review all Installation & Joining procedures prior to commencing cut -in (including square cutting, deburring & beveling, cleaning, dry fit checks). Depressurize and drain existing line prior to making the cut -in. Connect to the existing system prior to proceeding with the modification or repair. All pipe shavings, dirt, debris must be removed from the cut -in system and, water and residual moisture must be removed from all solvent cement areas. Vacuum lines and wipe dry with a clean dry rag. Moisture and dirt will slow the curing and can affect joint strength. Use only a new can of approved solvent cement when making cut -in connections. Verify cement expiration date on can prior to use. Cut -ins for modifications or system repairs are often made under less than ideal situations as compared to new installations. As a result, the following specified Minimum Cut -in Cure times must be used. FG-3-1010 © 2013 Spears® Manufacturing Company Page 36 Minimum Cut -in Cure Times Ambient Temperature During Cure Pipe Size 60° F to 120' F 40" F to 59' F 0° F to 39° F Nominal In. (16° C to 49° C) (4" C to 15° C) (-18° C to 3° C) 3/4" (DN20) 24 hours 24 hours 48 hours 1" (DN25) 24 hours 24 hours 48 hours 1-1/4" & 1-1/2" (DN32 - DN40) 24 hours 32 hours 10 days 2" (DN50) 24 hours 48 hours Note 1 2-1 /2" & 3" (DN65 - DN80) 24 hours 96 hours Note 1 Note'l: Solvent cement can be applied at temperatures below 40° F (4° C) in all sizes. For the 2-1/2" & larger, the temperature must be raised to 40' F (4° C) or above and allowed to cure for the recommended times before the system is filled and pressurized. Cement, pipe or fittings brought in from colder outside temperatures must be brought up to room temperature before using the 60° F to 120° F cure schedule. Following completion and proper cure, inspect for proper alignment and hanger placement prior to pressure testing. To pressure test the system, slowly fill the system with water and make sure that all air is bled from the farthest and highest point before test pressure is applied. The system MUST be pressure tested in accordance with NFPA 13, NFPA 24, or any other applicable NFPA standard requirements. The system must be tested with water. The purpose of the hydrostatic pressure test is to check for leakage, and it may not identify improperly assembled joints. This test MUST NOT be considered a substitute for full compliance to these published installation instructions. It is recommended that the portion of the sprinkler system containing the cut - in tee be isolated for pressure test where possible. The applied test pressure should not exceed 50 psi over the system pressure in order to minimize water damage in the event that a leak occurs. WARNING: Spears® FlameGuard® CPVC Fire Sprinkler Products must never be used in a system for distribution of compressed air or other gases. Air must be removed from piping systems. Entrapped air can generate excessive surge pressures, regardless of the piping materials used. Failure to follow this warning could result in product failure, property damage and severe personal injury or death. Page 36 © 2013 Spears® Manufacturing Company FG-3-1010 Engineering Data Pipe and Fining Specifications Spears" FlameGuard° CPVC Sprinkler Pipe is produced in SDR 13.5 dimensions, as specified in ASTM F 442. Engineering data on Material Properties and Expansion & Contraction are provided in this manual for (A) Spears° FlameGuard" or Victaulic FireLock° and (B) Harvel BlazeMaster° CPVC Fire Sprinkler Pipe. Consult other manufacturers for applicable variations Spears° FlameGuard° CPVC Sprinkler Fittings are,produced in Schedule 40 and Schedule 80 dimensions for sizes 3/4" through 1-1/4", and in Schedule 80 for sizes 1-1/2" through 3", in accordance with ASTM F 437, ASTM F 438, and ASTM F 439 as applicable. These products are UL Listed FM/Approved for a rated working pressure of 175 psi (1200kPa)at 150° F (65' C) for sprinkler service and LPCB listed for a rated working pressure of 175 psi (1200kPa) at 120° F (49° C). CPVC Fire Sprinkler Pipe Dimensions SDR 13.5 (Ref. ASTM F442) Weight Ibs/ft (kg/m) Size Average Average Nominal aches OD inches ID (mm) inches 3/4 1.050 0.874 0.168 (DN20) (26,7) (22,5) (0,2) 1 1.315 1.101 0.262 (DN25) (33,4) (28,2) (0,4) 1-1/4 1.660 1.394 0.418 (DN32) (42,2) (35,6) (0,6) 1-1/2 1.900 1.598 0.548 (DN40) (48,3) (40,7) (0,7) 2 2.375 2.003 0.859 (DN50) (60,3) (50,9) (1,2) 2-1/2 2.875 2.423 1.257 (DN65) (73,0) (61,5) (1,2) 3 3.500 2.950 1.867 (DN80) (88,9) (75,0) (1,2) Hydraulic Design Hydraulic calculations for the sizing of systems incorporating Spears® FlameGuard° CPVC Fire Sprinkler Products must be calculated using a Hazen -Williams C value of 150. Pipe friction loss calculations must be made according to NFPA Standard 13. The following table shows the allowance for friction loss for fittings, expressed as equivalent length of pipe. For additional information regarding friction loss, contact Spears°. FG-3-1010 © 2013 Spears® Manufacturing Company Page 37 Allowance for Friction Loss In Fittings Equivalent Feet (meters) of Pipe 3/4" 26,7 mm 1" 33,7 mm 1-1/4" 42,4 mm 1-1/2" 48,3 mm 2" 60,3 mm 2-1/2" 73,0 mm 3" 88,9 mm Tee Run 1 (0,3) 1 (0,3) 1 (0,3) 1 (0,3) 1(0,3) 2(0,6) 2(0,6) Tee Branch 3(0,9) 5(1,5) 6(1,8) 8(2,4) 10(3,1) 12(3,7) 15(4,6) 90° Elbow 4(1,2) 5(1,5) 6(1,8) 7(2,1) 9(2,7) 12(3,7) 13(4,0) 45° Elbow 1 (0,3) 1(0,3) 2(0,6) 2(0,6) 2(0,6) 3(0,9) 4(1,2) Coupling rl(O, 3) 1(0,3) 1(0,3) 1(0,3) 1(0,3) 2(0,6) 2(0,6) Hangers & Supports Since CPVC Fire Sprinkler pipe is rigid, it requires fewer supports than flexible, plastic systems. Spears" recommends use of hangers that are designed and listed for supporting the CPVC Fire Sprinkler pipe. However, some hangers designed for steel pipe may be used if their suitability is clearly established. These hangers must have a minimum 1/2-inch, load -bearing surface, and they must be selected to accommodate the specific pipe size. In addition, they cannot contain rough or sharp edges that contact the pipe, and they must not bind the pipe from axial movement. Vertical runs must be supported so that the weight of the run is not on a fitting or a joint. Horizontal runs must be braced so that the stress loads (caused by bending or snaking pipe) will not be placed on a fitting or a joint. Support spacing is shown in the following table. See "Snaking/Deflection of Pipe" in this manual for information regarding bending or snaking CPVC Fire Sprinkler Pipe. Pipe Size Nominal inches Maximum Support Spacing feet (meters) Wt. Water Filled Pipe Ibs/ft (kg/m) 3/4 (DN20) 5-1/2 (1,7) 0.427 (0,635) 1 (DN25) 6(1,8) 0.674 (1,003) 1-1/4 (DN32) 6-1/2 (2,0) 1.078 (1,604) 1-1/2 (DN40) 7(2,1) 1.412 (2,101) 2 (DN50) 8.(2,4) 2.223 (3,308) 2-1/2 (DN65) 9(2.7) 3.254 (4,842) 3 (DN80) 10(3,0) 4.831(7,189) Page 38 © 2013 Spears® Manufacturing Company FG-3-1010 NFPA 13D permits "support methods comparable to those required by local plumbing codes." The above hanger/support requirements must also be followed on NFPA 13D systems. CAUTION: DO NOT use hanger items such as plumber's tape or "nail -on" devices. Pipe hanger must comply with NFPA 13, 13D and 13R. When a sprinkler head activates, a significant reactive force can be exerted on the pipe. With a pendent head, this reactive force can cause the pipe to lift vertically if it is not secured properly, especially if the sprinkler drop is from small diameter pipe. The pipe must be braced against the vertical lift -up with the closest hanger. Refer to the following illustration and Table A & B. I•—AB -lam, H S agpod'y W A Brace/Support Brace/Support Flnished.Ceiling Line Table A - Maximum Support Spacing Distance End Line Sprinkler Head Drop Elbow Pipe Size Nominal inches Line Pressure <100 psi (<689kPa) Line Pressure >100 psi (>689kPa) 3/4 (DN20) 9 inches (228,6 mm) 6 inches (168,3 mm) 1 (DN25) 12 inches (304,8 mm) 9 inches (228,6 mm) 1-1/4 (DN32) 16 inches (406,4 mm) 12 inches (304,8 mm) 1-1/2 - 3 (DN40 - DN80) 24 inches (610,0 mm) 12 inches (304,8 mm) Note: Support spacing can be increased by approximately 50% for lower pressures. Table B - Maximum Support Spacing Distance Inline Sprinkler Head Drop Tee Pipe Size Nominal inches Line Pressure <100 psi (<689kPa) Line Pressure >100 psi (>689kPa) 3/4 (DN20) 4 feet (1,22 meters) 3 feet* (0,91 meters) 1 (DN25) 5 feet (1,52 meters) 4 feet' (1,22 meters) 1-1/4 (DN32) 6 feet (1,83 meters) 5 feet' (1,52 meters) 1-1/2 - 3 (DN40 - DN80) 7 feet (2,13 meters) 7 feet (2,13 meters) Note: *Support spacing can be increased by one foot for lower pressures. FG-3-1010 © 2013 Spears® Manufacturing Company Page 39 Numerous common methods are used to brace Fire Sprinkler Pipe. A few acceptable methods include: use of a standard band hanger by positioning the threaded support rod to 1/1 6-inch above the pipe (however, it is important that the rod does not contact the pipe), a wrap around U-hanger, a special escutcheon which prevents upward movement of the sprinkler through the ceiling or band hangers with Surge Restraints to provide surge protection for the system. Pipe hangers are available that are tested and UL Listed for fire sprinkler service. These hangers comply with NFPA 13 requirements for use with CPVC fire sprinkler piping systems. The following illustrations depict several of these. Band Hanger - designed to support CPVC piping systems when used in conjunction with a hanging steel threaded rod that is suspended from a ceiling or other flat, horizontal surface. The threaded rod must be leveled properly before installing the hanger and restraint. Surge Restraint - when installed with the Band Hanger, as shown below, provides surge protection for the system. One Hole Wrap -Around Strap - designed to support CPVC piping systems only when the hanger tab is in the vertical position, and the screw -type fastener is in the horizontal position. The one -hole strap can be used as a pipe restrainer when the hanger tab is in the downward position, but it cannot be used as a hanger to hold any weight of the system. In addition, the one -hole strap can be used as a piping system guide when the system lies on top of the beam, and the beam supports the system's weight. The one -hole strap is not intended to support the CPVC piping system from under a ceiling or any other flat, horizontal surface. For this application, install two -hole strap. luide e Hanger Page 40 © 2013 Spears® Manufacturing Company FG-3-1010 Two -Hole Strap -designed to support CPVC piping systems when attached to a flat, horizontal surface with the screw -type fasteners in the vertical position. In addition, the two -hole strap is designed to support CPVC piping systems when attached to a flat, vertical surface with one mounting tab in the vertical position and the screw -type fasteners in the horizontal position. The two -hole strap can be used as a piping system guide when the system lies on top of a beam, and the beam supports the system's weight. Two -Hole 90° Side Mount Strap - designed to support CPVC piping systems when attached to a horizontal beam with the screw -type fasteners in the horizontal position and the pipe hanging below the beam. The fastener's mounting edges are designed to allow the screws to be installed horizontally. This is a benefit when overhead clearance is limited. In addition, the 90° side mount strap can be used in a restrainer fashion when it is attached to the top of a beam, and the system lies on top of the beam. Riser Supports Risers must be supported by pipe clamps or by hangers located on the horizontal connection close to the riser. Only Listed hangers. and clamps can be used. Vertical lines must be supported at intervals to avoid placing excessive load on a fitting at the lower end. This can be done by using riser clamps or double -bolt pipe clamps listed for this service. Hangers and supports must not compress, distort, cut, or abrade the piping, and they must allow free movement of the pipe for thermal expansion and contraction. DO NOT use riser clamps that squeeze the pipe and depend on compression of the pipe to support the weight. Maintain vertical piping in straight alignmentwith supports at each floor level or 10-foot intervals, whichever is less. CPVC risers in vertical shafts or buildings with ceilings over 25 feet must be aligned straight and supported at each floor level or 10-foot intervals, whichever is less. FG-3-1010 © 2013 Spears® Manufacturing Company Page 41 Clamps must not exert compressive stresses on the pipe. If possible, the clamps should be located directly below a coupling so that the shoulder of the coupling rests against the clamp. A coupling can be modified to achieve this by cutting a CPVC coupling just above the stop at the socket bottom. Then, cut this piece in half lengthwise to provide two halves that do not contain the stop. Follow the "Solvent Cement Welding Instructions" to cement the two halves to the pipe at the required location, and make sure that the shoulder of the modified coupling rests on the clamp. Allow the assembly to cure before placing any stress on the joint. WARNING: CPVC pipe and/or system components must not be used to provide structural support for the system. Care should be used when installing, hanging, or bracing to prevent unnecessary stress loads