HomeMy WebLinkAboutHIGH EFFICIENCY AIRCONDITIONING421 21 6201 05 5/17/19Specifications subject to change without notice.
HIGH EFFICIENCY 16 SEER AIR CONDITIONER
ENVIRONMENTALLY BALANCED R−410A REFRIGERANT
1½ THRU 5 TONS SPLIT SYSTEM208 / 230 Volt, 1−phase, 60 Hz
REFRIGERATION CIRCUIT
Scroll compressors on select models
Filter−Drier supplied with every unit for field installation
Copper tube / aluminum fin coil
EASY TO INSTALL AND SERVICE
Easy Access service valves on all models
External high and low refrigerant service ports
Only two screws to access control panel
Factory charged with R−410A refrigerant
BUILT TO LAST
Baked−on powder coat finish over galvanized steel
Post−painted (black) coil fins
Coated, weather−resistant cabinet screws
Coated inlet grille with 3/8” (10mm) spacing for extra
protection
LIMITED WARRANTY*
5 year compressor limited warranty
5 year parts limited warranty (including compressor and
coil)
− With timely registration, an additional 5 year parts limited
warranty (including compressor and coil)
*For owner occupied, residential applications only. Seewarranty certificate for complete details andrestrictions, including warranty for other applications...
This product has been designed and manufactured tomeet ENERGY STAR criteria for energy efficiency whenmatched with appropriate coil components. However,proper refrigerant charge and proper air flow are criticalto achieve rated capacity and efficiency. Installation ofthis product should follow the manufacturer’s refrigerantcharging and air flow instructions. Failure to confirmproper charge and airflow may reduce energy efficiencyand shorten equipment life.
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org .
Model
Number
Size
(tons)
Nominal
BTU/hr
Min. Circuit
Ampacity
Max. Fuse
or Breaker
Operating Dimensions
height x width x depth in. (mm)
Ship / Operating
Weight lbs. (kg)
NXA618GKA 1½18,000 11.8 20 28−11/16 x 25−3/4 x 25−3/4
(729 x 654 x 654)
154 / 125
(70 / 57)
NXA624GKA 2 24,000 17.7 30 28−5/16 x 31−3/16 x 31−3/16
(719 x 792 x 792)
147 / 183
(83 / 67)
NXA630GKA 2½30,000 16.8 25 32−5/16 x 31−3/16 x 31−3/16
(821 x 792 x 792)
188 / 153
(85 / 69)
NXA636GKB 3 36,000 17.5 30 28−5/16 x 35 x 35
(719 x 889 x 889)
204 / 165
(93 / 75)
NXA642GKA 3½42,000 23.6 40 39−1/8 x 35 x 35
(994 x 889 x 889)
254 / 213
(115 / 96)
NXA648GKA 4 48,000 26.1 40 39−1/8 x 35 x 35
(994 x 889 x 889)
317 / 264
(144 / 120)
NXA660GKB 5 60,000 32.4 50 45−11/16 x 35 x 35
(1161 x 889 x 889)
318 / 280
(144 / 127)
NXA6
Performance Series
Product Specifications
PRODUCT SPECIFICATIONS Split System Air Conditioner: NXA6
2 421 21 6201 05Specifications subject to change without notice.
OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE (single phase)
Digit Position:1 2 3 4 5, 6 7 8 9 10 11 12
Example Part Number:N X A 6 18 G K A 1 0 0
T = Tempstar Mainline
N = Tempstar Entry BRANDING
X = R−410A REFRIGERANT
A = Air Conditioner
H = Heat Pump TYPE
4 = 14 SEER
6 = 16 SEER NOMINAL EFFICIENCY
18 = 18,000 BTUH = 1½ tons
24 = 24,000 BTUH = 2 tons
30 = 30,000 BTUH = 2½ tons
36 = 36,000 BTUH = 3 tons
42 = 42,000 BTUH = 3½ tons
48 = 48,000 BTUH = 4 tons
60 = 60,000 BTUH = 5 tons NOMINAL CAPACITY
A = Standard Grille
G = Coil Guard Grille
C = Coastal FEATURES
K = 208/230−1−60 VOLTAGE
Sales Code
Engineering Revision
Extra Digit
Extra Digit
ACCESSORIES PART NUMBER IDENTIFICATION GUIDE
Digit Position:1 2 3 4 5 6, 7 8, 9 10, 11
Example Part Number:N A S A 0 0 1 01 C H
N = Non−Branded BRANDING
A = Accessory PRODUCT GROUP
S = Split System (AC & HP)KIT USAGE
A = Original
B = 2nd Generation MAJOR SERIES
0 = Generic or Not Applicable
2 = R−22
4 = R−410A REFRIGERANT
Product Identifier Number
Package Quantity
Type of Kit (Example: CH = Crankcase Heater)
INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM Lbs Kgs Lbs Kgs INCH MM INCH MM
NXA618GKA100 1 Y N N N 25 3/4 654.0 28 11/16 728.7 3/4 19.1 4 7/16 113.0 21 1/4 539.9 9 1/8 231.3 5/16 7.9 3 76.2 13 5/8 346.1 13 1/2 342.9 12 3/4 323.9 125 56.7 154 69.9 27 7/8 708.2 33 3/16 843.1
NXA624GKA100 1 Y N N N 31 3/16 792.5 28 11/16 728.7 3/4 19.1 6 9/16 166.1 24 11/16 626.3 9 1/8 231.3 5/16 7.9 3 76.2 16 406.4 16 406.4 13 330.2 147 66.7 183 83.0 33 5/16 846.6 33 3/16 843.1
NXA630GKA100 1 Y N N N 31 3/16 792.5 32 1/16 815.1 3/4 19.1 6 9/16 166.1 24 11/16 626.3 9 1/8 231.3 5/16 7.9 3 76.2 15 1/2 393.7 16 406.4 14 1/4 362.0 153 69.4 188 85.3 33 5/16 846.6 36 5/8 929.5
NXA636GKA100 1 Y N N N 35 889.0 28 11/16 728.7 7/8 22.2 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 5/16 7.9 3 76.2 16 406.4 16 406.4 13 330.2 165 74.8 204 92.5 37 1/8 943.1 33 3/16 843.1
NXA642GKA100 1 Y N N N 35 889.0 38 7/8 987.8 7/8 22.2 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 5/16 7.9 3 76.2 16 1/2 419.1 17 1/2 444.5 17 1/2 444.5 213 96.6 254 115.2 37 1/8 943.1 43 3/8 1102.2
NXA648GKA100 1 Y N N N 35 889.0 38 7/8 987.8 7/8 22.2 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 5/16 7.9 3 76.2 17 1/2 444.5 16 1/2 419.1 15 381.0 264 119.7 317 143.8 37 1/8 943.1 43 3/8 1102.2
NXA660GKB101 1 Y N N N 35 889.0 45 11/16 1160.5 7/8 22.2 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 5/16 7.9 3 76.2 17 1/8 435.0 18 3/8 466.7 21 1/4 539.8 280 127.0 318 144.2 37 1/8 943.1 50 3/16 1274.9
NXA636GKB201 2 Y N N N 35 889.0 28 11/16 728.7 7/8 22.2 6 9/16 166.1 28 7/16 722.8 9 1/8 231.3 5/16 7.9 3 76.2 16 406.4 16 406.4 13 330.2 165 74.8 204 92.5 37 1/8 943.1 33 3/16 843.1
OPERATING
WEIGHT
SHIPPING
WEIGHT
SHIPPING
LENGTH /
WIDTH (Sq.)
U.S. ECCN: Not Subject to Regulation (N.S.R.)208-230-1-60208/230-3-60460-3-60575-3-60Y=YES
N=NO
NOTE: ALL DIMENSIONS IN INCH (MM)
C
SD4943-4 REV. G
SHIPPING
HEIGHTDEFUNITSERIESELECTRICAL
CHARACTERISTICS
A B G H I J K
NOTES:
1. CENTER OF GRAVITY .
UNIT SIZE
- 23 1/8 587.3 17 7/8 454.6
18 25 3/4 654.0 20 7/16 518.5
24,30 31 3/16 792.5 22 15/16 583.2
36,42,48,60 35 889.0 26 3/4 679.7
"Y"
MINIMUM ROOF-TOP MOUNTING
PAD APPLICATION DIMENSIONS
"X"
MINIMUM GROUND MOUNTING
PAD APPLICATION DIMENSIONS PRODUCT SPECIFICATIONS Split System Air Conditioner: NXA6421 6201 053Specifications subject to change without notice.
PRODUCT SPECIFICATIONS Split System Air Conditioner: NXA6
4 421 21 6201 05Specifications subject to change without notice.
PHYSICAL DATA
Model Size 18 24 30 36 42 48 60
Nominal Cooling Capacity (BTU/hr)18,000 24,000 30,000 36,000 42,000 48,000 60,000
Nominal SEER 16.0 16.0 16.0 16.0 16.0 16.0 16.0
Sound Rating (dBA)**76 76 76 76 78 78 74
PSC Fan Motor HP 1/12 1/10 1/10 1/12 1/5 1/4 1/3
Fan RPM (single speed)1100 1100 1100 830 830 830 817
Fan CFM 1900 2600 2600 3200 3800 4100 4000
Coil Face Area ft2 (m2)11.47
(1.1)
15.07
(1.4)
17.22
(1.6)
17.58
(1.6)
25.12
(2.3)
25.12
(2.3)
30.15
(2.8)
Coil Rows − fins per inch 1 − 25 1 − 25 1 − 25 1 − 25 1 − 25 2 − 20 2 − 20
Liquid Line Connection Size in. (mm)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)
Vapor Line Connection Size in. (mm)3/4 (19)3/4 (19)3/4 (19)7/8 (22)7/8 (22)7/8 (22)7/8 (22)
Rated Line Set Liquid Tube Diameter in.
(mm)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)
Rated Line Set Vapor Tube Diameter in. (mm)3/4 (19) *3/4 (19) *3/4 (19) *7/8 (22)*7/8 (22)*7/8 (22)*1−1/8
(29)*
Factory Charge R−410A lbs. (kg)4.61
(2.09)
6.00
(2.72)
6.81
(3.09)
7.00
(3.18)
8.62
(3.91)
13.00
(5.90)
14.00
(6.35)
Required Subcooling °F (°C)10 (6)10 (6)10 (6)10 (6)9 (5)8 (4)9 (5)
Weight, shipping lbs. (kg)154 (70)183 (83)188
(85)
204
(93)254 (115)317 (144)318 (144)
Weight, operating lbs. (kg)125 (57)147 (67)153
(69)
165
(75)213 (96)264 (120)280 (127)
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of
lineset. Note: See unit Installation Instruction for proper installation.
ELECTRICAL DATA (208/230−1−60, voltage range 197V − 253V)
Model Size 18 24 30 36 42 48 60
Minimum Circuit Ampacity −
MCA (amps)11.8 17.7 16.8 17.5 23.6 26.1 32.4
Maximum OverCurrent
Protective device − MOCP (amps)20 30 25 30 40 40 50
Compressor RLA (Rated Load Amps)
LRA (Locked Rotor Amps)
9.0
48.0
13.5
58.3
12.8
64.0
13.6
79.0
17.9
112.0
19.9
109.0
23.7
152.5
Fan Motor FLA (Full Load Amps).50 .75 .75 .50 1.2 1.2 2.8
**Sound Rating tested in accordance with AHRI Standard 270−08 (not listed with AHRI).
PRODUCT SPECIFICATIONS Split System Air Conditioner: NXA6
421 6201 05 5Specifications subject to change without notice.
REFRIGERANT CHARGE ADJUSTMENTS
Liquid Line Size R-410A Charge oz/ft
3/8 0.60
(Factory charge for lineset = 9 oz)
5/16 0.40
1/4 0.27
Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz. When using other length or
diameter liquid lines, charge adjustments are required per the chart above.
Charging Formula:
[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment
Example 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required?
Formula: (.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz.
Net result is to remove 4.95 oz of refrigerant from the system
Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?
Formula: (.40 oz/ft. x 45ft) – (9 oz.) = 9 oz.
Net result is to add 9 oz of refrigerant to the system
LONG LINE APPLICATIONS
An application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable
refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as
long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the charts below shows when an application requires a TXV and long line accessories due to lineset
length.
