RE:CERTIFICATION LETTER
Project Address: Thomas Residence
2006 N 37th St
Fort Pierce, FL 34947
Design Criteria:
- Applicable Codes = 2020 7th Edition FBC, 2020 7th Edition FRC, ASCE 7-16, and 2018 NDS
- Risk Category = II
- Wind Speed = 160 mph, Exposure Category B, Partially/Fully Enclosed Method
- Ground Snow Load = 0 psf
- Roof 1&2: 2x6 @ 24" OC, Roof DL = 7 psf, Roof LL/SL = 20 psf (Non-PV), Roof LL/SL = 0 psf (PV)
To Whom It May Concern,
Sincerely,
July 7, 2021
Yuri Yurianto, S.E., P.E.
A jobsite survey of the existing framing system of the address indicated above was performed by Freedom Forever. All structural
evaluation is based on the site inspection observations and the design criteria listed above.
Existing roof structural framing has been reviewed for additional loading due to installation of PV Solar System on the roof. The
structural review applies to the sections of roof that is directly supporting the solar PV system.
Based on this evaluation, I certify that the alteration to the existing structure by installation of the PV system meets the requirements of
the applicable existing building and/or new building provisions adopted/referenced above.
Additionally, the PV module assembly including attachment hardware has been reviewed to be in accordance with the manufacturer’s
specifications and to meet and/or exceed the requirements set forth by the referenced codes.
Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com
By Yuri at 9:19:14 AM, 7/7/2021
Roof 1&2
PV module weight 2.5 psf
Hardware assembly weight 0.5 psf
PV-DL 3 psf
Existing Roofing Material Comp Roof 1 layers 2.5 psf
Underlayment 0.5 psf
Plywood Sheathing 1.5 psf
Rafter Size and Spacing 2 x 6 @ 24 in. O.C.1.15 psf
Vaulted ceiling No 0 psf
Miscellaneous 1.5 psf
Total Roof Dead Load R-DL 7 psf
Expression
Roof Live Load Lo 20.0 psf
Member Tributary Area At < 200 sf
Roof 1&2 Roof Pitch 5/12 or 20°
Trubutary Area Reduction R1 1
Slope Roof Reduction R2 0.975
Reduced Roof Live Load Lr = Lo (R1) (R2)19.5 psf
Ground Snow Load pg 0
Effective Roof Slope 20°
Snow Importance Factor Is 1.0
Snow Exposure Factor Ce 1.0
Snow Thermal Factor Ct 1.1
Minimum Flat Roof Snow Load pf-min 0
Flat Roof Snow Load pf 0
Roof Slope Factor Cs-roof 1.00
ps-roof 0.00
Roof Slope Factor Cs-pv 0.83
ps-pv 0.00
Snow Load
Sloped Roof Snow Load on PV
Slope Roof Snow Load on Roof
Value
Material Panel AreaRoof Dead Load (R-DL)
Reduced Roof Live Load (Lr)
PV System Dead Load (PV-DL)
(All other surfaces)
(Unobstructed slippery surfaces)
Value
Barun Corp | Design and Engineering | 610.202.4506 | chrisk@barun-corp.com | www.barun-corp.com
COMPANY
July 7, 2021 19:30
PROJECT
Thomas Residence
Roof 1&2
Design Check Calculation Sheet
WoodWorks Sizer 2019 (Update 2)
Loads:
Load Type Distribution Pat- Location [ft] Magnitude Unit
tern Start End Start End
DL Dead Full Area No 7.00(24.0") psf
DL-PV Dead Partial Area No 3.00 11.50 3.00(24.0") psf
RFL Roof live Partial Area No 0.00 3.00 19.50(24.0") psf
RFL1 Roof live Partial Area No 11.50 12.50 19.50(24.0") psf
Maximum Reactions (lbs), Bearing Capacities (lbs) and Bearing Lengths (in) :
1.5'
1 3 .5 4 2 '
12.467'0'
Unfactored:
Dead 134 111
Roof Live 118 38
Factored:
Total 252 149
Bearing:
F'theta 471 471
Capacity
Joist 619 353
Support 586 469
Des ratio
Joist 0.41 0.42
Support 0.43 0.32
Load comb #2 #2
Length 0.50* 0.50*
Min req'd 0.21** 0.21
Cb 1.75 1.00
Cb min 1.75 1.00
Cb support 1.25 1.00
Fcp sup 625 625
*Minimum bearing length setting used: 1/2" for end supports and 1/2" for interior supports
**Minimum bearing length governed by the required width of the supporting member.
Roof 1&2
Lumber-soft, S-P-F, No.1/No.2, 2x6 (1-1/2"x5-1/2")
Supports: All - Timber-soft Beam, D.Fir-L No.2
Roof joist spaced at 24.0" c/c; Total length: 13.75'; Clear span(horz): 1.5', 10.938'; Volume = 0.8 cu.ft.; Pitch: 5/12
Lateral support: top = continuous, bottom = at supports; Repetitive factor: applied where permitted (refer to online help);
This section PASSES the design code check.