on the CPVC piping system. Exposed Installations For exposed installations that incorporate pendent or sidewall sprinklers, UL Listed support devices for thermoplastic sprinkler piping, or other listed support devices shall be used to mount the piping directly to the ceiling or sidewall. Earthquake Bracing Since CPVC fire sprinkler plastic piping is more ductile than metallic sprinkler pipe, it has a greater capacity to withstand earthquake damage. In areas subject to earthquakes, CPVC fire sprinkler systems should be designed and braced in accordance with local codes and NFPA Standard 13. Trenching The trench for underground fire service applications should be of adequate width to allow convenient installation, while at the same time being as narrow as possible. Minimum trench widths may be utilized by joining pipe outside of the trench and lowering it into the trench after adequate joint strength has been achieved. CAUTION - Refer to the set and cure times listed in this manual for solvent cement joints. Failure to follow these cure times before installing piping systems in trenches could result in joint separation. Trench widths have to be wider where pipe is joined in the trench or where thermal expansion and contraction is a factor. Refer to the "Snaking/Deflection of Pipe' section. Page 42 © 2013 Spears® Manufacturing Company FG-3-1010 LightTraffic Heavy Size Trench Ground Traffic Width Cover Ground Cover Nominal Actual Outside Minimum Minimum Diameter Diameter inches/ inches inches inches inches/mm mm 3 and under 3.500 and under 8 12 to 18 30 to 36 50 and under 60.3 and under • Water filled pipe should be buried at least 12 inches below the maximum expected frost line. • It is recommended that thermoplastic piping be run within a metal or concrete casing when it is installed beneath surfaces that are subject to heavy weight or constant traffic, such as roadways and railroad tracks. The trench bottom should be continuous, relatively smooth, and free of rocks. Where ledge rock, hardpan, or boulders are encountered, it is necessary to pad the trench bottom using a minimum of four inches of tamped earth or sand beneath the pipe as a cushion and for protection of the pipe from damage. Sufficient cover must be maintained to keep external stress levels below acceptable design stress. Reliability and safety of service is of major importance in determining minimum cover. Local, state, and national codes may also apply. Snaking/Deflection of Pipe NOTICE — • After CPVC pipe has been solvent cemented, snake the pipe, according to the following recommendations, beside the trench during its required drying time. • Be especially careful not to apply any stress that will disturb the undried joint. • Snaking is necessary to allow for any anticipated thermal contraction thatwill take place in the newly joined pipeline. Snaking is particularly necessary on the lengths that have been solvent cemented during the late afternoon or a hot summer's day because their drying time will extend through the cool of the night when thermal contraction of the pipe could stress the joints to the point of pull out. This snaking is especially necessary with pipe that is laid in its trench (necessitating wider trenches than recommended) and is back -filled with cool earth before the joints are thoroughly dry. The following information can be used in determining maximum deflection allowable for various run lengths and pipe sizes. FG-3-1010 © 2013 Spears® Manufacturing Company Page 43 Maximum Bending Deflections in Inches For Given Lengths of CPVC, SDR 13.5 (73° F) Pipe Length of Run (L) in Feet Size 2 1 5 7 1 10 1 12 1 15 1 17 1 20 1 25 1 30 1 35 1 40 1 45 F50 SDR 13.5 Pipe Deflection (D) in Inches 3/4 1.3 7.8 15.4 31.3 45.1 70.5 90.6 124.4 195.9 282.1 383.9 - I - 1 1.0 6.3 12.3 25.0 36.0 56.3 72.3 100.1 155.5 2252 306.6 400.4 - 1-1/4 0.8 5.0 9.7 19.8 28.5 44.6 57.3 79.3 123.9 178.4 242.8 317.2 4014 1-1/2 0.7 4.3 8.5 17.3 24.9 39.0 50.1 69.3 1082 155.9 212.2 277.1 350.7 433.0 2 0.6 3.5 6.8 13.9 20.0 31.2 40.0 55A 86.6 124.7 169.7 221.7 280A235.1 2.9 5.6 11.4 16.5 25.8 33.1 45.8 71.5 103.0 140.2183.1 231 E 2.4 4.6.9.4 13.5 21.2 27.2 37.6 58.8 84.6 1152 150.4 190 Lit D-in. Maximum SnaMng Deflections in Inches For Given Lengths of CPVC, SDR 13.5 (73° F) Length of Run (L) in Feet Pipe Size 2 1 5 7 10 12 1 15 1 17 1 20 1 25 1 30 1 35 1 40 1 45 1 50 SDR 13.5 Pipe Deflection (D) in Inches 3/4 0.3 2.0 3.8 7.8 11.3 17.6 22.6 31.3 49.0 70.5 96.0 125.41158.71 195.9 1 0.3 1.6 3.116.3 9.0 14.1 18.1 25.0 39.1 56.3 76.6 100.1 126.7 156.4 1-1/4 2.4 5.0 7.1 11.2 14.3 19.8 31.0 44.5 60.7 79.3 100.4 123.9 1-1/2 2.1 4.3 6.2 9.7 12.5 17.3 27.1 39.0 53.0 69.3 87.7 108.2 2 J0.21.2 1.7 3.5 5.0 7.8 10.0 13.9 21.6 31.242.4 55.4 70.1 86.6 2-1/2 +1.4446..4 8.3 11.4 17.9 25.8 35.1 45.8 57.9 71.5 3 3 6.8 9.4 14.7 212 28.8 37.6 47.6 56.8 �`-- L-ft. --►� " Page 44 © 2013 Spears® Manufacturing Company FG-3-1010 BACKFILLING CAUTION - Underground pipe must be thoroughly inspected and tested for leaks prior to backfilling (refer to section on hydrostatic pressure testing). Failure to follow this instruction could result in system failure. During periods of hot weather, backfilling should only be done early in the morning when the line is fully contracted, and there is no chance of insufficiently dried joints being subjected to contraction stresses. The pipe should be uniformly and continuously supported over its entire length on a firm, stable material. Blocking should not be used to change pipe grade or to intermittently support pipe across excavated sections. Pipe is installed in a wide range of sub -soils. These soils must be stable and applied in such a manner to physically shield the pipe from damage. Attention should be given to local pipe laying experience, which may indicate particular pipe bedding problems. Backfill materials that are free of rocks with a particle size of 1/2-inch or less should be used to surround the pipe with 6 to 8 inches of cover. It should be placed in layers. Each soil layer should be sufficiently compacted to uniformly develop lateral passive soil forces during the backfill operation. It may be advisable to have the pipe under pressure, 15 to 25 psi, during the backfilling. Vibratory methods are preferred when compacting sand or gravels. Best results are obtained when the soils are in a nearly saturated condition. Where water -flooding is used, the initial backfill should be sufficient to ensure complete coverage of the pipe. Additional material should not be added until the water flooded backfill is firm enough to walk on. Care should be taken to avoid floating the pipe. Sand and gravel containing a significant proportion of fine-grained material, such as silt and clay should be compacted by hand or, preferably, by mechanical tamper. The remainderof the backfill should be spread in uniform layers to fill the trench completely so that there will be no unfilled spaces around rocks or lumps of earth in the backfill. Large or sharp rocks, frozen clods, and other debris, greater than 3 inches in diameter, should be removed. Rolling equipment or heavy tampers should be used only to consolidate the final backfill. Maintenance shall be in accordancewith the Standard for Inspection, Testing and Maintenance of Water Based Extinguishing Systems, as defined by NFPA 25. FG-3-1010 © 2013 Spears® Manufacturing Company Page 45 Material Properties Table 1-A Modulus of Elasticity & Stress vs. Temperature For Spears" FlameGuard" orllictaulic FireLock' CPVC Fire Sprinkler Pipe Temperature ° F Property 73 80 90 100 110 120 140 150 Modulus of Elasticity 3.90 3.84 3.78 3.70 3.46 3.21 3.05 2.84 "E" x 105 psi Working Stress 1,900 1,785 1,630 1,485 1,345 1,270 950 875 S. psi Table I-B Modulus of Elasticity & Stress vs. Temperature For Harvel BlazeMaster" CPIIC Fire Sprinkler Pipe Temperature ° IF Property 73 80 90 100 110 120 140 1 150 Modulus of Elasticity 4.23 4.14 3.99 3.85 3.70 3.55 3.23 3.08 "E" x 105 psi Working Stress 2,000 1,875 1,715 1,560 1,415 1,275 1,000 875 "S" psi Page 46 © 2013 Spears® Manufacturing Company FG-3-1010 Table II Physical & Thermal Properties A -Spears° FlameGuard° B-Harvel Property or Victaulic BlazeMaster° ASTM Firel-ock" CPVC Pipe CPVC Pipe Specific Gravity "Sp. Gr." 1.51 1.55 D 92 VOID Impact Strength 5.0 3.0 D 256A (ft. Ibsfinch of notch Modulus of Elasticity, psi "E" 3.9 x 101 4.23 x 101 D 638 Ultimate Tensile Strength, psi 8,000 8,400 D 638 Compressive Strength, psi 9,000 9,600 D 695 Poisson's Ratio .35 - .38 .35 - .38 - Working Stress @ 73" F, psi 1,900 2,000 D 1598 Hazen -Williams "C" Factor 150 150 - Coefficient of Linear "e" 3.2 x 1 V 3.4 x 105 D 696 Expansion in./(in. " F) Thermal Conductivity "k" 0.95 0.95 C 177 BTU/(hr" F Win') Upper Temperature Limit "' F" 205 210 - Flammability Flame Retardant Flame Retardant Electrical Conductivity Non Conductor Non Conductor Expansion and Contraction Spears" FlameGuard° CPVC Fire Sprinkler Products, like all piping materials, expand and contract with changes in temperature. If the coefficient of linear expansion is 3.2 x10-5 inch/inch ° F. A 25° F change in temperature will cause an expansion of 1 inch fora 100-foot straight length. For most operating and installation conditions, expansion and contraction can be accommodated at changes of direction. FG-3-1010 @ 2013 Spears® Manufacturing Company Page 47 Table 1114 Thermal Expansion In Inches For Spears® FlameGuard° or Victaulkc Firdock•" CPVC Fire Sprinkler Pipe Temp. Change Length of Run in Feet 5 10 15 20 25 130 135 140 145 1 50 1 70 1 90 1120F160 Al ° F Thermal Expansion AL (in.) 20 0.04 0.08 0.12 0.15 0.19 0.23 0.27 0.31 0.35 0.38 0.54 0.69 0.92 1.23 30 0.06 0.12 0.17 0.23 0.29 0.35 0.40 0.46 0.52 0.58 0.81 1.04 1.38 1.84 40 0.08 0.15 0.23 0.31 0.38 0.46 0.54 0.61 0.69 0.77 1.08 1.38 1.84 2.46 50 0.10 0.19 0.29 0.38 0.48 0.58 0.67 0.77 0.86 0.96 1.34 1.73 2.30 3.07 60 0.12 0.23 0.35 0.46 0.58 0.69 0.81 0.92 1.04 1.15 1.61 2.07 2.76 3.69 70 0.13 0.27 0.40 0.54 0.67 0.81 0.94 1.08 1.21 1.34 1.88 2.42 3.23 4.30 80 0.15 0.31 0.46 0.61 0.77 0.92 1.08 1.23 1.38 1.54 2.15 2.76 3.69 4.92 90 U 0.17 0.35 0.52 0.69 0.86 1.04 1.21 1.38 1.56 1.73 2.42 3.11 4.15 5.53 100 0.19 0.38 0.58 0.77 0.96 1.15 1.34 1.54 1.73 1.92 2.69 3.46 4.61 6.14 Table 111-B Thermal Expansion in Inches For Haruel BlazeMaster® CPVC Fire Sprinkler Pipe Temp. Change Length of Run in Feet 5 10 15 20 1 25 '30 1 35 1 40 1 45 1 50 70 90 120 F160 Al ° F Thermal Expansion AL (in.) 20 0.04 0.08 0.12 0.16 0.20 0.24 0.29 0.33 0.37 0.41 0.57 0.73 0.98 1.31 30 0.06 0.12 0.24 0.24 0.31 0.37 0.43 0.49 0.55 0.61 0.86 1.10 1.47 1.96 40 0.08 0.16 0.33 0.41 0.41 0.49 0.57 0.65 0.74 0.82 1.14 1.47 1.96 2.61 50 0.10 0.20 0.41 0.51 0.51 0.61 0.72 0.82 0.92 1.02 1.43 1.84 2.45 3.26 60 0.12 0.24 0.49 0.61 0.61 0.73 0.86 0.98 1.10 1.22 1.71 2.20 2.94 3.92 70 0.19 0.29 0.57 0.71 0.71 0.88 1.00 1.14 1.29 1.43 2.00 2.57 3.43 4.57 80 0.16 0.33 0.65 0.82 0.82 0.98 1.14 1.31 1.47 1.63 2.28 2.94 3.92 5.22 90 0.18 0.37 0.73 0.92 0.92 1.04 1.10 1.29 1.47 1.66 2.84 3.30 4.41 5.88 100 0.20 0.4110.8211.021 1.02 1.22 1.43 1.63 1.84 2.04 2.86 3.67 4.90 6.53 AL = 12 eL (AT) e = 3.4 x10-1 in.Pn. ° F (Coefficient of Linear Expansion for Harvel BlazeMaster° CPVC Fire Sprinkler Pipe) -or- e = 3.2 x105 in./in. ° F (Coefficient of Linear Expansion for Spears° FlameGuard' CPVC Fire Sprinkler Pipe) L = Length of Run in Feet AT = Temperature Change in ° F Page 48 © 2013 Spears® Manufacturing Company FG-3-1010 Example: How much will a 40 ft. run of 2" Spears° FlameGuard° CPVC Fire Sprinkler Pipe expand if the expected ambient temperature will range from 45° F to 85' F? AL = 12 el- (AT) AL = 12 (.000032) x 40 x 40 AL = .61" Expansion Loop & Offset Configurations Hangers or guides should only be placed in the loop, offset or change of direction as indicated below. Piping supports should restrict lateral movement and should direct axial movement into the expansion loop. Expansion Loop and Offset Configurations Loop 215E i 6" Min!115E 6., Min Offset 1/2 E Change of Direction Long Pipe e e Hanger or Guide ' Restraint FG-3-1010 © 2013 Spears® Manufacturing Company Page 49 Table IV -A Expansion Loop Length In Inches For Spears® FlameGuard° or Victaulic Firelock'" CPVC Fire Sprinkler Pipe Nominal Pipe Size Avg O.D. Length of Run In Feet 5 1 10 15 20 1 25 1 30 1 35 1 40 1 45 1 50 70 1 90 120 160 Length of Loop (in.) Temperature =100* F - 30° F, AT = 70° F 314 1.050 7 10 13 15 19 21 22 23 27 31 36 41 1 1.315 8 11 14 16 22 23 24 26 30 34 40 46 1-1/4 1.660 9 13 16 18 $2224 24 26 27 29 34 39 45 52 1-1/2 1.900 10 14 17 20 26 28 29 31 37 41 48 55 2 2.375 11 15 19 22 29 31 33 35 41 46 54 62 2-1/2 2.875 12 17 21 24 27 30 32 34 36 38 45 51 59 68 3 3.500 13 19 23 27 30 1 33 35 38 40 42 50 1 56 65 75 Table IV-B Expansion Loop Length in Inches For Haruel BlazeMaster® CPVC Fire Sprinkler Pipe Nominal Pipe Size Avg O.D. Length of Run in Feet 5 1 10 1 15 20 1 25 1 30 1 35 1 40 1 45 1 50 1 70 1 90 1 120 160 Length of Loop (in.) Temperature =100° F - 30° F, AT = 70° F 314 1.050 7 11 13 15 17 18 20 21 22 24 1 28 32 37 42 1 1.315 8 12 14 17 19 20 22 24 25 26 31 35 47 1-1/4 1.660 9 13 16 19 21 23 25 26 28 30 35 40 53 1-112 1.900 10 14 20 22 22 25 27 28 30 32 38 43 r49 57 2 2.375 11 16 19 22 25 27 30 32 34 35 