EVALUATION R EPCIRIT
GAF Evaluation Report 01506.04.08-1121
1Campus Drive FL10626-1321
Parsippany, N1 07054 Date of Issuance: 04/25/2008
(800) 766-3411 Revision 21: 04/14/2021
SCOPE :
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida . The documentation submitted has been reviewed by Robert Nieminen,
P. E . for use of the product underthe Florida Building Code and Florida Building Code, Residential Volume . The products
described herein have been evaluated for compliance with the 71h Edition (2020) Florida Building Code sections noted
herein .
DESCRIPTION: GAF Roof Unde0apmehts for use in %F%B non-HVji2 jurisdictions
LABELING : Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein and FBC 1507. 1. 1.
CONTINUED COMPLIANCE : This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance or production facility location (s) changes, or Code provisions that relate to the product(s) change .
Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEW ETC, LLC of any
changes to the product(s), the Quality Assurance or the production facility location (s) . NEMO ETC, LLC requires a
complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Florida Product Approval Number ( FL#) preceded by the words "NEMO Ietc. Evaluated" may be
displayed in advertising literature . If any portion of the Evaluation Report is displayed, then it shall be done in its
entirety.
INSPECTION : Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official ,
This Evaluation Report consists of pages 1 through 8.
Prepared by: _
s"'" • ,yNo-59109� ��
Robert J .M. Nieminen, P. E. yp •., a_: : The facsimile seal appearing was authorized by Robert
Florida Registration No, 59166, Florida DCA ANE1983 '%� s '.Wfv'a'. ,;: , Nieminen, P.E. on 04/14/2021. This does not serve as an
`^ ••••, u!""` . - electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1, NEW ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3 . Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P. E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P. E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically forthat purpose.
02019 NEMO ETC, LLC
OMEMO I etc .
ROOFING COMPONENT EVALUATION :
Product Category: Roofing
Sub-Category: Underlayment
Compliance Statement: GAF Roof Underlayments, as produced by GAF, have demonstrated compliance with the
following sections of the 7" Edition (2020) Florida Building Code through testing in accordance with the following
Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth
herein .
STANDARDS:
Section ` ' `Property Standard Year
1504.3.1 Wind resistance FM 4474 2011
1507. 1.1, 1507.2.4, 1507.2.9.2 / Material standard ASTM D1970 2015
R905. 1.11 R905 .2.8.2
1507. 1. 1.1(2&3, Exception), Tear Strength ASTM D4533 2015
1507. 1.1.1(5) / R905. 1. 1. 1(2&3,
Exception), R905.1.1.1(5)
1507A,1. 1(2&3, Exception), Tensile strength ASTM D5035 2011
1507. 1.1. 1(5) / R905. 1AA(2&30
Exception), R905. 1.1. 1(5)
1507. 1. 1.1(5) / R905.1. 1. 1(5) Liquid water transmission ASTM D4869 2016
1507.1. 1 / R905. 1.1 Material standard ASTM D6757 2016
1507.3.31 R905.3.3 Material standard FRSA/TRI, Sixth Edition 2018
1507.11.2 Material standard ASTM D6164 2011
TAS 110 Accelerated Weathering ASTM D4798 2011
Entity 'Examination `. Reference Date
ERD (TST 6049) ASTM D1623 & FRSA/TRI (Slippage) G34150.08, 11 11/14/2011
ERD (TST 6049) ASTM D6164 (GA) G40630.01. 14-2B 01/07/2014
ERD (TST 6049) ASTM D6164 (GA) G46160.09.14-3A 09/09/2014
ERD (TST 6049) ASTM D1970 (GA) GAF-SC13285.03. 17-3 03/01/2017
ERD (TST 6049) ASTM D1970 (GA) GAF-SC13285.03. 17-4 03/01/2017
ERD (TST 6049) ASTM D1970 (GA) GAF-SC13285.03.17-1 03/08/2017
ERD (TST6049) ASTM D1970 (IN) GAF-SC16440. 12.17 12/31/2017
Intertek (TST 1558) ASTM D4869 (Dadra, India) F8549.02-106-18 11/08/2016
NEMO (TST 6049) Physical Properties (ON) 4q-GAF-I9-SSMBB-03.A 05/13/2019
NEMO (TST6049) ASTM D1970 4j-FTS-20-SSUDL-01.A 12/01/2020
NEMO (TST 6049) ASTM D4798, TAS 103 4j-GAF-2I-SSUDL-02.A 03/15/2021
PRI (TST 5878) ASTM D1970 (IN) GAF-324-02-01 11/30/2011
PRI (TST 5878) ASTM D226 (OK) GAF-339-02-01 03/13/2012
PRI (TST 5878) ASTM D4798 (NC) GAF-349-02-01 07/03/2012
PRI (TST5878) Wind Uplift GAF-434-02-01 09/16/2013
PRI (TST 5878) Wind Uplift GAF-434-02-03 09/16/2013
PRI (TST 5878) Wind Uplift GAF-434-02-04 09/16/2013
PRI (TST 5878) ASTM D4533 (various) GAF-818-02-01 12/05/2017
PRI (TST 5878) ASTM D1970 (At ) MSA-047-02-01 04/11/2018
PRI (TST5878) ASTM D4533 (LA) GAF-826-02-01 06/4/2018
PRI (TST 5878) ASTM D4533 (Dadra, India) GAF-847-02-01 06/4/2018
PRI (TST 5878) ASTM D4533 (Dadra, India) GAF-914-02-01 04/10/2019
PRI (TST 5878) ASTM D4533, D5035 (VA) 376TOO12 07/15/2019
PRI (TST 5878) ASTM D4533 (Umerkui Kilvani, India) 376TOO18 07/31/2019
PRI (TST 5878) ASTM D4533 (Parzai, India ) 376TOO18 07/31/2019
PR[ (TST 5878) ASTM D1970 (AR) 376T0032 10/22/2019
NEMO ETC, LLC Evaluation Report 01506.04.08-1321
Certificate of Authorization #32455 7Ta EDITION (2020) FBC NON-HVHZ EVALUATION F1.30626-1321
GAF Roof Underlayments Revision 21: 04/14/2021
Page 2 of 8
ONEMOletc .
Entitv `Examination `.Reference 'Date
PRI (TST 5878) ASTM D226 (S-CA) 376TOO54 02/18/2020
PRI (TST 5878) ASTM D5035 (various) 376TO103 09/11/2020
PRI (TST 5878) ASTM D4533, D5035 (Rajasthan, India) 376T0111 12/22/2020
UL (TST 1740) ASTM D6757 (TX) 02NK22569 06/04/2002
UL (TST 1740) ASTM D6757 INC) IONK11990 05/18/2011
NEMO ETC Traceability FBC Cross-Listing 04/22/2020
NEMO Traceability FBC Cross-Listing 04/08/2021
UL, LLC (QUA 9625) Quality Control Service Confirmation 03/23/2021
UL, LLC (QUA 9625) Quality Control Service Confirmation (AL) 05/04/2020
UL, LLC (QUA 9625) Quality Control Florida BCIS Current
Product Material Standard Plant(s) )
4A GAF Extended Dry-In Membrane ASTM D1970 Langley, BC Canada
4,2 Liberty"' SBS Self-Adhering Base/Ply ASTM D1970 Mt, Vernon, IN
Sheet Savannah, GA
4.3 StormGuard® Film Surfaced Leak Barrier ASTM D1970 Mt, Vernon, IN
Savannah, GA
Arkadelphia, AR
44 WeatherWatcho Mineral Surfaced Leak ASTM D1970 Mt. Vernon, IN
Barrier Savannah, GA
Tuscaloosa, AL
Deck-Armor'" Premium Breathable Roof 1507.1.1.1(2&3, Exception) /
4.5 Deck Protection R905. 1.1. 1(2&3, Exception) Dadra, India
1507.1.1. 1(2&3, Exception), Dadra, India
4,6 FeltBuster® High-Traction Synthetic 1507.1. 1. 1(5) / R905. 1.1A(2&30 Rajasthan, India
Roofing Felt Exception), R905. 1, 1. 1(5) Richmond, VA
Spartanburg, SC
4.7 Shingle-Mate® Roof Deck Protection ASTM D226, Type II (Table 1) Pryor, OK
Shafter, CA
/
4.8 StormSafe"" Anchor Sheet 1507. 1.1.1(2&3, Exception)R905. 1.1. 1(2&3, Exception) North Bay, ON
1507.1. 1. 1(2&3, Exception) / Dadra, India
4.9 Tiger Paw'" Roof Deck Protection R905. 1. 1. 1(2&3, Exception) Parzai, India
Umerkui Kilvani, India
4. 10 VersaShield® Fire-Resistant Roof Deck ASTM D6757 Conover, NC
Protection
ASTM D6164
4, 11 Ruberoid° Mop Granule FRSA/TRI 09-18 Savannah, GA
4. 12 Ruberoid® Mop Granule FIRASTM D6164
FRSA/TRI 09-18 Savannah, GA
5. 1 This is a building code evaluation . Neither NEMO ETC, LLC nor Robert Nieminen, P. E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions ( i.e., Broward and Miami -
Dade Counties) .