AC with R−410A Refrigerant Long Line Description ft (m) Beyond these lengths, a TXV is required
Total Length Outdoor Unit Above or Below Indoor Unit
TXV required beyond 50 ft. (15.2 m)TXV required beyond 20 ft. (6.1 m)
AC with R−410A Refrigerant Long Line Description ft (m) (Beyond these lengths, long line accessories are required)
Liquid Line Size Units On Same Level Outdoor Below Indoor Outdoor Above Indoor
1/4 + TXV No accessories needed within al
lowed lengths
No accessories needed within
allowed lengths 175 (53.3)
5/16 + TXV 120 (36.6)50 (15.2) vertical or 120 (36.6) total 120 (36.6)
3/8 + TXV 80 (24.4)35 (10.7) vertical or 80 (24.4) total 80 (24.4)
Note: See Long Line Guideline for details
PRODUCT SPECIFICATIONS Split System Air Conditioner: NXA6
6 421 21 6201 05Specifications subject to change without notice.
R−410A COOLING CAPACITY LOSS FOR VARIOUS LINE LENGTHS & TUBE DIAMETERS
Model
Size
Liquid
Line
in.(mm)
Acceptable
Vapor Line
Sizes
in. (mm)
Cooling Capacity Loss (%) at Total Equivalent Line Length, feet (m)
Refer to Long Line Application Guideline to calculate equivalent length
Standard Application Long Line Application (Requires Accessories)
25'
(7.6)
50'
(15.2)
80'
(24.4)
81'
(24.7)
100'
(30.5)
125'
(38.1)
150'
(45.7)
175'
(53.3)
200'
(61)
225'
(68.6)
250'
(76.2)
18
3/8 (10)
1/2 (13)1 2 3 3 4 6 7 8 9 10 12
5/8 (16)0 0 1 1 1 1 2 2 3 3 3
3/4 (19)0 0 0 0 0 1 1 1 1 1 1
24
5/8 (16)0 1 1 1 2 3 3 4 4 5 6
3/4 (19)0 0 0 0 0 1 1 1 1 1 2
7/8 (22)0 0 0 0 0 0 0 0 0 0 1
30
5/8 (16)1 2 3 3 3 4 5 6 7 8 9
3/4 (19)0 0 1 1 1 1 2 2 2 3 3
7/8 (22)0 0 0 0 0 1 1 1 1 1 1
36
5/8 (16)1 2 4 4 5 6 7 9 10 11 13
3/4 (19)0 0 1 1 1 2 2 3 3 4 4
7/8 (22)0 0 0 0 0 1 1 1 1 2 2
42
3/4 (19)0 1 2 2 2 3 4 4 5 6 6
7/8 (22)0 0 1 1 1 1 2 2 2 3 3
1−1/8 (29)0 0 0 0 0 0 0 0 0 0 1
48
3/4 (19)0 1 2 2 3 4 5 5 6 7 8
7/8 (22)0 0 1 1 1 2 2 2 3 3 4
1−1/8 (29)0 0 0 0 0 0 0 0 1 1 1
60
3/4 (19)1 2 4 4 5 6 7 9 10 11 12
7/8 (22)0 1 2 2 2 3 4 4 5 5 6
1−1/8(29)0 0 0 0 1 1 1 1 1 1 2
Consult the Long Line Application Guideline document before purchasing/installing line sets.
Applications in shaded area may have height restrictions that limit allowable total equivalent length when outdoor unit is
below indoor unit.
TESTED AHRI COMBINATION RATINGS
NOTE: For complete ratings information, use the AHRI website directory search: www.AHRIdirectory.org.
New ratings may be listed online before Specification Sheets are updated.
