HomeMy WebLinkAboutEvaluation Report; Metal RoofingCREEK TECHNICAL SERVICES, LLC Certificate of Authorization No. 29824 17520 Edinburgh Dr Tampa, FL 33647 (813) 480-3421 EVALUATION REPORT FLORIDA BUILDING CODE, r EDITION (2020) Manufacturer: Manufacturing: Quality Assurance: SCOPE DREXEL METALS, INC. 1234 Gardiner Lane Louisville, KY 40213 (502) 716-7143 www.drexmet.com Issued August 9, 2020 Drexel Metals Association of Regional Manufacturers (DM -ARM) Architectural Testing, Inc., An Intertek Company (QUA1844) Category: Roofing Subcategory: Metal Roofing Code Edition: Florida Building Code, 71'h Edition (2020) High -Velocity Hurricane Zones (HVHZ) Code Sections: 1518.9.1, 1523.1.1, 1523.6.5, 1523.6.5.2.4, 1523.6.5.2.4.1 Properties: Wind Resistance REFERENCES 99& Report No. Standard Year Architectural Testing (TST1558) 56840.02-122-18 TAS 100 1995 Architectural Testing (TST1558) 56842.02-122-18 TAS 100 1995 Architectural Testing (TST1558) 58461.01-122-44 TAS 125 2003 Architectural Testing (TST1558) 58641.02-122-44 TAS 100 1995 Architectural Testing (TST1527) H3245.01-450-18 TAS 125 2003 Architectural Testing (TST1527) H3245.02-450-18 TAS 100 1995 Architectural Testing (TST1527) H9058.02-450-18 TAS 125 2003 Architectural Testing (TST1527) H9058.01.450-18 TAS 125 2003 Architectural Testing (TST1527) H9058.03-450-18 TAS 100 1995 Hurricane Test Laboratory (TST1527) 0287-0209-07 TAS 125 2003 Hurricane Test Laboratory (TST1527) 0287-0308-07 TAS 125 2003 Hurricane Test Laboratory (TST1527) 0287-0311-07 TAS 125 2003 Hurricane Test Laboratory (TST1527) 0287-0312-07 TAS 125 2003 Hurricane Test Laboratory (TST1527) 0287-0313-07 TAS 125 2003 Hurricane Test Laboratory (TST1527) 0287-0512-07 TAS 125 2003 Hurricane Test Laboratory (TST1527) 0287-0706-07 TAS 125 2003 PRI Construction Materials Technologies (TST5878) VL8-005-02-01 ASTM B 117 2016 TAS 110 2000 PRI Construction Materials Technologies (TST5878) VLS-004-02-01 ASTM G 155 2013 TAS 110 2000 PRI Construction Materials Technologies (TST5878) DMC-002-02-01 TAS 100 1995 PRI Construction Materials Technologies (TST5878) DMC-004-02-01 TAS 125 2003 PRI Construction Materials Technologies (TST5878) DMC-005-02-01 TAS 125 2003 PRI Construction Materials Technologies (TST5878) DMC-006-02-01 TAS 125 2003 PRI Construction Materials Technologies (TST5878) DMC-007-02-01 TAS 100 1995 PRI Construction Materials Technologies (TST5878) DMC-008-02-01 TAS 100 1995 PRI Construction Materials Technologies (TST5878) DMC-009-02-01 TAS 100 1995 PRI Construction Materials Technologies (TST5878) DMC-014-02-01 TAS 125 2003 PRI Construction Materials Technologies (TST5878) DMC-016-02-01 TAS 100 1995 PRI Construction Materials Technologies (TST5878) DMC-030-02-01 TAS 100 1995 PRI Construction Materials Technologies (TST5878) HTL-013-02-01 TAS 100 1995 PRI Construction Materials Technologies (TST5878) HTL-014-02-01 TAS 100 1995 DRX15002.6 FL17679-R6 Page 1 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. x: CREEK TECHNICAL, SERVICES, LLC PRODUCT DESCRIPTION DREXEL METALS, INC. Metal Roofing (HVHZ) DMC 100NS Profile: 1 in. snap lock seam; Max. 16 in. coverage Description: Non-structural, snap lock standing seam roof panel with integral perorated nail strip Material: Min. 24 ga. Fluropon® coated ASTM A792 AZ50, or ASTM A653 G90; Fy = min. 50 ksi; Shall conform with FBC Section 1507.4.3 Is" DMC 150SS Profile: 1.5 in. mechanical seam; Max. 16 in. coverage Description: Non-structural, mechanical lock standing seam roof panel Material: Min. 