HomeMy WebLinkAboutPROJECT INFORMATION'VikAtlg L- VJ I -J LL-T
42-r-10 N A t A. AA, cl 1s
Transferring
•GeneratorPower�' •
wer
1. Return all circuit selector switches to the LINE position,
2. Follow the procedures in the generator owner's manual to turn off the generator.
3. Unplug the power cord.
Model#
A304
A306
A506
A308
A310
A510
Max. Watts
7500
7500
12500
7500
7500
12500
Max sipg1e7pole circuits
Max. double -pole and multi -wire
circuits
4,
6
6
8
10
10
2
3
3
4
5
5
# of handle ties provided
1
1
1
2
2
2
Max. combined loads @ 125
VAC
60A
60A
100A
60A
60A
100A
Max. combined loads
@ 250VAC
30A
30A
50A
30A
30A
50A
Max. load/circuit from generator
2-30A
2-20A
2-30A
4-20A
2-30A
4-20A
2-30A
6-20A
2-30A
8-20A
2-30A
8-20A
Max. load/circuit from load
center
2-30A
2-20A
2-30A
4-20A
2-30A
4-20A
2-30A
6-20A
2-30A
8-20A
2-30A
8-20A
Power inlet, NEMA*
configuration
L14-30
L14-30
CS6375
non-NEMA
L14-30
L14-30
CS6375
non-NEMA
Minimum cord gauge
AWG 10
AWG 10
AWG 6
AWG 10
AWG 10
4
AWG 6
4
No. of conductors (wires)
4
4
4
4
Conduit length
18"
18"
18"
18'
18"
18°,
Conduit, trade -size diameter
3/a"
/a"
1"
1"
1„
Optional Power Inlet Catalog #
PB30
[LT;PB50
PB30
PB30
PB50
*National Electrical
Manufacturer's Association
Watt Meters AIE�� ao.
(select models only)
Tie
witches A e C D F
allrs
PRO/TRAM` 2
O
Handle
Circuit Selector S
Circuit Breake
Circuit Breaker
Compartment
Cover
a
Power Inlet Filler Plate
(indoor Models)
or
Power Inlet
(Outdoor Models)
Circuit breakers. Each transfer switch circuit has a 1-in interchangeable circuit breaker
that protects the branch circuit when the circuit selector switch is in the GEN position. In
the LINE position, each branch circuit is protected by the breaker in the load center.
Circuit selector switches. These switches allow you to select either GEN (generator) or
LINE (utility) as the power source for the branch circuits that have been wired through the
transfer switch. The OFF position is generally not used, as a switch in the OFF position
removes that branch circuit from both utility and generator power.
Handle ties. Handle ties are used for 240-volt circuits or multi -wire branch circuits. They
may be removed for 120-volt circuits. See page 6 for instructions on removing and adding
handle ties.
Power inlet filler plate. This can be replaced with a power inlet that is included in the
suffix A and B models (see page 7 for installation instructions). The power cord from the
generator is plugged into this inlet. The inlet is supplied separately for indoor models to
encourage the use of a remote connection outdoors reducing the likelihood of running the
generator indoors which is extremely dangerous. If this indoor model is installed outdoors,
make sure it is installed in a dry location.
Circuit Breaker Compartment Cover. Remove to change circuit breakers. Also includes
a wiring space that can be used to hard -wire the unit to a remote power inlet box.
Analog wattmeters (suffix A and C models). These meters indicate the total load,
watts, on each side of the enerator when the generator is s, jnnlvinn nn%A/ar no T. 11^,a
The left meter measures the load on
A, C, and E 6-circuit
A,C,E, and G 8-circuit
A, C, E, G and I 10-circuit
The right meter measures the load onv
B, D and F 6-circuit
B,D,F and H 8-circuit
LB, D, F, H and J 10-circuit
®yore: ► "E;watt meters will register only if power is being used from the generator.
2