HomeMy WebLinkAboutWeathermaster 200 peel n stick CREEK
Technical Services, LLC
ATL14001.7A FL17322-R7 Page 1 of 6
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that a re not
specifically addressed herein.
Certificate of Authorization No. 29824
17520 Edinburgh Dr
Tampa, FL 33647
(813) 480-3421
EVALUATION REPORT FLORIDA BUILDING CODE, 7TH EDITION (2020)
Manufacturer: ATLAS ROOFING CORPORATION Issued October 16, 2020
2000 Riveredge Parkway, Suite 800
Atlanta, GA 30328
(770) 612-6267
www.atlasroofing.com
Quality Assurance: PRI Construction Materials Technologies, LLC (QUA9110)
SCOPE
Category: Roofing
Subcategory: Underlayments
Code Edition: Florida Building Code, 7th Edition (2017) including High-Velocity Hurricane Zones
(HVHZ)
Code Sections: 1507.1.1, 1518.4, 1523.1.1, 1523.6.5.2.1
Properties: Physical properties
REFERENCES
Entity Report No. Standard Year
PRI Construction Materials Technologies (TST6049) ATL-033-02-01 ASTM D 226 2009
PRI Construction Materials Technologies (TST6049) ATL-068-02-01 ASTM D 1970
ASTM D 4798
TAS 110
2015a
2011(2016)
2000
PRI Construction Materials Technologies (TST6049) ATL-069-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) ATL-149-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) ATL-164-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) ATL-254-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) ATL-255-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) BWR-534-02-01 ASTM D 1970
ASTM D 4798
TAS 110
2015a
2011(2016)
2000
PRI Construction Materials Technologies (TST6049) BWR-543-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) MSA-004-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) MSA-007-02-01 UL 1897 2012
PRI Construction Materials Technologies (TST6049) MSA-026-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) WRMI-011-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) MSA-004-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) MSA-007-02-01 UL 1897 2012
PRI Construction Materials Technologies (TST6049) MSA-026-02-01.1 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) MSA-030-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) MSA-047-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) MSA-054-02-01.1 TAS 103
TAS 110
2020
2000
PRI Construction Materials Technologies (TST6049) MSA-057-02-01 ASTM D 1970 2015a
PRI Construction Materials Technologies (TST6049) MSA-062-02-01.1 ASTM D 1623 2017
PRI Construction Materials Technologies (TST6049) 1085T0002 TAS 110 2000
PRI Construction Materials Technologies (TST6049) 1085T0007 ASTM D 1623 2017
PRI Construction Materials Technologies (TST6049) 117T0001 ASTM D 1623 2017
PRI Construction Materials Technologies (TST6049) 117T0004 TAS 110 2000
PRI Construction Materials Technologies (TST6049) 117T0005 UL 1897 2012
PRI Construction Materials Technologies (TST6049) 1085T0011 ASTM D 1623
TAS 103
2017
2020
UL LLC (TST1740) 02-NK40952 ASTM D 1970 2015a
UL LLC (TST1740) 02-NK40952 ASTM D 226 2009
UL LLC (TST1740) 02-NK40952 ASTM D 2626 2004(2012)E1
UL LLC (TST1740) 02-NK40952 ASTM D 4869 2016
UL LLC (TST1740) 02-NK40952 ASTM D 6380 2003 (2013)E1
A CREEK
Technical Services, LLC
ATL14001.7A FL17322-R7 Page 4 of 6
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that a re not
specifically addressed herein.
ATLAS ROOFING CORPORATION
Roofing Underlayments
PRODUCT DESCRIPTION
#15 Specification Felt ASTM D 226, Type I asphalt saturated organic felt underlayment for use in the
HVHZ.
#30 Organic Saturated Felt ASTM D 4869, Type II asphalt saturated organic felt underlayment for use in the
non-HVHZ only.
#30 Specification Felt ASTM D 226, Type II asphalt saturated organic felt underlayment for use in the
HVHZ and non-HVHZ.
#43 Base Sheet ASTM D 2626 asphalt saturated and coated, non-perforated, organic felt
underlayment for use in the HVHZ and non-HVHZ.
#90 Mineral Surface Roll
Roofing
ASTM D 6380, Class M asphalt-saturated organic roll roofing sheet for use in the
HVHZ and non-HVHZ.
Gorilla Guard® EVERFELT 30 Asphalt-saturated organic felt underlayment reinforced with glass fiber that meets
the performance requirements of ASTM D 226, Type I for use in the HVHZ.
Slate/Tile Underlayment ASTM D 6380, Class M asphalt-saturated organic roll roofing sheet for use in the
HVHZ and non-HVHZ.
WeatherMaster® Ice and
Water 100
ASTM D 1970 SBS modified, self-adhering underlayment reinforced with a
fiberglass mat and a granular surface for use in the HVHZ and non-HVHZ. The
self-adhesive side is covered with a release film, which is removed during
installation.
WeatherMaster® Ice and
Water 200
ASTM D 1970 SBS modified, self-adhering underlayment reinforced with a
fiberglass mat and a granular surface for use in the HVHZ and non-HVHZ. The
self-adhesive side is covered with a split-release film, which is removed during
installation.
WeatherMaster® Ice and
Water 216
ASTM D 1970 SBS modified, self-adhering underlayment reinforced with a
fiberglass mat and a granular surface for use in the HVHZ and non-HVHZ. The
self-adhesive side is covered with a split-release film, which is removed during
installation.
WeatherMaster® Flexible Ice
and Water
ASTM D 1970 SBS modified, self-adhering underlayment with plastic film surface
for use in the HVHZ and non-HVHZ. The self-adhesive side is covered with a
split-release film, which is removed during installation.