0.032 in. Fluropon® coated ASTM B209 aluminum; Fy = min. 16 ksi; Shall conform with FBC Section 1507.4.3 Min. 24 ga. Fluropon® coated ASTM A792 AZ50, or ASTM A653 G90; Fm = min. 50 ksi; Shall conform with FBC Section 1507.4.3 I � 2 9n I I 1�,fig _T 16" I DMC 175S Profile: 1.75 in. snap lock seam; Max. 18 in. coverage Description: Non-structural, snap lock standing seam roof panel Material: 0.032-inch (Fy = min. 24 ksi) or 0.040-inch (Fy = min. 20 ksi) Fluropon® coated ASTM B209 aluminum; Shall conform with FBC Section 1507.4.3 Min. 24 ga. Fluropon® coated ASTM A792 AZ50, or ASTM A653 G90ASTM A792 or ASTM A653; Fy = min. 50 ksi; Shall conform with FBC Section 1507.4.3 1e L 18, DRX15002.6 FL17679-R6 Page 2 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL. SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) DMC 200S Profile: 2 in. mechanical seam; Max. 16 in. coverage Description: Non-structural, mechanical lock standing seam roof panel Material: Min. 0.040 in. Fluropon® coated ASTM B209 aluminum; Fy = min. 20 ksi; Shall conform with FBC Section 1507.4.3 Min. 24 ga. Fluropon®•coated ASTM A792 AZ50, or ASTM A653 G90; Fy = min. 50 ksi; Shall conform with FBC Section 1507.4.3 2" 2° 1 DMC 5V Profile: 13/8 in. ribs; Min. 21 in., Max. 24 in. coverage Description: Non-structural, through fastened roof panel Material: Min. 26 ga. Fluropon® coated ASTM A792 or ASTM A653 G90 ; Fy = min. 50 ksi; Shall conform with FBC Section 1507.4.3 Min. 0.032 in. Fluropon® coated ASTM B209 aluminum; Fy = min. 19 ksi; Shall conform with FBC Section 1507.4.3 — ;21"Up_to 24" Couerage, S. LIMITATIONS 1. Fire classification is not within the scope of this evaluation. 2. The roof deck and the roof deck attachment information are provided based on testing. FBC requirements for the rational design of the roof deck, including the attachment, are not within the scope of this evaluation. 3. Roof slope shall be 2:12 or greater. 4. Reroofing shall be in accordance with Section 1521. 5. Installation of the evaluated products shall comply with this report, RAS 133, and the manufacturer's published application instructions. Where discrepancies exist between these sources, the more restrictive and FBC compliant installation detail shall prevail. 6. All products listed in this report shall be manufactured under a quality assurance program in compliance with Rule 61G20-3. DRX15002.6 FL17679-R6 Page 3 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. W� CREEK TECHNICAL SERVICES, LLC COMPLIANCE STATEMENT DREXEL METALS, INC. Metal Roofing (HVHZ) The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building Code, 7"' Edition (2020) High -Velocity Hurricane Zones (HVHZ) as evidenced in the referenced documents submitted by the named manufacturer. 01111 u1till G�PY R P,Q/�i,�. E'0 No 74021 '.. STATE OF .' / .-,FS,O N A; CERTIFICATION OF INDEPENDENCE 2020.08.09 v. 15:10:24 OgittlyYW4ML Nry N'P*t ao -04'00' Zachary R. Priest, P.E. Florida Registration No. 74021 Organization No. ANE9641 CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing products under this evaluation. CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under this evaluation. Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products under this evaluation. Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. APPENDICES 1) APPENDIX A— Installation (9 pages) 2) APPENDIX B —Approved Roof Systems (5 pages) 3) APPENDIX C — Design Wind Loads(3 pages) DRX15002.6 FL17679-R6 Page 4 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK MeMETALS, INC. Metal w Metal Roofing (HVHZ) TECHNICAL, SERVICES, LLC APPENDIX A INSTALLATION Note - Refer to the APPROVED ROOF SYSTEMS section of this report for specific installation details of a Selected system. Unless otherwise specified in this report the following installation details shall be met for the named products: Component . Product Installation Detail #9-15 HWH wood screw with sealing washer Shall penetrate through the sheathing a minimum 3/8 in. Must be corrosion resistant in accordance with FBC section 1507.4.4. #10-13 PH wood screw Fasteners #10-16.DP3 PH self - drilling screw Shall penetrate through the top rib of the steel deck a minimum 3/4 in. Must be #14-13 DP1 PH self- corrosion resistant in accordance with FBC section 1507A.4. drilling screw Bearing Plates 18 ga. Bearing Plate 3" ® Y 24 ga. SS in -seam clip 1 24 ga. DMC 15OSS Clip ;3 8 Clips 2" 24 ga. in -seam clip Tn / 16' 1. 1 24 ga. DMC 150SS Fixed 3o T 19 Clip 0 o „ _"' B `'4 22 ga. SS in -seam clip �s Clips 22 ga. DMC 150SS Clip 1 � e- T o_ 0 DRX15002.6 FL17679-R6 Page 1 of 9 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX A Component Product Installation Detail 22 ga. in -seam clip 7 22 ga. DMC 15OSS Fixed Clip 1 301 8 T o 0 o 6k 22 ga. base; 24 ga. butterfly in -seam clip DMC 15OSS Butterfly Clip *fir r '— �`r ' 1 518 r ` d 4': 22 ga. base; 24 ga. butterfly in -seam clip Er DMC 150SS Continuous Butterfly Clip i' 18 ga. in -seam clip l� \ Clips DMC 175S UL Clip Li o DRX15002.6 FL17679-R6 Page 2 of 9 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. A�7 CREAK TECHNICAL. SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX A Component Product Installation Detail 22 ga. SS in -seam clip 4.A l DMC 200S Clip" T A 18 ga. base; 22 ga. butterfly in -seam clip; 4.5 in. length DMC 200S Butterfly Clip 4 lips (Cont'd) e 18 ga. base; 22 ga. butterfly inseam clip; 120 in. length; top slider 12 in. o.c. �a DMC 200S Continuous r Butterfly Clip f s, r� Sealants Bostik 70-05A Shall be applied in continuous beads along the seam Bostik Chem -Calk 915 Fastening Details Nomenclature Attachment DMC 1L 0NS PANE. 1 — 13 Prlw DMC 100NS Standard DRX15002.6 FL17679-R6 3of9 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL, SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX A Fastening Details Nomenclature Attachment � ] GION&P A LHW DMC 100NS Enhanced DMC 15OSS PANEL DMC 1508S CONTINUOUS BUTTERFLY CLIP----� (2) #10 -13 PHW' UNDERLAYMENT — DMC 15OSS Continuous SUBSTRATE Butterfly T i DMC 1508S PANEL--- DMC: 15OSS BUTTERFLY CLIP (2)'#10 -13 PHW UNDERLAYMENT DMC 15OSS Butterfly SUBSTRATE — r DMC 15OSS PANEL 24 GA DMC 150SS FIXED CLIP (2) #1 D -13 PHW UNDERLAYMENT SUBSTRATE DMC 15OSS Fixed - 90 1 C DRX15002.6 FL17679-R6 4 of 9 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX A Fastening Details Nomenclature `` Attachment DMC 15OSS PANEL 24 GA DMC150S9 CLIP (2) #1.0 -13 PHW UNDERLAYMENT DMC 15OSS Standard (Al) .SUBSTRATE 174" BEAD'BOSTIK 70=05A--� DMC 15OSS PANEL `22 GA DMC, 150SS''FIXED CLIP - --- --- DMC 15OSS Fixed (2) #10 -13 PHW - ---- Enhanced -90 UNDERLAYMENT SUBSTRATE j DMC 150SS PANEL 22 GA DMC 1508S FIXED CLIP (2) #10 =13 PHW � UNDERLAYMENT DMC 15OSS Fixed SUBSTRATE Enhanced - 180 DRX15002.6 FL17679-R6 .. Page 5 of 9 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX A Fastening Details Nomenclature Attachment 1/4" BEAD BOSTIK70-05A—` DMC 150SS PANEL-� 22 GA DMC 150SS CLIP ,� (2).