42 48 63 2-1/2 2.875 12 18 21 25 27 30 33 35 37 39 46 52 70 3 3.500 13 19 24 27 30 33 36 38 1 41 43 51 1 581 67 77 Note: Table IV -A and IV-13 are based on Stress & Modulus Elasticity at 100* F C = 3EDAL 2S 9 = Length of Expansion Loop in Inches E = Modulus of Elasticity (Table I -A or I-B) D = Average O.D. of Pipe AL = Change in Length of Pipe Due to Change in Temperature (Table III -A or III-B) S = Working Stress (Table I -A or 1-13) Page 50 © 2013 Spears® Manufacturing Company FG-3-1010 Note: Data in Table I -A must be used with Table III -A and data in Table I-B with Table III-B Example: How much expansion can be expected in a 200 ft. run of 2" Spears° FlameGuard° CPVC Fire Sprinkler Pipe and how long should the expansion loop be to compensate for this expansion? (The expected temperature range will be from 40' F to 110" F). First Find: AT = (Change in Temperature) AT = T2—T1 AT = 110' F-40° F AT = 70' F To Find: AL = (Amount of Expansion in inches from Table III -A) AL = AL of 160 ft. with a AT of 70" F + AL of 40 ft. with a AT of 70° F AL = 4.30" + 1.08" AL = 5.38" 912 AL = 12eL(AT) e = 3.2 x 10s (from Table II, Victaulic FireLockTm CPVC Pipe) L = Length of Run in Feet AT = Change in Temperature in ° F AL = 12 x .000032 x 200 x 70 AL = 5.38" To find the length of the expansion loop or offset in inches: ¢ = I 3EDAL 2S ¢ = Length of Expansion Loop in Inches E = Modulus of Elasticity at 110° F (Table I -A) D = Average O.D. of Pipe AL = Change in Length of Pipe Due to Change in Temperature (Table III -A) S = Working Stress at 110° F (Table I -A) ¢ = 3EDAL 2S 2.375 x 5.38 2 x 1345 ¢ = 4931 e = 70.2" FG-3-1010 © 2013 Spears® Manufacturing Company Page 51 Review — Do's & Don'ts Do's • Read the manufacturer's installation instructions. • Follow recommended safe work practices. • Make certain that thread sealants, gasket lubricants, or fire stop materials are compatible with CPVC. • Keep pipe and fittings in original packaging until needed. • Cover pipe and fittings with an opaque tarp if stored outdoors. • Follow proper handling procedures. • Use tools specifically designed for use with plastic pipe and fittings. • Use the proper solvent cement and follow application instructions. • Use a drop cloth to protect interior finishes. • Cut the pipe ends square. • Deburr and bevel the pipe end with a chamfering tool. • Rotate the pipe 1/4 turn when bottoming pipe in fitting socket. • Avoid puddling of cement in fittings and pipe. • Make certain no solvent cement is on sprinkler head and adapter threads. • Make certain that solvent cement does not run and plug the sprinkler head orifice. • Follow the manufacturer's recommended cure times prior to pressure testing. • Flush the entire system including drops to remove pipe shavings, dirt and debris left from installation. • Fill lines slowly and bleed the air from the system prior to flushing and pressure testing. • Support sprinkler head properly to prevent lift up of the head through the ceiling when activated. • Keep threaded rod within 1/16" of the pipe or use a surge arrestor. • Install Spears°FlameGuard° CPVC Fire Sprinkler Products in wet systems only. • Use only glycerin and water solutions for freeze protection. • Allow for movement due to expansion and contraction. • Renew your Spears' FlameGuard° CPVC Fire Sprinkler Products installation training every two years. Page 52 © 2013 Spears® Manufacturing Company FG-3-1010 Don'ts • Do not use edible oils such as Crisco as a gasket lubricant. • Do not use petroleum or solvent -based sealants, lubricants, or fire stop materials. • Do not install tape, insulated wire or cable in direct contact with CPVC. • Do not use any glycol -based solutions as an anti -freeze. • Do not mix glycerin and water solutions in contaminated containers. • Do not use solvent cement that exceeds its shelf life or has become discolored or jellied. • Do not allow solvent cement to plug the sprinkler head orifice. • Do not connect rigid metal couplers to CPVC grooved adapters. • Do not thread, groove, or drill CPVC pipe. • Do not use solvent cement near sources of heat, open flame, or when smoking. • Do not pressure test with air. • Do not pressure test until recommended cure times are met. • Do not use ratchet cutters below 50° F. • Do not use CPVC pipe that has been stored outdoors, unprotected and is faded in color. • Do not allow threaded rod to come in contact with the pipe. • Do not install Spears° FlameGuard° CPVC Fire Sprinkler Products in cold weather without allowing for expansion. Material Safety Data Sheet IPS WELD -ON Date Revised: FEB 2000 Supersedes: FEB 1999 Information on this form is furnished solely for the purpose of compliance with the Occupational Safety and Health Act and shall not be used for any other purpose. IPS Corporation urges the customers receiving this Material Safety Data Sheet to study it carefully to become aware of the hazards, if any, of the product involved. In the interest of safety, you should notify your employees, agents and contractors of the information on this sheet. Section I Manufacturer's Name: IPS Corporation Address:17109 S. Main St., PO Box 379, Gardena, CA 90248 Transportation Emergencies: CHEMTREC: (800) 424-9300 or 3 E COMPANY (800) 451-8346 Medical Emergencies: 3 E (24 Hour No.) (800) 451-8346 Business: (310) 898-3300 CHEMICAL NAME and FAMILY: Solvent Cement for CPVC Plastic Pipe Mixture of CPVC Resin and Organic Solvents Trade Name: SPEARS" FS-5 Formula: Proprietary FG-3-1010 © 2013 Spears® Manufacturing Company Page 53 Section II - Hazardous Ingredients None of the ingredients below are listed as carcinogens by ]ARC, NTP or OSHA Ingredient: Chlorinated Polyvinyl Chloride Resin (CPVC) Cas#: NON/HAZ ACGIH-TLV: N/A OSHA-PEL: N/A Ingredient: Tetrahydrofuran (THF)** Cas#: 109-99-9 ACGIH-TLV: 200 PPM ACGIH-STEL: 250 PPM OSHA-PEL: 200 PPM OSHA-STEL: 250 PPM DUPONT (A) AEL: 25 PPM DUPONT (B) STEL: 75 PPM Ingredient: Methyl Ethyl Ketone (MEK) Cas#: 78-93-3 Approx%: 2* ACGIH-TLV: 200 PPM ACGIH-STEL: 300 PPM OSHA-PEL: 200 PPM OSHA-STEL: 300 PPM Ingredient: Cyclohexanone Cas#: 108-94-1 ACGIH-TLV: 25 PPM Skin OSHA-PEL: 25 PPM Skin Ingredient: Acetone Cas#: 67-64-1 ACGIH-TLV: 750 PPM ACGIH-STEL: 1000 PPM OSHA-PEL: 750 PPM OSHA-STEL: 1000 PPM *Title III Section 313 Supplier Notification: This product contains toxic chemicals subject to the reporting requirements of Section 313 of the Emergency Planning and Community Right -to -Know Act of 1986 and of 40CFR372. This information must be included in all MSDS's that are copied and distributed for this material. (A) Dupont's Acceptable Exposure Limit (AEL) guidelines for 8 hour and 12 hour TWA, (B) Dupont's recommended STEL for 15 minute TWA. ** Information found in a report from the National Toxicology Program (NTP) on an inhalation study in rats and mice suggests that Tetrahydrofuran (THF) can cause tumors in animals. In the study the rats and mice were exposed to THF vapor levels up to 1800 PPM for two years (their lifetime), 6 hours/day, 5 days/week. Test results showed evidence of liver tumors in female mice and kidney tumors in male rats. No evidence of tumors was seen in female rats and male mice. There is no data linking Tetrahydrofuran exposure with cancer in humans. Page 54 © 2013 Spears® Manufacturing Company FG-3-1010 1 BULK SHIPPING INFORMATION (CONTAINERS GREATER THAN ONE LITER DOT Shipping Name: Adhesive DOT Hazard Class: 3 Identification Number: UN 1133 Packaging Group: II Label Requirement: Flammable Liquid SHIPPING INFORMATION FOR CONTAINERS LESS THAN ONE LITER DOT Shipping Name: Consumer Commodity DOT Hazard Class: ORM-D HMIS NFPA HAZARD RATING HEALTH: 2 2 0 - MINIMAL FLAMMABILITY: 3 3 1- SLIGHT REACTIVITY: 0 1 2 - MODERATE PROTECTIVE: 3 - SERIOUS EQUIPMENT: H 4-SEVERE H = Eye, Hand/Skin, Respiratory Protection and Impermeable Apron Section III - Physical Data Appearance: Red, medium syrupy liquid Specific Gravity @ 73° F ± 3.6° (20' C ± 2°): Typical 1.0 ± 0.040 Vapor Density (Air =1): 2.49 ODOR: Ethereal VAPOR PRESSURE (mm Hg.): 143mm Hg. based on first boiling component, THE @ 68' F (20° C) EVAPORATION RATE (BUAC =1): >1.0 BOILING POINT (° F/° C): 151° F (67° C) Based on first boiling component: THE t PERCENT VOLATILE BY VOLUME (%): Approx. 70 - 80% VOC STATEMENT: VOC as manufactured: 720 Grams/Liter. Maximum VOC emission per SCAQMD Rule 1168, Test Method 316A: 490 Grams/Liter. Section IV - Fire and Explosion Hazard Data FLASH POINT: -4° F (20' C) T.C.C. based on THE FLAMMABLE LIMITS (Percent by Volume) LEL: 2.0 UEL:11.8 FG-3-1010 © 2013 Spears® Manufacturing Company Page 55 FIRE EXTINGUISHING MEDIA: Ansul "Purple K" potassium bicarbonate dry chemical, carbon dioxide, National Aer-O-Foam universal alcohol resistant foam, water spray. SPECIAL FIRE FIGHTING PROCEDURES: Evacuate enclosed areas, stay upwind. Close orconfined quarters require self-contained breathing apparatus, positive, pressure masks or airline masks. Use water spray to cool containers, to flush spills from source of ignition and to disperse vapors. UNUSUAL FIRE AND EXPLOSION HAZARDS: Fire hazard because of low flash point and high volatility. Vapors are heavier than air and may travel to source(s) of ignition at or near ground or lower levels and flash back. Section V - Health Hazard Data PRIMARY ROUTES OF ENTRY: Inhalation, Skin Contact EFFECT OF OVEREXPOSURE ACCUTE: Inhalation: Severe overexposure may result in nausea, dizziness, headache. Can cause drowsiness, irritation of eyes and nasal passages. Skin Contact: Skin irritant. Liquid contact may remove natural skin oils resulting in skin irritation. Dermatitis may occur with prolonged contact. Skin Absorption: Prolonged or widespread exposure may result in the absorption of harmful amounts of material. Eye Contact: Overexposure may result in severe eye injury with corneal or conjunctival inflammation on contact with the liquid. Vapors slightly uncomfortable. Ingestion: Moderately toxic. May cause nausea, vomiting, diarrhea. May cause mental sluggishness. CHRONIC: Symptoms of respiratory tract irritation and damage to respiratory epithelium were reported in rats exposed to 5000 ppm THE for 90 days. Elevation of SGPT suggests a disturbance in liver function. The NOEL was reported to be 200 ppm. REPRODUCTIVE EFFECTS: N. AP. TERATOGENICITY: N. AP. MUTAGENICITY: N. AP. EMBROYOTOXICITY: N. AP. SENSITIZATION TO PRODUCT: N. AP. SYNERGISTIC PRODUCTS: N. AV. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Individuals with pre-existing diseases of the eyes, skin or respiratory system may have increased susceptibility to the toxicity of excessive exposures. Page 56 © 2013 Spears® Manufacturing Company FG-3-1010 EMERGENCY AND FIRST AID PROCEDURES Inhalation: If overcome by vapors, remove to fresh air and if breathing stopped, give artificial respiration. If breathing is difficult, give oxygen. Call physician. Eye Contact: Flush eyes with plenty of water for 15 minutes and call a physician. Skin Contact: Remove contaminated clothing and shoes. Wash skin with plenty of soap and water for at least 15 minutes. If irritation develops, get medical attention. Ingestion: Give 1 or 2 glasses of water or milk. Do not induce vomiting. Call physician or poison control center immediately. Section VI - Reactivity Stabili : Stable Conditions to Avoid: Keep away from heat, sparks, open flame and other sources of ignition. Incompatibility: (Materials to avoid) Caustics, ammonia, inorganic acids, chlorinated compounds, strong oxidizers and isocyanates. Hazardous Decomposition Products: When forced to bum, this product gives out carbon monoxide, carbon dioxide, hydrogen chloride and smoke. Hazardous Polymerization: Will not occur. Conditions To Avoid: Keep away from heat, sparks, open flame and other sources of ignition. Section VII - Spill Or Leak Procedures Steos To Be Taken In Case Material Is Released Or Spilled: Eliminate all ignition sources. Avoid breathing of vapors. Keep liquid out of eyes. Flush with large amount or water. Contain liquid with sand or earth. Absorb with sand or nonflammable absorbent material and transfer into steel drums for recovery or disposal. Prevent liquid from entering drains. Waste Disposal Method: Follow local, State and Federal regulations. Consult DISPOSAL EXPERT. Can be disposed of by incineration. Excessive quantities should not be permitted to enter drains. Empty containers should be air dried before disposing. Hazardous Waste Code: 214, Section Vlll - Special Protection Information Respiratory Protection (Specify type) Atmospheric levels should be maintained below established exposure limits contained in Section ll. If airborne concentrations exceed those limits, use of a NIOSH approved organic vapor cartridge respirator with full face -piece is recommended. The effectiveness of an air purifying respirator is limited. Use it only for a single short-term exposure. For emergency and other conditions where short-term exposure guidelines may be exceeded, use an approved positive pressure self-contained breathing apparatus. FG-3-1010 © 2013 Spears® Manufacturing Company Page 57 Ventilation - Use only with adequate ventilation. Provide sufficient ventilation in volume and pattern to keep contaminants below applicable exposure limits set forth in Section II. Use only explosion