WeatherMaster® Pro-Grade
Ice and Water
ASTM D 1970, TAS 103, and FRSA/TRI Florida High Wind Concrete and Clay
Tile Installation Manual, Sixth Edition compliant compliant SBS modified, self-
adhering underlayment with a fiberglass mat reinforcement and a poly -fabric
surface for use in the HVHZ and non-HVHZ. The self-adhesive side is covered
with a release film, which is removed during installation.
WeatherMaster® Tile ASTM D 1970, TAS 103, and FRSA/TRI Florida High Wind Concrete and Clay
Tile Installation Manual, Sixth Edition compliant compliant SBS modified, self-
adhering underlayment with a fiberglass mat reinforcement and a poly-fabric
surface for use in the HVHZ and non-HVHZ. The self-adhesive side is covered
with a release film, which is removed during installation.
A CREEK
Technical Services, LLC
ATL14001.7A FL17322-R7 Page 4 of 6
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that a re not
specifically addressed herein.
ATLAS ROOFING CORPORATION
Roofing Underlayments
APPLICATION METHOD
Installation shall be in accordance with the published manufacturer’s installation instructions, the FBC, and the
requirements below.
Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck shall be
checked for protrusion and corrected prior to underlayment application.
The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction. Plywood deck
shall be installed in accordance with FBC requirements. Roof decks shall have no more than 1/8” gap at abutting
joints.
Exposure of the underlayments shall be limited to a maximum 30 days except as follows:
a) #15 Specification Felt, #30 Specification Felt, and #40 Base Sheet – exposure for greater than 24 hours
may adversely affect product performance
b) WeatherMaster® Ice and Water 100, WeatherMaster® Ice and Water 200, WeatherMaster® Ice and
Water 216 – maximum 45 days
c) WeatherMaster® Pro-Grade Ice and Water – maximum 180 days
d) WeatherMaster® Tile – maximum 180 days
Self-adhering underlayments may be adhered to primed or unprimed plywood substrates in the non-HVHZ.
Roof coverings shall be mechanically fastened through the underlayment to the roof deck except as follows (or as
indicated in other current FBC product approval documents):
a) WeatherMaster® Pro-Grade Ice and Water – DAP Touch ‘n Seal Storm Bond Roof Tile Adhesive or
DuPont Tile Bond
b) WeatherMaster® Tile – DAP Touch ‘n Seal Storm Bond Roof Tile Adhesive or DuPont Tile Bond
Allowable Roof Coverings:
Underlayment
Asphalt
Shingles
Metal Roof
Panels and
Shingles
Composite
or
Photovoltaic
Shingles
Wood
Shingles
and Shakes
Slate
Shingles
Clay and
Concrete
Tile
#15 Specification Felt (HVHZ
only) Y Y N Y2 Y N
#30 Organic Saturated Felt Y Y Y Y Y N
#30 Specification Felt Y Y Y Y Y Y
#43 Base Sheet Y Y Y N Y Y
#90 Mineral Surface Roll
Roofing Y1 N N N N Y
Gorilla Guard® EVERFELT 30 Y Y Y Y2 Y N
Slate/Tile Underlayment Y1 N N N N Y
WeatherMaster® Ice and
Water 100 Y Y Y N Y N
WeatherMaster® Ice and
Water 200 Y Y Y N Y N
WeatherMaster® Ice and
Water 216 Y Y Y N Y N
WeatherMaster® Flexible Ice
and Water Y Y Y N Y N
WeatherMaster® Pro-Grade
Ice and Water Y Y Y N Y Y
WeatherMaster® Tile Y Y Y N Y Y
Notes: 1) Open valley applications per 1507.2.9.2
2) Wood shingles only
A CREEK
Technical Services, LLC
ATL14001.7A FL17322-R7 Page 4 of 6
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that a re not
specifically addressed herein.
ATLAS ROOFING CORPORATION
Roofing Underlayments
WIND RESISTANCE (NON-HVHZ ONLY)
The Maximum Design Pressures shown below were calculated using a 2:1 margin of safety per FBC Section 1504.9.
Underlayment System No.1 – WeatherMaster® Tile only
Roof Deck: Min. 15/32-inch CDX plywood attached to wood supports spaced a maximum 24” o.c.
Underlayment: WeatherMaster® Tile shall be fully adhered to the optionally primed plywood deck.
Maximum Design
Pressure:
-52.5 psf
Underlayment System No.2 – WeatherMaster® Pro-Grade Ice and Water only
Roof Deck: Min. 15/32-inch APA plywood attached to wood supports spaced a maximum 24” o.c.
Underlayment: WeatherMaster® Pro-Grade Ice and Water shall be backnailed 12-inches o.c. to the
plywood deck using min. 12ga, 1-1/4” galvanized, ring shank roofing nails with min. 32ga
1-5/8” diameter tin caps.
Maximum Design
Pressure:
-105 psf
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Roof slope limitations shall be in accordance with FBC requirements.
3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer’s published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) Products described within this report may be used as described in other current FBC product approval
documents.
5) Roof coverings shall not be adhered directly to the underlayment unless otherwise approved in this or other
current FBC product approval documents.
6) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
A CREEK
Technical Services, LLC
ATL14001.7A FL17322-R7 Page 4 of 6
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
ATLAS ROOFING CORPORATION
Roofing Underlayments
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest P.E. have demonstrated compliance with the Florida Building
Code, 7th Edition (2020) including High-Velocity Hurricane Zones (HVHZ) as evidenced in the referenced documents
submitted by the named manufacturer.
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT