HomeMy WebLinkAboutAPPROVED MYERS boral_estate__s__tile_product_approval_.pdfMIAMI-DADE COUNTY
M��IA��MI•I]�AI}l± PRODUCT CONTROL SECTION
►�11L11� 11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (7M) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) %iiig.miamidade.gov/economv
Boral Roofing, LLC
7575 Irvine Center Drive, Suite 100
Irvine, CA 92618
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER -Product Control Section to be
used in Miami -Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (in
Miami -Dade County) and/or the AHJ (in areas other than Miami -Dade County) reserve the right to have this product or
material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the
manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of
such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is determined by
Miami -Dade County Product Control Section that this product or material fails to meet the requirements of the applicable
building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code including
the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Estate "S" Tile
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in
the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for
sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall
be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA No, 19-1021,03 and consists of pages 1 through 9.
The submitted documentation was reviewed by Freddy Sentino
NOA No. 21-0107.03
M AMMADE COUNTY Expiration Date: 08/23/21
Approval Date: 03104/21
Page 1 of 9
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub Category: Roofing Tiles
Material: Concrete
1. SCOPE
This approves a roofing system using Boral Estate "S" Concrete Roof Tile, as manufactured by Boral Roofing, LLC in
Okeechobee, FL as described in Section 2 of this Notice of Acceptance, designed to comply with the Florida Building
Code for High Velocity Hurricane Zone. For use in locations where the pressure requirements, as determined by
applicable Building Code, do not exceed the design pressure values obtain by calculations in compliance with RAS 127
using the values listed in section 4 herein. The attachment calculations shall be prepared as a moment based system.
2. PRODUCT DESCRIPTION
Manufactured by Dimensions
Applicant
Boral Estate `S' Roof Tile Length = 16-1/2"
Width = 13"
Trim Pieces
1= varies
w = varies
varying thickness
2.1 MANUFACTURING LOCATION
1. Okeechobee, FL
Test
Product
Specifications
Description
TAS 112
Low profile, interlocking, extruded
Type lb
concrete roof tile equipped with two nail
Class III
hole and double roll ribs. For direct deck
or battened nail -on, mortar or adhesive
set applications.
TAS 112
Accessory trim, concrete roof pieces for
use at hips, rakes, ridges and valley
terminations. Manufactured for each tile
profile.
2.2 PRODUCTS MANUFACTURED BY OTHERS
Product Name
ICP Adhesives Polyset® AH-160
TILE BONDTM Roof Tile Adhesive
Product Description
Two component polyurethane
foam adhesive.
Single component polyurethane
foam roof tile adhesive.
Touch 'N Seal StormBond® 2 Two- Two component polyurethane
Component Polyurethane Roof Tile foam adhesive.
Adhesive
Manufacturer
(With Current NOA)
ICP Adhesives and Sealants, Inc.
DuPont de Nemours, Inc.
DAP Foam, Inc.
NOA No. 21-0107.03
Expiration Date: 08/23/21
Approval Date: 03/04/21
Page 2 of 9
2.3 EVIDENCE SUBMITTED:
Test Aeency
Test Identifier
Test Name/Report
Date
Redland Technologies
7161-03
PA 102
Dec. 1991
7161-03
PA 102(A)
Dec. 1991
7161-03
PA 108
Dec. 1991
P0402
Withdrawal Resistance Testing of
Sept. 1993
screw vs. smooth shank nails
P0631-01
PA 108
July 1994
Letter Dated Aug. 1, 1994
PA 108
Aug. 1994
Professional Service
22447099
PA 112
Sept. 1994
Industries, Inc.
The Center for Applied
94-060B
PA 101
March, 1994
Engineering, Inc.
94-084
PA 101
May 1994
25-7094-1
PA 102
Oct. 1994
25-7094-7
PA 102
Oct. 1994
25-7094-4
PA 102
Oct. 1994
Project No. 307025
PA 100
Oct. 1994
Test #MDC-76
25-7183-1
PA 102
Feb. 1995
25-7183-2
PA 102
Feb. 1995
25-7214-2
PA 102
March, 1995
25-7214-6
PA 102
March, 1995
Celotex Corporation Testing
528454-2-1
PA 101
Sep. 1998
Services
520109-2
Dec. 1998
Walker Engineering, Inc.
Calculations
Aerodynamic Multiplier
March 1999
IBA Consultants, Inc.