NEMO ETC, LLC Evaluation Report 01506.04.08-R21
Certljlcate ofAuthodzatlon s32455 7'" EDITION (2020) FBC NON-HVHZ EVALUATION FL10626-R21
GAF Roof Underlayments Revision 21: 04/14/2021
Page 3 of 8
ONEM01jetc .
5.3 This Evaluation Report pertains to above-deck roof components. Roof decks and structural members shall be in
accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
5A This Evaluation Report does not include evaluation of fire classification. Refer to FBC 1505 for requirements and
limitations regarding roof assembly fire classification . Refer to FBC 2603 for requirements and limitations
concerning the use of foam plastic insulation.
5. 5 GAF Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced
within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for
approval based on this evaluation combined with supporting data for the prepared roof covering.
5 .6 Allowable Roof Covers:
TABLE, 1: ROOF COVER OPTIONS ! _
'FBC Sectlon: 1507,2 1507.3 1507.4 and 1507.5 ISOZ7 1507.8 and 1507.9
Clay and Concrete Tile ' Metal Slate or Wood
Underlayment Asphalt
Mechanical Adhesive- Slate-Type
Shingles Attach Set Panels Shingles . Shingles Shingles Shakes '
' ':
Yes Yes
GAF Extended Dry-In Membrane Yes No No Yes Yes Yes (mintstrips, (Jolntsulps,
1507.1.1.3 / 1507.1.1.3 /
R905.1.1.3) R905.1.1.3)
Yes Yes
Liberty'" SBS Self-Adhering Yes No No No No Na (joint strips, pointsnips,
Base/Ply Sheet R05.11a / R05.1.13 /
R905.1.1.31 R905.1.1.3)
Yes Yes
StormGuard® Film Surfaced Leak Yes No No Yes Yes Yes point strips, (jolmsvips,
Barrier 1507.1.1.3/ 1507.1.1.3/
R905.1.1.3) R905.1.1.3)
Yes Yes
WeatherWatch° Mineral Surfaced Yes No No No No No Ijointstrips, ipmtstrips,
Leak Barrier 1507.1.1.3 / 1507.1.18 /
R905.1.1.3) R905.1.1.3)
Deck-Armor'" Premium Breathable
Yes No No Yes Yes Yes No No
Roof Deck Protection
FeltBustera High-Traction Yes No No No No No No No
Synthetic Roofing Felt
Shingle-Mate® Roof Deck Yes No No No No No No No
Protection
Tiger Paw'" Roof Deck Protection Yes No No Yes Yes Yes No No
VersaShield° Fire-Resistant Roof yes No No No No No No No
Deck Protection
Yes Yes
Ruberoid° Mop Granule No (Cap Sheet in (cap sheet in No No No No No
2-ply system) 2-plysystem)
See 5.6.1
Yes
Yes
Ruberoid Mop Granule FR No (Cap Sheet in (Cap Sheet in No No No No No
tem) 2-ply system)
2-pysys see 5.6.1
5. 6A Adhesive-set is limited to use of following underlayment / tile-adhesive combinations .
