Loading...
HomeMy WebLinkAboutAPPROVED LP_Table 402.4(28) Schedule 40 Metallic PipeGAS PIPING INSTALLATIONS TABLE 402.4(28) SCHEDULE 40 METALLIC PIPE Gas Undiluted Propane Inlet Pressure 11.0 in. w.c. Pressure Drop 0.5 in. w.c. Specific Gravity 1.50 INTENDED USE Pipe sizing between single- or second -stage (low pressure) regulator and appliance. PIPE SIZE (inch) Nominal 1/2 b 1 41 1% 2 2% 3 4 Actual ID 0.622 0.824 f.043 1.380 1 1.610 2.067 2.469 3.068 4.026 Length (ft) Capacity in Thousands of Btu per Hour 10 291 608 1,150 2,350 3,520 6,790 10,800 19,100 39,000 20 200 418 787 1,620 2,420 4,660 7,430 13,100 26,800 30 160 336 632 1,300 1,940 3,750 5,970 10,600 21,500 40 137 287 541 1,110 1,660 3,210 5,110 9,030 18,400 50 122 255 480 985 1,480 2,840 4,530 8,000 16,300 60 110 231 434 892 1,340 2,570 4,100 7,250 14,800 80 101 212 400 821 1,230 2,370 3,770 6,670 13,600 100 94 197 372 763 1,140 2,200 3,510 6,210 12,700 125 89 185 349 716 1,070 2,070 3,290 5,820 11,900 150 84 175 330 677 1,010 1,950 3,110 5,500 11,200 175 74 155 292 600 899 1,730 2,760 4,880 9,950 200 67 140 265 543 814 1,570 2,500 4,420 9,010 250 62 129 243 500 749 1,440 2,300 4,060 8,290 300 58 120 227 465 697 1,340 2,140 3,780 7,710 350 51 107 201 412 618 1,190 1,900 3,350 6,840 400 46 97 182 373 560 1,080 1,720 3,040 6,190 450 42 89 167 344 515 991 1,580 2,790 5,700 500 40 83 156 320 479 922 1,470 2,600 5,300 550 37 78 146 300 449 865 1,380 2,440 4,970 600 35 73 138 283 424 817 1,300 2,300 4,700 650 33 70 131 269 403 776 1,240 2,190 4,460 700 32 66 125 257 385 741 1,180 2,090 4,260 750 30 64 120 246 368 709 1,130 2,000 4,080 800 29 61 115 236 354 681 1,090 1,920 3,920 850 28 59 Ill 227 341 656 1,050 1,850 3,770 900 27 57 107 220 329 634 1,010 1,790 3,640 950 26 55 104 213 319 613 978 1,730 3,530 1,000 25 53 100 206 309 595 948 1,680 3,420 1,100 25 52 97 200 300 578 921 1,630 3,320 1,200 24 50 95 195 292 562 895 1,580 3,230 1,300 23 48 90 185 277 534 850 1,500 3,070 1,400 22 46 86 176 264 509 811 1,430 2,930 1,500 21 44 82 169 253 487 777 1,370 2,800 1,600 20 42 79 162 243 468 746 1,320 2,690 1,700 19 40 76 156 234 451 719 1,270 2,590 1,800 I9 39 74 151 226 436 694 1,230 2,500 1,900 18 38 71 146 219 422 672 1,190 2,420 2,000 18 37 69 142 212 409 1 652 1,150 1 2,350 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 rem, 1 pound per square inch = 6.895 kPa, 1-inch water column = 0.2488 kPa, 1 British thermal unit per hour = 0.2931 W, 1 cubic foot per hour = 0.0283 m'/h, 1 degree = 0.01745 rad. Nate: All table entries have been rounded to three significant digits. FLORIDA BUILDING CODE - FUEL GAS, 7th EDITION (2020) 53 ` Copyright®zozo ICC. ALLRIGHTS RESERVED Accessed by Rodney Rosado LaIlgasserviceincCagmait.core),L-)Order Numbrr s3otoce�is on Apr ot,,io2--s AM (PDT) pursoaottoLicense Agreement with IRTM •1 3CC. No further reproduction, no further rep-d-li.- by any third party, or di=ibution a nbotized. Single user only, copying and netwoddng prohibited. ANY UNAUTHORIZED REPRODUCTION OR