proof ventilation equipment. Protective Gloves: PVA coated Eye Protection: Splash proof chemical goggles Other Protective Eguioment And Hygienic Practices: Impervious apron and a source of running water to flush or wash the eyes and skin in case of contact. Section IX - Special Precautions Precautions To Be Taken In Handling And Storing: Store in the shade between 40- F '- 90- F (4- C - 32.5° C). Keep away from heat, sparks, open flame and other sources of ignition. Avoid prolonged breathing of vapor. Use with adequate ventilation. Avoid contact with eyes, skin and clothing. Train employees on all special handling procedures before they work with this product. Other Precautions: Follow all precautionary information given on container label, product bulletins and our solvent cementing literature. All material handling equipment should be electrically grounded. The information contained herein is based on data considered accurate. However, no warranty is expressed or implied regarding the accuracy of this data or the results to be obtained from the use thereof. Page 58 © 2013 Spears® Manufacturing Company FG-3-1010 NOTES FG-3-1010 © 2013 Spears® Manufacturing Company Page 59 NOTES Page 60 © 2013 Spears® Manufacturing Company FG-3-1010 NOTES FG-3-1010 © 2013 Spears® Manufacturing Company Page 61 NOTES Page 62 © 2013 Spears® Manufacturing Company FG-3-1010 S� PfARS SPEARS® MANUFACTURING COMPANY CORPORATE OFFICE 15853 Olden St., Sylmar, CA 91342 PO Box 9203, Sylmar, CA 91392 (818) 364-1611 • www.spearsmfg.com PACIFIC SOUTHWEST 15860 Olden St Sylmar (Los Angeles), CA 91342 (818) 364-1611 • (800) 862-1499 Fax (818) 367-3014 ROCKY MOUNTAIN 4880 Florence St. Denver, CO 80238 (303) 371-9430 • (800) 777-4154 Fax (303) 375-9546 NORTHEAST 590 Industrial Dr., Suite 100 Lewisberry (Harrisburg), PA 17339-9532 (717) 938-8844 • (800) 233-0275 Fax (717)938.6547 MIDWEST 1 Gateway CL, Suite A Bolingbrook (Chicago), IL 60440 (630) 759-7529 • (800) 66245330 Fax (630) 759-7515 NORTHWEST 4103 C St. NE Suite 200 Auburn (Seattle), WA 98002 (253)9394433•(800)347-7327 Fax (253) 939-7557 UTAH 5395 West 1520 South Salt Lake City, UT 84104 (303) 371-9430 • (800) 777-4154 Fax (303) 375-9546 SOUTH CENTRAL 1000 Lakeside Parkway Flower Mound, TX 75028 (469)528-3000•(800)441-1437 Fax (469) 528-3001 FLORIDA 9563 Parksouth Court Orlando,FL 32837 (407) 843-1960 • (800) 327-6390 Fax (407) 425.3563 SOUTHEAST 4205 Newpolnt PI., Suite 100 Lawrenceville (Atlanta), GA 30043 (678)985-1263•(800)662-6326 Fax (678) 985-5642 INTERNATIONAL SALES 15853 Olden St. Sylmar (Los Angeles), CA 91342 (818) 364-1611 • Fax (818) 898-3774 Authorized Distributor 0 0 FG-3-1010 © 2013 Spears® Manufacturing Company Page 63 ... DO IT CORRECTLY! Failure to follow instructions can result in thread breaks from too much tape, difficult assembly from not enough, or leaks due to exposed starting threads. DO NOT USE TAPE & PASTE! DO NOT USE with Gasket Sealed Head Adapters USE a TFE tape with a min. thickness of 2.5 mil. Cover male starting threads to prevent seizing. • Wrap tape in direction of threads. — For Regular Head Adapters, use 2 to 3 wraps. Tighten to specified torque (see front cover). — For Female Adapter Transitions to metal pipe, use ONLY 5 to 5-1/2 wraps. • Joint Assembly — tighten 1-2 turns beyond finger tight. DO NOT back up. DO NOT over tighten! SPEARS® MANUFACTURING COMPANY 15853 Olden Street, Sylmar CA 91342 PO Box 9203, Sylmar, CA 91392 (818) 364-1611 www.spearsmfg.com 0 Copyright 2013 Spears° Manufacturing Company All Rights Reserved. Printed in the United States of America 01/13. FG-3-1010 FlameGuard' CPVC FIRE SPRINKLER PIPING PRODUCTS Mnilamhar NMI; s� =�\°N CER LPCB ° w z o UAAS O a M ixr FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS The information contained in this section is based on current information and Product design at the time of publication and is subject to change without notification. Our ongoing commitment to product improvement may result in some variation. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability for particular applications or results to be obtained therefrom. For verification of technical data or additional information not contained herein, please contact Spears" Technical Services Department [West Coast: (818) 364-1611—East Coast: (678) 985-1263]. General Information RECOMMENDATIONS FOR INSTALLERS AND USERS: Plastic piping systems should be ENGINEERED, INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS AND PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the installer and/or user prior to installation of a plastic piping system. All Installation and maintenance personnel should be trained in the proper handling and installation requirements and precautions of plastic piping systems. PRIOR TO ASSEMBLY, all piping system components should be inspected for damage or irregularities. Mating components should be checked to assure that tolerances and engagements are compatible. Do not use any components that appear irregular or do not fit properly. Contact the appropriate manufacturer of the component product in question to determine usability. Consult all applicable codes and regulations for compliance prior to installation. Installation must be made in accordance with Spears" Manufacturing Company FlameGuard® CPVC Fire Sprinkler Piping Products Installation Instructions - FG-3 NOTE — Individual or group instruction in correct solvent welding procedures is available by contacting your local distributor or your servicing Spears" Regional Distribution Center. SOLVENT CEMENT CONNECTIONS — Spears° Manufacturing Company recommends the use of Spears° FS-5 One Step solvent cement for joining Spears" products. Use of solvent cementing products not approved for CPVC fire sprinkler systems, or failure to follow installation instructions will automatically void the warranty. THREADED CONNECTION — Spears° Manufacturing Company recommends the use of Spears° BLUE 75TM Thread Sealant. This product has been tested by Spears° and the sealant manufacturer for compatibility with the Spears" CPVC fire sprinkler products. Consult the sprinkler head manufacturer before using this product. WARNING: OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN THE CPVC OR OTHER FITTING COMPONENTS. Care must be taken to avoid over torquing - generally 1 to 2 tums beyond finger tight is all that is required to make up a threaded connection. Factory testing has indicated 10-25 ft. lbs. of torque is adequate to obtain a leak free seal. GASKET SEALED THREAD CONNECTIONS —This type of connection can only be made with Spears@ TorqueSafeTM, SofTorqueTM or QuickTorqueTM style Gasket Sealed Female Sprinkler Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER. Tape or paste may impair proper sealing and function. Testing has shown that hand tight until snug for the TorqueSafeTM adapter and finger tight plus 1-turn is all that is needed to seal this special connection. Sprinkler heads in these specialty fittings can then be additionally tightened clockwise to bring sprinkler frames into desired alignment without stressing the fitting. See specific adapter instructions in package for details. GripLocTM CONNECTIONS — This type of connection can only be made with Spears@ GdpLocTM Couplings or Repair Couplings. DO NOT USE ANY TYPE OF SOLVENT CEMENT OR SEALANT WHEN INSTALLING THIS TYPE OF CONNECTION. Uses an internal stainless steel gripper ring with an internal elastomer gasket seal. Connection allows immediate system use. See specific instructions in package for details. Installation Training Available - Contact Spears° Technical Services for Details FlameGuardql Products must be installed in accordance with Spears° FlameGuard° CPVC Fire Sprinkler Piping Products Installation Instructions, National Fire Protection Association Standards 13,13R,13D, and in accordance with local codes. Code requirements and field conditions may differ. It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements. Dimension Reference G = (LAYING LENGTH) Intersection of center lines to bottom of socket/thread; 90' elbows, tees, crosses; ± 1/32 inch. M = Outside diameter of socket/thread hub; ± 1/16 inch. H = Intersection of center lines to face of fitting; 90° elbows tees, crosses; ± 1/32 inch. N = Socket bottom to socket bottom; couplings; ± 1/16 inch. J = Intersection of center lines to bottom of socket/thread; 45' elbows; ± 1/32 inch Q = Width of flats; ±1/16 inch. L = Overall length of fittings; ± 1/16 inch. W = Height of cap; ± 1/16 inch. CPVC FIRE SPRINKLER PIPE SDR 13.5 (ASTM F 442) Part Number Nominal Size Average O.D. Average I.D. Approx. Weight Lbs.IFt. Inches (mm) Inches (mm) Inches (mm) CP-007 314 (19.1) 1.050 (26.7) .874 (22.5) 0.168 CP-010 1 (25.4) 1.315 (33.4) 1.101 (28.2) 0.262 CP-012 1-1/4 (31.8) 1.660 (42.2) 1.394 (35.6) 0.418 CP-015 1-1/2 (38.1) 1.900 (48.3) 1,598 (40.7) 0.548 CP-020 2 (50.8) 2.375 (60.3) 2.003 (50.9) 0.859 CP-025 2-1/2 (63.5) 2.875 (73.0) 2.423 (61.5) 1.257 CP-030 3 (76.2) 3.500 (88.9) 2.950 (75.0) 1.867 "Lead Free" low lead certification — unless other wise specified, all Spears" FlameGuard° fittings specified here -in are certified by NSF International to ANSI/NSF° Standard 61, Annex G and is in compliance with California's Health & Safety Code Section 116825 (commonly known as AB1953) and VermontAct 193. Weighted average lead content <=0.25%. Spears° PVC and CPVC Pipe, Fittings and Valves have always been lead-free and Certified by NSF International for use in potable water systems. Spears° offers a wide range of lead-free specialty fittings and transition adapters for plumbing applications. However, certain brass threaded adapter fittings for applications that are not intended to convey water for human consumption through drinking or cooking are still produced and available. SPEARS® MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS on SOCKET DIMENSIONS SCH 40 -ASTM F438 �'- C SCH 80 -ASTM F439 A Size Socket Socket Tolerance SCH 40 Minimum SCH 80 Minimum Entrance A Bottom B Socket Length C Socket Length C 3/4 1.058 1.046 ± .004 .719 1.000 1 1.325 1.130 ±.005 .875 1.125 1-1/4 1.670 1.655 ±.005 .938 1.250 1-1/2 1.912 1.894 ±.006 1.094 1.375 2 2.387 2.369 ± .005 1.156 1.500 2-1/2 2.889 2.868 ±.007 1.750 1.750 3 3.516 3.492- ± .008 1.875 1.875 TEE Socket x Socket x Socket I I - - j- L tH�G -►I Part Number Size G H L M Approx. Wt. (Lbs.) 4201-007 3/4 9/16 1-1/2 2-31/32 1-5/16 .11 4201-010 1 718 1-13/16 3-5/8 1-5/8 .20 4201-012 1-1/4 15/32 2-3/32 4-7/32 2 .29 4201-015 1-1/2 1-5/32 2-9/16 5-3132 2-11/32 .54 4201-020 2 1-13/32 2-15/16 5-7/8 2-7/8 .86 4201-025 2-1/2 1-23/32 3-1/2 7 3-15/32 1.62 4201-030 3 2-1/16 3-31/32 7-15/16 4-5/32 2.53 REDUCING TEE -rM1 Socket x Socket x Socket I M M M2 1 G1 1 G2 H H2 L Part Approx. Size G G1 G2 H 1-11 H2 L M M1 M2 Number Wt. (Lbs.) 4201-102 3/43/41 3/4 3/4 3/4 1-11/16 1-25/32 1-11/16 3-13/32 1-5/16 1-21/32 15/16. .13 4201-125 1x314314 23/32 7/8 23/32 1-25/32 1-13/16 1-21/32 3-7/16 1-19/32 1-11/32 1-5/16 .16 4201-126 10141 23/32 23132 3/4 1-27/32 1-27/32 1-3/4 3-19/32 1-5/8 1-5/8 1-5116 .17 4201-131 lxlx3/4 11/16 13116 11116 1-13116 1-13/16 1 1-13/16 3-5/8 1-5/8 1-5/16 1-5/8 .17 4201-157 1-1/410/4 11/16 1-1/32 11/16 1-15/16 2-1/32 1 1-13/16 3-25/32 2-3/32 1-13/32 1-23/32 .32 MADE IN THE U.S.A. 7 wo FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS REDUCING TEE (continued) r--►fM1 Socket x Socket x Socket T HI M tM2 G1 G2 H2 LHL Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4201-158 1-1/4xlxl 27/32 29/32 25/32 2-1/16 2-1/32 1-29/32 3-15/16 1-31/32 1-5/8 1-518 .24 4201-159 1-114xlxl-1/4 31/32 31/32 31/32 2-7/32 2-7/32 2-3/32 4-11/32 2-1/8 2-1/8 1-23/32 .36 4201-167 1-1/41-1/43/4 21/32 1 21/32 1-29/32 2 1-29132 3-13116 2 1-5/16 2 .22 4201-168 1-1/41-1/41 13/16 1 1 13/16 2-1/16 1 2-118 2-1/16 1 4-1/8 1-31/32 1 1-21/32 1-31/32 1 .24 4201-169 1-1/4x1-114x1-112 1-1/8 15116 1-1/8 2-3/8 2-11/32 2-3/8 4-3/4 2-3/32 2.11132 2-3/32 .51 4201-201 1-1/2xl-1/4x314 11116 1 1/4 2-1/16 2 1-15/16 4 2-5/16 1-3/8 2-1/16 .41 4201-202 1-1/2xl-1/4xl 27/32 1-1/32 1 2-7/32 2-5/32 2-1/4 4-15/32 2-5/16 1-11/16 2-1/16 .42 4201-210 1-1/2xl-112x3/4 11/16 1-1/32 11/16 2-1/16 2-1/32 2-1/16 4-5/32 2-11/32 1-13/32 2-11/32 .39 4201-211 1-112xl-112xl 13/16 1-3/32 13/16 2-3/16 2-1/4 2-3/16 4-3/8 2-11/32 1-3/4 2-11/32 .41 4201-212 1-112xl-1/2xl-1/4 1-1/32 1-3/32 1 1-1/32 2-13/32 1 2-11/32 2-13/32 1 4-13/16 2-11/32 1 2-1/8 2-11/32 1 .49 4201-213 1-1/2xl-112x2 1-9/32 1-5/32 1-9132 2-21/32 2-21/32 2-21132 5-11/32 2-11132 2-29/32 2-11/32 1 .64 4201-248 2x2x314 11/16 1-13/32 11/16 2-7/32 2-7/16 2-7/32 4-7116 2-27/32 1-3/8 2-27132 .52 4201-249 2x2xl 27/32 1-13/32 27/32 2-11/32 2-9/16 2-11/32 4-23/32 2-7/8 1-3/4 2-7/8 .58 4201-250 WA-1/4 1-1/32 1-11/32 1-1/32 2-17/32 2-19/32 2-17/32 5-3/32 2-7/8 2-3/32 2-7/8 .65 4201-251 WA-1/2 1-5/32 1-7/16 1-5/32 2-11/16 2-13132 2-11/16 5-318 2-7/8 2-13/32 2-7/8 .79 4201-289 2-102-112A 27/32 1-23132 1 27/32 2-5/8 1 2-27/32 2-5/8 1 5-1/4 3-17/32 1 1-23/32 3-17132 1.01 4201-290 2-1/2x2-101-1/4 1-3/32 1-23132 1-1/32 2-13/16 2-31/32 2-13/16 5-21/32 3-9/16 2-3132 3-9/16 1 1.13 4201-291 2-1/2x2-112xl-1/2 1-3/16 1/2 1-3/16 2-15116 1-7/8 2-15/16 5-7/8 3-15/32 2-11/32 3-15/32 1.26 4201-292 2-102-1/2x2 1-13/32 1-5/8 1-13/32 3-3/16 3-1/8 3-3/16 6-3/8 3-1/2 2-7/8 3-1/2 