#10 -13 PHW \- DMC 15OSS Enhanced (Al) UNDERL"ENT SUBSTRATE DMC 175S Panel—\ DMC 175S UL Clip #10-13 PH Screw— (2) per clip i\ DMC 175S #10 Standard DMC 1739 PANEL�� , DMC 175S UL CLIP �t •� 914 -13 DP1 PHDD (2 Per Gip) WO-18GA13EARINGPLATE—� \ METAL DECK ISO INSULATION' I, DMC 175S #14 Standard 1 - DRX15002.6 FL17679-R6 Page 6 of 9 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX A Fastening Details Nomenclature Attachment DMC200S PANEL DMC'2608 BUTTERFLY CLIP (2)'#10--13 PHW UNDERLAYMENT SUBSTRATE DMC 200S Butterfly 111 DMG 200S PANEL DMG`200S:BUTTERFLY CLIP -� #10 .16 DP3 PHD UNDERLAYMENT METAL DECK DMC 200S Butterfly (Steel) Use 18 ga. bearing plate over polyisocyanurate insulation DMC200S. (PANEL-\ DMC 200S CONTINOU.S BUTTERLY CLIP�. - #10 -- 6 DP.& PHD ---,`. UNDERLAYMENT METAL DECK `V `` - DMC 200S Continuous Butterfly (Steel) Use 18 ga. bearing late over polyllsocyanurate insulation DRX15002.6 FL17679-R6 7of9 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. FzZvW ;t CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX A Fastening Details Nomenclature Attachment DMC 200S PANEL DMC 200S .CLIP (2) #10 -13 PHW UNDERLAYMENT SUBSTRATE DMC 200S Fixed 8 1/4" BEAD BOSTIK 70-05A DMC 200S PANEL DMC 200S CLIP (2) #10 -13 PHW DMC 200S Fixed Enhanced UNDERLAYMENT SUBSTRATE I SEALING .WAS HER ` �#915 HWHWOOD SCREW WITH DMC 5V Standard DRX15002.6 FL17679-R6 8of9 This'evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC Fastening Details Nomenclature Attachment #10 - 14 DREXMET WO.OD,SCREW DMC 5V PANEL METSHIELD HT UNDERLAYMENT DMC 5V #10 Standard PLYWOOD DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX A DRX15002.6 FL17679-R6 Page 9 of 9 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC APPROVED ROOF SYSTEMS DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX B The following notes shall be observed when using the assembly tables below. 1. Maximum Design_Pressure (MDP) was calculated using a 2:1 margin of safety per FBC Section 1523.4. 2. Refer to LIMITATIONS and sections of this evaluation when using the table(s) below. 3. Refer to INSTALLATION section of this report for installation detail when the information is not explicitly stated for the selected assembly. 4. The on -center (o.c.) spacing given is the maximum allowable attachment spacing for the rated system. 5. Underlayment shall be installed in accordance with FBC requirements. The minimum underlayment shall be ASTM D 226, Type II installed as described in FBC Section 1518.2.1 with nails and tin caps per 1517.5. 6. Steel Deck shall be designed by others in accordance with FBC requirements and shall be minimum 22 ga (Fy = min.40 ksi) Wide Rib Deck (Type WR) conforming to ANSI/SDI-RD1.0 & FBC. In no case shall the panels be installed on less than two continuous spans, which are spaced a maximum 5-ft o.c. At minimum, the deck shall be attached with one (1) #12 x 1.5-inch HWH self -drilling screws at the bottom of each flute (maximum. 6-inch o.c. along the support). At minimum, the deck side laps shall be fastened a maximum 6-inch o.c. with #12 x 1.5-inch HWH self -drilling screws. 