2381-264
TAS 112
01/08/08
American Test Lab of South
RT1210.03-15
TAS 112
12/17/15
Florida
PRI Construction Material
DAPF-004-02-05
TAS 101
07/26/18
Technologies
DAPF-004-02-07
Static Uplift Resistance
07/26/18
(Adhesive Set)
NEMO ETC, LLC
4c-DPBS-20-LSOTM-0l.C.R1
TAS 101
12/17/20
3. LIMITATIONS:
3.1 Fire classification is not part of this acceptance.
3.2 For mortar or adhesive set tile applications, a static field uplift test in accordance with TAS 106 may
required, refer to applicable building code.
3.3 Applicant shall retain the services of a Miami -Dade County Certified Laboratory to perform quarterly test in
accordance with TAS 112, appendix `A'. Such testing shall be submitted to the Miami -Dade Product
Control Section for review.
3.4 Minimum underlayment shall be in compliance with the applicable Roofing Applications Standards listed
section 4.1 herein.
3.5 Minimum slope 4/12 for mechanically attached tile.
NOA No. 21-0107.03
Expiration Date: 08/23/21
Approval Date: 03/04/21
Page 3 of 9
3.6 30/90 hot mopped underlayment applications may be installed perpendicular to the roof slope unless stated
otherwise by the underlayment material manufacturers published literature.
3.7 This acceptance is for wood deck applications. Minimum deck requirements shall be in compliance with
applicable building code.
3.7 All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code
and Rule 61 G20-3 of the Florida Administrative Code.
4. INSTALLATION
4.1 Boral Estate "S" Concrete Roof Tile and its components shall be installed in strict compliance with Miami
Dade County Roofing Application Standard RAS 118, RAS 119, and RAS 120.
4.2 Data For Attachment Calculations.
Table 1: Average Weight (W) and Dimensions (I x w )
Tile Profile
Weight-W (Ibf)
Length -I (ft.)
Width w (ft.)
Boral Estate 'S' Roof Tile
10.0
1.375
1.08
Table 2: Aerodynamic Multipliers - X (ft3)
Tile
Profile
X (ft3)
Batten Application
)L (ft3)
Direct Deck Application
Boral Estate'S' Roof Tile
0.267
0.289
Table 3: Restoring Moments due to Gravity - M9 (ft. Ibf)
Tile
Profile
3":12"
4":12"
5":12"
6":12"
Greater than
7":12"
Boral Estate 'S'
Roof Tile
Battens
Direct
Deck
Battens
Direct
Deck
Battens
Direct
Deck
Battens
Direct
I Deck
Battens
Direct
Deck
NIA
6.74
1 5.82
6.64
1 5.70
6.50
1 5.56
1 6.33
1 5.40
6.14
Table 4: Attachment Resistance Expressed as a Moment - Mr (ft-lbf)
for Nail -On Systems
Tile
Fastener Type
Direct Deck
Direct Deck
Battens
Profile
(min 15/32" plywood)
(min.19/32" plywood)
Boral Estate
2-10d Ring Shank Nails
27.8
37.4
28.8
'S' Roof Tile
1-10d Smooth or Screw
8.8
11.8
4.1
Shank Nai12
2-10d Smooth or Screw
16.4
21.9
7.1
Shank Nails
1 #8 Screw2
25.8
25.8
22.9
2 #8 Screw
47.1
47.1
49.1
1-10d Smooth or Screw
24.3
24.3
24.2
Shank Nail Field Cli 2
1-10d Smooth or Screw
19.0
19.0
22.1
Shank Nail Eave Cli 2
2-10d Smooth or Screw
35.5
35.5
34.8
Shank Nails Field Clip)
NOA No. 21-0107.03
Expiration Date: 08/23/21
Approval Date: 03/04/21
Page 4 of 9
2-10d Smooth or Screw
Shank Nails Eave Clip)
31.9
31.9
7-5-2.2—
2-10d Ring Shank Nails' 43.0 67.5 50.9
1 Installation with a 4" the headlap and fasteners are located a min. of 2YY' from head of tile.
2 When using only one fastener use the hole that is approximately 4-3/4" away from interlocking edge
Table 5: Attachment Resistance Expressed as a Moment Mf (ft.-Ibf)
for Two Patty Adhesive Set Systems
Tile
Tile Application
Minimum Attachment
Profile
Resistance
Boral Estate 'S' Roof Tile
Adhesive3
3
See manufactures component approval for installation requirements.