1.37 4201-335 3x3xl 7/8 1-15/16 7/8 2-3/4 3-1116 2-3/4 5-15/32 4-3/16 1-23/32 4-3/16 1.26 4201-336' 3x3xl-1/4 1-3/8 1-3/4 1-3/8 3-5/16 3-1/2 3-5/16 6-5/8 4-1/8 2-7/8 4-1/8 1.94 4201-337 3x3xl-1/2 1-5/32 1 2-1116 1 1-5/32 1 3-1/32 1 3-7/16 1 3-1/32 1 6-3/32 4-3/16 1 2-3/8 1 4-3/16 1.46 4201-338 3x3x2 1-7116 1-13/16 1 1-7/16 1 3-5/16 3-5/16 3-5/16 1 6-19/32 4-3/16 L 2-7/8 1 4-3/16 1.69 4201-339 &W-112 1 1-3/4 1-31/32 1 1-3/4 1 3-5/8 3-23/32 3-5/8 1 7-1/4 4-3/16 1 3-17/32 1 4-3/16 1 2.11 ' Branch Outlet Sized with Bushing TorqueSafeTM SPRINKLER HEAD TEE Gasket Sealed Brass Thread Insert Style Socket x Socket x Gasket Fipt H1 With Elastomer Seal - Use NO Thread Sealant T!tf G G2 H H2 L Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101 G 3/43/41/2 7/16 1-3/16 7116 1-7/16 1-7116 1-17/32 2-29/32 1-3/8 1-3/8 1-3/8 .22 4202-124 G 10141/2 7/16 1-11/32 9/16 1-9/16 1-11/16 1-9116 3-1/8 1-11/16 1-3/8 1-3/8 .26 4202-130 G 1x1xl/2 7/16 1-11/32 7/16 1-9/16 1-11/16 1-9/16 3-1/8 1-23/32 1-3/8 1-23/32 .28 4202-131 G 1x1x314 17/32 15/16 17/32 1-11/16 1-5/8 1-11116 3-11/32 1-23132 1-9/16 1-23/32 .31 4202-166 G 1-1/4x1-1/4x112 7/16 1-5/8 7/16 1-11/16 1-15/16 1-11/16 3-3/8 2-1/16 1-3/8 2-1/16 .34 4202-209 G 1-101-10112 1/2 1-13/16 1/2 1-7/8 2-3/32 1-7/8 3-3/4 2-11/32 1-3/8 2-11/32 .41 4202-247 G 2x2x112 112 2-1/16 112 2 2-11/32 2 4-1/32 2-27/32 1-318 2-27/32 .54 Not intended to convey or dispense water for human consumption through drinking or cooking SPEARS° MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El SPRINKLER HEAD TEE M, Brass Thread Insert Style G, Socket x Socket x Fipt -- -1- H1 - MII2 lM G G2 II�f-H L H2 Part Number Size G G1 I G2 I H H1 H2 I L M I M1 I M2 I Approx. Wt. (Lbs.) 4202-010 lxlx1 1 21/31 1 1-1/8 1 21/31 1 1-25/32 1 1-29/32 1 1-25132 1 3-19/32 1 1-23132 1 1-23/32 1 1-23/32 1 .37 Not intended to conveyor dispense water for human consumption through drinking or cooking SofTorqueTM SR REDUCING TEE Gasket Sealed Special Reinforced Plastic Thread Style Socket x Socket x SR Fipt M1 With Elastomer Seal - Use NO Thread Sealant I ?il -- •— —LF H H2 I� G2 L Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101GSR 3/43/41/2 7/16 1-1/2 7/16 1-3/8 1-7/8 1-3/8 2-3/4 15/16 1-3/8 1-5116 .16 4202-130GSR 1x1x1/2 7/16 1-5/8 7/16 1-1/2 2 1-1/2 1 3 1-518 1-3/8 1-5/8 .20 SPRINKLER REDUCING HEAD TEE Brass Thread Insert Style Socket x Socket x Fipt M, . H1 M - - M2 G1 GH H2 2 L Part Number Size G 131 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101 3143/4112 7/16 1-1/16 7/16 1-15/32 1-5/8 1-15/32 2-29/32 1-13/32 1-3/16 1-13/32 .20 4202-124 1041/2 7/16 1-11/32 9/16 1-9/16 1-11/16 1-9/16 3-1/8 1-11/16 1-3/8 1-3/8 .26 4202-130 1x1x1/2 7/16 1-7/32 7/16 1-9/16 1-25/32 1-9/16 3-1/8 1-3/4 1-3/16 1-3/4 .26 4202-156 1-1/41A/2 7/16 1-7/16 9/16 1-11/16 2-1/32 1-11/16 3-3/8 2-3/32 1-3116 1-23132 .30 4202-166 1-1/41-1/41/2 7/16 1-15132 7/16 1-11/16 2-1/32 1-11/16 1 3-3/8 2-3/32 1 1-3/16 2-3132 .31 4202-199 1-112A-1/4112 1/2 1-5/8 9/16 1-7/8 2-3/16 1-13/16 3-11/16 2-11132 1-3/16 2-1/16 .37 4202-209 1-112x1-1/2x1/2 1/2 1-518 1/2 1-7/8 2-3/16 1-7/8 3-314 2-11/32 1-3/16 2-11/32 .38 4202-237 2xl-1/2x112 1/2 1-27/32 17/32 2 2-7116 1-29/32 3-15/16 2-7/8 1-3/16 2-11/32 .47 4202-247 2x2x112 1/2 1-7/8 1/2 2 2-7/16 2 4-1/32 2-27/32 1-3/16 2-27/32 .50 Not intended to convey or dispense water for human consumption through drinking or cooking MADE IN THE U.S.A. El FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS SPRINKLER HEAD TEE Special Reinforced Plastic Thread Style Socket x Socket x SR Fipt Part Number Size G G1 G2 H H1 H2 I L I M I M1 I M2, Approx. Wt. (Lbs.) 4202-010SR 1x1x1 21132 3/4 21/32 1-25/32 1-5/8 1-25/32 3-19/32 1-23/32 1-11/16 1-23/32 .26 SPRINKLER REDUCING HEAD TEE Special Reinforced Plastic Thread Style Socket x Socket x SR Fipt I. M1 ►I "' M2 G1 M PHH L J Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101SR 3/43/41/2 19/32 25/32 19/32 1-19/32 1-7/16 1-19/32 3-7/32 1-13/32 1-3/16 1-13/32 .15 4202-124SR 1014112 7/16 29132 9116 1-19/32 1-5/8 1-9/16 3-5/32 1-23/32 1-3/16 1-17/32 .19 4202-130SR 1x1x1/2 7/16 29/32 7/16 1-9/16 1-5/8 1-9/16 3-1/8 1-23/32 1-3/16 1-23/32 .20 4202-156SR 1-114xlxl/2 15/32 1-5/32 19132 1-23/32 1-7/8 1-23/32 3-13/32 2-3/32 1-3/16 1-23/32 .26 4202-166SR 1-1/41-1/41/2 7/16 1-1/8 1 7/16 1-11/16 1 1-27/32 1-11/16 1 3-3/8 2-3/32 1-3/16 2-3/32 .26 4202-168SR 1-1/4x1-1/4x1 27/32 1-1/32 27/32 2-3/32 1-29/32 2-3/32 4-7/32 1 2-3/32 1-11/16 2-3/32 .34 4202-199SR 1-1/2xl-1/4xl/2 9/16 1-9/32 17132 1-15/16 2 1-25/32 3-23/32 2-11/32 1-3/16 2-3/32 .33 4202-209SR 1-112x1-1/2x112 1/2 1-1/4 112 1-7/8 1-31/32 1-7/8 3-3/4 2-11/32 1-3/16 2-11132 .35 4202-211SR 1-1/2xl-1/2xl 27/32 1-7/32 27/32 2-7/32 2-1/8 2-7/32 4-15/32 2-11/32 1-23/32 2-11132 .44 4202-237SR 2xl-1/2xl/2 23132 1-9/16 3/8 2-7/32 2-9/32 1-3/4 3-31/32 2-7/8 1-3/16 2-11/32 .45 4202-247SR 2x2x1/2 1/2 31/32 1/2 2 1-11116 19/32 4 2-7/8 1-3116 2-7/8 .48 4202-287SR 2-1/2x2-112xl/2 17/32 1-3/4 17/32 2-9/32 2-112 2-9/32 4-19/32 3-1/2 1 1-7/32 3-1/2 1 78 SOFTORQUETM SR SPRINKLER HEAD TEE i Gasket Sealed SpecialTI Reinforced Plastic Thread Style Socket x SR Fipt x Socket M _ _ _ i _ _ M G I j Stainless Steel Collar With Elastomer Seal - Use L G G2 NO Thread Sealant H H2 Part Number Size G G1 G2 H H1 H2 I L M M1 M2 Approx. Wt. (Lbs.) 4203-122GSR 1xl/2x1 1 13/16 13/16 1-1/2 1-27/32 1-27/32 1 1-31/32 3-13/16 1 1-5/8 1-5/8 1-3/8 .22 5 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS TorqueSafeTM SPRINKLER HEAD TEE M1 Gasket Sealed Brass Thread Insert Style Socket x Gasket Fipt x Socket G1 ' � H1 M __ -+__ M2 With Elastomer Seal - Use NO Thread Sealant G-- G2 H H2 L Part Number I Size I G I G1 I G2 H I H1 I H2 I L M M1 M2 Approx. Wt. Lbs.) 4203-122 G I 1xl/2x1 1 19/32 1 13/16 1 1-13/32 1 1-19/32 1 1-27/32 1 1-3/4 1 3-11/32 1 1-5/8 1 1-5/8 1 1-3/8 .25 Not intended to convey or dispense water for human consumption through drinking or cooking SPRINKLER HEAD TEE M1 Brass Thread Insert Style Socket x Fipt x Socket I G1 F—f H1 M M2 H G2 H2 L Part Number Size I G I G1 G2 H H1 H2 I L I M M1 M2 Approx. Wt. (Lbs.) 4203-122 1 lxl/2x1 1 23/32 1 3/4 1 1-1/4 1 1-5/8 1 1-5/8 1-15/16 1 3-1/2 1 1-23/32 1 1-23/32 1 1-3/16 1 .25 Not intended to convey or dispense water for human consumption through drinking or cooking SPRINKLER HEAD TEE Special Reinforced Plastic Thread Style Socket x SR Apt x Socket Part Number Size G G1 G2 H H1 H2 I L M M1 M2 Approx. Wt. (Lbs.) 4203-122SR 1xl/2xl 27/32 23/32 1-3/32 1-23/32 1-5/8 1-25/32 1 3-13/32 1-3/4 1-3/4 1-3/16 .21 MADE IN THE U.S.A. 6 El FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS STREET TEE Spigot x Socket x Socket M1 M2 O.D. H1 ZG2 G1 G H --►tom H2 L Part Number Size G G1 G2 H H1 H2 L M1 M2 Approx. Wt. (Lbs.) 4244-007 3/4 13/16 27/32 27/32 1-13/16 1-7/8 1-7/8 3-5/8 1-13132 1-13/32 .16 4244-010 1 1-5/32 1-1/32 1-1/32 2-1/8 1-29/32 1-29132 4-3/16 1-3/4 1-3/4 .27 4244-012 1-1/4 1-1/4 1 1 2-7/16 2-9/32 2-9/32 4-27/32 2-3/32 2-3/32 .42 4244-015 1-1/2 1-13/16 1-1/8 1-1/8 2-7/8 2-9/16 1 2-9/16 1 5-11/32 2-11/32 2-11132 .56 4244-020 2 1-23/32 1-7/16 1-13/32 1 3-1/4 2-15/16 1 2-15/16 1 6-5/32 2-7/8 1 2-7/8 .84 900 ELBOW Socket Socket H G i•. M Part Number Size G H M Approx. Wt. (Lbs.) 4206-007 314 9/16 1-1/2 1-5/16 .07 4206-010 1 3/4 1-5/8 1-5/8 -.11 4206-012 1-1/4 15/16 2-3116 2 .22 4206-015 1-1/2 15/32 2-17132 2-3/8 .41 4206-020 2 1-13132 2-29/32 2-7/8 .62 4206-025 2-1/2 1-15/32 3-3/8 3-1/2 1.15 4206-030 1 3 1-5132 3-3/32 4-3/16 1.83 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El SIDE OUTLET ELBOW Socket x Socket x Socket I- -- M G t-' H Part Number Size G H M Approx. Wt. (Lbs.) 4213.007 3/4 27/32 1-19/32 1-5/16 .09 4213-010 1 13/16 1-7/8 1-5/8 .18 REDUCING 900 ELBOW Socket x Socket H1 G1- G t I H M Part Number Size G G1 H H1 M M1 Approx. Wt. Lbs. 4206.131 1x314 21/32 13116 1-25/32 1-13/16 1-19132 1-5/16 .11 TorqueSafeT"' 90° SPRINKLER HEAD ELBOW Gasket Sealed Brass Thread Insert Style Socket x Gasket Fipt With Elastomer Seal - Use NO Thread Sealant H1 G1- G _ — M1 H M Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101 G 3/4x1/2 9/16 1-7/32 1-13/32 1-17/32 1-13/32 1-3/8 .19 4207-130 G 1x1/2 7/16 1-3/16 1-9/16 1-11/16 1-23/32 1-3/8 .23 4207-166 G 1-1/4x1/2 15/32 1-19/32 1-15/16 1-11/16 2-3132 1-3/8 .25 Not intended to convey or dispense water for human consumption through drinking or cooking MADE IN THE U.S.A. Qr,P,AR, FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS SPRINKLER HEAD 900 ELBOW Brass Thread Insert Style H1 Socket x Fipt G1 G — - M1 H I II �I M - ►1 FAH-- Part Number Size G G1 H1 M M1 Approx. Wt. (Lbs.) 4207-101 3/41 /2 1 /2 1-3/32 1-112 1-5/8 1-13/32 1-3/16 .17 4207-130 1x1/2 7/16 1-7/32 1-19132 1-25/32 1-23/32 1-3/16 .21 4207-131 1 x3/4 17/32 1-11 /32 1-21132 1-31 /32 1-23/32 1-3/8 .25 4207-166 1-1/41/2 15/32 1-17/32 1-11/16 1-15/16 2-3/32 1-17/32 .33 Not intended to convey or dispense water for human consumption through drinking or cooking SofforqueTM SR 900 ELBOW SPRINKLER HEAD ADAPTER Gasket Sealed Special Reinforced Plastic Thread Style Socket x SR Apt G With Elastomer Seal -Use NO Thread Sealant —•II G H i �I I h-- M --H Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101GSR 3/4xl/2 7/16 1-17/32 1-3/8 1-27/32 1-11/32 1-3/8 .17 4207-130GSR 1x1/2 7/16 1-11116 1-1/2 2 1-21/32 1-3/8 .19 4207-166GSR 1-1/4xl/2 7/16 1-7/8 1-11/16 2-7/32 2 1-3/8 .22 SPRINKLER HEAD 900 ELBOW Special Reinforced Plastic Thread Style H1 --►i Socket x SR Fipt G1 G .T - M1 H M —.1 I Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101SR 314x1/2 11/32 13/16 1-15/32 1-1/2 1-13/32 1-3/16 .14 4207-130SR 1x112 7116 718 1-9/16 1-5/8 1-23/32 1-3/8 .20 4207-131SR 1x314 1/2 718 1-5/8 1-9/16 1-23/32 1-3/8 .16 4207-166SR 1-114x112 13/32 1-1/32 1-21/32 1-23/32 1 2-3132 1-7/32 .19 SPEARS® MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS El 900 STREET ELBOW Spigot x Socket H1,1 c1 G M1 H L �-- .I- PIPE O.D. Part Number Size G G1 H H1 M1 Approx. Wt. (Lbs.) 4209-007 3/4 29/32 19/32 1-15/16 1-11/16 1-13/32 .12 4209-010 1 1-9/32 23/32 2-13/32 1-27/32 1-3/4 .21 4209-012 1-1/4' 1-9116 27/32 2-13/16 2-3/32 2-3/32 .32 4209-015 1-112 1-15/32 1-3116 2-27/32 2-9/16 2-11/32 .42 4209-020 2 1-23/32 1-3/8 3-7132 2-15116 2-27/32 .65 22-1/20 ELBOW Socket x Socket &-M Part Number Size H J M Approx. Wt. (Lbs.) 4216-007 314 1-3/16 7/32 1-13/32 .09 4216-010 1 1-3/8 9/32 1-25/32 .14 4216-012 1-1/4 1-1/2 5116 2-3/32 .20 4216-015 1-1/2 1-7/16 13132 1-3/8 .19 4216-020 2 1-7/8 3/8 2-27/32 .43 4216-030 3 2-3/8 1/2 4-5132 1.00 22-1/20 STREET ELBOW Spigot x Socket M1 H1 J1 H J PIPE O.D. Part Number Size H H1 J J1 M1 Approx. Wt. (Lbs.) 4242-007 314 1-1/4 1-1/2 1/4 1/2 1-3/8 .08 4242-010 1 1-7/16 1-11132 5116 7132 1-23/32 .14 4242-012 1-1/4 1-9116 1-25/32 17/32 11/16 2-1/16 .21 4242-015 1-1/2 1-13132 1-23/32 1/2 11/32 2-11132 .28 4242-020 2 1-29/32 2-1/8 7/32 5/8 2-7/8 .42 4242-025 2-1/2 2-1/8 2-1/4 13/32 1/2 3-1/2 .68 4242-030 3 2-13/32 2-13/32 9/16 17132 4-5/32 .99 MADE IN THE U.S.A. • 10 FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS 450 ELBOW Socket x Socket i H I I`— M —►I Part Number Size H J M Approx. Wt. (Lbs.) 4217-007 3/4 1-5/16 5/16 1-5/16 .07 4217-010 1 1-13/32 3/8 1-5/8 .11 4217-012 1-1/4 1-5/8 3/8 2-5/32 .21 4217-015 1-1/2 1-27132 15/32 2-11/32 .32 4217-020 2 2-1/8 21/32 2-718 .48 4217-025 2-1/2 2-17/32 3/4 3-112 .88 4217-030 3 2-29/32 29132 4-5/32 1.17 CROSS Socket x Socket x Socket x Socket G1 M - L1 H1 G H L Part Number Size G G1 H H1 L L1 M Approx. Wt. (Lbs.) 4220-007 314 518 5/8 1-21/32 1-21/32 3-5116 3-5116 1-13/32 .22 4220-010 1 3/4 3/4 1-5/8 1-5/8 3-1/4 3-1/4 1-23132 .20 4220-012 1-1/4 1-1/8 1-1/8 2-3/8 2-3/8 4-3/4 4-3/4 2-3/32 .63 4220-015 1-1/2 1-7/32 1-7/32 2-5/8 12-5/8 5-7/32 5-7/32 2-3/8 .80 4220-020 2 1-1/2 1-1/2 3 3 6 6 3 1.43 4220-025 2-1/2 1-11116 1-11/16 3-7/16 3-7/16 6-7/8 6-7/8 3-17/32 2.16 4220-030 3 2-3/32 2-3/32 3-31/32 3-31/32 7-15/16 7-15/16 4-7116 3.37 SPEARS" MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS SPEARS 450 STREET ELBOW Spigot x Socket H1 J1 M1 d IH L I= ►PIPE O.D. Part um er Size H Hl i ill mi Approx. s. 4227-010 1 1-1/2 1-5/ 16 1 /2 1 /4 1-5/8 .10 4227-012 1-1/4 1-25/32 1-9/16 9/16 11/32 1-31/32 .16 4227-015 1-1/2 2-1/32 2-1/8 19132 25132 2-11/32 .29 4227-020 2 2-5/16 1-15/16 25/32 13132 2-7/8 .44 REDUCING CROSSr Socket x Socket x Socket x Socket ►! Ml I H1 M — — — L1 L TI G1 I G H L Part Number Size G G1 H H1 L L1 M M1 Approx. Wt. (Lbs.) 4220-131 lx314 23/32 5/8 1-5/8 1-5/8 3-1/4 3-1/4 1-7/8 1-1/2 .31 4220-167 1-1/4x3/4 1-1/16 23/32 2-1/16 1-31/32 4-3/32 3-31/32 2-1/16 1-13/32 .35 4220-210 1-1120/4 11/16 1-5/32 2-3/32 2-3/16 4-3/16 4-11/32 2-3/8 1-13/32 .42 4220-248 20/4 1 11/16 1 1-7/16 2-7/32 2-7/16 4-13/32 4-7/8 2-29/32 1-13132 .56 4220-289 2-1/2x1 1 29132 1 1-3/4 2-11/16 2-7/8 5-11/32 5-3/4 3-1/2 1-3/4 .98 COUPLING Socket x Socket ---- N 7 --- M Part Number Size L M N Approx. Wt. (Lbs.) 4229-007 3/4 2-1/8 1-5/16 3/16 .05 4229-010 1 2-3116 1-5/8 3/32 .08 4229-012 1-1/4 2-19/32 2 3/32 .13 4229-015 1-1/2 2-7/8 2-11132 3132 .22 4229-020 2 3-1/8 2-7/8 1/8 .33 4229-025 2-1/2 3-11/16 3-15/32 3116 .48 4229-030 3 4 4-3116 1/4 .89 MADE IN THE U.S.A. 12 El FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS REDUCER COUPLING Socket x Socket T- -T IM -- — -- M1 L Imo--- L Part Number Size L M M1 N Approx. Wt. (Lbs.) 4229-131 1x3/4 2-3/8 