Loading...
HomeMy WebLinkAboutdoc02652720210804151107SAINT LUCIE COUNTY FiR}, 011STRICr- PLAN REVIEW FORM 5160 N.W. !Milner U.rsve Port Saint Lu.ie, F: 3198- Telephoner 772-62-3322 Fax: 772-621-.3 ,C Web Address: vrwu'.si.,d.r alr Building Dept. LSLC --_--` Project Name JAurozone Address 4892 Forth Kings Hwy - --- — Contractor Address FMO Permit # B-21-302 —^--- --_ - BLDG Permit # 12106 0224 City Ft Pierce Hann. Design Group 1955 Va st Downey Place 'A Sri. I! zip '00506 Architect/Engineer Phil "Pcord Occupancy Type lA4erc•;r.t':_ ------------ --------_.—_.i Telepnone Cons:rvction Type i'IE -.-_._.--___ .._—.__ i 7 Occupant Load 1122 pet pi&n. ; Number of Stories AFSPermit !Required FA Permit 'RCGllired General Notes t Telephone �847) 719-b376 90 t 1495-8716 Square Feet 7343 ?equirec Access Key Switch —� FFP Fermit 1. An electronic copy of tic construction documents subiri+ted on a CD is required. The file format shall be .pdf only. 2. All revisions, including the electronic copy must be received prior to permitting. 3. The Fire Marshal requires 24 hour notice on all inspections. 4. A Radio coverage Pre Surrey Signal StrenSth inspection is required before any final inspection is schedulec.. 5. The respective Building DepartL-rent shall schedule all final inspections ,:hough the Fira Marshal's Office. 6. Failed inspections require payment- Jaf fee prior to rescheduling of further inspect;oni.. 7. Penetrations through rated asserrrblies shall be of the proper Ul. design. Design criteria shall be submitted with the construction plans. 8. Fire alarm panels shall be located -indoors within air conditioned space. 9. Plans and construction are oubject to corrections in the field to maintain code compliance. 10. Automatic fan st,utdown is required for HVAC system/s that exceed 2,000 cfm design capacity. 11. The Installation or Alteration of Fire Sprint ier-, Fire Alarms, and Fired Fire Protection Systems require a separate review and permit. THE CURRENTLY ADOPTED Vi RSION OF THE FLORIDA FIRE PREVENTION CODE IS ENFORCED. BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUC nON SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3,012 AND 69A-E0.0081 PRIOR TO RECEIVING A CERTIFICATE OF OCCUPANCY. See General Notes Above and Reciulrad Revisions Below ?. A separate review and hermit is requii d for the insta!!ati r or alteration of the f -e alarm and fire sprinkler systems. 2. Automatic fan shutdown i5 required for HVAC systerws that exceed 2,000 cfm design capacity. Provide a remote _est and 1inspect appliance equipped with an audibie/visua;,indicatcr for each HVAC duct smoke detector. HVAC duct smoke detector(s) shall be tied into the fire aiarm sv;tem. 3. Portable fits extinguishers from a licensed c�mtractc- ar& required j Page �� of 1 Reviewed sy i^U_'y jerger — — -i Date j08-03-20, j