TABLE 1A: ALLOWABLE UNDERLAYMENT / TILgrADHESIVE% COMBINAYIONS3
%Underlayment Adhesive Florida Product Approval
Ruberoid® Mop Granule; Ruberoid® Mop Granule FR Dupont "Tile Bond'" Roof Tile Adhesive" FL22525
1 Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
NEMO ETC, LLC Evaluation Report 01506.04.08-R21
Certificate of Authorization N32455 7N EDITION (2020) FBC NON-HVHZ EVALUATION FL10626-R21
GAF Roof Underlayments - Revision 21: 04/14/2021
Page 4 of 8
ONEMOletc .
5. 7 Allowable Substrates :
TABLE 2; SUBSTRATE QPTIONS'FOR ADHERED UNDERigYMENTS
Underlayment Application Primer Substrates
GAF Extended Dry-In Membrane self-adhering None plywood
Liberty'" SBS Self-Adhering Base/Ply Sheet
StormGuard® Film Surfaced Leak Barrier self-adhering (Optional) plywood
ASTM D41
Weather Watch® Mineral Surfaced Leak Barrier
Liberty"' SBS Self-Adhering Base/Ply Sheet
StormGuard® Film Surfaced Leak Barrier self-adhering None ASTM D226 felt, Type II
Weather Watch® Mineral Surfaced Leak Barrier
LibertyT'" SBS Self-Adhering Base/Ply Sheet
StormGuard® Film Surfaced Leak Barrier self-adhering ASTM D41 metal (flashing metal, valley metal,
etc.)
Weather Watch® Mineral Surfaced Leak Barrier
Ruberoid® Mop Granule
Ruberoid® Mop Granule FIR hot asphalt ASTM D41 structural concrete
Ruberoid® Mop Granule hot asphalt None GAFGLAS° #80 Ultima'" Base Sheet
Ruberoid® Mop Granule FIR or Ruberoid® 20 Smooth
5.8 Attachment Limitations:
5 .8 . 1 For use under mechanically attached NON-TILE prepared roof coverings, attachment shall be in accordance with
the manufacturer's installation instructions, but — for mechanically attached underlayments or base sheets - not
less than FBC 1507. 1. 1 or R905. 1.1.
5.8. 2 For use under tile roof systems, attachment shall be in accordance with the manufacturer's installation
instructions, but — for mechanically attached base sheets - not less than :
• FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, Appendix A,
Table 1 (for Two-Ply Asphalt Applied Hot Mop Underlayment)
or
• Section 5 .8.3 herein (for other underlayment systems).
5.8.3 Wind Resistance for Underlayment Systems in Tile Roof Applications :
The following wind uplift limitations apply to underlayment systems that are not prescriptive in the FRSA/TRI
Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition , The Maximum Design Pressure
is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing
pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied) .
5 .8.3. 1 Direct-to-Deck :
The maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI
Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, Appendix A, Table 1A or the
critical (highest) design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3.
#1 Maximum Design Pressure = -442.5 psf.
Deck: Min . 2,500 psi structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction
Base Sheet: GAFGLAS #75 Base Sheet, Tri-Ply #75 Base Sheet, GAFGLAS #80 Ultima Base Sheet, GAFGLAS Ply 4,
Tri-Ply Ply 4 or GAFGLAS Flex Ply 6 applied in full mopping of ASTM D312, Type IV hot asphalt at 20
to 25 Ibs/square.
Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FIR applied in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25 Ibs/square.
NEMO ETC, LLC Evaluation Report 01506.04.08-1121
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION F1.30626-1121
GAF Roof Underlayments Revision 21: 04/14/2021
Page 5 of 8
ONEMOletc.
5.8.3. 2 Mechanically-Attached Base Sheet:
The maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI
Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, Appendix A, Table 1A or the
critical (highest) design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed at least the Zone 1
design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3. Elevated pressure zones
shall employ an attachment density designed by a qualified design professional to resist the elevated pressure
criteria . Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29, Roofing Application
Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the
limitations set forth in Section 2.2. 10. 1 of FM Loss Prevention Data Sheet 1-29 ( February 2020) for
enhancements.
#2 Maximum Design Pressure = -45 psf.
Deck: Min . 19/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction .
Base Sheet: GAFGLAS® #80 Ultima'"' Base Sheet or Ruberoid® 20 Smooth mechanically attached with 12 ga .,
min . 1.25-inch long ring shank nails through 32 ga., 1-5/8-inch diameter tin caps spaced 9-inch o .c.
at the min . 4-inch wide side laps and 9-inch o.c. at two (2), equally spaced, staggered center rows
in the field of the sheet.
Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FIR applied in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25 Ibs/square.
#3 Maximum Design Pressure = -75 psf.
Deck: Min . 19/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction .
Base Sheet : GAFGLAS® #80 Ultimar"' Base Sheet or Ruberoid® 20 Smooth mechanically attached with 12 ga.,
min . 1.25-inch long ring shank nails through 32 ga ., 1-5/8-inch diameter tin caps spaced 8-inch o .c.
at the min . 4-inch wide side laps and 8-inch o. c. at three (3), equally spaced, staggered center rows
in the field of the sheet.
Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FIR applied in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25 Ibs/square.
#4 Maximum Design Pressure = -97.5 psf.
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction .
Base Sheet: GAFGLAS® #80 Ultima'" Base Sheet or Ruberoid® 20 Smooth mechanically attached with 11 ga.,
min. 1.25-inch long ring shank nails through 32 ga ., 1-5/8-inch diameter tin caps spaced 4-inch o.c.
at the min . 2-inch wide side laps and 4-inch o.c. at four (4), equally spaced center rows in the field
of the sheet.
Cap Sheet: Ruberoid® Mop Granule or Ruberoid® Mop Granule FIR applied in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25 Ibs/square.
NEW ETC, LLC Evaluation Report 01506.04.08-R21
Certificate of Authorizotion #32455 7T" EDITION (2020) FBC NON-HVHZ EVALUATION FL10626-R21
GAF Roof Underlayments Revision 21: 04/14/2021
Page 6 of 8
OMEMO I etc .
5 .9 Exposure Limitations :
TABL%E3: EXPOSURE LIMITATIONS
P Maximum
Prepared Roof Cover
Underlayment Exposure
Installation Type (days)
Deck-Armor'"' Premium Breathable Roof Deck Protection, FeltBuster® High-Traction
Synthetic Roofing Felt, Shingle-Mate® Roof Deck Protection, StormSafe'"' Anchor
Sheet, Tiger Paw'" Roof Deck Protection, VersaShield® Fire-Resistant Roof Deck Mechanically attached 30
Protection, GAF Extended Dry-In Membrane, Liberty'"' SBS Self-Adhering Base/Ply
Sheet, StormGuard® Film Surfaced Leak Barrier and WeatherWatch® Mineral
Surfaced Leak Barrier
Ruberoid® Mop Granule and Ruberoid® Mop Granule FR Adhesive-set tile roof system 180
Mechanically attached UNLIMITED
5, 10 Tile Slippage Limitations : When loading roof tiles on the underlayment in direct-deck tile roof assemblies, the
maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during
loading of the roof tiles.
TAaLE 4: TILE SLIPyAGt LIMITATIONS FORiDIRECr-DECK TILE INSTAVLATION5
Underlayment Tile Profile Staging Method Maximum Staging Slope
Flat Max. 10-tile stack 4: 12
Ruberoid® Mop Granule Flat Max. 6-tile stack (4 over 2) 5:12
Lugged Max. 10-tile stack 5:12
Ruberoid® Mop Granule FR Flat or Lugged Max. 6-tile stack (4 over 2) 5:12
Lugged Max. 10-tile stack 4:12
& INSTALLATION :
6. 1 GAF Roof Underlayments shall be installed in accordance with GAF published installation instructions subject to
the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to
remove any dust and debris prior to application and prime the substrate (if applicable).
6.3 Decl�Arttlor'"' Premium Breathable Roof Deck Protegtiolf or Tiger Pew'"' Roof Dock Protection:
6.3. 1 Shall be installed in compliance with requirements for synthetic underlayment in FBC 1507.1. 1. 1(2, Exception)
or 1507.1. 1. 1(3, Exception) or FBC Residential R905 .1.1. 1(2, Exception) or R905.1. 1.1(3, Exception) for the type
of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take
precedence over the manufacturer's installation instructions .