1-23/32 1-13/32 7/32 .10 4229-167 1-1143/4 2-19/32 2-3/32 1-5/8 11/32 .17 4229-168 1-1141 2-11/16 2-3/32 1-23/32 5/16 .18 4229-210 1-1/204 2-13/16 2-11/32 1-13/32 15/32 .19 4229-211 1-1/2xl 2-7/8 2-11/32 1-15/16 3/8 .24 4229-212 1-1/2x1-1/4 2-13/16 2-13132 2-1/8 5132 .23 4229-248 20/4 3-3/16 2-7/8 1-7/16 23/32 .32 4229-249 2x1 3-1/8 2-7/8 1-23/32 112 .31 4229-250 2xl-1/4 3-3/16 2-7/8 2-1/8 17/32 .33 4229-251 2xl-1/2 3-3/16 2-27/32 2-11/32 9132 .31 4229-291 2-101-1/2 3-23/32 3-15/32 2-11/32 21/32 .51 4229-292 2-1/2x2 3-21/32 3-1/2 2-7/8 13/32 .52 4229-337 3x1-1/2 3-1/2 4-3/16 2-3/8 7/32 .71 4229-339 3x2-1/2 3-27/32 4-3/16 3-1/2 3/16 .80 GripLoCTM COUPLING - LEAD FREE w/EPDM 0-Ring Seals L 175 psi Maximum Internal Pressure @ 150°F L1� WARNING: DO NOT INSERT FINGERS. Part Number Size L M1 N Approx. Wt. (Lbs.) GL4229-007 3/4 4 1-15116 1-29/32 .25 GL4229-010 1 4-5/32 2 2-1/4 .34 13 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS Mid GROOVED COUPLING ADAPTER Groove x Socket PIPE _ _ M1 OR N L Part Number Size L M1 N Approx. Wt. (Lbs.) 4233-012 1-1/4 3-5/8 2-3/32 2-11/32 .72 4233-015 1-1/2 3-3/4 2-11/32 2-11/32 .83 4233-020 2 3-27/32 2-27132 2-11/32 1.27 4233-025 2-1/2 4-3/16 3-15/32 2-7/16 2.02 4233-030 3 4-5/16 4-1/8 2-7116 2.76 Not intended to convey or dispense water for human consumption through drinking or cooking FEMALE ADAPTER Brass Thread Insert Style Socket x Fipt IM — - L N�L M1 Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-007 3/4 2 1-13132 1-3/8 5/16 .23 4235-010 1 2-3116 1-3/4 1-11/16 11132 .25 4235-012 1-1/4 2-3/8 2-3/32 2-1/16 3/8 .36 4235-015 1 1-1/2 1 2-17132 1 2-3/8 2-7/16 1 3/8 1 .47 4235-020 2 2-25/32 2-27/32 3-3116 7/16 1.05 Not intended to convey or dispense water for human consumption through drinking or cooking FEMALE ADAPTER Special Reinforced Plastic Thread Style Socket x SR Fipt M ---- M1 DN Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-007SR 3/4 1-7/8 1-13/32 1-3/8 3/32 .08 4235-010SR 1 2-5132 1-23/32 1-7/8 3/32 .22 4235-012SR 1-1/4 2-5/16 2-1/8 2-1116 3/16 .20 MADE IN THE U.S.A. 14 El FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style Socket x SR Fipt r M ----- — M1 - LL Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101SR 3/402 1-29/32 1-13/32 1-3/16 118 .08 4235-130SR 1x112 1-31/32 1-23/32 1-3/8 3/32 .16 4235-131SR 1x314 2-3/32 1-3/4 1-3/8 1/4 .13 FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style with Socket Wrench Flats Socket x SR Fipt M-------- ---- M1 M = Flat -to -Flat Dimension N L Part Number Size L M M1 N Approx. Wt. (Lbs.) W4235-101SR 3/4112 2-9/32 1-13/32 1-3116 17/32 .09 W4235-130SR 1x112 2-9/32 1-3/4 1-3116 13/32 .12 15 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El SPIGOT FEMALE ADAPTER Brass Thread Insert Style Spigot x Fipt PIPE1 O.ID. L L4N Part Number Size L M1 N Approx. Wt. (Lbs.) 4278-007 3/4 2-5/32 1-3/8 17/32 .15 4278-010 1 2-9/32 1-11/16 7/16 .22 Not intended to convey or dispense water for human consumption through drinking or cooking SPIGOT FEMALE ADAPTER Special Reinforced Plastic Thread Style Spigot x SR Fipt PIPE _ - _ - M1 OR L Nld L� Part Number Size L M1 N Approx. Wt. (Lbs.) 4278-007SR 3/4 1-15/16 1-3/8 11/32 .08 4278-010SR 1 2-1/4 1-23/32 13/32 .13 TorqueSafe"rm FEMALE SPRINKLER HEAD ADAPTER Gasket Sealed Brass Thread Insert Style Socket x Gasket Fipt With Elastomer Seal - Use NO Thread Sealant M - — - — - M1 N fl- Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101 G 3/4112 1-7/8 1-13/32 1-3/8 9116 .15 4235-130GS 1x112 2-1/32 1-11/16 1-3/8 17132 .17 4235-131 G 1x3/4 2 1-11/16 1-9/16 9/16 .18 Not intended to convey or dispense water for human consumption through drinking or cooking MADE IN THE U.S.A. 16 0. FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS FEMALE SPRINKLER HEAD ADAPTER Brass Thread Insert Style Socket x Fipt M — -- M1 N L Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101 3/41/2 1-7/8 1-13132 1-17/32 15/32 .19 4235-130 1x1/2 2-11132 1-11/16 1-3/16 5/8 .16 4235-131 1x3/4 2-5/16 1-11/16 1-3/8 17/32 .18 Not intended to convey or dispense water for human consumption through drinking or cooking SofTorqueTM SR FEMALE SPRINKLER HEAD ADAPTER Gasket Sealed Special Reinforced Plastic Thread Style Socket x SR Fipt With Elastomer Seal - Use NO Thread Sealant �L� N Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101GSR 3/41/2 2-5/16 1-5/16 1-3/8 31/32 .11 4235-130GSR 1x1/2 2-13/32 1-19/32 1-3/8 31/32 .13 4235-131GSR 10/4 2-13/32 1-5/8 1-23132 1 .16 QuickTorqueTM SR FEMALE SPRINKLER HEAD ADAPTER Gasket Sealed Special Reinforced Plastic Thread Style Socket x SR Metal Fipt With Elastomer Seal - Use NO Thread Sealant L r M ----- �� M1 L N—� Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-101GMR 3/41/2 1-15116 1-5/16 1-9/16 13/16 .17 4235-13OGMR 1x1/2 2-3/16 1-19/32 1-9/16 15/16 .19 17 SPEARS® MANUFACTURING COMPANY FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS El FEMALE SPRINKLER HEAD ADAPTER Brass Thread Insert Style M ----- M1 with Long Body Socket x Fipt N L Part Number Size L M M1 N Approx. Wt. (Lbs.) L4235-130 I 1x1/2 1 2-3/16 1 1-23/32 1 1-7/32 1/2 .19 Not intended to convey or dispense water for human consumption through drinking or cooking FEMALE SPRINKLER HEAD ADAPTER Brass Thread Insert Style with Positioning Ring M --- M1 Socket x Fipt L Part Number Size L M M1 N Approx. Wt. (Lbs.) R4235-101 3/41/2 2-1/32 1-7/16 1-3/16 1 15/32 .15 Not intended to convey or dispense water for human consumption through drinking or cooking FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style with Positioning Ring Socket x SR Fipt Part Number I Size I L I M I M1 I N I Approx. Wt. (Lbs.) I R4235-101SR 3/4x1/2 1-15/16 1-7/16 1-7/32 7132 .09 TorqueSafeTm FEMALE SPIGOT SPRINKLER HEAD ADAPTER Gasket Sealed Brass Thread Insert Style Spigot x Gasket Fipt With Elastomer Seal - Use NO Thread Sealant O.D. PIPE ______ M1 N L Part Number Size L M N Approx. Wt. (Lbs.) 4238-101 G 3/41/2 1-15/16 1-3/8 21132 .14 4238-130 G 1x1/2 2-1/16 1-3/8 19/32 .15 Not intended to convey or dispense water for human consumption through drinking or cooking MADE IN THE U.S.A. 18 FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS SPIGOT FEMALE SPRINKLER HEAD ADAPTER Brass Thread Insert Style Spigot x Fipt PIPE O.D. _______ M1 �I .1 L Part Number Size L M1 N Approx. Wt. (Lbs.) 4238-101 3/4112 1-15116 1-17132 17132 .18 4238-130 1x1/2 2-1/4 1-3/16 11/32 .19 Not intended to convey or dispense water for human consumption through drinking or cooking TorqueSafeTm BUSHING - GASKET SEALED Brass Thread Insert Style Spigot x Gasket FIPT With Elastomer Seal - Use NO Thread Sealant O.D. L Part Number Size L Approx. Wt. (Lbs.) 4238-130BR G 1x1/2 1-7/32 .10 Not intended to convey or dispense water for human consumption through drinking or cooking BUSHING with BRASS THREAD INSERT Spigot x Fipt O.D. XT Part Number Size L Approx. Wt. (Lbs.) 4238-130BR 1x1/2 1 .13 Not intended to convey or dispense water for human consumption through drinking or cooking SPIGOT FEMALE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style Spigot x SR Fipt PIPE O.D. J� L-►1 Part Number Size L M1 N Approx. Wt. (Lbs.) 4238-101SR 3/41/2 1-29132 1-7/32 1/8 .07 4238-130SR 1x1/2 2-1/32 1-7/32 7/32 .09 19 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS MALE ADAPTER With CPVC Lined Thread Brass Insert Mipt x Socket ------ — - — - N L M1 Part Number Size L M1 N Approx. Wt. (Lbs.) 4236-007 314 2-17/32 1-13/32 13/16 .26 4236-010 1 2-15/16 1-23/32 29/32 .43 4236-012 1-1/4 3-1/8 2-3/32 31/32 .66 4236-015 1-1/2 3-9/32 2-11/32 31/32 .80 4236-020 2 3-7/16 2-27/32 31/32 1.00 ADJUSTABLE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style Socket x SR Apt Q 77 N Body L Width Part Number Size L N Q Body Width Approx. Wt. (Lbs.) Min Max Min Max 42001SR 3/4x1/2 6-9/32 8 4-7/16 6-1/4 1-7116 2-3116 .66 42011SR 1x112 6-13/32 8 4-1/2 6-1/8 1-7116 2-1/8 .68 ADJUSTABLE SPRINKLER HEAD ADAPTER Special Reinforced Plastic Thread Style Spigot x SR Fipt PIPE Q �= �N Body Width L L N Part Number Size Q Body Width Approx. Wt. (Lbs.) Min Max Min Max 42004SR 314x1/2 5-1/32 6-5/16 3-3116 4-15/32 1-5116 2-1/8 .36 42014SR 1x1/2 6-7/16 8-1/8 4-7116 6-1/4 1-7/16 2-3/16 .67 MADE IN THE U.S.A. 20 FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS REDUCER BUSHING Flush Style Spigot x Socket PIPE _ O.D. L N L Part Number Size L N Approx. Wt. (Lbs.) 4237-131 1x314 1-1/4 1/4 .04 4237-167 1-1/43/4 1-7116 7/16 .10 4237-168 1-1/41 1-13/32 9/32 .06 4237-210 1-1120/4 1-5/8 5/8 .19 4237-211 1-112xl 1-17/32 13/32 .13 4237-212 1-112xl-1/4 1-9/16 5/16 .07 4237-248 2014 1-29/32 29/32 .28 4237-249 2x1 1-23/32 9/16 .23 4237-250 2x1-114 1-11/16 7/16 .21 4237-251 2x1-112 1-11/16 5/16 .15 4237-290 2-1/2xl-1/4 2-5/32 7/8 .41 4237-291 2-1/2xl-1/2 2-5/32 3/4 .39 4237-292 2-112x2 2-9/32 3/4 .28 4237-338 3x2 2-7/32 11/16 .63 4237-339 3x2-112 2-5116 1/4 .42 TRANSITION BUSHING IPS Spigot x CTS Socket PIPE - - -_-_ O.D. L N L Part Number Size L N Approx. Wt. (Lbs.) 4240-101 1 3/41/2 1-1/8 5/8 .03 4240-130 1 W/2 1-1/4 23/32 .05 CAP Socket M - W Part Number Size M W Approx. Wt. (Lbs.) 4247-007 3/4 1-5116 1-5/16 .04 4247-010 1 1-5/8 1-9/16 .06 4247-012 1-1/4 2-3132 1-27/32 .13 4247-015 1-112 2-11132 2 .17 4247-020 2 2-27132 2-9/32 .39 4247-025 2-1/2 3-17132 2-5/8 .50 4247-030 3 4-3/8 3 .92 21 SPEARS® MANUFACTURING COMPANY r�FlcameGuardOCPVC FIRE SPRINKLER PIPING PRODUCTS SPEARS . TEST PLUG - 0-ring Sealed Mipt - For Pressure Testing Only, Not For use with Z4235 Series Adapters L F, M1 — --.--' M 1/2-14 NPT Part Number Size L M M1 Approx. Wt. (Lbs.) FTP-005 1/2 1-27/32 1-15/16 1-7/32 .03 TEST PLUG for TorqueSafeTM Gasket Sealed Head Adapters Mipt - For Pressure Testing Only. Use ONLY with Gasket Sealed Head Adapters L M1 = = M 112-14 NPT Part Number Size L M M1 Approx. Wt. (Lbs.) FTP-005GS 1/2 1-25/32 2-1/32 1-1/4 .05 TEST PLUG (PVC White) Not UL Listed; For Pressure Testing Only, Mipt �•— L —►I Part Number Size L Approx. Wt. (Lbs.) 4250-005 1/2 27/32 .02 MADE IN THE U.S.A. 22 FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS FLANGE - ONE PIECE 4 Bolt Holes, 175 psi Socket � M —� L R N I Is- BOLT CIRCLE DIA. �I � MAX O.D. No. of Bolt Min. Bolt Max. Approx. Wt. Part Number Size L M N R Bolt Circle Bolt Holes Dia. Size Length O.D. (Lbs.) 4251-007 3/4 1-5/32 1-1/2 1/8 17/32 4 2-3/4 1/2 2 3-29/32 .31 4251-010 1 1-5116 1-13/16 1/8 11/16 4 3-1/8 1/2 2-1/4 4-9/32 .35 4251-012 1-1/4 1-13/32 2-7/32 5/32 11116 4 3-1/2 1/2 2-1/4 4-5/8 .44 4251-015 1-1/2 1-19/32 2-1/2 3/16 23/32 4 3-27/32 1/2 2-1/2 5-1/16 .61 4251-020 2 1-27/32 3 5/16 27/32 4 4-3/4 5/8 3 5-31/32 .95 4251-025 2-1/2 2-7132 3-1/2 7/16 1-1/32 4 5-1/2 5/8 3-1/4 7 1.50 BLIND FLANGE 4 Bolt Holes, 175 psi R i• - BOLT CIRCLEDIA. O.D. Bolt No. of Bolt Min. Bolt Part Number Size R Bolt Size Max. O.D. Approx. Wt. (Lbs.) Circle Dia. Holes Length 4253-007 314 17/32 2-3/4 4 1/2 2 3-27132 .30 4253-010 1 23/32 3-1/8 4 112 2-1/4 4-1/4 .35 4253-012 1-1/4 21/32 3-1/2 4 1/2 2-1/4 4-5/8 .40 4253-015 1-1/2 23/32 3-27/32 4 1/2 2-1/2 5-1/16 .52 4253-020 2 27132 4-3/4 4 5/8 3 5-31/32 .86 4253-025 2-1/2 1-1/32 5-1/2 4 5/8 3-1/4 6-15/16 1.70 4253-030 1 3 11-5/16 6 4 5/8 3-1/4 1 7-5/8 1.72 FLANGE - TWO PIECE Van Stone Style, 4 Bolt Holes, 175 psi Socket M L R i N-BOLT CIRCLE DIA.-►� MAX O.D. Bolt Circle No. of Bolt Min. Bolt Part Number Size L M N R Dia. Holes Bolt Size Length Max. O.D. Approx. Wt. (Lbs.) 4254-030 1 3 1 2-1/8 1 4-1/4 1 9132 1-1/32 1 6 1 4 1 5/8 1 3-1/4 1 7-15/32 1 1.75 23 SPEARS® MANUFACTURING COMPANY FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS El FLANGE - TWO PIECE Van Stone Style, 4 Bolt Holes, 175 psi PIPE O.D. Spigot L 4N R OLTC�— .. Bolt No. of Bolt Min. Bolt Approx. Wt. Part Number Size L N R Bolt Size Max. O.D. Circle Dia. Holes Length (Lbs.) 4256-007 3/4 1-15/16 13/16 17/32 2-3/4 4 112 2 3-27/32 .30 4256-010 1 2-7/32 1-1/32 11/16 3-1/8 4 1/2 2-1/4 4-1/4 .41 4256-012 1 1-1/4 2-3/8 1 11/16 3-1/2 4 112 2-1/4 1 4-5/8 .50 4256.015 1-1/2 2-7/16 1-3/32 23/32 3-7/8 4 1/2 2-1/2 4-31/32 .65 4256.020 2 2-3/4 1-5/32 25/32 4-3/4 4 518 3 5-15/16 1.00 4256-025 2-1/2 3-1/16 1-9132 1-1/32 5.1/2 4 5/8 3-1/4 6-15/16 1.62 4256-030 3 3-3/8 1-13/32 1-1/32 6 4 5/8 3-114 7-9/16 1.76 TRANSITION UNION Brass Thread Insert Style Socket x Fipt 175 psi NUT O.D. M -- N L Part Number Size L M N Nut O.D. Approx. Wt. (Lbs.) 4259-010BR 1 2-13/16 1-7/8 1-1/32 2-7/8 .52 4259-012BR 1-1/4 3 2-3/16 1-1/8 3-9/32 .98 4259-015BR 1-1/2 3-3/4 2-1/2 1-9/16 3-17/32 .93 4259-020BR 2 3-5/8 2-7/8 1-1/4 4-5/16 1.64 Not intended to convey or dispense water for human consumption through drinking or cooking UNION Socket x Socket 175 psi NUT M — — O.D. N L —►1 Part Number Size L M N Nut O.D. Approx. Wt. (Lbs.) 4257-007 3/4 2-3/8 1-17/32 3/8 2-1/2 .38 4257-010 1 2-9/16 1-27132 3/8 2-718 .41 4257-012 1-1/4 2-27/32 2-7/32 11/32 3-5/16 .52 4257-015 1-1/2 3-1/8 2-1/2 3/8 3-17132 .63 4257-020 1 2 1 3-5/8 1 3-1/32 9/16 4-3/16 1.09 MADE IN THE U.S.A. 24 FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS SofTorqueTM SR FEMALE SPIGOT SPRINKLER HEAD ADAPTER Gasket Sealed Special Reinforced Plastic Thread Style Spigot x SR Fipt With Elastomer Seal - Use NO Thread Sealant PIPE M1 O.D. ----- -L -:1- 1 N - ►I L Part Number Size L M1 N Approx. Wt. (Lbs.) 4278-101GSR 3/41/2 2-1/4 1-3/8 1 .11 SHORT REPAIR COUPLING Spigot x Socket 175 psi L2 L1- f-► L3 I S