UNIT SIZE INDOOR
MODEL
AHRI STANDARD RATINGS
FURNACE MODELCOOLING
CAPACITY FACTORY
ENHANCE
SEER EERSTANDARDTDRTXV
18 EN(A,D)4X19*17**18,000 TXV 14.50 12.00
24 EN(A,D)4X31*17**23,600 TXV 14.50 12.00
30 EN(A,D)4X31*17**28,600 TXV 14.50 12.00
36 EN(A,D)4X37*17**34,400 TXV 14.50 12.00
42 EN(A,D)4X43*24**41,000 TXV 14.50 12.00
48 *ED*4X60L**46,000 TXV 14.50 12.00
60 EN(A,D)4X61*24**57,500 TXV 15.00 12.50
AHRI — Air Conditioning, Heating & Refrigeration InstituteEER— Energy Efficiency Ratio − 80 F (26.6 C) indoor db/67 F (19.4 C) indoor wb & 95 F (35 C) outdoor db.SEER — Seasonal Energy Efficiency RatioTDR —Time−Delay Relay. In most cases, only one method should be used to achieve TDR function. Using more than one method in a system may cause degradation in performance. Use either the accessory Time−Delay Relay or a furnace equipped with TDR. Most ICP furnaces are equipped with TDR.NOTES:1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other combinations are determined under DOE computersimulation procedures.3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.4. Do not apply with capillary tube coils as performance and reliability are significantly affected.
TESTED AHRI COMBINATION RATINGS*Or scan this QR code:
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates, please refer to the AHRI directory. www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Tempstar database:
http://www.icpeqp.com/AHRIratings/ratings.aspx?Brand=Tempstar
PRODUCT SPECIFICATIONS Split System Air Conditioner: NXA6
421 6201 05 7Specifications subject to change without notice.
ACCESSORY USAGE GUIDELINES
Accessory
REQUIRED FOR
LOW−AMBIENT APPLICATIONS
{Below 55°F (13°C)}
REQUIRED FOR
LONG−LINE APPLICATIONS*
Crankcase Heater Yes Yes
Evaporator Freeze Thermostat Yes No
Winter Start Control Yes**No
TXV Yes Yesǂ
Hard Start Kit (Capacitor & Relay)Yes Yes
Low Ambient Kit (Pressure Switch)Yes No
Support Feet, 4” (102mm) tall Recommended No
* Refer to the Long Line Application Guideline document.
** Can only be installed in conjunction with the Low Pressure Switch
ǂ TXV required beyond 20 ft (6.1m) vertical separation or 50 ft (15.2) total length.
ACCESSORIES
Part Number Description Used On
Model Size
NASA003CH Crankcase Heater for Scroll Compressor (208/230 V)18, 24, 30, 36
NASA001CH Crankcase Heater for Scroll Compressor (208/230 V)42, 48, 60 *
NASA001SC Start Component − PTC Device ALL
NASA00201FS Evaporator Freeze Thermostat ALL
NASA403PS Low Pressure Switch, AC, R−410A ALL
NASA404PS High Pressure Switch, AC or HP, R−410A ALL
NASA401LS Liquid Line Solenoid Valve, R−410A ALL
NASA001TD Time Delay Relay, Indoor Blower ALL
NASA00201WS Winter Start Control ALL
NASA001AC Anti−Cycle Timer (5 minute delay)ALL
NASA005SC Hard Start Kit (Capacitor & Relay)18 − 48
NASA012SC Hard Start Kit (Capacitor & Relay)60
NASA401LA Low Ambient Kit (Pressure Switch), R−410A ALL
NASA001SF Support Feet, 4” (102mm) tall, 5 included ALL
NASA001SJ Sound Jacket, Compressor 18, 24, 30, 36, 42, 48
NASA00101SJ Sound Jacket, Compressor 60
NAEA40501TX TXV Kit, R−410A − for use with copper or tin fan coils 18, 24, 30
NAEA40601TX TXV Kit, R−410A − for use with copper or tin fan coils 36, 42
NAEA40701TX TXV Kit, R−410A − for use with copper or tin fan coils 48, 60
NAEB40501TX TXV Kit, R−410A − for use with aluminum fan coils 18, 24, 30
NAEB40601TX TXV Kit, R−410A − for use with aluminum fan coils 36, 42
NAEB40701TX TXV Kit, R−410A − for use with aluminum fan coils 48, 60
* Some models may be factory installed.
PRODUCT SPECIFICATIONS Split System Air Conditioner: NXA6
8 421 21 6201 05Specifications subject to change without notice.
NOTES:
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
Copyright 2019 International Comfort ProductsLewisburg, Tennessee 37091 USAwww.GoTempstar.com