7. Wood Deck shall be designed by others in accordance with FBC requirements and shall be minimum 19/32-inch thick APA Span -Rated plywood sheathing or wood plank at maximum 24-inch span for new construction. Existing construction shall be the minimum plywood sheathing or wood plank thickness at maximum 24-inch span as stated in the approval tables on following pages. In no case shall the attachment be less than 8d ring shank nails spaced 6-inch o.c. Roof System Numbers and Definitions 100NS-W# DMC 100NS over Wood Deck New or Existin 150SS-W# DMC 15OSS over Wood Deck New or Existing) 175S-S# DMC 175S over Steel Deck New or Existing) 175S-W# DMC 175S over Wood Deck new or Existing 200S-S# DMC 200S over Steel Deck New or Existing) 200S-W# DMC 200S over Wood Deck New or Existing 5V-W# DMC 5V over Wood Deck New or Existing Approved Systems for DMC 100NS over Wood Deck (New or Existing) . System Deck Fire Barrier Underlayment Roof Panel Panel Attachment MDP No. (psf) 100NS-W1 Min. 15/32 OPTIONAL As required per FBC 24 ga. DMC 10ONS DMC 100NS Standard attachment -97.5 COX plywood Versashield Solo Max 16-inch wide with fasteners spaced 10.5 in. o.c. 100NS-W2 Min. 15/32 OPTIONAL As required per FBC 24 ga. DMC 10ONS DMC 100NS Standard attachment -120 COX plywood Versashield Salo Max 16-inch wide with fasteners spaced 5.25 in. o.c. 100NS-W3 Min. 15/32 OPTIONAL As required per FBC 24 ga. DMC 100NS DMC 10ONS Enhanced attachment -135 COX plywood Versashield Solo Max 16-inch wide with fasteners spaced 5.25 in. o.c. DRX15002.6 FL17679-R6 1 of 5 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LL,C DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX B Approved Systems for DMC 15OSS over Wood Deck (New or Existing) System No. Deck Fire Barrier Underlayment Roof Panel Panel Attachment' MDP (pso 150SS-W1 Min. 15/32 OPTIONAL As required per FBC 0.032" AI DMC 15OSS Max 16-inch wide DMC 15OSS Standard (Al) attachment -90 CDX plywood Versashield Solo 180" seam with clips spaced 16 in. o.c. 150SS-W2 Min. OPTIONAL As required per FBC 24 ga. DMC 15OSS Max 16-inch wide DMC 150SS Fixed - 90 attachment -90 CDX plywood Versashield Solo 90" seam with clips spaced 16 in. o.c. 150SS-W3 Min. 15/32 OPTIONAL As required per FBC 24 gDMC 15OSSa. Max 16-inch wide DMC 150SS Butterfly attachment -99.25 CDX plywood Versashield Solo- 180° seam with clips spaced 16 in. O.C. 150SS-W4 Min. 15/32 OPTIONAL As required per FBC 24.gDMC 15OSSa. Max 16-inch wide DMC 150SS Continuous Butterfly attachment -114.25 CDX plywood Versashield Solo 180° seam with fasteners spaced 12 in. o.c. 150SS-W5 Min. 15/32 OPTIONAL As required per FBC 24 gDMC 150SSa. Max 16-inch wide DMC 150SS Fixed Enhanced - 90 attachment -150 CDX plywood Versashield Solo Min. 90' seam with clips spaced 12 in. o.c. 150SS-W6 Min. 15/32 OPTIONAL As required per FBC 24 ga. DMC 15OSS Max 16-inch wide DMC 150SS Fixed Enhanced - 180 attachment -165 CDX plywood Versashield Solo Min. 180" seam with clips spaced 8 in. o.c. 150SS-W7 Min. 15/32 OPTIONAL As required per FBC 0.032" AI DMC 150SS Max 16-inch wide DMC 150SS Enhanced (Al) attachment -180 CDX plywood Versashield Solo 180" seam with clips spaced 8 in. o.c. Approved Systems for DMC 175S over Steel Deck New or Existing) System No. Deck Fire Barrier Insulation Underlayment Roof Panel Panel Attachment MDP (psq 175S-Si Min. 22 ga. As required Min. 1 in. Approved polyisocyanurate As required per FBC AI DMC DMC 175S Standard attachment -88 Type B Steel insulation board Max. wide175S Max. 17.5-inch wide s#14 with clips spaced 18 in, o.c. clips DRX15002.6 FL17679-R6 2of5 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX B Approved S tems for DMC 175S over Steel Deck New or Ex sting) System No. Deck Fire Barrier Insulation Underlayment Roof Panel Panel Attachment MDP (Pso 175S-S2 Min. 22 ga. As required Min. 1 in. Approved polyisocyanurate As required per FBC 0.040" AI DMC 175S DMC 175S #14 Standard attachment 429.25 Type B Steel insulation board Max. 17.5-inch wide with clips spaced 12 in. o.c. Approved Systems for DMC 175S over WoodDeck (New or Existing) System No. Deck Fire Barrier Underayment Roof Panel Panel Attachment MDP (Psf) ASTM D 226, Type II roofing felt attached per 175S-W1 Min. 15/32 - 1518.2.1 with nails and tin caps per 1517.5 0.032" AI DMC 175S DMC 175S #10 Standard attachment 74.75 CDX plywood followed by Metshield High -Temp Max. 18-inch wide with clips spaced 24 in. o.c. Underlayment self -adhered to felt 175S-W2 Min. 15/32 OPTIONAL Versashield As requited per FBC 24 ga. DMC 175S DMC 175S #10 Standard attachment -84.25 CDX plywood Solo Max. 18-inch wide with clips spaced 16 in. o.c. 175S-W3 Min. 15/32 OPTIONAL Versashield As required per FBC 0.040" AI DMC 175S DMC 1755 #10 Standard attachment -106.75 CDX plywood Solo Max. 17.5-inch wide with clips spaced 18 in. o.c. 175S-W4 Min. 15/32 OPTIONAL Versashield As required per FBC 24 ga. DMC 175S DMC 175S #10 Standard attachment -121.75 CDX plywood Solo Max. 18-inch wide with clips spaced 8 in. o.c. ASTM D 226, Type II roofing felt attached per 175S-W5 Min. 15/32 _ 1518.2.1 with nails and tin caps per 1517.5 0.032" AI DMC 175S DMC 175S #10 Standard attachment 431 CDX plywood followed by Metshield High -Temp Max. 18-inch wide with clips spaced 6 in. o.c. Undedayment self -adhered to felt Approved Systems for DMC 200S over Steel Deck New or Existing System No. Deck Fire Barrier Insulation Underlayment Roof Panel Panel Attachment MDP (Pso 20OS-S1 Min. 22 ga. As required Min. 1 in. Approved polyisocyanurate As required per FBC 24 ga. DMC 200S Max. 16-inch wide DMC 200S Butterfly (Steel) attachment -88 Type B Steel insulation board 180" seam with clips spaced 24 in. o.c. DRX15002.6 FL17679-R6 3 of 5 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX B Approved Systems for DMC 200S over Steel Deck New or Ex sting) System No. Deck fire Barrier Insulation Underlayment Roof Panel Panel Attachment MDP (psfl 200S-S2 Min. 22 ga. required None As required per FBC 24 ga. DMC 200SAs Max. 16-inch wide DMC (Steel) attachment -91.75 Type B Steel 180° seam with lips spaced with clips spaced 24 in. o.c. 200S-S3 Min. 22 ga. As required Min. 1 in. Approved polyisocyanurate As required per FBC 24 ga. DMC 200S Max. 16-inch wide DMC 200S Continuous Butterfly (Steel) -121.75 Type B Steel insulation board 180° seam attachment with clips spaced 12 in. o.c. 200S-S4 Min. 22 ga. Type B Steel As required None As required per FBC 24 ga. DMC 200S Max. 164nch"wide DMC 200S Continuous Butterfly (Steel) attachment with clips spaced 12 in. o.c. -151.75 180° seam Approved Systems for DMC 200S over Wood Deck (New or Existing) System No. Deck Fire Barrier Underlayment Roof Panel Panel Attachment MDP (psfl 200S-W1 Min. 19/32 OPTIONAL As required per 0Max. 1 DMC 200S Max 1 wide DMC 200S Fixed attachment -105 CDX plywood Versashield Solo FBC * sea 180° seam with clips spaced 16 in. o.c. 200S-W2 Min. 19/32 OPTIONAL As required per 0.040" AI DMC 200S Max.16-inch wide DMC 200S Fixed Enhanced attachment 480 CDX I plywood Versashield Solo FBC 180° seam with clips spaced 8 in. o.c. Approved Systems for DMC 5V over Wood Deck (New or Existing) System No. Deck Fire Barrier Underlayment Roof Panel Panel Attachment MDP (Psfl Min. 15132 OPTIONAL ASTM D 226, Type II roofing felt attached per 1518.2.1 with nails and tin caps per 0.032" AI DMC 5V DMC 5V #10 Standard attachment 5V-W1 CDX plywood Versashield Solo 1517.5 followed by Metshield High -Temp Min. h with 4 HWH wood screws