4
Dupont de Nemours, Inc, TILE BONDTm Roof Tile Adhesive weight per patty 8 grams.
* SEE NOTE* 2a
35
5
ICP Adhesives and Sealants, Inc, ICP Adhesve Polyset® AH-160 two -component foam
weight per patty 8 grams
26.1
6
DAP Foam, Inc. Touch 'N Seal StormBond® 2 Two -Component Polyurethane Roof Tile
Adhesive two -component foam weight per paddy 8 grams.
35
7
Dupont de Nemours, TILE BONDTM Roof Tile Adhesive weight per patty 16 grams.
67
* SEE NOTE* 2b
*NOTE"
SEE 2A- page 8 of 9 for details/data.
SEE 2b- page 9 of 9 for details/data.
Table 6: Attachment Resistance Expressed as a Moment - Mr (ft.-Ibf)
for Single Patty Adhesive Set Systems
Tile
Tile Application
Minimum Attachment
Profile
Resistance
Boral Estate 'S' Roof
Adhesive'
Tile
8
See manufactures component approval for installation requirements.
9
ICP Adhesives and Sealants, Inc, ICP Adhesve Polyset® AH-160 two -component
foam weight per patty 54 grams. 86.6
10
ICP Adhesives and Sealants, Inc, ICP Adhesve Polyset® AH-160 two -component
foam wei ht per patty 24 grams 45.5
11
DAP Foam, Inc.Touch 'N Seal StormBonda 2 Two -Component Polyurethane Roof Tile Adhesive 60
two -component foam weight per paddy 60 grams.
Table 7: Attachment Resistance Expressed as a Moment - Mf (ft.-Ibf)
for Mortar or Adhesive Set Systems
Tile
Tile Application
Minimum Attachment
Profile
Resistance
Boral Estate 'S' Roof
Mortar Set
20.6
Tile
NOA No. 21-0107.03
Expiration Date: 08/23/21
Approval Date: 03/04/21
Page 5 or 9
5. LABELING
All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo as seen below or following
statement: "Miami -Dade County Product Control Approved".
OR
7�7ENTENRR
BORAL ESTATE "S" TILE LABEL (LOCATED ON UNDERSIDE OF TILE)
6. BUILDING PERMIT REQUIREMENTS:
6.1 Application for building permit shall be accompanied by copies of the following:
6.1.1 This Notice of Acceptance.
6.1.2 Any other documents required by Building Official or Applicable building code in order to properly
evaluate the installation of this system.
NOA No. 21-0107.03
Expiration Date: 08/23/21
Approval Date: 03/04/21
Page 6 of 9
Nail Holes
PROFILE DRAWING
BORAL ESTATE "S" CONCRETE ROOF TILE
a
NOA No. 21-0107.03
Expiration Date: 08/23/21
Approval Date: 03/04/21
Page 7 of 9
Set No.: y _ Photograph
Interdependent: Two(2)beads/paddys,
Attachment: minimum 1` x I" x 8" minimum contact area
of 26 ml each
SET 2A
Paddy
Type I Placement
Minimum Attachment
Min. Tile Contact Characteristic Resistance Expresseo
Area, in=per Tile Resistance Force, Ibf as a Moment, ft•lbf
Attachment: Two 12) headsJpaddys,
Interdependent minimum I in. x I -in. x 8-in. 32 33 35
Adhesive Rates: 8 gram/paddy
BORAL ESTATE " S" CONCRETE ROOF TILE
NCA No. 21.0107.03
Expiration Date: 08/23/21
Approval Dote: 03/04/21
Page 8 of 9
sI
InJependenC iwo�2�bestaads/paddys,
Attachment: minimum 2' x 2' x 4 rting 1' back from
head of underlying tile, minimum contact
area of 8 in/ each
SET 2B
Photograph
Paddy _ Minimum Attachment
LTYPe
[--p—
lacement Min. Tile Contact Characteristic ResistanceExpressed
Area, In=per Tile Resistance Force, Ibf as a Moment, ft-lbf
Attachment: Two (2) beads/paddys,
Independent minimum 2-in, x 2-in. x4-in., starting 16 61 l 67
1" back from head of underlying the
Adhesive Rates: 16 gram/paddy
BORAL ESTATE "S" CONCRETE ROOF TILE
END OF THIS ACCEPTANCE
NOA No. 21-0107.03
Expiration Date: 08/23/21
Approval Date: 03/04/21
Page 9 of 9