Part Number Size L1 L2 L3 M S Approx. Wt. (Lbs.) SH118-07CO 3/4 4-13116 5-17/32 3/4 1-3/4 2-3116 .31 SH118-1000 1 4-3/4 5-5/8 31/32 2-1/16 2-5132 .40 GripLocTm REPAIR COUPLING — LEAD FREE w/EPDM 0-Ring Seals L 175 psi Maximum L—>-gam L Pressure @ 150°F L2 WARNING: DO NOT INSERT FINGERS. Part Number Size L L1 L2 M S Approx. Wt. Lbs. SG118-1000 1 1-17/32 7-17/32 4-1/4 2-1/4 2-27132 .73 25 SPEARS® MANUFACTURING COMPANY =FicameGuardO CPVC FIRE SPRINKLER PIPING PRODUCTS FlameGuard° CPVC Drain & Swing Check Valves for NFPA 13D Applications Only 7 00 Application: FlameGuard® CPVC Orange Swing Check Valves and PVC/CPVC True Union Drain Valves are for use in configuring CPVC Fire Sprinkler System connection to water supply (riser/drain assembly) in NFPA 13D installations only. These valves are not UL Listed and NOT for use in any other locations within the fire sprinkler system. TRUE UNION INDUSTRIAL DRAIN VALVES CPVC Gray Valve with CPVC Orange End Connector Socket x Socket D S— A Part Number Size A B C D E 1822-007CFG 3/4 2-1/4 2-3/4 4-3/4 2-7/8 3-3/8 1822-010CFG 1 2-1/2 2-7/8 5-1/8 3-1/8 3-7/16 1822-012CFG 1-1/4 3-1/16 3-1/4 5-3/4 3-5/8 3-7/8 1822-015CFG 1-1/2 3-1/2 3-1/2 6-1/4 4 4-3/16 1822-020CFG 2 4-1/4 4-3/4 7-3/4 4-1/2 5-118 Not UL Listed TRUE UNION DRAIN VALVES PVC Valve with CPVC End Connector Socket x Socket � E D — — A B C Part Number Size A B C D E 3622-007FG 3/4 2-1/4 2-3/4 4-3/4 2 3 3622-010FG 1 2-1/2 2-7/8 5-118 2-5/16 3-7/16 Not UL Listed MADE IN THE U.S.A. 26 FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS COMPACT 2000 DRAIN VALVE Socket x Socket E A WBI� j— D C Part Number Size A B C D E 6622-007C0 3/4 1-13/16 1-1/2 3-9/16 2 3 6622-01000 1 2-1/16 1-3/4 4 2-5/16 3-7116 Not UL Listed CPVC SWING CHECK VALVES Socket x Socket p — — — D .4 B C Part Number Size A B C D Approx. Wt. (Lbs) S1520-1000 1 1-11/16 2-5/16 4-9/16 2-5/8 .33 S1520-12C0 1-114 2-1/16 2-15/16 5-1/2 3-3/8 .42 S1520-15C0 1-1/2 2-7/16 3 5-5/8 3-3/8 .89 Not UL Listed CPVC SPECIAL REINFORCED THREAD INLET SWING CHECK VALVES SR Fipt x Socket B —► C Part Number Size A B C D Approx. Wt. (Lbs) S1520-10FSRSCO 1 1-11/16 2-15/16 4-9/16 2-5/8 .33 S1520-12FSRSCO 1-1/4 2-1/16 3-5/8 5-1/2 3-3/8 .42 S1520-15FSRSCO 1-1/2 2-7/16 3-11/16 5-5/8 3-3/8 .89 Not UL Listed 27 SPEARS® MANUFACTURING COMPANY NOTES PRODUCT LIMITED LIFETIME WARRANTY El Except as otherwise specified for certain products, mandated by law or herein provided, Spears° Manufacturing Company ("Company") warrants Standard Catalog Products ("Products") which have been directly manufactured by them to be free from defects in material and workmanship for as long as the original intended end user of the Products ("End User) retains ownership and possession of the Products and complies with this Warranty ("Warranty Period"). Each other person or entity acquiring or employing the Products, including buyers, contractors and installers ("Buyer') and End Users ("Buyer/End User") agrees that this Warranty shall be effective only during the Warranty Period so long as the Products are used solely for the normal purposes for which they are intended and in conformance with industry established standards, engineering, installation, operating, and maintenance specifications, recommendations and instructions including explicit instructions by the Company; the Products are properly installed, operated and used, and have not been modified; and all the other terms of this Warranty are complied with. Any violation thereof shall void this Warranty and relieve Company from all obligations arising from this Warranty and the Products. Upon receipt or discovery of any Products that appear questionable or defective each Buyer/End User shall promptly inspect and return any such Prod- uct to the Company at 15853 Olden Street, Sylmar, California 91342, accompanied by a letter stating the nature of any problems. If the Prod- ucts are determined by Company to be defective in materials or workmanship directly provided by Company, Company, at its sole option, may ei- ther repair or replace the defective Products, or reimburse applicable Buyer/End User for the cost of such Products. The applicable Buyer/End User shall bear all applicable shipping costs. THIS SHALL BE BUYERS/END USERS' SOLE REMEDY. EACH BUYER/END USER AGREES THAT COMPANY WILL NOT BE RESPONSIBLE FOR ANY OTHER OBLIGATIONS RELATING TO THE PRODUCTS, INCLUDING ANY OTH- ER MATERIALS OR LABOR COSTS, LOSS OF USE OR ANY OTHER ITEM OR FOR ANY DELAYS IN COMPLYING WITH THIS WARRANTY BEYOND COMPANY'S REASONABLE CONTROL, COMPANY SHALL NOT BE LIABLE FOR, DOES NOT ASSUME, AND EXPRESSLY DISCLAIMS, ANY LIABILITY, RESPONSIBILITY AND DAMAGES: DUE TO ANY BUYER/END USER'S FAILURE TO COMPLY WITH THIS WARRANTY, INCLUDING IMPROPER INSTALLATION, USE OR OPERATION; USE WITH PRODUCTS FROM OTHER MANUFACTURERS THAT DO NOT MEET ASTM OR OTHER APPLICABLE PRODUCT STANDARDS; IMPROPER CONTROL OF SYSTEM HYDRAULICS, IMPROPER WINTERIZATION PROCEDURES, IMPROPER VOLTAGE SUPPLY, CON- TACT WITH INCOMPATIBLE MATERIALS OR CHEMICALS, EXCAVATION/DIGGING, EXCESSIVE WEIGHT, AND VANDALISM; DUE TO REASONABLE WEARAND TEARAND DUE TOANYACTS OF NATURE, INCLUDING LIGHTNING, EARTHQUAKES, GROUND MOVEMENT, FROST HEAVE, OR FLOODS. COMPANY EXTENDS ONLYTHIS WARRANTYAND EXPLICITLY DISCLAIMS ALL OTHER WARRANTIES, WHETHER IMPLIED OR OTHERWISE EXPRESSED, WHETHER ORAL, STATUTORY OR OTHERWISE, INCLUDINGANY IMPLIED WARRANTIES ORAFFIRMATIONS FOR SUITABILITY, MERCHANTABILITY OR FITNESS FORA PARTICULAR PURPOSE. NOAFFIRMATION BY COMPANY ORANY OF ITS REPRESENTATIVES, BY WORDS, CONDUCTOR OTHERWISE, SHALL CONSTITUTE A WARRANTY. THIS WARRANTY MAY NOT BE TRANSFERRED, EXTENDED, ALTERED OR OTHERWISE MODIFIED IN ANY MANNER, EXCEPT BY WRITTEN AGREEMENT SIGNED BY COMPANY. BY ITS ACCEPTANCE OF THE PRODUCTS, EACH BUYER/END USER EXPRESSLY WAIVES ALL OTHER LIABILITY OR OBLIGATION OF ANY KIND OR CHARACTER OF. COMPANY, INCLUDING LIABILITY PREDICATED UPON CONTRACT, TORT, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE GROUNDS, AND ALL, IF ANY, DAMAGES AND LOSSES AS A RESULT THEREOF, INCLUDING ALL, IF ANY, COMPENSATORY, GENERAL, SPECIAL, CONSEQUENTIAL, INCIDENTAL, OR PUNITIVE DAMAGES. WITH RESPECT TO SUCH WAIVERS, EACH BUYER/END USER EXPLICITLY WAIVES CALIFORNIA CIVIL CODE §1542 WHICH STATES "A GENERAL RELEASE DOES NOT EXTEND TO CLAIMS WHICH THE CREDITOR DOES NOT KNOW OR SUSPECT TO EXIST IN HIS FAVOR AT THE TIME OF EXECUTING THIS RELEASE, WHICH IF KNOWN BY HIM MUST HAVE MATERIALLY ADVERSELY AFFECTED HIS SETTLEMENT WITH DEBTOR" AND ALL OTHER SIMILAR STATU- TORY, COMMON AND CASE LAW RIGHTS, DEFENSES AND LIMITATIONS. Having previously independently inspected the Products, or a sample, as fully as desired, or having the opportunity to and having not done so, upon acceptance of delivery of the Products, and except as otherwise herein explicitly provided, each Buyer/End User by acceptance or use of the Products accepts them in their "AS IS" and "WITH ALL FAULTS" condition without any other warranty, expressed, implied or otherwise, and accepts and assumes the entire risk and cost of all servicing, remediation and consequences thereof. This Warranty shall be governed by California law and any unenforceable provisions severed without affecting the remaining provisions. As used herein, "including" includes "without limitation." Spears" Quality Policy It is the policy and objective of Spears® Manufacturing Company to produce a superior quality product suitable for its intended use, with regard to functionality, structural integrity and conformance to established industry standards and practices. It is the commitment of this Company to do so in a manner which provides consistency of product quality, optimum availability, and superior customer service, while maintaining efficiency of operations and profitability necessary to perpetuate product improvement and customer satisfaction. Furthermore, it is recognized that the attainment of these objectives is the responsibility of all Company operations and personnel according to their respective functions. The information contained in this publication is based on current information and product design at the time of publication and is subject to change without notification. Our ongoing commitment to product improvement may result in some variations. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability for particular application or results to be obtained therefrom. For information not contained herein, please contact Spears° Technical Services Department iWest Coast: (818) 364-1611— East Coast: (678) 985-1263]. Reproduction of this publication in whole or in part is prohibited without the authorized consent of Spears" Manufacturing Company, Sylmar, California. © Copyright 2014 Spears" Manufacturing Company. All Rights Reserved. Printed in the United States of America. SPEARS® MANUFACTURING COMPANY ,�, T$� � ® Corporate Office SPEARS � •s 15853 Olden Street • Sylmar, CA 913429 PO Box 9203 • Sylmar, CA 91392 (818) 364-1611 • http://www.spearsmfg.com ���x► rR�9w © Copyright 2015 Spears® Manufacturing Company. All Rights Reserved. Printed in the United States of America 11/15. FG-4-1115 , ' . Fig. 22 - Hanger for CPVC Plastic Pipe Single Fastener Strap Type Size Range — 3/4" thru 2" CPVC pipe Material — Pre -Galvanized Steel Function — Intended to perform as a hanger to support CPVC piping used in automatic fire sprinkler systems. The product acts as a hanger when tab is upward and the fastener screw is in the horizontal position. Figure 22 can be installed on the top of a beam, but in this situation acts as a guide to the piping which is supported by the beam itself. It is not intended to sup- port CPVC pipe from under a flat horizontal surface, such as a ceiling. For this type of installation, use the TOLCOO Fig. 23, Double Fastener Strap for CPVC Piping. Fig. 22, when inverted, with the hanger tab downward, can function as a restrainer to prevent the upward movement of the sprinkler head during activation. Approvals — Underwriters' Laboratories Listed in the USA (UL) and Canada (cUL) to support fire sprinkler piping. May be installed in wood using fasteners supplied with product, or into minimum 20 gauge steel using (1) 1/4" x 1" tek type screw. Meets and exceeds the requirements of NFPA 13, 13R and 13D. C UL US LISTED Features — Fig. 22 incorporates features which protect the pipe and ease installation. The flared edge design pro- tects CPVC pipe from any rough surface. It is easily attached to the building structure using the special UL Listed hex head self threading screw* furnished with the product. It is recommended that rechargeable electric drills fit- ted with a hex socket attachment to be used as installation tools. No impact tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No pre -drilling of a pilot hole in wood is required. Finish — Pre -Galvanized Order By — Figure number and CPVC pipe size. * Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. Dimensions • Weights CPVC Max. Hanger Fastener Hex Approx. Pipe Size A B C Spacing (Ft.) Head Size wt./100 3/4 27/1 s 15/16 13/ 6 51/2 5/16 9 1 211/16 17/16 13/16 6 5/16 9 11/4 31/ 6 15/6 13/ 6 61/2 5/16 11 11/2 35/16 13/4 13/16 7 5/16 12 2 33/4 21/8 13/16 8 5/16 15 OFFICE/MANUFACTURING FACILITY -1375 SAMPSON AVE. - CORONA, CA 92879 - PH: 951.737.5599 - FAX: 951.737.0330 CUSTOMER SERVICE - 800.786.5266 www.tako.com Fig. 23 - Hanger for CPVC Plastic Pipe Double Fastener Strap Type Size Range — 3/4" thru 3" CPVC pipe Material — Pre -Galvanized Steel Function — Intended to perform as a hanger/restrainer to support CPVC piping used in automatic fire sprinkler systems. Fig. 23 can be installed on the top, bottom or side of a beam. The Fig. 23 also functions as a restrainer to prevent the upward movement of the sprinkler head during activation. Approvals — Underwriters' Laboratories Listed in the USA (UL) and Canada (cUL) sizes 3/4" thru 2" to support fire sprinkler piping. May be installed in wood using fasteners supplied with product, or into minimum 20 gauge steel using (2) 1/4" x 1" tek type screw. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Features — Fig. 23 incorporates features which protect the pipe and ease installation. The flared edge design protects the CPVC pipe from any rough surface. It also incorporates snap restrain- ers allowing easier and faster installation. Easily attaches to the building structure using the two UL Listed hex head self thread- ing screws* furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No pre -drilling of a pilot hole in wood is required. Finish — Pre -Galvanized Order By — Figure number and pipe size * Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. C &Us LISTED Dimensions -Weights CPVC Max. Hanger Fastener Hex Approx. Pipe Size A B C Spacing (Ft.) Head Size WtJ100 3/4 31/8 19/16 13/16 51/2 5/16 9 1 33/8 111/16 13/16 6 5/16 9 11/4 43/16 23/32 13/16 61/2 5/16 11 1 1/2 47/16 27/32 13/16 7 5/16 12 2 47/8 27/16 13/16 8 5/16 15 21/2 109/32 211/16 13/16 Consult Factory 5/16 22 3 117/8 3 13/16 Consult Factory 5/16 25 OFFICEIMANUFACTURING FACILITY -1375 SAMPSON AVE. - CORONA, CA 92879 - PH: 951.737.5599 - FAX: 951.737.0330 CUSTOMER SERVICE - 800.788.5265 www.tdko.com 38 Fig. 28M - Offset Hanger and Restrainer for CPVC Plastic Pipe and IPS Pipe Size Range — 3/4" thru 1-1/4" Material — Carbon Steel, Pre -Galvanized Function — Designed to be used as a hanger and restrainer for CPVC piping or steel piping where the "stand-off" design will ease installation by eliminating the need for wood blocking. Features — • Flared edge design protects CPVC pipe from any rough or abrasive surfaces • Unique snap -on design holds pipe firmly in place and allows retrofit type of installation • The "Stand -Off" design eliminates the need for wood block extension • Can be installed on horizontal or vertical piping regardless of mounting surface orientation • Attaches easily to wood structure with two hex head self -threading screws furnished with product • Installs easily using rechargeable electrical driver with 5/16" extension socket eliminating impact tool damage to pipe • Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1" tek type self drilling tapping screws • cULus Listed as a hanger and a restrainer for fire sprinkler piping Installation Note — When installed in wood structural member and threads from the #10 x 1 " screws are exposed, use FIG. 27B speed nut to secure Approvals — Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fas- teners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28M satisfies the UL vertical restraint requirements where needed. Order By — Figure number and pipe size Patent #7,744,042 _ -�-----------, I l� p I I I I I I I 1 I I I I I I I I I I I � � I I I I - I RESTRAINT ________- -------- ------------ ----I I I I Q I I d d I I d I I � I I p I I � I I I d I a I 1 d d I �� I RESTRAINT Z` Dimensions • Weights Max. Spacing Pipe required per Approx Size A B C NFPA 13 for WtJ100 CPVC plastic pipe 3/4 2 3/16 3-5/16 5'-6" 9 1 2-1/8 3/16 3-1/2 6'-0" 12 1-1/4 2-5/16 3/16 3-1/2 6'-6" 13 TOLCO FIG. 27B (2) REQUIRED C @US LISTED II II LI HANGER AND RESTRAINT APPLICATION TOLCO FIG. 27B (1) REQUIRED HIGH SIDE OFHANGER DETAIL A HANGER APPLICATION m OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 - FAX: 951.737.0330 CUSTOMER SERVICE - 800.786.5266 www.taka.com High-performance intumescent firestop sealant FS-ONE MAX Applications ■ For effectively sealing most common through penetrations in a variety of base materials ■ For use on concrete, masonry and drywall ■ Mixed and multiple penetrations ■ Metal pipe penetrations: copper, steel and EMT ■ Insulated metal pipe penetrations: steel and copper ■ Plastic pipe penetrations: closed or vented Advantages ■ US -produced: "Buy American" compliant ■ One product for a variety of common through penetrations ■ Cost-effective, easy -to -use solution ■ Water -based and paintable ■ Industry -leading VOC results ■ Ethylene glycol -free FB erameeoxraneu: �mm�me�ac Chemical Mold and mildew resistant resistant F IM *us ss)a� FILL, VOID OR CAVITY MATERIAL FOR USE IN THROUGH -PENETRATION FIRESTOP SYSTEMS g "PROVEDus SEE UL FIRE RESISTANCE DIRECTORY 66W Intertek ___ Technical data Chemical basis Water -based acrylic dispersion Approx. Density 84.3 Ib/113 Color Red Application temperature range 41 - 104 IF Approx. cure time') 4 mm/3 days Temperature resistance range -4 to 212 IF Mold and mildew performance Class 0 (ASTM G21-96) Mold and mildew resistance Yes Surface burning characteristics UL 723 (ASTM E84) Flame spread: 0 Smoke development: 10 Tested in accordance with UL 1479, ASTM E814, ASTM E84, CAN/ ULC-S115, ASTM G21, ASTM E90 California State fire marshal approval CSFM Listing 4485-1200:0108 for FS-ONE MAX Intumescent Firestop Sealant Expansion ratio (unrestricted, up to) 1:5 ') at 75°F/24°C, 50 % relative humidity F Order Designation _ - _ Package Content - '" - .. Itemmumber IFS -ONE MAX 20oz foil (3 case + disp) 1 x Foil pack dispenser manual CS 270-P1, 75x Firestop sealant FS-ONE MAX 20 oz foil 3530252 FS-ONE MAX 10oz tube (1 case) 12xFirestop sealant FS-ONE MAX 1 Ooz cartridge 3530249' FS-ONE MAX 5 gallon (18 pails) 18x Firestop sealant FS-ONE MAX 5 gallon pail 3530263 �FS-ONE MAX 2ooz foil (1 case) 25X Firestop sealant FS-oNE'' MAX 20 oz foil 3530250 FS-ONE MAX 20oz foil (3 cases) FS-ONE MAX 20oz Foil -Pallet FS-ONE MAX 10 oz cartridge 75x Firestop sealant FS-ONE MAX 20 oz foil 600x FSONE-MAX 20 oz foil, 290x Bulk Shipping Condition 3530251 3534713 2101531 FS-ONE,MAX 5 gallon pail 2101533. Hilti. Outperform. Outlast. © © T10 Hilti, Inc. (USA) 1-800-879-8000 1 www.us.hilti.com I en espanol 1-800-879-5000 1 Hilti (Canada) Corp. 1-800-363-4458 1 www.hilti.ca ZURN® Model700XLFP W� High Capacity Dual Check Valve Application Ideal for use where Lead -Free* valves are required. Designed for installation on potable water lines to protect against both backsiphonage and backpressure of polluted water into the potable water supply. The Model 700XLFP shall provide pro- tection where a potential health hazard does not exist. Standards Compliance • ULO Classified • ASSEO Listed 1024 • CSAO Certified B64.6 • Certified to NSF/ANSI 372* by IAPMO R&T *(0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT) Materials Main valve body Low Lead Cast Bronze ASTM B 584 Elastomers Buna Nitrile (FDA approved) Silicone (FDA approved) EPDM (FDA approved) Polymers Delrin O, NSF Listed Springs Stainless Steel, 300 Series Connections Legend U = Indicates location of "union" connection FNPT = Female National Pipe Tapered Thread FC = Female Copper Sweat FMTC = Female Meter Thread Connection Features Sizes: 1 ", 1 1/4", 1 1/2" Max. pressure: 175 PSI Max. temp: 180°F Connections: Threaded ANSI B 1.20.1 Copper sweat ANSI B 16.22 (1-1/2" only) Dimensions & Weights (do not include pkg.) MODEL SIZE in. I mm DIMENSIONS WEIGHT lbs. I kg A in. mm B in. mm 1 25 6 5/16 160 3 3/8 86 3.6 1.6 1 1/4 32 6 5/16 160 3 3/8 86 3.4 1.5 1 1/2 40 6 5/16 160 3 3/8 86 3.3 1.5 Accessories ❑ Repair kit (RK1-700FP) ❑ Thermal expansion tank (Model XT) Configurations FEMALE UNION INLET X FEMALE OUTLET INLET (UNION) OUTLET PART NUMBER 1" FNPT 1" FNPT 1UFX1F-700XLFP 1-1/4" FNPT 1-1/4" FNPT 114UFX114F-700XLFP 1-1/2" FNPT 1-1/2" FNPT 112UFX112F-700XLFP 1-1/4" FMTC* 1-1/4" FMPT 114UFMX114F-700XLFP 1-1/4" FMTC* 1" FNPT 114UFMX1F-700XLFP 1-1/2" FC 1-1/2" FNPT 112UFCX112F-700XLFP *1-1/4" NPSH threads are used on 1" water meters oB Zurn Industries, LLC I Wilkins 1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766 In Canada I Zurn Industries Limited 3544 Nashua Drive, Mississauga, Ontario L4V 1 L2 Ph. 905-405-8272, Fax 905-405-1292 Rev. A Date: 1 /14 Document No. BF-700XLFP Product No. Model 700XLFP WWW.ZU n.COM I Page 1 of 2 Flow CharacteristicsO Rated Flow (established byapproval agencies) MODEL 700XLFP,1 ",1-1/4" & 1-1/2" (STANDARD & METRIC) FLOW RATES (Vs) 0.00 0.63 1.26 1.89 2.52 3.16 3.79 4.42 5.05 5.68 6.31 o 25 rn a 20 to O 15 J luj 10 w 5 w 0 m Y 138 U) rn 103 0 69 34 U) w a 0 a 0 10 20 30 40 50 60 70 80 90 100 FLOW RATES (GPM) Typical Installation Local codes shall govern installation requirements. Unless otherwise specified, the installation shall be in accordance with the manufacturer's instructions and the latest edition of the Uniform Plumbing Code. The installation shall be made so that no part of the unit can be submerged. Capacity thru Schedule 40 Pipe (GPM) Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec 1" 13 20 27 40 1 1 /4" 23 35 47 70 1 1 /2" 32 48 63 95 2" 52 78 105 167 WATER METER MODEL 700XLFP II" ' it "= > DIRECTION OF FLOW VERTICAL INSTALLATION INDOOR INSTALLATION Specifications The Dual Check Valve Backflow Preventer shall be certified to NSF/ANSI 372 and ASSEO Listed 1024. The main body shall be low lead cast bronze (ASTM B 584), the check assemblies shall be DELRIN O. The seal ring and o-rings shall be Buna Nitrile or Silicone. The Dual Check Valve shall be a ZURN WILKINS Model 700XLFR Zurn Industries, LLC I Wilkins 1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766 In Canada I Zurn Industries Limited 3544 Nashua Drive, Mississauga, Ontario L4V 1 L2 Ph. 905-405-8272, Fax 905-405-1292 www.ZUM.00m Page 2 of 2 FlameGuardTM CPVC Drain & Check Valves For NFPA 13D Applications Only Application: FlameGuardTM CPVC Orange Drain Valves and Check Valves are for use in configuring CPVC Fire Sprinkler System connection to water supply (riser/drain assembly) in NFPA 13D installations only. These valves are NOT for use in any other locations within the fire sprinkler system. Drain Valve Check Valve M'µ1 Special Reinforced (SR) Threaded Inlet Check Valve CPVC Drain Valves Disc Price Part Number Size Code I Each Socket x Socket 6622-007C0 3/4 004 22.68 6622-01000 11 004 28.36 CPVC Check Valves Disc Price Part Number Size I Code Each Socket x Socket S1520-1000 I 1 1 004 22.56 S1520-12C0 1-1/4 004 25.22 S152015C0 1-1/2 004 28.36 CPVC Special Reinforced Thread Inlet Check Valves Disc Price Part Number Size Code I Each SR Fist x Socket S1520-10FSRSCO 11 004 24.44 S1520-12FSRSCO 1-1/4 0041 28.22 S1520-15FSRSCO 1-1/2 1 0041 33.47 General Installation Information: Socket end connections should be installed using Spears® FS-5 One -Step Cement for use with Spears® CPVC Fire Sprinkler Products. Threaded connections should be made using Spears® BLUE 75T11 Thread Sealant tested for compatibility with CPVC materials. Swing check valves are designed for horizontal installations, but may be installed in up -flow only vertical position. Check valves MUST be installed with the valve's FLOW arrow pointing in the direction of the flow. Do not install valve upside down. . NOT FOR USE WITH COMPRESSED AIR OR GAS Page 1 Spears® Manufacturing Company Progressive Products from Spears® Innovation and Technology FlameGuardT"' CPVC Drain & Check Valves For NFPA 13D Applications Only Drain Valve: Nominal Size Range Type Material Seats Seals Handle End Connections Check Valve: Nominal Size Range Type Material Seat End Connections Specifications 3/4" 1" 1/4-Turn Ball Valve, Maintenance -free Sealed Unit CPVC, Orange PTFE/HDPE EPDM Polypropylene, Red Socket x Socket J Socket x Socket Part Number Nominal Size Dimension Reference(Inches, t 1/16 A B C D E 6622-007C0 3/4 1-13/16 1-1/2 3-9/16 2 2 6622-01000 1 2-1/16 1-3/4 4 2-5/16 2-5/16 1", 1-1/4", 1-1/2" Swing Check, Maintenance -free Sealed Unit CPVC, Orange EPDM Socket x Socket Socket x Special Reinforced (SR) Female Plastic Thread Socket x Socket Part Number SR Thread x Socket Part Number Nominal Size Dimension Reference(Inches,* 1/16 C„ (GPM) A B C D Socket SR Thread S1520-1000 S1520-10FSRSCO 1 1-11/16 2-5/16 2-15/16 4-9/16 2-5/8 33 S1520-12CO S1520-12FSRSCO 1-1/4 2-1/16 2-15/16 3-5/8 51/2 3 3/8 42 S1520-15CO S1520-15FSRSCO 1-1/2 2-7/16 3 1 3-11116 5-5/8 3-3/8 89 Made in the U.S.A. NOT FOR USE WITH COMPRESSED AIR OR GAS Progressive Products from Spears® Innovation and Technology Page 2 -1 00 O O CA) .p CO IV tV C• CG GC G C9 O FPPI" 28 Pressure Gauges Pressure Gauges and Accessories Each gauge features an impact and corrosion resistant case made from ABS (plastic). Features a phosphor bronze bourdon tube movement with white enameled brass dial face with large numbers for easy reading. Dual scale to 300 PSI/2000Kpa. UUULc Listed and FM Approved. Part No. Description Box Qty. 11-550 Water Gauge 0-300 UUFM 60 11-551 Air Gauge 0-300 UUFM 60 11-552 Air Gauge w/Retard 60 11-553 Air/Water Gauge 07300 UUFM 60 11-555 Resid. 2" Spr. Gauge 0-300 100 11-560 Liquid Filled, 0-300 100 Pressure Gauge Kits Each kit contains a pressure gauge*, 1/4" 3-way valve*, 1/4" x 4" black pipe nipple, 1/2" and 1/4" bushing and a 1/4" IPS pipe plug, blister packed to make sure all components get to the job. Part No. Description Box Qty. 11-565 Gauge Kit, Water 8 11-566 Gauge Kit, Air -Water 8 11-567 Gauge Kit, Air 8 11-568 Gauge Kit, Air w/Retard 8 * Components are UUULc or FM approved or both. 1) ARGCO' "mi'FE THREAD SEAL TAPE (INDUSTRIAL) Meets MIL Spec T-27730A -For all industrial, applications. -Made from 100% virgin PTFE. *No pigments, no additives. -Exceeds MILSpec T-27730A. *Temperature range of -450F to +550F. -Available in a variety of sizes and densities. -May be used on all applicationsincluding water, oil, chemical, medical, and food processing where non -contamination standards are high. 60-10-260 1/2" x 260" STANDARD 0.4 DENSITY INDUSTRIAL GRADE 60-10-262 1/2" x 520" STANDARD 0.4 DENSITY INDUSTRIAL GRADE 60-10-264 1/2" x 1296" STANDARD 0.4 DENSITY INDUSTRIAL GRADE 60-10-262 3/4" x 260" STANDARD 0.4 DENSITY INDUSTRIAL GRADE 60-10-267 3/4" x 520" STANDARD 0.4 DENSITY INDUSTRIAL GRADE 60-10-269 3/4" x 1296" STANDARD 0.4 DENSITY INDUSTRIAL GRADE 60-10-270 1" x 260" STANDARD 0.4 DENSITY INDUSTRIAL GRADE 60-10-271 1" x 520" STANDARD 0.4 DENSITY INDUSTRIAL GRADE 60-10-272 1" x 1296" STANDARD 0.4 DENSITY INDUSTRIAL GRADE The information contained herein is produced in good faith and is believed to be reliable but is for guidance only. ARGCO and its agents cannot assume liability or responsibility for results obtained in the use of its product by persons whose methods are outside or beyond our control. It is the user's responsibility to determine the suitability of any of the products, methods of use, or preparation prior to use, mentioned in our literature. It is the user's responsibility to observe and adapt such precautions as may be advisable for the protection of personnel and property in the handling and use of any of our products. FOR MORE INFORMATION CALL ARGCO AT 1-800-854-1015 OR LOG ONTO WWW.ARGCO.COM