with -56 Underlayment self -adhered to felt Max 24-inch coverage inch c e sealing w sealing washers spaced 18 in. o.c. DRX15002.6 FL17679-R6 4of5 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVH2) APPENDIX B Approved Systems for DMC 5V over Wood Deck (New or Existing) System No. Deck Fire Barrier Undedayment Roof Panel Panel Attachment MDP (Psi 5V-W2 Min. OPTIONAL As required per FBC 26 ga, DMC 5V Min. 21-inch to DMC 5V Standard attachment .60 CDX plywood Versashield Solo Max 24-inch coverage with clips spaced 16 in. o.c. Min. OPTIONAL ASTM D 226, Type II roofing felt attached per 15follow with nails and tin caps per 26 ga. DMC 5V DMC 5V #10 Standard attachment 5V-W3 CDX plywood plywood Versashield Solo 1517.5 followed Metshield High -Temp Min. 21-inch to with #10-14 HWH wood screws with -71 - t Underiaymentseff-adhered to felt Max 24-inch coverage sealing washers spaced 24 in. o.c. 5V-W4 Min. OPTIONAL As required per FBC 26 ga, DMC 5V Min. 214nch to DMC 5V Standard attachment -121.75 CDX plywood Versashield Solo Max 24-inch coverage with clips spaced 8 in. o.c. ASTM D 226, Type II roofing felt attached 26 ga. DMC 5V or DMC 5V #10 Standard attachment 5V-W5 Min. 15/32 OPTIONAL per 1518.2.1 with nails and tin caps per 0.032" AI DMC 5V with #10-14 HWH wood screws with -206 CDX plywood Versashield Solo 1517.5 followed by Metshield High -Temp Min. 21-inch to sealing washers spaced 6 in. o.c. Underlayment self -adhered to felt Max 24-inch coverage DRX15002.6 FL17679-R6 5of5 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. ft CREEK TECHNICAL SERVICES, LLC DESIGN WIND LOADS DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX C The following tables provide design wind loads for components and cladding in accordance with Section 1620 of the FBC and ASCE 7-16 under the following provisions: 1. Wind speeds for risk category I, Il, III, and IV buildings shall be as defined in Section 1620 of the FBC. 2. Exposure C and D shall be as defined in section 1620 of the FBC. 3. Design wind load provided only for gable/hip roofs with roof slopes between 2:12 and 6.1:12 4. All calculations are based on an effective wind area of 10-fe or less. 5. Topographic factors such as escarpments or hills have been excluded from the analysis 6. Overhangs have been excluded from the analysis. 7. Wind directionality factor, Kd = 0.85 8. Design wind loads are calculated using Pasd = 0.6Put. 9. Zone 2 is inclusive of Zone 2e, Zone 2n, and Zone 2r 10. Zone 3 is inclusive of Zone 3e and Zone 3r 11. Projects with mean roof heights greater than 60-ft shall be evaluated by a licensed design professional 12. Zones 1, 2, and 3 shall be defined as shown below. Dimension "a" shall be 10% of the least horizontal dimension or (0.4 x Mean Roof Height), whichever is smaller, but not less than either 4% of the least horizontal dimension or 3ft Gable Hip �\ X DRX15002.6 FL17679-R6 Page 1 of 3 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX C Gable/Hip Roofs in Exposure C In Miami -Dade 8'Broward County Roof slopes between 2:12 and 12:12 Building Type Zone Mean Roof Height (ft) 9 .. Wind Speed Basic W (mph)LL . Risk Catt _ : - Risk Cat I Risk Cat II Risk Cat II"r Risk Cat III, IV- � Risk Cat III,IV 156 ", 165 170 175 180 186_ Enclosed/ Partially Open 1 20 -62.3 -69.7 -74.0 -78.5 -83.0 -88.6 25 -65.1 -72.8 -77.3 -81.9 -86.7 -92.6 30 -67.9 -75.9 -80.6 -85.4 -90.4 -96.5 40 -72.0 -80.6 -85.6 -90.7 -95.9 -102.4 50 -75.5 -84.5 -89.7 -95.0 -100.5 -107.3 60 -78.3 -87.6 -93.0 -98.5 -104.2 -111.3 2 20 -90.9 -101.7 -108.0 -114.4 -121.1 -129.3 25 -95.0 -106.3 -112.8 -119.5 -126.5 -135.0 30 -99.0 -110.8 -117.6 -124.6 -131.8 -140.8 40 -105.1 -117.6 -124.8 -132.2 -139.9 -149.4 50 -110.1 -123.2 -130.8 -138.6 -146.6 -156.6 60 -114.2 -127.7 -135.6 -143.7 -152.0 -162.3 3 20 -108.1 -120.9 -128.4 -136.0 -143.9 -153.7 25 -112.9 -126.3 -134.1 -142.1 -150.3 -160.5 30 -117.7 -131.7 -139.8 -148.1 -156.7 -167.3 40 -124.9 -139.7 -148.3 -157.2 -166.3 -177.6 50 -130.9 -146.5 -155.5 -164.7 -174.3 -186.1 60 -135.7 -151.8 -161.2 -170.8 -180.7 -192.9 Partially Enclosed 1 20 -72.9 -81.6 -86.6 -91.8 -97.1 -103.7 25 -76.2 -85.2 -90.4 -95.8 -101.4 -108.3 30 -79.4 -88.8 -94.3 -99.9 -105.7 -112.9 40 -84.3 -94.3 -100.1 -106.0 -112.2 -119.8 50 -88.3 -98.8 -104.9 -111.1 -117.6 -125.5 60 -91.6 -102.4 -108.7 -115.2 -121.9 -130.2 2 20 -101.5 -113.6 -120.6 -127.8 -135.2 -144.3 25 -106.0 -118.6 -125.9 -133.4 -141.2 -150.7 30 -110.5 -123.7 -131.3 -139.1 -147.2 -157.1 40 -117.3 -131.2 -139.3 - -147.6 -156.2 -166.8 50 -123.0 -137.5 -146.0 -154.7 -163.7 -174.8 60 -127.5 -142.6 -151.4 -160.4 -169.7 -181.2 3 20 -118.7 -132.8 -140.9 -149.3 -158.0 -168.7 25 -124.0 -138.7 -147.2 -156.0 -165.0 -176.2 30 -129.2 -144.6 -153.5 -162.6 -172.0 -183.7 40 -137.1 -153.4 -162.9 -172.6 -182.6 -195.0 50 -143.7 -160.8 -170.7 -180.9 -191.4 -204.3 60 -149.0 -166.7 -177.0 -187.5 -198.4 -211.8 DRX15002.6 FL17679-R6 Page 2 of 3 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC DREXEL METALS, INC. Metal Roofing (HVHZ) APPENDIX C Ga le/Hip Roofs in Exposure D In Miaml-Dade & Broward County Roof slopes between 2:12 and 12:12 Building Type Zone Mean Roof Height.(ft) Basic Wind Speed (mph) Risk Cat I. Risk Cat I Risk Cat II Risk Cat II Risk Cat III, IV' Risk Cat III,IV 156 165 170 - 175 180 186 - Enclosed/ Partially Open 1 20 -74.8 -83.7 -88.8 -94.1 -99.6 -106.3 25 -77.6 -86.8 -92.1 -97.6 -103.3 -110.3 30 -80.4 -89.9 -95.4 -101.1 -107.0 -114.2 40 -84.5 -94.5 -100.4 -106.3 -112.5 -120.1 50 -88.0 -98.4 -104.5 -110.7 -117.1 -125.1 60 -90.7 -101.5 -107.8 -114.2 -120.8 -129.0 2 20 -109.1 -122.1 -129.6 -137.3 -145.3 -155.1 25 -113.2 -126.6 -134.4 -142.4 -150.7 -160.9 30 -117.2 -131.1 -139.2 -147.5 -156.0 -166.6 40 -123.3 -137.9 -146.4 -155.1 -164.1 -175.2 50 -128.3 -143.6 -152.4 -161.5 -170.8 -182.4 60 -132.4 -148.1 -157.2 -166.6 -176.2 -188.2 3 20 -129.7 -145.1 -154.0 -163.2 -172.7 -184.4 25 -134.5 -150.5 -159.7 -169.3 -179.1 -191.2 30 -139.3 -155.9 -165.4 -175.3 -185.5 -198.1 40 -146.5 -163.9 -174.0 -184.4 -195.1 -208.3 50 -152.5 -170.6 -181.1 -192.0 -203.1 -216.8 60 -157.3 -176.0 -186.8 -198.0 -209.5 -223.7 Partially Enclosed 1 20 -87.5 -97.9 -103.9 -110.1 -116.5 -124.4 25 -90.7 -101.5 -107.8 -114.2 -120.8 -129.0 30 -94.0 -105.1 -111.6 -118.3 -125.1 -133.6 40 -98.8 -110.6 -117.4 -124.4 -131.6 -140.5 50 -102.9 -115.1 -122.2 -129.5 -137.0 -146.3 60 -106.1 -118.7 -126.0 -133.6 -141.3 -150.9 2 20 -121.8 -136.3 -144.7 -153.3 -162.2 -173.2 25 -126.3 -141.3 -150.0 -159.0 -168.2 -179.6 30 -130.8 -146.4 -155.4 -164.7 -174.2 -186.0 40 -137.6 -154.0 -163.4 -173.2 -183.2 -195.6 50 -143.3 -160.3 -170.1 -180.3 -190.7 -203.6 60 -147.8 -165.3 -175.5 -186.0 -196.7 -210.1 3 20 -142.4 -159.3 -169.1 -179.2 -189.6 -202.5 25 -147.7 -165.2 -175.4 -185.8 -196.6 -210.0 30 -153.0 -171.1 -181.6 -192.5 -203.6 -217.4 40 -160.9 -180.0 -191.0 -202.4 -214.2 -228.7 50 -167.5 -187.3 -198.9 -210.7 -223.0 -238.1 60 -172.7 -193.2 -205.1 -217.4 -230.0 -245.6 DRX15002.6 FL17679-R6 3of3 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein.