Evaluation Report 812D
August 04, 2020
Product Description: Series 8100 PVC Single Hung, Large Missile Impact, 51 7/8” x 61 3/4” unit size,
+/-70 PSF, no anchors in sill
Manufacturer: Custom Window Systems, Inc. 1900 SW 44th Ave, Ocala, FL 34474
Statement of Compliance: This report evaluates the above-listed product per the requirements of FAC
Product Approval Rule Chapter 61G20-3.005 (4). This product complies with the requirements of the7th
Edition (2020) Florida Building Code including the High Velocity Hurricane Zone. The product testing
standards performed are outlined below.
Technical Documentation:
1) This report, prepared by Lucas A. Turner, PE, at 2428 Old Natchez Trc Trl, Camden, TN
2) Approval drawing CWS-812D, signed and sealed by Lucas A. Turner, P.E.
3) Test Report NCTL-210-3815-1A, -2, and -2A, by National Certified Testing Laboratories,
Orlando, FL, signed and sealed by Gerard J. Ferrara, with testing performed: TAS 201/202/203-
94, ASTM E 1886-02/04/05, 1996-02/04/06/09, and AAMA/WDMA/CSA 101/I.S.2/A440-08
4) Supplemental Calculations to support CWS-812D, signed and sealed by Lucas A. Turner, P.E.
Installation: Units must be installed according to approval document CWS-812D.
Limitations of Use: This product:
• May be used in O/X configuration in sizes and with max. glass DLO heights as shown in CWS-
812D
• Is impact resistant and does not require the use of shutters
• May be used in the High Velocity Hurricane Zone
• Requires 7/8” Insulating Glass consisting of 1/8 Annealed or Tempered outboard lite (Tempered
required above 30 ft in HVHZ) – Air – 5/16 Laminated (1/8Ann-.090PVB-1/8Ann) inboard lite
• Requires Kuraray Butacite PVB Interlayer per Miami-Dade NOA 19-0305.02†
• Requires Quanex or Veka white rigid PVC framing per Miami-Dade NOA 17-0206.10† or 17-
0228.04†
† I have evaluated the interlayer and framing materials in these Kuraray, Quanex, and Veka NOAs
and find that they comply with the requirements of the 7th Ed. (2020) Florida Building Code for use in
this product.
Certification of Independence: I do not have, nor do I intend to acquire, nor will I acquire, a financial
interest in Custom Window Systems or in any company manufacturing or distributing products for which
this report is being issued. I do not have, nor do I intend to acquire, nor will I acquire, a financial interest
in any other entity involved in the testing or approval process of this product.