Analysis vs. Allowable Stress and Deflection using NDS 2018 :
Criterion Analysis Value Design Value Unit Analysis/Design
Shear fv = 25 Fv' = 135 psi fv/Fv' = 0.18
Bending(+) fb = 495 Fb' = 1177 psi fb/Fb' = 0.42
Bending(-) fb = 97 Fb' = 981 psi fb/Fb' = 0.10
Live Defl'n 0.01 = < L/999 0.59 = L/240 in 0.02
Total Defl'n 0.41 = L/344 0.79 = L/180 in 0.52
WoodWorks® Sizer SOFTWARE FOR WOOD DESIGN
WoodWorks® Sizer 2019 (Update 2) Roof 1&2 Page 2
Additional Data:
FACTORS: F/E(psi) CD CM Ct CL CF Cfu Cr Cfrt Ci Cn LC#
Fv' 135 1.00 1.00 1.00 - - - - 1.00 1.00 1.00 2
Fb'+ 875 0.90 1.00 1.00 1.000 1.300 - 1.15 1.00 1.00 - 1
Fb'- 875 1.00 1.00 1.00 0.750 1.300 - 1.15 1.00 1.00 - 2
Fcp' 425 - 1.00 1.00 - - - - 1.00 1.00 - -
E' 1.4 million 1.00 1.00 - - - - 1.00 1.00 - 2
Emin' 0.51 million 1.00 1.00 - - - - 1.00 1.00 - 2
CRITICAL LOAD COMBINATIONS:
Shear : LC #2 = D + Lr
Bending(+): LC #1 = D only
Bending(-): LC #2 = D + Lr
Deflection: LC #2 = D + Lr (live)
LC #2 = D + Lr (total)
Bearing : Support 1 – LC #2 = D + Lr
Support 2 – LC #2 = D + Lr
D=dead Lr=roof live
All LC's are listed in the Analysis output
Load combinations:
CALCULATIONS:
V max = 158, V design = 136 lbs; M(+) = 312 lbs-ft; M(-) = 61 lbs-ft
EIy = 29.12 lb-in^2
"Live" deflection is due to all non-dead loads (live, wind, snow…)
Total deflection = 1.5 dead + "live"
Bearing: Allowable bearing at an angle F'theta calculated for each support
as per NDS 3.10.3
Lateral stability(-): Lu = 11.88' Le = 18.50' RB = 23.3; Lu based on full span
Design Notes:
1. Analysis and design are in accordance with the ICC International Building Code (IBC 2018) and the National Design
Specification (NDS 2018), using Allowable Stress Design (ASD). Design values are from the NDS Supplement.
2. Please verify that the default deflection limits are appropriate for your application.
3. Continuous or Cantilevered Beams: NDS Clause 4.2.5.5 requires that normal grading provisions be extended to the
middle 2/3 of 2 span beams and to the full length of cantilevers and other spans.
4. Sawn lumber bending members shall be laterally supported according to the provisions of NDS Clause 4.4.1.
5. SLOPED BEAMS: level bearing is required for all sloped beams.
6. The critical deflection value has been determined using maximum back-span deflection. Cantilever deflections do not
govern design.
Ultimate Wind Speed (mph)160 Roof Pitch (degrees) 20
Risk Category II Roof Type Gable
Exposure Category B Kd 0.85
Mean Roof Height (ft)15 Kzt 1
PV DL (psf)3 Kz 0.57
qh = 0.00256*Kz*Kzt*Kd*V^2 = 32.02
a (ft) = 4.00
array edge factor γE= 1.00
Solar panel pressure eq. factor γa= 0.8
Hardware Type
Allowable Load (lb) 982.50 lbs for S pine 2.5" Embed
Maximum X - Spacing (ft) (Zone 1,2e) 4.00
Maximum Y - Spacing (ft) (Zone 1,2e)1.70
Maximum X - Spacing (ft) (Zone 2n-3r) 3.00
Maximum Y - Spacing (ft) (Zone 2n-3r)1.70
Roof Zone GCp (-) Uplift Uplift Pressure (psf) Pullout Force (lbs)
1,2e -2.00 -29.04 197.49
2n,2r,3e -3.00 -44.41 226.49
3r -3.60 -53.63 273.52
Site Information
Design Calculations
Design Wind Pressure Calculation for Solar Panel on Roof
Effective Wind Area (ft2)
for d1 < 0.5 h = 7.5 ft
* Wind Calculation is based on ASCE7-16, 29.4 - C&C
6.80
Effective Wind Area (ft2)
5.10
PLAN