6.4 FgltBuste O High-Traction Synthetic Roofing Felt
6.4. 1 Shall be installed in compliance with requirements for a synthetic underlayment in FBC 1507.1. 1.1(2, Exception),
1507. 1.1.1(3, Exception) or 1507.1. 1.1(5) or FBC Residential R905. 1.1.1(2, Exception), R905.1. 1.1(3, Exception)
or R905. 1. 1.1(5) for the type of prepared roof covering to be installed, and the manufacturer's installation
instructions. FBC requirements take precedence over the manufacturer's installation instructions .
6.5 StorMSafeT" Anchor Sheets
6.5. 1 StormSafeTm Anchor Sheet is limited to use as a mechanically attached base layer in 2-ply underlayment systems .
NEMO ETC, LLC Evaluation Report 01506.04.08-1321
Certificate of Authorization #32455 7THEDITION (2020) FBC NON-HVHZ EVALUATION FL10626-R21
GAF Roof Underlayments Revision 21: 04/14/2021
Page 7 of 8
fONEMOJetc.
6.5.2 Shall be installed in compliance with requirements for a synthetic underlayment in FBC 1507.1. 1. 1(2, Exception)
or 1507. 1. 1. 1(3, Exception) or FBC Residential R905.1. 1.1(2, Exception) or R905.1 .1.1(3, Exception) for the type
of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take
precedence over the manufacturer's installation instructions .
6.5 .3 One the same day, install Liberty'"' SBS Self-Adhering Base/Ply; StormGuard® Film Surfaced Leak Barrier or
WeatherWatch® Mineral Surfaced Leak Barrier over the StormSafe'" Anchor Sheet.
6,6 ' Shingle•Nlate• Roof Aeak Prol loni
6.6A Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM
D226, Type II ) in FBC Table 1507.1. 1.1 or FBC Residential Table R905. 1. 1. 1 for the type of prepared roof covering
to be installed, and the manufacturer's installation instructions . FBC requirements take precedence over the
manufacturer's installation instructions.
6,7 + VersaShleltla Fire-Resistant ROO Deck Rrotection:
6.7. 1 Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM
D6757) in FBC Table 1507. 1.1 .1 or FBC Residential Table R905.1. 1.1 for the type of prepared roof covering to be
installed, and the manufacturer's installation instructions . FBC requirements take precedence over the
manufacturer's installation instructions.
&S' GIAF Extended Dry-In Membrane, Liberty'"` SBS Self4ohering Base/Ply Sheet; StormGparda ,Film Surfacetl Leak
ellBarrier or WeafherlNatch® )Wrierai Surfaced Leak )3arrYer:
6.8. 1 Shall be installed in compliance with requirements for an approved self-adhering underlayment (ASTM D1970) in
FBC 1507. 1. 1.1 or 1507. 1.1.3 or FBC Residential R905. 1.1. 1 or R905.1.1.3 for the type of prepared roof covering
to be installed, and the manufacturer's installation instructions .
6 .8. 2 Back-nailing is required. Back-nailing shall consist of Approved cap nails spaced 18-inch D.C., encapsulated within
min . 4-inch side laps.
6.8.3 When installed over a mechanically attached, FBC Approved ASTM D226 Type II felt, the felt shall be fastened in
accordance with FBC 1507.1.1 or R905.1. 1.
6.8.4 GAF Extended Dry-In Membrane, Liberty"" SBS Self-Adhering Base/Ply Sheet, StormGuard® Film Surfaced Leak
Barrier or WeatherWatch® Mineral Surfaced Leak Barrier may be installed as a secondary water barrier using
minimum 4-inch wide rolls to seal plywood deck joints prior to installation of the primary underlayment system .
rams e;eft eroid'i Mop granule
6.9. 1 Shall be installed in compliance with requirements as an alternate to the "Hot Asphalt Applied Cap Sheet" in the
"Two Ply System" in the FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth
Edition, and the manufacturer's installation instructions .
6.9.2 Refer to Sections 5.8. 2 and 5 .8.3 herein for attachment limitations.
6.9.3 Refer to Table 4 for tile staging limitations.
7a BUILDING PERMIT REQUIREMENTS: l � -
As required by the Building Official or Authority Having Jurisdiction to properly evaluate the installation of this
product.
Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements . Refer
to Section 4 herein for products and production locations having met codified material standards .
•
UL, LLC. — QUA9625; (414) 248-6409; karen . buchmann@ul . com
- END OF EVALUATION REPORT -